施工图深化设计要求标准

施工图深化设计要求标准
施工图深化设计要求标准

施工设计提交成果

Deliverables of Construction Drawings

灯光照明

Lighting

对于灯光照明专业施工图设计深度标准及技术深度文件现规定如下:

The design depth and technical scope of special lighting working drawing are specified as follows: 一.各区域,各房间的照度计算书及灯具选型、灯位布置;

I.Illumination calculation sheet and type selection and positioning of lights each in room in all areas;

二.照明控制系统中所采用设备的说明书;

II.I nstructions of equipment used in the lighting control system;

三.灯具资料表(用EXCEL表格做出,格式如下,第一行内容为示范);

III.Data sheet of lighting (in EXCEL, with the format as follows; contents in the first row are filled in as an example);

四. 对施工图纸的要求如下:

IV. Requirements for Construction Drawings

用于设计方案阶段的一套完整的图纸至少应包括封面、图纸目录、工程设计说明及图例、设备材料清单、系统图、平面图。

A complete set of drawings used in the design stage shall at least include the cover, drawing content, engineering design instructions and graphic symbols, list of equipment and materials, system diagram, and plan view.

用于施工阶段的图纸至少应包括封面、图纸目录、工程设计说明及图例、设备材料清单、系统图、平面图及设备的安装大样图。

A complete set of drawings used in the construction stage shall at least include the cover, drawing content, engineering design instructions and graphic symbols, list of equipment and materials, system diagram, plan view, and the detail drawing of equipment installation.

照明专业图纸范围如下:

Scope of drawings for lighting is as follows:

必须包括封面、图纸目录、工程设计说明及图例、设备材料清单、系统图、平面图、机房设备布置图、安装大样图。安装详图根据项目情况,应由设计师根据项目的可实现性和各专业分项工程的配合决定绘图深度,设计出满足项目需求的可实施的拓展性安装详图。

It shall include the cover sheet, drawing content, engineering design instructions and graphic symbols, list of equipment and materials, system diagram, plan view, layout of equipment in equipment room, and detail drawing of equipment installation. Feasible and extendable detail drawing for equipment installation shall be designed according to the project situations by the designer who shall decide the depth of drawing according to the project feasibility and coordination between all subdivisional works of each discipline to satisfy the project requirements.

4.1封面Cover

封面应包含项目名称、图纸性质(初步设计、施工图、竣工图等)、公司名称、日期。

-可编辑修改-

The cover shall bear the project name, drawing property (preliminary design, construction drawing, as built drawing, etc.), company name, and date.

4.2图纸目录Drawing content

图纸目录应包含以下内容:项目名称、项目编号、设计公司名称、专业、图纸名称、图纸编号、图幅、出图日期、制图人及审核人等内容。

The drawing content shall include the following: project name, project ID, name of design corporation, discipline, drawing name, drawing number, sheet, drawing finishing date, the person who draws, and the auditor.

4.3工程设计说明及图例Engineering design instructions and graphic symbols

设计总说明须包括但不限于:工程概况、设计依据、各子系统施工内容、施工要求和注意事项、设计特殊要求和施工配合要点、设计范围内智能化系统与相关专业的技术接口要求、图例符号等。

The general design instructions shall include, without limitation to: Project profile, design basis, construction contents of each sub system, construction requirements and notices, special design requirements and key points in construction cooperation, technical interface requirements for the intelligent system and relevant disciplines within the scope of design, graphic symbols, and so on. 4.4设备材料清单List of equipment and materials

在材料表中的图形符号图例应采用国标,其次是部标、行标。未予规定的自拟图形图例,应在图例中标出且加以说明。当使用国标图形图例,又给予不同含义时也应加以说明,一套图纸的图例符号应前后一致。

Graphic symbols in the list of materials shall adopt those in national standards, followed by ministerial standards and industry standards. Self made graphic drawings not specified shall be marked in the graphic symbols with explanations. Explanations shall also be given when graphic symbols in national standards are given different meanings. The graphic symbols used in one set of drawings shall be in consistence with each other.

-可编辑修改-

设备材料清单,按系统开列组成系统主要设备和材料,应标明设备名称、规格型号、主要技术指标、品牌(产地)、数量。非标设备、材料应备注说明技术要求。

The list of equipment and materials shall list the major equipment and materials constituting the system, with an indication of the equipment name, specification and model, key technical indicators, brand (origin), and quantity. Technical requirements for nonstandard equipment and materials shall be marked.

各个平面图、设备房图应随附图例并标注数量。包括电脑、软件、编程工具、机柜、电源、变压器等设备材料都必须在图纸上或设备材料中体现出来,并且注明型号、规格、数量总和。

All plan views and equipment room drawings shall be attached with graphic symbols and quantity. Equipment and materials including computers, software, programming tools, cabinets, power supply and transformers shall be indicated in the drawings or list of equipment materials, with clear indication of the model, specification and total quantity.

4.5系统图

System diagram

4.5.1照明供配电系统图:应注明系统结构、主要配置、终端分布、主干线缆、供电要求、文字说明等。具体设计原则请参考《民用建筑电气设计规范》JGJ 16-2008第3章,第4章。当有类似5D剧场有人员参与演出涉及舞台照明时,舞台照明的供电与负荷计算应参照《民用建筑电气设计规范》JGJ 16-2008第9章9.6节的相关规定。

Drawing of lighting power supply and distribution system: With clear indication of the system structure, major configuration, terminal distribution, trunk cables, power supply requirements, explanatory notes, etc. For detailed principles for design, please refer to chapters 3 and 4 of JGJ 16-2008 Code for Electrical Design of Civil Buildings.When there are personnel participating in the stage show in likely-to-be 5D theater with stage illumination involved, power supply and load calculation of stage illumination shall refer to the related regulations of Section 9.6, Chapter 9 of JGJ 16-2008 Code for Electrical Design of Civil Buildings.

注意:

Notes:

1.当采用可控硅做调光设备时,其电源变压器宜采用接线方式为△/Y0的变压器。

When SCR components are used as dimmer device, the supply transformer shall be △/ Y0 transformer.

-可编辑修改-

2.为抑制高次谐波对照明控制装置及其它系统设备的干扰,除应满足《民用建筑电气设计规范》JGJ 16-2008第22章第22.3节的规定外,还应注意:电声,电视转播设备的电源不宜接在照明用电变压器上。To restrain the interference of ultraharmonics on illumination control devices and other system equipments, except that the regulations of Section 22.3, Chapter 22 of JGJ 16-2008 Code for Electrical Design of Civil Buildings shall be met, shall take note of the following: the power supply of electroacoustic and television relay equipment shall not connect to the transformers for illumination.

4.5.2配电箱系统图:应标注配电箱编号、型号、进线回路编号;标注各开关(或熔断器)型号、规格;标注出线回路编号、导线型号规格;负荷量;对于单相应标明相别;并标明负荷名称。具体设计原则请参考《民用建筑电气设计规范》JGJ 16-2008第7章,《建筑照明设计标准》GB 50034-2004第7章。System diagram of switch box: It shall indicate the switch box No., model, and lead-in loop No.; it shall also indicate the model and specification of switches (or fuses), outgoing line loop No., and model and specification of leads, as well as the load capacity; the phase sequence shall be marked for single-phase wire; the load name shall also be marked. For details, please refer to chapter 7 of JGJ 16-2008 Code for Electrical Design of Civil Buildings and chapter 7 of GB 50034-2004 Standard for Lighting Design of Buildings.

4.5.2.1配电箱系统图须考虑三相平衡,三相配电干线的各相负荷宜分配平衡,最大相负荷不宜超过三相负荷平均值的115%,最小相负荷不宜小于三相负荷平均值的85%。

In making the system diagram of switch box, equilibration of the three-phase system shall be considered; load on each wire of the three-phase distribution trunk shall be distributed in equilibration; the maximum phase load shall not exceed 115% of the mean loads of the three-phase system, and the minimum phase load shall not be smaller than 85% of the mean loads of the three-phase system.

4.5.2.2如有供给气体放电灯的三相配电线路,其中性线截面应满足不平衡电流及谐波电流的要求,且不应小于相线截面。

If there is three-phase power distribution line for the gas discharge lamp, its neutral line section shall meet the requirements of unbalance current and harmonic current and shall not be smaller than the phase line section.

4.5.2.3照明配电箱应保留备用回路,备用回路的数量不应低于配电箱回路数量的30%。

The light distribution box shall have a backup loop, and the number of backup loops shall not be smaller than 30% of the number of switch box loop.

4.5.2.4照明设备的接电方法,应采用专用接插件连接,接插件额定容量应有足够余量。

Power connection of lighting equipments shall adopt the dedicated connectors and the rated capacity shall be enough.

4.5.2.5由晶闸管调光装置配出的舞台照明线路宜采用单相配电。当采用三相配电时,宜每相分别配置中性导体,当共用中性导体时,中性导体截面不宜小于相导体截面的2倍。

For the stage lighting lines distributed by thyristor light-controlling device, single-phase distribution shall be adopted. When adopting three-phase distribution, it is appropriate to distribute neutral conductor respectively in

-可编辑修改-

each phase; when neutral conductor is used in common, its cross section shall be not less than 2 times that of phase conductor.

4.5.2.6照明设备应根据低压配电系统的接地形式确定采用接地保护措施。

Lighting equipments shall determine ground protection measures according to the earthing form of low-voltage distribution system.

4.5.3.照明控制系统图:应标注控制箱编号、型号;标注控制回路编号、导线型号规格、通讯协议、接口界面、控制系统若与其它设备有接口,须标明接口类型。

Lighting control system diagram: It shall indicate the controlling box No. and model; control loop No., model and specification of leads, communication protocol, and interface; if the control system has an interface with other equipment, mark the type of interface.

4.5.3.1控制系统采用专用接地装置时,接地电阻值不应大于4Ω。采用共用接地装置时,接地电阻值不应大于1Ω。

When the control system adopts special earthing device, the resistance to earth shall not be greater than 4Ω. When a common earthing device is used, the resistance to earth shall not be greater than 1Ω.

4.5.3.2乙级及乙级以上电影院观众厅(主演区,预演区)的照明应能渐亮渐暗平滑调节或分档调节。Lighting in the audience hall of class B or above cinemas (performance area and rehearse area) shall be capable of changing from bright to dim state gradually and smoothly or can be adjusted by different grades.

4.5.3.3入口、排队区、上客区、下客区、主演区、预演区等直接为观众服务的地区的照明控制开关应集中单独控制。

The lighting control switches in the areas directly serving the audiences, such as the entry, queue area, load on/off areas, performance area and rehearse area shall be intensively and independently controlled.

4.5.3.4 当采用调光设备时,每一照明回路的可载容量,应与所选用的调光设备的回路输出容量相适应。When using the light-controlling devices, the load capacity for each lighting loop shall be compatible with the output capacity of the selected light-controlling device.

4.5.3.5类似5D剧场有人员参与演出的舞台调光控制装置的选择和安装应符合下列要求:

The selection and installation of stage light-controlling devices withpersonnel’s participation in the stage show in the likely-to-be 5D theatershall conform to the follwing requirements:

1. 舞台照明调光控制器的选型:小型剧场,可选用带预选装置的控制器,中型及以上规模的剧场,宜选用带计算机的控制器。

Model selection of stage illumination light-controller: for small-sized theater, the controller with pre-elected device could be selected; for the theater with middle size and above, the controller with computer could be selected.

2. 舞台照明调光控制台宜安装在观众厅后部的灯控室内,并应符合下列规定:

Stage illumination lighting console shall install in the lighting control room in the back of auaditorium and conform to the following regulations:

(1)调光柜和舞台配电设备应设在靠近舞台的单独房间内;

Dimmer cabinet and stage distribution equipment shall be set up within the single room close to the stage;

(2)舞台表演区应在灯光控制人员的视野范围内;

-可编辑修改-

Stage acting area shall be in the field of view of light-controlling personnel;

(3)灯控人员应能容易的观察到观众席的情况;

Light-controlling personnel shall be able to easily observe the auditorium;

(4)应与舞台布灯配光联系方便;

Shall be in convenient contact with lamp collocation and light distribution of the stage.

(5)调光设备与线路应安装敷设方便。

Light-controlling equipments and pipelines shall be conveniently installed and laid.

4.6平面图

Plan view

4.6.1总体要求

General requirements

(1)照明配电箱宜设置在靠近照明负荷中心便于操作维护的位置。

The light distribution box shall be placed in the place which is near to the lighting load center and convenient for operation and maintenance.

(2)其他具体设计标准参考我国电影行业标准?电影院建筑设计规范?JGJ58-2008中对于电气及照明方面的要求。

Other detailed design criteria shall conform to the relevant requirements about electricity and lighting in China's cinema industry standard JGJ58-2008 Code for Architectural Design of Cinema.

4.6.2线槽设计

Trunking design

由强、弱电竖井或控制机房引向用电负荷的电气线路,在回路众多的情况下应采用线槽布线。

The electric wiring drawn from vertical shaft for light-current and strong-current or control cabinet shall adopt trunking when there are numerous loops.

4.6.2.1灯光专业线槽种类按走向通常分为:水平线槽、垂直线槽。灯光专业线槽种类按系统通常分为:弱电控制信号线综合线槽、强电电缆线槽。强、弱电线槽应分别设置,不允许共用。具体设计原则请参考《民用建筑电气设计规范》JGJ 16-2008第8章。

According to the trend, special lighting trunking can usually be divided into: horizontal trunking and vertical trunking. According to the system, special lighting trunking can usually be divided into: integrated trunking for light-current control signal lines and trunking for strong-current cables. Trunking for strong-current and light-current shall be set respectively and shall not be shared. For detailed principles for design, please refer to chapter 8 of JGJ 16-2008 Code for Electrical Design of Civil Buildings.

4.6.2.2灯光专业线槽绘制时,原则上应按线槽实际宽度按图纸比例绘制,线槽截面应采用空心闭合图形。

In principle, the special lighting trunking shall be drawn according to the actual width of trunking and the drawing, and the trunking section shall be a hollow closed figure.

4.6.2.3在进行对线槽的标注时,应能清楚地分辨出线槽的型号、规格、敷设方式。

When marking the trunking, the model, specification and laying method shall be clearly distinguished.

-可编辑修改-

4.6.3管线图

Piping plan

具体设计原则请参考《民用建筑电气设计规范》JGJ 16-2008第8章。《建筑照明设计标准》GB 50034-2004第7章。

For details, please refer to chapter 8 of JGJ 16-2008 Code for Electrical Design of Civil Buildings and chapter 7 of GB 50034-2004 Standard for Lighting Design of Buildings.

以下所述在设计时应特别注意:

Special attention shall be paid to the following during design:

4.6.3.1标明或注明设备的类别、编号、平面位置、安装高度、安装方式,管线、线槽走向、管线规格,敷设方式、引上引下、图例、数量、文字说明等。

Indicate or note equipment type, S/N, plan position, mounting height, mounting method, pipeline and trunking trend, pipeline specification, laying method, leading up/down, graphic symbols, quantity, explanatory note, etc.

4.6.3.2每一照明单相分支回路的电流不宜超过16A,所接光源数不宜超过25个;连接建筑组合灯具时,回路电流不宜超过25A,光源数不宜超过60个;连接高强度气体放电灯的单相分支回路的电流不应超过30A。

Current of each single-phase subcircuit for lighting shall not exceed 16A, and there shall be less than 25 illuminants; when connecting the combined lights, the loop current shall not exceed 25A, and there shall be less than 60 illuminants; current of the single-phase subcircuit connecting high capacity gas discharge lamp shall not exceed 30A.

4.6.3.3照明配电干线及分支线,应采用铜芯绝缘电线或电缆,分支线截面不应小于1.5mm2。

Trunk lines and branch lines for light distribution shall be copper core insulated conductor or cable; section of branch line shall not be smaller than 1.5mm2.

4.6.3.4观众厅及放映机房等处墙面及吊顶内的照明线路应采用阻燃型铜芯绝缘导线或铜芯绝缘电缆穿金属管或金属线槽敷设。

Illuminating lines inside the walls and suspended ceiling in audience halls and projector chambers shall adopt flame retardant copper core insulated conductor or copper core insulated cable wrapped with metal tube or metal raceway.

4.6.3.5插座不应和照明设备接在同一回路。

Sockets shall not be connected with lighting equipment in the same loop.

4.6.3.6原则上采用不同发光原理的光源的灯具不要接在同一回路上,特别是以气体放电灯为光源的灯具不要和其他类型光源的灯具接在同一回路上。

In principle, lighting fixtures using different illuminants shall not be connected in the same loop; in particular, lighting fixtures with gas discharge lamp as the illuminant shall not be connected with the lighting fixtures using other illuminants in the same loop.

4.6.3.7照明电气管线布线平面图上应注明其管线来自配电箱的编号和回路编号以便于审查是否与配电

-可编辑修改-

箱系统图的回路编号相对应,且是否回路连接的负荷总量与配电箱系统图上标明的相符。

The pipeline wiring diagram of lightings shall indicate the No. of switch box from which the pipeline is drawn and the No. of loop, so as to check whether it coincides with the No. of loop of the switch box system diagram, and whether the total load connected with the loop coincides with that on the switch box system diagram.

4.6.3.8图纸中管线的走向应考虑现场施工条件及后期检修维护的便利,并尽可能与实际的排管布线方向一致。

Trend of pipelines in the drawing shall consider the site operation conditions and provide convenience for future repair and maintenance, and shall be the same as the actual pipeline trend as much as possible.

4.6.3.9为抑制高次谐波对照明控制装置及其它系统设备的干扰,除应满足《民用建筑电气设计规范》JGJ 16-2008第22章第22.3节的规定外,还应满足以下要求:需要调光的回路应选用金属导管、槽敷设,并不宜于电声等电信线路平行敷设。当调光回路与电信线路平行敷设时,其间距应大于1米;当垂直交叉时,其间距应大于0.5米。

To restrain the interference of ultraharmonics on illumination control devices and other system equipments, except that the regulations of Section 22.3, Chapter 22 of JGJ 16-2008 Code for Electrical Design of Civil Buildings shall be met, shall conform to the following requirements: the loop that needs light control shall select metal conduit and trunking for lay-up, and parallel lay-up of electroacoustics etc. telecommunication lines is not suitable. When light-controlling loop are in parallel lay-up with telecommunication lines, the distance shall be more than 1m; when in squre crossing, the distance shall be more than 0.5m.

4.6.4机房、竖井布置平面图

Plane arrangement drawing of equipment room and vertical shaft

照明设备机房和竖井布置平面中的电气设备、管线布置应遵循以下原则:

The electric installation and pipeline layout in the plane arrangement drawing of lighting equipment room and vertical shaft shall conform to the following principles:

(1)机房布置图中应包括配电柜/控制箱平面位置布局、局部立面图,注明管线、线槽走向,写出文字说明等。

The equipment room arrangement drawing shall include the plane layout and partial elevation of the power distributing cabinet and controlling box, giving clear indication of the trend of pipelines and trunking, explanatory notes, and so on.

(2)平面图上的设备位置、数量、编号,缆线规格、管线与线槽走向应与立面图上的设备位置、数量、编号,缆线规格、管线与线槽走向相对应。

The equipment position, quantity, No., and cable specification, pipeline and trunking trend on the plan drawing shall coincide with those on the elevation drawing.

(3)机房内的控制箱、柜等设备应注明尺寸,间距、并标明设备型号。

The controlling box and cabinet inside the equipment room shall be marked with the dimension, spacing and equipment type.

(4)机房布置图应注明机房空间内各设备安装位置、相互关系及安装工艺要求。

-可编辑修改-

The equipment room arrangement drawing shall give clear indication of the installation position, correlations between equipment, and technical requirements of installation of the equipment inside the equipment room.

(5)控制信号的强、弱电井布置图应具体反映强、弱电井内所有线槽、管路、设备箱等的位置、尺寸The arrangement drawing of strong and weak electricity well of control signals shall specifically reflect the position and dimension of all trunkings, pipelines and equipment boxes inside the strong and weak electricity well.

4.7安装大样图

Detail drawing of installation

安装大样图是明确灯具安装与建筑关系的说明图。

The detail drawing of installation is the explanatory drawing which defines the relationship between lighting installation and the structure.

当采用一些特殊形式或定制灯具时采用安装大样图来介绍这些灯具的安装方法。安装大样图中应包括设备安装固定方式、设备尺寸、材料名称、型号、规格、在单张大样图中的设计使用数量、开孔/留洞尺寸、接线端子图、接线颜色、接线序号、线缆型号、线缆规格、回路编号、文字说明等。

When special or customized lightings are used, the detail drawing of installation shall be used to introduce the installation method of these lightings. The detail drawing of installation shall include the equipment installation and mounting form, equipment dimension, material name, model and specification, designed use quantity in each detail drawing, opening/hole dimension, connecting terminal drawing, color and serial number of connection, cable model, cable specification, loop No. and explanatory notes.

-可编辑修改-

Sound reinforcement

扩声专业施工图设计深度标准及技术深度文件的标准扩声部分现规定如下:

The design depth of sound reinforcement working drawing and the standard sound reinforcement part in the technical scope documents are specified as follows:

一、提供各区域(包括排队区、预演区、主演区)扩声系统形式:使用单声道、立体声或者环绕声扩声。

I. Provide the form of sound-reinforcement system in each area (including the queue area, rehearse area and performance area): use single track, stereophonic sound or surround sound for sound reinforcement.

二、提交各区域(包括排队区、预演区、主演区)扩声系统的直达声声压级(Direct

SPL)、总声压级(Total SPL)。

II. Provide sound pressure level of direct sound (Direct SPL), total sound pressure lever (Total SPL) in each area (including the queue area, rehearse area and performance area).

三、提交扩声系统中所采用设备的说明书。

III. Provide instructions of the equipment used in the sound-reinforcement

-可编辑修改-

-可编辑修改- 四、提供扩声系统设备资料表。(用EXCEL 表格做出,格式如下,第一行内容为示范)。

IV. Provide the equipment data sheet of the sound-reinforcement system (in EXCEL, with the format as follows; contents in the first row are filled in as an example).

地Austr

五、对施工图纸的要求如下:

V. Requirements for construction drawings are as follows:

用于设计方案阶段的一套完整的图纸至少应包括封面、图纸目录、工程设计说明及图例、设备材料清单、系统图、平面图。

A complete set of drawings used in the design stage shall at least include the cover, drawing content, engineering design instructions and graphic symbols, list of equipment and materials, system diagram, and plan view.

用于施工阶段的图纸至少应包括封面、图纸目录、工程设计说明及图例、设备材料清单、系统图、平面图及设备的安装大样图。

A complete set of drawings used in the construction stage shall at least include the cover, drawing content, engineering design instructions and graphic symbols, list of equipment and materials, system diagram, plan view, and the detail drawing of equipment installation.

-可编辑修改-

扩声专业图纸范围如下:

Scope of drawings for sound reinforcement is as follows:

必须包括封面、图纸目录、工程设计说明及图例、设备材料清单、系统图、平面图、机房设备布置图、安装大样图。安装详图根据项目情况,应由设计师根据项目的可实现性和各专业分项工程的配合决定绘图深度,设计出满足项目需求的可实施的拓展性安装详图。

It shall include the cover, drawing content, engineering design instructions and graphic symbols, list of equipment and materials, system diagram, plan view, equipment layout in equipment room, and detail drawing of equipment installation. Feasible and extendable detail drawing for equipment installation shall be designed according to the project situations by the designer who shall decide the depth of drawing according to the project feasibility and coordination between all subdivisional works of each discipline to satisfy the project requirements.

5.1封面Cover

封面应包含项目名称、图纸性质(初步设计、施工图、竣工图等)、公司名称、日期。

The cover shall bear the project name, drawing property (preliminary design, construction drawing, as built drawing, etc.), company name, and date.

5.2图纸目录Drawing content

-可编辑修改-

图纸目录应包含以下内容:项目名称、项目编号、设计公司名称、专业、图纸名称、图纸编号、图幅、出图日期、制图人及审核人等内容。

The drawing content shall include the following: project name, project ID, name of design corporation, discipline, drawing name, drawing number, sheet, drawing finishing date, the person who draws, and the auditor.

5.3工程设计说明及图例Engineering design instructions and graphic symbols 设计总说明须包括但不限于:工程概况、设计依据、各子系统施工内容、施工要求和注意事项、设计特殊要求和施工配合要点、设计范围内智能化系统与相关专业的技术接口要求、图例符号等。

General engineering design instructions shall include, without limitation to: project profile, design basis, construction contents of each sub system, construction requirements and notices, special design requirements and key points in construction cooperation, technical interface requirements for the intelligent system and relevant disciplines within the scope of design, graphic symbols, and so on.

5.4设备材料清单List of equipment and materials

在材料表中的图形符号图例应采用国标,其次是部标、行标。未予规定的自拟图形图例,应在图例中标出且加以说明。当使用国标图形图例,又给予不同含义时也应加以说明,一套图纸的图例符号应前后一致。Graphic symbols in the list of materials shall adopt those in national standards,

-可编辑修改-

followed by ministerial standards and industry standards. Self made graphic drawings not specified shall be marked in the graphic symbols with explanations. Explanations shall also be given when graphic symbols in national standards are given different meanings. The graphic symbols used in one set of drawings shall be in consistence with each other.

设备材料清单,按系统开列组成系统主要设备和材料,应标明设备名称、规格型号、主要技术指标、品牌(产地)、数量。非标设备、材料应备注说明技术要求。

The list of equipment and materials shall list the major equipment and materials constituting the system, with an indication of the equipment name, specification and model, key technical indicators, brand (origin), and quantity. Technical requirements for nonstandard equipment and materials shall be marked.

各个平面图、设备房图应随附图例并标注数量。包括电脑、软件、编程工具、机柜、电源、变压器等设备材料都必须在图纸上或设备材料中体现出来,并且注明型号、规格、数量总和。

All plan views and equipment room drawings shall be attached with graphic symbols and quantity. Equipment and materials including computers, software, programming tools, cabinets, power supply and transformers shall be indicated in the drawings or list of equipment materials, with clear indication of the model, specification and total quantity.

-可编辑修改-

5.5系统图System diagram

系统图应将弱电流、小功率设备(如话筒、音源、音频处理器)与强电流、大功率设备(如功率放大器、有源音箱、无源音箱)用不同的颜色区分标示、注释。

On the system diagram, light-current and small-power equipment (such as microphones, sources of sound and audio processors) and strong-current and heavy duty equipment (such as power amplifier, active loudspeaker and passive loudspeaker) shall be distinguished with marks and notes in different colors.

系统图中要求体现所有音频设备的输入、输出接口形式,以便统计接口规格与数量。

The system diagram is requested to show the input and output interface form of all audio equipment, so as to be convenient to make statistics about the interface specification and quantity.

系统图中涉及到强电流、大功率设备,需标注有效输出功率。

The system diagram shall mark the useful output of strong-current heavy duty equipment.

5.6平面图Plan view

5.6.1总体要求General requirements

参考我国扩声行业标准《电气装置安装工程电缆线路施工及验收规范》(GB50168-92)、《电声系统设备互联的优选电气配接值》(SJZ112-86)中

-可编辑修改-

对于扩声及电气方面的要求。

Please refer to the requirements for sound reinforcement and electricity specified in the sound reinforcement industry standard Code for Construction and Acceptance of Cable Levels Electric Equipment Installation Engineering (GB50168-92) and Prefered Electrical Matching Values for Interconnection of Electroacoustic Systems (SJZ112-86).

5.6.2线槽设计Trunking design

由强电、弱电、音频&控制竖井或控制机房引向用电负荷的电气线路,在回路众多的情况下应采用线槽布线。

The electric wiring drawn from vertical shaft for light-current and strong-current and audio & control shall adopt trunking when there are numerous loops.

5.6.3管线图Piping plan

具体设计原则请参考《电气装置安装工程施工及验收规范》(GBJ232-92)。For detailed design principles, please refer to Specifications for Construction and Acceptance of Electrical Apparatus Installation Work (GBJ232-92).

5.6.4机房、竖井布置平面图Plane arrangement drawing of equipment room and vertical shaft

扩声设备机房和竖井布置平面中的电气设备、管线布置应遵循以下原则:The electric installation and pipeline layout in the plane arrangement drawing of sound reinforcement facility room and vertical shaft shall conform to the

-可编辑修改-

following principles:

(1)机房布置图中应包括配电柜/控制箱平面位置布局、局部立面图,注明管线、线槽走向,写出文字说明等。

The equipment room arrangement drawing shall include the plane layout and partial elevation of the power distributing cabinet and controlling box, giving clear indication of the trend of pipelines and trunking, explanatory notes, and so on.

(2)平面图上的设备位置、数量、编号,缆线规格、管线与线槽走向应与立面图上的设备位置、数量、编号,缆线规格、管线与线槽走向相对应。The equipment position, quantity, No., and cable specification, pipeline and trunking trend on the plan drawing shall coincide with those on the elevation drawing.

(3)机房内的控制箱、柜等设备应注明尺寸,间距、并标明设备型号。The controlling box and cabinet inside the equipment room shall be marked with the dimension, spacing and equipment type.

(4)机房布置图应注明机房空间内各设备安装位置、相互关系及安装工艺要求。

The equpiment room arrangement drawing shall give clear indication of the installation position, correlations between equipment, and technical requirements of installation of the equipment inside the equipment room.

-可编辑修改-

施工图设计深度规定

施工图设计深度规定 总平面设计 一、在施工图设计中,总平面专业设计,包括图纸目录、设计说明、设计图纸。 二、设计说明 一般工程分别写在有关的图纸上,列出主要技术经济指标表,注明设计依据、尺寸单位、比例、坐标及高程系统。 三、总平面图 1、保留的地形和地物。 2、测量坐标网、坐标值。 3、场地四界测量坐标(或定位尺寸),道路红线和建筑红线或用地红线的位 置。 4、场地四邻原有及规划道路的位置,以及主要建筑物和构筑物的位置、名 称、层数。 5、建筑物、构筑物(人防工程、地下车库、油库、水池等隐蔽工程以虚线 表示)的名称或编号、层数、定位(坐标或相互关系尺寸)。 6、广场、停车场、运动场、道路、无障碍设施、排水沟、挡土墙、护墙的 定位(坐标或相互关系)尺寸。 7、指北针或风玫瑰图。 8.、总平面图应画图例。 四、竖向布置图 1、场地测量坐标网,坐标值。 2、场地四邻的道路、水面、地面的关键性标高。

3、建筑物、构筑物名称,室内外地面设计标高。 4、广场、停车场、运动场地的设计标高。 5、道路、排水沟的起点、变坡点、转折点和终点的设计标高,纵坡度、纵 坡距、关键性坐标,道路表明双面坡或单面坡。 6、挡土墙、护坡或土坎顶部和底部的主要设计标高及护坡坡度。 7、指北针或风玫瑰图。 8、地面坡度用箭头表示。 五、详图:道路横断面、路面结构、挡土墙、护坡、排水沟、广场、运动场地、 停车场等。(以上项目如另外委托作环境设计,本设计可不画。) 六、总图制图规定 1、计量单位: (1)总图中的坐标、标高、距离宜以米为单位,并应至少取至小数点后两位,不足时以“0”补齐,详图宜以毫米为单位。 (2)建筑物、构筑物、道路的方位角,宜注写到“秒”。 (3)道路的纵坡度、场地平整坡度、排水沟底纵坡度宜以百分计,并应取至小数点后一位,不足时以“0”补齐。 2、坐标注法: (1)总图应按上北下南方向绘制,可向左或右偏移,但不宜超过45°,x为南北方向轴向,x的增量在x轴线上; y为东西方向轴向,y的增量在y轴线上; (2)坐标网格应以细实线表示,测量坐标网应画成交叉十字线,坐标代号宜用“x、y”表示; (3)表示建筑物、构筑物位置的坐标,宜注其三个角的坐标,如建筑物、构筑物与坐标轴线平行,可注其对角坐标。 3、标高注法: (1)应以含有±0.00标高的平面和屋面标高平面分别作二张总平面图。 (2)总图中标注的标高应为绝对标高,如标注相对标高,则应注明相对

施工图设计制图要求

建筑设计作图要求 (参照《房屋建筑制图统一标准GB/T50001-2010》、《建筑制图标准GB/T50104-1010》、《总图制图标准GB/T50103-2010》、《建筑工程设计之件编制深度规定2016年11月》)。 一、一个工程设计中的图纸一般不宜多于三种幅面(不含A4)。一.dwg 二、图线不得与文字、数字或符号重叠、混淆。二.dwg 三、文字的高度:(在1:100比例下): 1.房间名称:5.0P 2.局部引出线的注明之字 3.5P 3.门窗编号,楼梯“上、下”文字分别用“天正”自带的字高──3.5P和 3.0P。 4.图号标注:7.0P 四、绘图的比例: 1.平、立、剖一般采用:1:100 ,1:150, 1:200, 1:300(最小)。先排图、设置标注的高度 2.总图: 1:500, 1:1000, 1:2000 。 3.大样图:楼梯、电梯、房间放大图──1:50 (墙身大样若细部不多,可用1:50) 复杂立面放大图、墙身大样、节点构造──1:20(局部构件可用1:10, 1:5)。 1:25不是房屋建筑中的常见比例,但是,也是符合建筑制图标准的。 五、符号: 1.剖切符号宜用阿拉伯数字,一般是剖切位置线为上下时往左看,剖切位 置线为左右时往上看。五-1.dwg 2.索引符号时的剖切索引一定要清晰“粗短线为剖切位置线,引出线所在 一侧为剖视方向。详《房屋建筑制图统一标准GB/T50001-2010》第7.2.2

条五-2.dwg 3.各引出线尽量平行,不交叉。五-3.dwg 六、轴线定位: 1.不能采用“I.0.Z”作轴号。 2.复杂的平面可以分区编号,用“分区号──该分区编号”形式。六-2.dwg 七、建筑外部边墙宜轴线平外墙外边,内部注墙中,(布置内部柱子时应注意 避免内走廊有柱时净空不够的情况,或要求梁边平墙的某一侧时要特意告知结构工种) 。六-2.dwg 八、尺寸标注: 1.方案及初步设计注两道尺寸,所有两道尺寸:端点应平齐。若突出最外 侧轴线尺寸标注,侧根据图形的标注层级,对应在相应的第几道尺寸 向上标注。八-1.dwg 2.尺寸界线不能与建筑图形接触。八-1.dwg 3.尺寸数字不能与图形重叠及互相遮挡,不够位置注写可错位。 4.总平面图室外地坪应用黑三角──“▼”, 且注室内标高时为 “151.00(±0.00)”。即室内±0.00标高相当于绝对标高151.00。详 《总图制图标准GB/T50103-2010》第13页续表3.0.1 5.建议图形外部和内部可采用不同字高的标注,以避免与内部过于密集的 图形重叠。八-5.dwg 6.建议内部标注时,一串的标注一标到底,方便查看内部各部位的尺寸关 系。八-5.dwg -----补充图层的线性宽度等所内统一要求的章节 九、约定的数据: 1.排水坡度: 1)阳台、露台、淋浴间为2%,卫生间、铁艺栏杆空调位地面为1%。( 绘 制有地面排水要求的平面图时,应画出排水箭头)。九-1(1).dwg 2)倒置式平屋面为3%,正置式平屋面为2%。结构找坡为3%。屋面排水

景观设计深度 施工图设计文件深度要求

1、目的 保证设计质量和设计深度,结合本公司专业的设置情况,对园林与建筑工程设计文件编制深度的规定作适当补充和调整,特制定本规定。2、范围 适用于公司开发项目的景观施工图设计。 3、职责 吉林公司设计部负责本公司开发项目的景观施工图设计。 4、园林专业施工图设计文件编制深度规定 4.1封面 图幅与2#图纸同。 4.2 设计总说明 (a)该项目工程量概述; (b)对照总体规划说明书提出全面技术分析和技术处理措施; (c)各专业设计配合关系中关键部位的控制要点; (d)材料、设备、造型、色彩选择的原则; (e)各分项工程需详加说明的分列于各分项图纸上; 4.3 总平面图 (a)总平面图应套在原地形图上绘制,准确表明道路、硬地、水体、山石、建筑、绿地、园灯、陈设的平面形状、位置、相 互关系; (b)有准确的放样依据,关键定位点的地形坐标值,必要时可用方格网表示具体定点尺寸,方格网为2m X 2m—10mX10m, 方格网应与测量地形图的坐标格在方向上一致。以建筑为主 的庭院空间,方格网应与建筑主要轴线在方向上一致; (c)庭院或小型绿地要详细标出放样尺寸 (d)建筑设施名称,面积列表。 (e)指北针,详图索引,图纸比例1/200~1/500,庭院1/100,根据具体项目情况选择。 (f)根据项目具体情况,上述内容亦可分别出图。 4.4 竖向设计 (a)绘出原有地形地貌及现状标高; (b)准确绘出园路、硬地、水体、山石、建筑、绿地的平面形状、位置、相互关系; (c)用等高线绘出地形改造后的起伏情况,注出各高程点的原有及设

计标高; (d)标出建筑物室内外设计标高; (e)标出构筑物标高,挡土墙上下标高,水体驳岸的岸顶标高,常水位标高,池底标高; (f)硬地标出中心及四周标高; (g)道路起止点、交叉点、变坡点、转弯点标高,纵向每10-30m 标出标高; (h)用箭头标出道路、硬地、绿地的排水坡向,用暗管排水时,标明雨水口位置; (i)土石方挖填范围,注出原地面标高,设计标高,填挖高度,填挖分界线,土方量调配平衡表; (j)指北针、图纸比例与总平面图同; (k)重点地段,地形变化复杂地段增加剖面图说明,标出关键部位标高。 4.5 道路广场设计 (a)硬地外轮廓,道路宽度线型控制尺寸均在总平面图上标明,如总图比例较小,每块硬地外轮廓可另行放大画出,注明总尺 寸及细部尺寸; (b)道路、硬地标高在竖向设计平面图上标明,考虑无障碍设计; (c)横剖面设计,标明道路,硬地从表层至基础层的具体做法; (d)局部设计,标明园路、硬地面层形式,具体尺寸; (e)标明不同宽度,不同形式路面交接点处理,道路与硬地交接点处理; (f)标明伸缩缝做法; (g)列出园路、硬地工程量总表; (h)作法说明,例如图中未详需加以说明的要点,如铺装缝允许尺寸,铺装地与道牙的衔接处理,规则形铺装地折点、转弯 处做法。 4.6 绿化种植设计 (a)图纸比例一般为1/200,简单工程1/500,庭院及配植精细的1/100; (b)图纸规格按国标CBJ1-86执行,图幅过大的,可分张分块绘制,图幅分块应以完整绿地为单位,并绘出周围的园路建筑等设 施,以便于衔接,并方便施工;

暖通施工图设计深度要求

暖通施工图设计深度要求 标签:空调系统风路转换采暖热负荷空调制冷系统 在施工图设计阶段,采暖通风与空气调节专业设计文件应包括图纸目录、设计与施工说明、设备表、设计图纸、计算书。图纸目录应先列新绘图纸,后列选用的标准图或重复利用图。 ⒈设计说明应介绍设计概况和暖通空调室内外设计参数、热源、冷源情况;热媒、冷媒参数;采暖热负荷、耗热量指标及系统总阻力;空调冷热负荷、冷热量指标,系统形式和控制方法,必要时,需说明系统的使用操作要点,例如空调系统季节转换,防排烟系统的风路转换等。 ⒉施工说明应说明设计中所要求使用的材料和附件;系统工作压力和试压技术要求;施工安装要求及施工注意事项。采暖系统还应说明散热器型号。 ⒊图例一般使用通用图例,并将图例放置在设计说明页或首页中,也可单独成图。 ⒋设备表施工图阶段,型号、规格栏应注明详细的技术数据。 当设计单位只设计部分工程内容,或由多家设计单位共同承担设计任务时,应明确交待配合的设计分工范围。 设备平面图建筑平面图应绘出建筑轮廓、主要轴线号、轴线尺寸、室内外地面标高、房间名称。在底层平面图上绘出指北针。通风、空调平面图,一般采用双线绘风管,单线绘空调冷热水、凝结水管道的画法。标注风管尺寸、标高以及末端设备或风口尺寸时(圆形风管注管径、矩形风管注宽×高),应标注水管管径及标高、管道坡度和坡向,以及各种设备及风口安装的定位尺寸和编号。还应标出消声器、调节阀、防火阀等各种部件位置及风管、风口的气流方向。当建筑装修方案未最终确定时,风管和水管可先画出单线走向示意图,并注明房间送、回风量及以风机盘管数量、规格。在建筑装修确定后,一般按规定要求绘制平面图。 剖面图当风管或管道与设备连接交叉复杂,光靠平面图表示不清时,应绘制剖面图或局部剖面。在剖面图中绘出的风管、水管、风口等设备,应表示清楚管道与设备、管道与建筑梁、板、柱、墙以及地面的尺寸关系。还应表示清楚风管、风口、水管等尺寸和标高,气流方向及详图索引编号等。 通风、空调、制冷机房平面图机房图应根据需要增大比例,绘出通风、空调、制冷设备(如冷水机组、新风机组、空调器、冷热水泵、冷却水泵、通风机、消声器、水箱等)的轮廓位置及编号,注明设备和基础距离墙或轴线的尺寸。绘出连接设备的风管、水管位置及走向;注明尺寸、管径、标高。标注机房内所有设备、管道附件(各种仪表、阀门、柔性短管、过

施工图设计规范模板

施工图设计规范

前言 在室内设计工作的过程中,施工图的绘制是表示设计者设计意图的重要手段之一,是设计者与各相关专业之间交流的标准化语言,是控制施工现场能否充分正确理解消化并实施设计理念的一个重要环节,是衡量一个设计团队的设计管理水平是否专业的一个重要标准。专业化、标准化的施工图操作流程规范不但能够帮助设计者深化设计内容,完善构思想法,同时面对大型公共设计项目及大量的设计定单行之有效的施工图规范与管理亦可帮助设计团队在保持设计品质及提高工作效率方面起到积极有效的作用。 本书是以制图标准为基础,结合具体工程实例书写而成。书中内容更贴近于实际工程,对于图样画法的基础与理论读者可参见相关专业书籍。书中除涉及施工图构成的一些基本元素外,还对施工图的前期规划,绘制过程中的深化设计,以及施工图纸如何与施工现场衔接,和后期竣工图文件归档均作了一定的描述。另外书中还针对计算机绘图方式与制图标准的结合作了具体的描述,特别是模型空间与布局空间相互转换的绘图方法不但方便平面图的修改,提高工作效率,还能够在保证图纸的一致性以及图层管理,比例输出等方面起到重要作用。书中所附光盘内图纸均含标准图层。符号在布局空间内按1:1比例绘制,所制成的标准图按图幅规格在布局空间内可直接调用。图例也分别在模型空间与布局空间内按比例绘制,均可直接调用。写此书的目的一方面的对于以往学习工作过程中积累的关于室内设计施工图方面的知识经验作一次较详尽的梳理,另一方面希望起到抛砖引玉的作用,把自己一些浅薄的

认知以书面的形式与同道做一个交流,希望大家批评指正,以期引起专家同道对室内设计专业制图更深层次的关注。 目录 一、图纸幅面规格 二、符号的设置 三、材质图例的设置 四、尺寸标注与文字标注的设置 五、线型与笔宽的设置 六、电脑图层的设置 七、比例的设置 八、图面构图的设置 九、施工图编制的顺序 十、图表 十一、平、立、剖面图及节点大样图的绘制及相关标准 十二、施工图在各设计阶段应注意的事项 十三、施工图与现场深化设计 十四、施工图的归档与分类 十五、关于布局空间与模型空间在实际绘图中的应用 十六、施工图工程实例 宾馆类:天骄宾馆 办公空间:商务部会议室

项目施工图设计规范标准

前言 在室设计工作的过程中,施工图的绘制是表达设计者设计意图的重要手段之一,是设计者与各相关专业之间交流的标准化语言,是控制施工现场能否充分正确理解消化并实施设计理念的一个重要环节,是衡量一个设计团队的设计管理水平是否专业的一个重要标准。专业化、标准化的施工图操作流程规不但可以帮助设计者深化设计容,完善构思想法,同时面对大型公共设计项目及大量的设计定单行之有效的施工图规与管理亦可帮助设计团队在保持设计品质及提高工作效率方面起到积极有效的作用。 本书是以制图标准为基础,结合具体工程实例书写而成。书中容更贴近于实际工程,对于图样画法的基础与理论读者可参见相关专业书籍。书中除涉及施工图构成的一些基本元素外,还对施工图的前期规划,绘制过程中的深化设计,以及施工图纸如何与施工现场衔接,和后期竣工图文件归档均作了一定的描述。此外书中还针对计算机绘图方式与制图标准的结合作了具体的描述,特别是模型空间与布局空间相互转换的绘图方法不但方便平面图的修改,提高工作效率,还可以在保证图纸的一致性以及图层管理,比例输出等方面起到重要作用。书中所附光盘图纸均含标准图层。符号在布局空间按1:1比例绘制,所制成的标准图按图幅规格在布局空间可直接调用。图例也分别在模型空间与布局空间按比例绘制,均可直接调用。写此书的目的一方面的对于以往学习工作过程中积累的关于室设计施工图方面的知识经验作一次较详尽的梳理,另一方面希望起到抛砖引玉的作用,把自己一些浅薄的认知以书面的形式与同道做一个交流,希望大家批评指正,以期引起专家同道对室设计专业制图更深层次的关注。

目录 一、图纸幅面规格 二、符号的设置 三、材质图例的设置 四、尺寸标注与文字标注的设置 五、线型与笔宽的设置 六、电脑图层的设置 七、比例的设置 八、图面构图的设置 九、施工图编制的顺序 十、图表 十一、平、立、剖面图及节点大样图的绘制及相关标准十二、施工图在各设计阶段应注意的事项 十三、施工图与现场深化设计 十四、施工图的归档与分类 十五、关于布局空间与模型空间在实际绘图中的应用十六、施工图工程实例 宾馆类:天骄宾馆 办公空间:商务部会议室 文化空间:哈工程大学大学生活动中心 住宅样板间:某住宅项目

规范对初步设计图纸深度要求

拟采用 1、相关批复。成果文件是否符合有关主管部门对本工程批示的规划许可技术条件(用地性质、道路红线、建筑控制线、城市绿线、用地红线、安全间距、容积率、建筑密度、绿化率等),以及对总平面布局、周围环境、空间处理、交通组织、环境保护、文物保护、分期建设等方面的特殊要求; 2、总平面图。设计是否结合地域特点、自然环境、气候、交通以及环境保护等要求因地制宜,远近期统筹兼顾、预留发展用地,充分考虑拟保留的地形、地物合理分区和布置工艺区、建构筑物及场地道路等; 3、竖向设计。(1)竖向设计依据(如城市道路和管道的标高、地形、排水、土方平衡等情况);(2)竖向设计是否合理利用地形,综合考虑功能、安全、景观、排水等要求进行竖向布置;(3)防灾措施是否合理,如针对洪水、滑坡、潮汐及特殊工程地质(湿暗性或膨胀性土)等的技术措施。 4、文通组织。(1)人流和车流的组织、道路、出入口、场地布置等是否合理;(2)道路主要的设计技术条件(路面宽度、路面类型、最大及最小纵坡等)。 5、输送管道 (1)设计输送能力是否合适;管道材质、管径壁厚、设计压力是否合理;路由是否最优,合理减少管道长度; (2)交通条件,是否结合实际情况设置了必要的维检修

(3)大中型河流、公路、铁路的穿跨越位置是否满足当地主管部门和规划部门的要求; (4)大开挖穿越是否有无稳管和水工保护措施; (5)定向钻穿越地层是否适宜,埋深是否符合规范要求;穿越曲线否合理,出入土点是否有合适的施工场地; (6)山体隧道的洞口位置、衬砌型式选择是否合理,地质条件是否适合; (7)管道敷设是否与周围环境相协调; 6、工艺安装 7、建筑结构。(1)建筑物使用功能、功能分区、平面布局等;(2)是否达到规定的设计深度要求;(3)是否符合《工程建设标准强制性条文》和其他有关工程建设强制性标准; (4)地基基础和结构设计等是否安全;(5)建筑防火设计;(6)外立面、屋面及内部装修风格。 1、是否符合《工程建设标准强制性条文》和其他有关工程建设强制性标准。 2、地基基础和结构设计等是否安全。 3、是否符合公众利益。 4、施工图是否达到规定的设计深度要求。 5、是否符合作为设计依据的政府有关部门的批准文件

住宅小区外网施工图设计要求

住宅小区 室外综合管线专业设计任务指导书 1 目标 为统一我公司室外综合管线的设计,加强设计质量控制,在满足国家设计规范和济南地方相关设计规程、标准的前提下,规范设计任务书中的技术要求,在提高工作效率的同时逐步实行工程管理标准化。 2 设计总则 2.1 应按最新版国家设计规范、施工规范及济南地方相关设计规程及标准执行。 2.1 对于设计规范中以黑体字标注的强制性条文,必须严格执行,不得有任何违反。 2.3 应执行建设部《建筑工程设计文件编制深度的规定》(2003版)。 2.4 设计应符合山东省工程建设标准图集。 3 相关设计规范、规程及标准 3.1 给排水专业 《建筑给排水设计规范》50015-2003(2009年版) 《建筑中水设计规范》50336-2002 《室外给水设计规范》50013-2006 《室外排水设计规范》50014-2006 《给排水制图标准》50106-2001 《城市居民生活用水量标准》50331-2002 《建筑设计防火规范》50016-2006

《高层民用建筑设计防火规范》50054-95(2005年版)《汽车库、修车库、停车场设计防火规范》50067-97 《自动喷水灭火系统设计规范》50084-2001 《建筑灭火器配置设计规范》50140-2005 《建筑给水排水及采暖工程施工质量验收规范》50242-2002 《自动喷水灭火系统施工及验收规范》50261-2005 3.2 暖通专业 《采暖通风与空气调节设计规范》50019-2003 《民用建筑热工设计规范》50176-93 《民用建筑节能设计标准》(采暖居住建筑部分)26-95 《暖通空调制图标准》50114-2001 《建筑设计防火规范》50016-2006 《高层民用建筑设计防火规范》50054-95(2005年版)《汽车库、修车库、停车场设计防火规范》50067-97 《供热计量技术规程》173-2009 《地面辐射供暖技术规程》142-2004 《直埋式预制保温管道工程设计技术规程》9-94 《城镇燃气设计规范》50028-2006 《建筑给水排水及采暖工程施工质量验收规范》50242-2002 《直埋式预制保温管道工程施工及验收规范》11-94 《山东省居住建筑节能设计标准》14-037-2012 《低温热水地板辐射供热技术规程》1414-2002 3.3 电气专业 《民用建筑电气设计规范》16-2008

施工图设计规范要求

施工图设计规范 1.建筑工程施工质量验收统一标准(GB50300—2001) 2.建筑装饰装修工程质量验收标准(GB50201—2001) 3.住宅装饰装修工程施工规范(GB50327—2001) 4.建筑地面工程质量验收规范(GB50209—2002) 5.钢结构工程施工质量验收规范(GB50205—2001) 6.木结构工程施工质量验收规范(GB50206—2002) 7.地下工程防水技术规范(GB50108—2002) 8.地下防水工程施工质量验收规范(GB50206—2002) 9.建筑工程给排水及采暖工程施工质量验收规范(GB50242—2002) 10.建筑电气工程施工质量验收规范(GB50303—2002) 11.金属与石材幕墙工程技术规范(JGJ133—2001) 12.建筑设计防火规范(GB50016—2006) 13.高层民用建筑设计防火规范(GB50045—95 2005年版) 14.建筑内部装修设计防火规范(GB50222—95 2001年修订版) 15.建筑节能工程施工验收规范(GB50401—2007) 16.工程建设施工企业质量管理规范(GB/T50430—2007) 17.建筑内部装修设计防火规范(GB50222) 18.建筑材料放射性核素限量(GB6566—2001) 19.人造板及其制品中甲醛释放限量(GB18580—2001) 20.溶剂型木器涂料中有害物质限量(GB18581—2001) 21.内墙涂料中有害物质限量(GB18582—2001)

22.胶黏剂中有害物质限量(GB18583—2001) 23.木家具中有害物质限量(GB18584—2001) 24.壁纸中有害物质限量(GB18585—2001) 25.地毯、地毯衬垫及地毯胶黏剂有害物质释放限量(GB18587—2001) 26.聚氯乙烯卷材地板中有害物质限量(GB18586) 27.混凝土外加剂中释放氨的限量(GB18588) 28.室内用水性阻燃剂、防水剂、防腐剂有害物质限量(GB50325)

施工图设计规范

园林景观制图规范 一、总则 1、工作目标 1.1规范化--有效提高设计的工作质量; 1.2标准化--提高设计的工作效率; 1.3网络化--便于网络上规范化管理和成果的共享。 2、工作范围 本标准是依据“建筑CAD制图的统一规则”、“总图制图标准”,适用于景观工程及相关领域中的CAD制图。 3、工作风格 本标准为形成公司CAD绘图表达的风格的统一。CAD制图的表达应清晰、完整、统一。 二、制图 1、制图规范 工程制图严格遵照国家有关建筑制图规范制图,要求所有图面的表达方式均保持一致。 2、图纸目录 各个专业图纸目录参照下列顺序编制: 封面 图纸目录 景观专业:景观设计说明;总图;竖向图;放线图;索引图;分区图;节点详图;铺装详图。 电气专业:电气设计说明;主要设备材料表;平面图;详图;系统图;控制线路图。大型工程应按强电、弱电、火灾报警及其智能系统分别设置目录。 给排水专业:给排水设计说明;总图;平面图(自下而上);详图;给水、消防、排水、雨水系统图。 绿化专业:绿化设计说明;苗木材料表;总图;乔木种植图;灌木种植图;地被种植图; 3、图纸深度 工程图纸除应达到国家规范规定深度外,尚须满足业主提供例图深度及特殊要求。 4、图纸字体 除投标及其特殊情况外,均应采取Windows字体文件,尽量不使用TureType字体,以加快图形的显示,缩小图形文件。同一图形文件内字型数目不要超过四种。 5、图纸版本及修改标记

5.1图纸版本 5.1.1施工图版本号 第一次出图版本号为0 第二次修改图版本号为1 第三次修改图版本号为2 5.1.2方案图或报批图等非施工用图版本号 第一次图版本号为A 第二次图版本号为B 第三次图版本号为C 5.1.3档案号: 档案编号为:年+ 月+室+第几套施工图 例: 5.2图面修改标记 图纸修改可以以版本号区分,每次修改必须在修改处做出标记,并注明版本号。 简单或单一修改尽量使用变更通知单。 6、图纸幅面 6.1图纸图幅采用A0、A1、A2、A3四种标准,以A1、A2图纸为主。 图纸尺寸规格表2 图纸种类图纸宽度(mm)图纸高度(mm) 备注 A0 1189 841 A1 841 594 A2 594 420 A3 420 297 A4 297 210 (主要用于目录、变更、修改等)6.2一个专业所用的图纸,不宜多于两种幅面(目录及表格所用A4幅面除外)。 6.3图纸比例 常用比例1:1,1:2;1:5,1:10,1:20,1:50,1:100,1:200,1:500,1:1000 可用比例1:3,1:15,1:25;1:30,1:150,1:250,1:300,1:1500 7、图层及文件交换格式 见CAD图层

室内施工图深度要求

室内设计施工图深度要求 为规范各设计公司对于施工图纸的绘图深度,确保施工单位在现场能够按图施工,避免因为施工图纸表达深度不确切,而出现的如:施工进度缓慢、施工任务不明确、频繁现场沟通等不利于施工作业的问题出现(包含但不仅限于上述问题),特拟写此施工图深度要求。此深度要求,包含但不仅限于此列表之深度要求,各专业之间的相互配合须做到无缝衔接,具体工作可另以书面的形式表达相关工作内容,总体宗旨要求现场施工无设计障碍、无设备障碍、无沟通障碍等,确保施工现场顺利操作,项目保质、保量如期竣工。室内设计施工图须有完整的图纸结构及顺序,以完整、准确的表达设计思想为目的,包含但不仅限于下述表达:一:图纸封面 二:设计及施工说明 三:图例索引表 四:材质索引表 五:图纸目录 六:平面系统图 七:立面详图 八:细部节点剖面放大详图 九:门表详图 十:线条放大列表详图 上述列表之内容,为室内设计施工图必须表达之图纸结构及顺序,各专业之间相互配合所需之图纸,如:中央影视、背景音乐、整体厨房等,可另出具完整、准确的图纸,以确保施工现场之需要。现对室内设计施工图所需图纸结构及顺序做以下深度要求: 一:图纸封面须完整、准确的表达:项目名称、项目图纸所属阶段(扩初图及施工图)、设计公司名称、出图日期。 二:设计及施工说明须完整、准确的表达:设计的依据、设计图纸表达的尺寸单位、室内施工之地坪、天花、墙身的具体施工工艺(包含但不仅限于石材做法、瓷砖做法、木饰做法、油漆做法、防水做法、金属做法、玻璃做法等)、电气及给排水设计说明。 三:图例索引表须完整、准确的表达:施工图纸所引用图例的详细说明,包含但不仅限于制图图例(立面索引、剖面索引、放大索引、门窗编号、天花标高、材质标注、图名标识等)、剖面节点详图材质填充图例、术语缩写图例、灯具电气消防图例、强弱电插座图例、材质名称图例等。 四:材质索引表须完整、准确的表达:材质名称、材质名称图例、材质使用区域、材质尺寸、材质品牌及生产厂家等。 五:图纸目录须完整、准确的表达:图纸的序号、图纸的图号、图纸的名称、图纸的比例、图纸的图幅等。 六:平面系统图平面系统图包含但不仅限于下列图目:原始建筑平面图、原始建筑梁位图、平面家具布置图、墙体尺寸定位图、天花布置图、地坪布置图、天花尺寸图、灯具

初步设计图纸深度要求(修订)样本

中煤国际工程集团重庆设计研究院 民用建筑工程初步设计文件图纸深度规定 ( 修订版) 中煤国际工程集团重庆设计研究院 二○○九年十一月 初步设计图纸深度要求

一总平面 1、区域位置图( 根据需要绘制) 2、总平面图 1) 保留的地形和地物 2) 测量坐标网、坐标值, 场地范围的测量坐标( 或定位尺寸) , 道路红线、建筑红线或用地界线。 3) 场地四邻原有及规划道路的位置( 主要坐标或定位尺寸) 和主要建筑物及构筑物的位置、名称、层数、建筑间距。 4) 建筑物、构筑物的位置( 人防工程、地下车库、油库、贮水池、生化池等隐蔽工程用虚线表示) , 其中主要建筑物、构筑物应标注坐标( 或定位尺寸) 、名称( 或编号) 、层数; 总平面图中应准确表示建筑物外轮廓线。 5) 道路、广场的主要坐标( 或定位尺寸) , 停车场及停车位, 必要时加绘交通流线示意; 6) 绿化、景观及休闲设施的布置示意, 围墙、大门的布置图。 7) 指北针或风玫瑰图。 8) 主要技术经济指标表。 9) 说明栏内注写: 尺寸单位、比例、地形图的测绘单位、日期、坐标及高程系统名称( 如为场地建筑坐标网时, 应说明其测量坐标网的换算关系) , 补充图例及其它必要的说明等。 3、消防分析图 ( 1) 在已完成的总平面布置图上表示, 主要内容为消防车道的宽度、坡度、转弯半径、尽端车道的回车场( 高层为18m×18m小高层为15m×15m) , 消防扑救场地范围及坡度, 范围: 建筑底边至少有一个长边或周边长度的1/4且不小于一个长边的长度, 场地进深高层围18m, 小高层可15m, 此范围内必须设有直通室外的楼梯或直通楼梯间的出口, 场地坡度不大于5%。

《施工图出图标准》

施工图出图标准

A.精装修施工图设计: 一、设计范围与设计要求 1.设计范围与设计内容: 1.1区域范围: 1.2专业范围:包括所有精装区域的装修、水电(含智能 化、消防)、暖通机电设备、VI标识系统、灯光、软装配饰、 艺术摆件等专业的施工图设计或整合 1.3设计内容:包括装修以及涉及装修的相关专业的平、剖、立面图纸,大样图(放样图)、系统图、节点详图、物料册、材料样板、设计说明、图纸清单概算等; 2.设计要求: 2.1由装修专业负责协调、整合装修阶段所有专业的图纸设计工作,确保提交图纸的统 一性、完整性和协调性,避免出现不用专业间图纸矛盾或者同一专业内大样与平立面矛盾等问题; 2.2图纸深度必须达到一次到位即施工单位拿到图纸即可开始施工无需二次深化、优化; 2.3图纸及所选材料必须满足消防验收规范等国家强制性法规的要求,确保工程能够顺 利通过验收; 2.4满足施工过程及日后运营维护的低成本、节能、绿色、环保等现代化建设工程特点 的要求,充分考虑经营管理者使用维护的便利性和经济性 二、设计成果(要求设计方提供的设计成果) 01.图纸封面 深度要求:包括项目名称、图纸名称、编制单位、编制时间 02.图纸目录 深度要求:包括图纸编号、图纸名称、图纸张号、图幅

03.施工图设计说明(有关规范、材料和工艺的说明) 深度要求:有关设计依据、设计规范、主要施工做法的说明、施工过程中应注意的技术性说明文字等 04.建筑原始结构图(现场测量) 深度要求:标有详细、准确的现场测量的平面尺寸及标高,客观反映场地实际情况 05.平面布置图 深度要求:包括平面布局、家居布置、地面材质、地面高差;可将立面索引图合并在此图中,但不可索引任何剖面;尺寸标注在平面布置外围,需有建筑轴线尺寸、开间尺寸、进深尺寸、隔墙轴线尺寸及开间、进深的总尺寸 06.平面布置图中各立面索引图 深度要求:清晰反映立面与平面的方位、坐标、轴线关系,准确索引所有立面图纸编号07.砌筑定位图 深度要求:包括隔墙使用材料、隔墙厚度、隔墙的轴线尺寸;不同材料隔墙的做法详图索引;如建筑设计院已出隔墙定位图,在装饰设计无改动的情况下,以建筑设计院图纸为准 08.地面铺装(材质)图(含分隔尺寸) 深度要求:地面面层材料的名称、种类、规格尺寸、地面标高;活动家具及可移动的地毯需删除,注意房间中的固定衣柜、卫生间的洗手台、座便器下方地面及厨房的橱柜等地面是否铺地材,需与施工中地面面材的施工范围一致;地面做法的大样、地面拼花的大样、地面高差或不同材质衔接的细部节点等在此图上索引 09.天花布置图(包括灯具、风口、烟感、喷淋等机电的定位) 深度要求:包括天花造型、窗帘盒、灯具排布、使用材料、各部位标高;尺寸标注同平面布置图 010.天花开线图 深度要求:包括天花造型、窗帘盒及灯具相对尺寸、天花使用材料、各部位的标高;可将天花造型大样索引和天花剖面索引合并在此图中

施工图设计深度管理

第一条施工图的设计深度要求 施工图的设计深度应满足以下要求: 1、能根据设计文件编制施工图预算。 2、能根据设计文件安排材料、设备订货及非标准材料的加工。 3、能根据设计文件进行工程施工。 4、能根据设计文件进行工程验收。 第二条施工图设计说明的内容 1、设计依据及设计要求:应注明采用的设计规范、设计标准及其它设计依据。 2、设计范围:应说明红线范围内设计内容。 3、标高及单位:应说明图纸文件中采用的标注单位,坐标采用的为相对坐还是绝对坐标;如为相对坐标,须说明采用的依据。 4、材料选择及要求:应说明对各部分材料的材质要求及建议。包括:铺装材料、饰面材料、木材、钢材、防水排水材料及种植土等。 5、施工要求:强调需注意工种配合及对气候有要求的施工部分。 6、用地指标:应包含:总设计面积、绿地面积、道路面积、铺地面积等。 第三条总图专业设计深度 1、总图专业图纸应包括:景观总平面图、分区平面图、铺装与索引总图、竖向总图、放线总图等。 2、景观总平面图 (1)景观总平面图应包括的内容: A、标示用地红线。(用粗虚线表示) B、标示建筑物的编号,建筑物、构筑物、人防出入口、车库出入口、围墙等位置。(建筑物及构筑物在总平面图中采用轮廓线表示,采用粗实线) C、标示主道路、园路、广场、小品、绿化、停车场位置和名称。当有地下车库时,地下车库位置用中粗虚线表示出来。 D、标示指北针,图名及绘图比例。 E、以图例方式表示全园性设施。 (2)对于面积较大、内容较复杂的总平面图,通常需要分图绘制。分图原则是分割开的区域其放线、竖向等相对独立、完整。分图线向外扩1~5米为裁图线(外扩尺寸以完整表达为原则,但一个工程项目中应统一)。 3、铺装及索引总图 (1)铺装及索引总图应包括的内容 A、标示铺装分格示意。 B、标示道路、园路铺装的材质及颜色。

(完整版)施工图设计深度要求

施工图设计深度要求 4.1 一般要求 4.1 1 施工图设计文件。 1 合同要求所涉及的所有专业的设计图纸(含图纸目录、说明和必要的设备、材料表,见第4.2节至第4.8节)以及图纸总封面;对于涉及建筑节能设计的专业,其设 计说明应有建筑节能设计的专项内容; 2 合同要求的工程顶算书; 注:对于方案设引后直抵进入施工图田设计的项目,若合同未要求编制工程预算书,施工图设计文件应包括工程概算书(见第3.10节)。 3 各专业计算书。计算书不属于必须交付的设计文什,但应按本规定相关条款的要求编制并归档保存。 4.1.2 总封面标识内容。 1 项目名称; 2 设计单位名称; 3 项目的设计编号; 4 设计阶段; 5 编制单位法定代表人、技术总负责人和项目总负责人的姓名及其签字或授权盖章; 6 设计日期(即设计文件交付日期)。 4. 2 总平面 4.2. 1 在施工图设计阶段,总平面专业设计文件应包括图纸目录、设计说明、设计图纸、计算书。 4,2.2 图纸目录。应先列新绘制的图纸,后列选用的标准图和重复利用图。 4.2.3 设计说明。一般工程分别写在有关的图纸上。如重复利用某工程的施工图图纸及其说明时,应详细注明其编制单位、工程名称、设计编号和编制日期;列出主要技术经济指标表(见表3.3.2,该表也可列在总平面图上),说明地形图、初步设计批复文件等设计依据、基础资料: 4.2. 4 总平面图。 1 保留的地形和地物; 2 测量坐标网、坐标值; 3 场地范围的测量坐标(或定位尺寸)、道路红线、建筑控制线、用地红线等的位置; 4 场地四邻原有及规划的道路、绿化带等的位置(主要坐标或定位尺寸),以及主要建筑物和构筑物及地下建筑物等的位置、名称、层数; 5 建筑物、构筑物(人防工程、地下车库、油库、贮水池等隐蔽工程以虚线表示)的名称

建筑施工图设计规范及深度规定

建筑施工图设计规及深度规定 一版面 1、以标准层图副大小为基准,一般情况下只一种高度大小图副。长度加长增加一种。特殊情 况特殊对待。 2、图层,天正默认的图层及颜色好线性,以天正默认为准,不允修改 家具图库以给定的家具图库图层为准。 3、打印线宽控制 墙体为0.50,填充、家具为0.15(淡浅70),门窗为0.20,其他均为0.25. 详图线宽控制? 4、封闭阳台为三根线表示、不封闭阳台为两根线表示。 5、图纸加图纸会签栏,以后的图纸签名及会签全部手签,厉禁止使用电子签名。 二平面图 1、大型或复杂的项目,特别是分段绘制者应增加防火分区示意图(比例缩小集中绘制)和轴线关系与分段示意图,分段轴线号前面应加注分段序号; 各层平面的防火分区界限宜用粗点划线示出,并在分界线两侧框示出分区序号和建筑面积(这对设备专业十分有用)。 2、平面图中标注的尺寸,可分为总尺寸、定位尺寸和细部尺寸三种; 总尺寸---建筑物外轮廓尺寸;若干定位尺寸之和。 定位尺寸——轴线尺寸;建筑物构配件如:墙体、门窗、洞口、洁具等,相应于轴线或其他构配件确定位置的尺寸。

细部尺寸——建筑物构配件的详细尺寸。 外墙三道:第一道外包(或轴线)总尺寸(错台或分段外包尺寸可在二、三道之间单注),第二道开间进深轴线尺寸,第三道门窗洞口和窗间墙、变形缝等尺寸及轴线关系; 4、所有定位尺寸及细部尺寸都要以轴线为准,不以墙线为准。即都与轴线发生关系。 5、钢筋混凝土墙应视情况确定是否标注,但应在图注中写详见结施图,且应在施工图中深入研究、配合、确保无误。 钢筋混凝土墙应表示为异形柱,不允粗单线绘制。 部门窗洞应注定位尺寸、高窗应注窗台距地高,门洞(指不装门的洞口)应注洞宽、洞高尺寸; 6、所有平面节点放大或详图索引要注全(层层共用的详图索引号层层标注) 7、门窗编号要注全。“人防工程门窗表”一般都直接放在人防平面图中,便于主管部门审图; 8、门的开启向和形式应在平面图上区别表示: 1000以下门的开启式为单扇半开,1200及以上为双扇半开 户门为甲级防火门(钢质)时应与其它甲级防火门(木)区别对待 9、室外、各层楼地面均应标注标高; 10、厨、洁具和家具——厨、洁具和家具自始(发作业图起)至终保留。 11、房间名称——各类建筑的平面均应注明房间名称或编号; 12、房间面积——住宅单元放大平面应注出各房间使用面积、阳台面积,在图中注明各单元平面的使用面积、阳台面积和、建筑面积、本层建筑面积,其他类建筑各层平面亦宜在图名下注出建筑面积;

施工图设计深度规定.

析说施工图设计——代序 随着我国经济建设的蓬勃发展,作为支柱产业之一的建筑业日新月异,建筑设计市场也因之兴旺起来,国家、集体及私人设计单位竞争激烈。面对这种局面,建筑方案的设计能否出奇制胜,固然成为设计单位取得设计权的重要保证,但施工图的设计能力与质量,同样成为设计单位整体水平的体现。 然而,有些建筑师却只热衷于方案设计,视施工图设计为雕虫小技,难以展现自己的才华。这种片面认识,主要是由于对施工图设计的下述特点缺乏了解所致。 一、施工图设计的严肃性 施工图是设计单位最终的“技术产品”,是进行建筑施工的依据,对建设项目建成后的质量及效果,负有相应的技术与法律责任。因此,常说“必须按图施工”。未经原设计单位的同意,任何个人和部门不得擅自修改施工图纸。经协商或要求后,同意修改的,也应由原设计单位编制补充设计文件,如变更通知单、变更图、修改图等,与原施工图一起形成完整的施工图设计文件,并应归档备查。 即便是在建筑物竣工投入使用后,施工图也是对该建筑进行维护、修缮、更新、改建、扩建的基础资料。特别是一旦发生质量或使用事故,施工图则是判断技术与法律责任的主要根据。 因此,《中华人民共和国建筑法》第五十六条中规定:“……设计文件应当符合有关法律、行政法规的规定和建筑工程质量、安全标准、建筑工程勘察、设计技术规范以及合同的约定。设计文件选用的建筑材料、建筑构配件和设备,应当注明其规格、型号、性能等技术指标,其质量要求必须符合国家规定的标准”。 二、施工图设计的承前性 建筑工程设计分为方案设计、初步设计和施工图设计3个阶段(小型和技术简单者,可以方案设计代替初步设计,简化为两个阶段)。其实质可以认为是从宏观到微观、从定性到定量、从决策到实施逐步深化的过程。后者是前者的延续,前者是后者的依据。就施工图设计论,它必须以方案与初步设计为依据,忠实于既定的基本构思和设计原则。如有重大修改变化时,应对施工草图进行审定确认或者调整初步设计,甚至重做再审。 值得提醒的是:为了保证施工图设计的顺利进行,开始前除充分准备内部作业所需的技术资料外,还应协助业主落实并提供必要的设计基础资料(详见附录二)。否则往往欲速而不达。难免返工! 由此可见,建筑师只有参与施工图设计,通过本工种和其他工种间反复推敲、协调的量化过程,才能深化、修正、完善最初的建筑构思。也即首先确保施工图设计不变形,才能使建筑竣工后“不走样”! 三、施工图设计的复杂性 就一般民用建筑而言,如果说建筑方案的优劣,主要取决于建筑师构思的水平。那么建筑施工图的优劣,不仅取决于处理好建筑工种本身的技术问题,同时更取决于各工种之间的配合协作。诚然,建筑工种在施工图设计阶段,仍然处于“龙头”地位,因为建筑的总体布局、平面构成、空间处理、立面造型、色彩用料、细部构造以及功能、防火、节能

方案设计初步设计施工图设计要求内容

方案设计、初步设计、施工图设计(1) 方案设计 2.1 一般要求 2.1.1 方案设计文件 1 设计说明书,包括各专业设计说明以及投资估算等容; 2 总平面图以及建筑设计图纸 3 设计委托或设计合同中规定的透视图、鸟瞰图、模型等。 2.1.2 方案设计文件的编排顺序 1 封面:写明项目名称、编制单位、编制年月; 2 扉页:写明编制单位法定代表人、技术总负责人、项目总负责人的,并经上述人员签署或授权盖章; 3 设计文件目录; 4 设计说明书; 5 设计图纸。 注:投标方案按标书要求密封或隐盖编制单位和扉页。 2.2 设计说明书 2.2.1 设计依据、设计要求及主要技术经济指标 1 列出与工程设计有关的依据性文件的名称和文号,如选址及环境评价报告、地形图,项目的可行性研究报告,政府有关主管部门对立项报告的批文、设计任务书或协议书等。 2 设计所采用的主要法规和标准。 3 设计基础资料,如气象、地形地貌、水文地质、地震、区域位置等。 4 简述建设方和政府有关主管部门对项目设计的要求,如对总平面布置、建筑立面造型等。当城市规划对建筑高度有限制时,应说明建筑、构筑物的控制高度(包括最高和最低高度限值)。 5 委托设计的容和围,包括功能项目和设备设施的配套情况。 6 工程规模(如总建筑面积、总投资、容纳人数等)和设计标准(包括工程等级、结构的设计使用年限、耐火等级、装修标准等)。 7 列出主要技术经济指标,如总用地面积、总建筑面积及各分项建筑面积(还要分别列出地上部分和地下部分建筑面积)、建筑基底总面积、绿地总面积、容积率、建筑密度、绿地率、停车泊位数(分室、外和地上、地下),以及主要建筑或核心建筑的层数、层高和总高度等项指标。根据不同的建筑功。还应表述能反映工程规模的主要技术经济指标,如住宅的套型、套数及每套的建筑面积、使用面积,旅馆建筑中的客房数和床位数,医院建筑中的门诊人次和病床数等指标。当工程项目(如城市居住区规划)另有相应的设计规或标准时,技术经济指标还应按其规定执行。 2.2.2 总平面设计说明 1 概述场地现状特点和周边环境情况,详尽阐述总体方案的构思意图和布局特点,以及在竖向设计、交通组织、景观绿化、环境保护等方面所采取的具体措施。 2 关于一次规划、分期建设,以及原有建筑和古树名木保留、利用、改造(改建)方面的总体设想。 2.2.3 建筑设计说明建筑方案的设计构思和特点: