HPP3500智能定位器
OPTIMUX TECHNICAL
BULLETIN
OVERVIEW
The HPP3500 model SVXA02 is a microprocessor-equipped,
current pneumatic smart valve positioner for rotary and linear
valves.
The HPP3500 receives a DC current signal from control
devices and controls pneumatic valves. In addition to this
basic function, the HPP3500 has communications
capabilities, automatic configuration program, and self-
diagnostics functions that will greatly increase the productivity
and efficiency of plant operations.
Calibration, configuration and self-diagnostics can be
performed by using a HART communicator, or Yamatake’s
SFC160 or SFC260, Smart Field Communicators.
FEATURES
Easy to use
? Auto setup
The auto-setup function is a fully-automatic configuration program which specifies the actuator and adjusts the zero and span of the rotary valve. The program can be turned
on simply from an switch so that adjustments to the rotary valve can be performed quickly and safely in hazardous areas.
Valve diagnostic
(for model SVXA02, software version 4.9 or newer) Following parameters can be monitored by HART communicator or Control Valve Maintenance Support System Valstaff.
? Stick Slip ? Cycle Count
? Total Stroke ? Shut-off Count
? Travel Histogram ? Max. Travel Speed.
Flexibility in installation
The models HPP3500 is available either as a stroke lever type or a fork lever type to facilitate installation on rotary valves.
? Direct mounting type
The HPP3500 can be installed to NAMUR cylinder actuator without linkage.
? Stroke lever type
The valve stem can be adjusted with a pipe wrench. (For manual operation)? Fork lever type
The HPP3500 can be mounted compactly on the upper part of the valve stem.
This type of installation complies with the VDI/VDE3845. High reliability
? Positive seating
The positive seating function completely shuts off the valve if the input signal becomes lower than previously set. This in turn enhances the full shut-off capabilities of the valves.? Self-diagnostic
The self-diagnostic function provides with the ability to check the status of the positioner at any time and to alert in case of failure.
Single model for multiple specifications
The HPP3500 settings can be changed without replacing any parts. A single model can be modified to suit any application.? Flow characteristic: Linear, EQ%, quick opening or custom user characteristics (16 points)
? Actuator type: Double or single acting actuator HART communication HART communicator model 275 can be used for calibration, configuration and self-diagnostics.
Smart Valve Positioner For Rotary and Linear Valves HPP3500 Series
OPTIMUX HPP3500 Series
FUNCTIONAL SPECIFICATIONS
Control signal input
4-20 mA DC
Input resistance
Approx. 600 ?/ 20 mA DC
(voltage between terminals 12V DC)
Approvals
KEMA/ATEX Intrinsically safe approval
II 1 G EEx ia IIC T4
Approval No. 04ATEX1176X
The barriers should be ATEX certified types and comply with the following conditions as follows.
Input circuit (terminals I IN)
Ui=29V, Ii=95mA(resistively limited), Pi=690mW,
Ci=10nF, Li=220μH
From the safety point of view the supply/input circuit shall be considered to be connected to earth.
FM Intrinsically Safe Approval
Intrinsically safe for Class I, II, III, Division 1, Groups A, B, C, D, E, F and G, T4 Ta=80oC
Intrinsically safe for Class I, Zone 0, AEx ia IIC T4
Nonincendive for Class I, Division 2, Groups A, B, C
and D, T4
Suitable for Class II, III, Division 2, Groups F and G, T4 Approval No. 3021344
The barriers should be FM approved types and comply with the following conditions as follows.
Input circuit: Vmax=30V, Imax=100mA, Pi=1W,
Ci=15nF, Li=0.22mH
Installation should comply with NEC.
Output Characteristics
? Linear, Equal percentage, Quick opening
? Custom user characteristics (16 points).
Bypass Operation
Auto/Manual switch (For single acting actuator only)
Air Supply Pressure
140 to 700 kPa (20 to 100 psi)
Air Consumption
At stable output: 50%
10 l/min.(N) maximum at 400 kPa (60 psi)
Maximum Delivered Air Flowrate
250 l/min.(N) at 400 kPa (60 psi)
Output Balanced Pressure
55 ±5%
Lightning Protection
Peak value of voltage surge: 12 kV
Peak value of current surge: 1000A
Vibration Tolerance
2 G (5 to 400 Hz)(with standard mounting kit on Yamatake HA actuator) Feedback Lever Angle
±4 to ±20
Ambient Temperature Limits
-40oC to 80oC for general model
KEMA/ATEX Intrinsically safe: -40oC to 60oC
FM Intrinsically safe: -40oC to 80oC
Ambient Humidity Limits
10% to 90% RH
Configuration Tools
Model SFC160 or SFC260 (SFC Smart Field Communicator, Software version 7.5 or newer)
HART communication model 275 (According to need,please update a software and device description files.)
CE Conformity
Electromagnetic compatibility
EN 61326: 1997 (CE marking)
PERFORMANCE SPECIFICATIONS
Accuracy
±1.0% F.S.
(±2.5% F.S. with custom output characteristics)
Turning Range
50o to 90o
PHYSICAL SPECIFICATIONS
Enclosure Rating
JISC 0920 watertight
NEMA type 4X
IP66 FM
Finish Color Material
Baked acrylic Grey Cast aluminum
Weight
Without pressure gauge : 1.8 kg
With pressure gauge : 2.2 kg
INSTALLATION
Air Connections
Rc1/4 or 1/4NPT internal thread
Electrical Connections
G1/2 or 1/2NPT
Conditions of Supply Air
Particles
Maximum diameter 3 μm
Oil Mist
None acceptable
Dew Point
10C below ambient temperature
TECHNICAL BULLETIN
OPTIMUX
HPP3500 Series
TECHNICAL BULLETIN
Figur e 2Wiring for model SVX02
A U T O
M A N .
DOWN
UP
SFC
TRAVEL SW 4-20 mA DC
Smart Field Communicator Model SFC160/260
Controller
HART
communicator model 275
78
9
456
12
30
_
H A R
T
TYPICAL INSTALLATION
Wiring for model SVXA02
OPTIMUX HPP3500 Series
SVXA02
SVXA02
F
L
Intrinsically safe FM CL I, II, III, Div 1 Groups A, B, C, D, E, F & G, T4
Intrinsically safe KEMA/ATEX II 1G EEx ia II CT4
S Standard (Baked acrylic)
N
Electrical Connecton Air Piping Connection Mounting Thread
S Standard 20 to 100 psi (130 to 700 kPa)
X Not included
X Not included
R Fork lever type (Rotary valves)
XX Not included
Code Hazardous Rating
Code Pressure Regulator with Filter
Code Enclosure Finish
Code Connection
Code Supply Air Pressure Classification
Code Pressure Gauges
Code Feedback Lever Type
Code Mounting Brackets for Actuators1
Code Options
X No selection
D With Namur joints for direct
mounting type
P For single acting actuator (with plug
for OUT2)2
25For Optimux 25 & 50 LA/RA Actuators
100For Optimux 100 LA/RA Actuators
S Stroke lever type (Linear valves)
D Direct Mounting type (Rotary valve)
1Model OPAFR pressure regulator with filter
Y Included
1/2 NPT1/4 NPT M8 HART Smart Valve Positioners
?
TECHNICAL BULLETIN
MODEL SELECTION
1) Also available a large selection of mounting brackets for Fisher?, Masoneilan?and Neles?
actuators. Mounting brackets for other valve actuators can be designed and manufactured upon request.
2) In the case of using the device as a single acting actuator, close the output air pressure connection
plug (OUT2). The device cannot be used when the output air pressure plug (OUT1) is closed.
16.7
42
OPTIMUX
HPP3500 Series
TECHNICAL BULLETIN
Fork lever type (without pressure gauges)
DIMENSIONS
OPTIMUX
HPP3500 Series
TECHNICAL BULLETIN
16.7
42Fork lever type (with pressure gauges)
DIMENSIONS
OPTIMUX
HPP3500 Series
TECHNICAL BULLETIN
Connector pin should be installed within this range when mounting model SVXA02 to an actuator.
42
Stroke lever type (without pressure gauges)
DIMENSIONS
OPTIMUX
HPP3500 Series
TECHNICAL BULLETIN
Stroke lever type (with pressure gauges)
DIMENSIONS
Connector pin should be installed within this range when mounting model SVXA02 to an actuator.
OPTIMUX
HPP3500 Series
TECHNICAL BULLETIN
Direct mounting type (without pressure gauges)
DIMENSIONS
OPTIMUX
HPP3500 Series
TECHNICAL BULLETIN
Direct mounting type (with pressure gauges)
DIMENSIONS
OPTIMUX
HPP3500 Series
TECHNICAL BULLETIN
OPTIMUX
HPP3500 Series
TECHNICAL BULLETIN
HART is a registered trademark of the HART Comunication Foundation.Yamatake is a registered trademark of Yamatake Corporation.
Optimux Controls, LLC
3884 NW 124th Ave.Coral Springs, FL 33065Phone: 954-227-8353Fax: 954-227-8253
https://www.360docs.net/doc/9713882148.html,
Cat. # TB-HPP3500-07-04