Factory Acceptance Test Report

测试报告

Lens Factory Acceptance Test Report

Factory Acceptance Test Report

Test Content:

1. Lens Appearance: □OK □Damaged

2. IR Calibration: □Yes □No

3. Mount Adapter Lock: □Yes □No

4. Focusing Lock: □Yes □No

5. Zoom Lock: □Yes □No

6. Iris Lock: □Yes □No

7. Sliding Structure: □Yes □No

8. Specification:

● Image Size: □1/3” □1/2”

● Interface Type: □CS □C

● Iris Operation: □Manual □Motorized

□Auto (DC) □Video Drive

● Focusing Operation: □Manual □Motorized

● Zoom Operation: □Manual □Motorized

● Iris: □F/1.0 □F/1.2 □F/1.4

□F/1.6 □F/1.8 ● Focal Length (mm Whether does the actual near end focal length error satisfy ±10% □Yes □No Whether does the actual near end focal length error satisfy ± 5% □Yes □No ● Max. Outside Diameter (mm ): Ф● Total Length (mm ): ● Weight (g):

Test Date:

免费下载该文档:Factory Acceptance Test Report

Factory Acceptance Test Report的相关文档搜索

相关文档
Factory acceptance testing guideline Process[1]
2006-08-25 Factory Acceptance Testing Guideline Comments on this report are ...Each test procedure shall be described in a logical sequence i.e. how to...
出厂验收测试FAT
16 3 / 16 制造商 Supplier 工厂测试方案 嘉华通软 Factory Acceptance Test ...1.3.2 如何填写测试报告 1.3.2 How to fill in test report 结果 Result...
出厂验收测试FAT
16 3 / 16 制造商 Supplier 工厂测试方案 嘉华通软 Factory Acceptance Test ...1.3.2 如何填写测试报告 1.3.2 How to fill in test report 结果 Result...
PCS-915现场验收调试报告英文版
Factory Acceptance Test Report Project: Panel Name: Panel NO. : Serial No. of Panel: Serial No. of Device: Device Type: DC Power Supply: AC Voltage...
工程验证和相关文件清单
Factory Acceptance Test 工厂验收测试 10.4 Mechanical completion 机械性完工 10...Report Generation 最终总结性报告的形成 14.6 Change Control 变更控制 15 ...
计算机系统验证
(Integrated Test), 工厂验收测试 (Factory Acceptance Test), 现场验收测试 (...验证文档实例变更控制 Test Fault Report and Log ? 测试错误报告 (Test Fault...
常用缩略语详解(未排序)
EOMR——End Of Manufacturing Report 制造完工报告 57、FAT——Factory Acceptance Test 出厂验收试验 58、SSC——System Safety Criteria 系统安全准则 59、NCC——...
PCS-902现场验收报告英文版
Factory Acceptance Test Report Project: Panel Name: Panel NO. : Serial No. of Panel: Serial No. of Device: Device Type: DC Power Supply: AC Voltage...
美国FDA验证高级培训
FACTORY ACCEPTANCE TEST COMPLAINTS SAFETY “AS-BUILT” DRAWINGS 10 DOCUMENTED ...? ? ? ? Master Plan Protocol Data Sheets D t Sh t Report p Procedures...
美国FDA药物审批
Protocols Amend Protocol Collect Data Evaluate Data Report Results Results OK?...FACTORY ACCEPTANCE TEST “AS-BUILT” DRAWINGS STANDARD OPERATING PROCEDURES MFG...