Mod.SCV01
STI
SC/V Pneumatic Piston Actuator Data Sheet Doc.n°71560SC 01Sheet 01of 021Project :MINQUAN 2X600MW, 361 VALVE
Customer :2Purchase Order N° and date 310695 DATED 22 MAY 2007
Project :202209-1/23Customer :UNITED POWER RESOURCES, LTD
STI Order :4Valve Service :361 VALVE
Tag :TBD 5Ambient Temp. :Q.ty :2+26Required Thrust : to Open N 14723
to Close N 21168To seat N:552667Air Supply: 7 bar
< 5CLOSE 8Stroking Time Sec to Open:< 20
to Close:< 209On Air Failure Valve :IN PLACE
Actuat. Stem Extended Valve : close 10Actuator Type:Type of Service:modulating 11Actuator Size:SC/V 320 STROKE 6"
Nominal Stroke :12Positioner model :CCI /STI / SY-1 SMART Inlet signal :4-20 mA Size:
13Increasing signal :TO OPEN VALVE Characteristic:LINEAR
14Positioner accessories :Gauges:15Handwheel with bypass :side Handwheel Type :GR 2
16Handwheel Position :Ref. DWG. No 17Air Lock Model :Setting :3,8 bar (55 psig)
18Air Tank + Check Valve :Air Set:19Tubing Mater. :Fitting Mater. :20Air Supply Connections:3/4" NPTF Electrical Certification STANDARD STANDARD 21Limit Switches Type:Contact Type:22Limit Switches Position:Model :23Solenoid Valve: 2 x 3 way 1/4" U Supply:220Vac 50 Hz Mod :
ASCO 8320P17224Position Transmitter:Output Signal:25Valve mounting Yoke:CLAMP CARBON STEEL RSM SUPPLIED Stem coupling:1" 1/8"1" 1/2"RSM SUPPLIED
26Actuator installation :VERTICAL Valve stem projection :7,125inches
27Ambient Condition STANDARD JUNCTION BOX SS 1 mm TICKNESS
28
Check Valve :Electrical Connection NPT 29
Volume booster QTY 2 VB 1/4"30
Painting Specification :BLUE RAL 5002 CV0231
32
33
34
35
36
37
38
39
40
41
42
43
44
AIR SUPPLY OK OK OK 45
SOLENOID 2ENER ENERG DE-ENERG 46
SOLENOID 1ENER DE-ENERG ENER/DE-ENE 47
INPUT SIGNAL OK OK OK 48
VALVE POSITION MODULATING CLOSE IN PLACE 49A Dimensional Drawing:DD 22804_152Pneumatic Diagram:TD 22804_01REMARKS :
STI SERIAL NUMBER : STI CODE :(1)
Volume Tank RSM SUPPLIED Vol. Tank Port Conn. N/R (2)Upon Loss of Signal IN PLACE
AIR FILTER SET AT 6,9 BAR (100 psig)
Bonnet Connection CLAMPED - 1.5" STEM Stem Projection (seated) 7,125 inches
REV.Date Name REV.Date Name 07/06/2007M.FORESTI
FAIL IN PLACE ENER/DE-ENE ENER/DE-ENE OK/FAIL 72146OK ENER/DE-ENE ENER/DE-ENE FAIL IN PLACE VALVE OPERATION TABLE A pressure switch is required, it is norgren 18D series 0880320, CCI P/N: 258400034, SET @50 psig.DCA is needed same as used 201646-1, and DCA should be mounted in junction box. RSM DCA P/N is 258400039Emergency :4/20 mA
Enclosure Certification
Mechanical 1 in open + 1 in closed 205 mm (Reg. 152 mm + 53 EXTRA)2 x 3 WAY VALVES FOR CLOSE FUNCTION Air Filter 3/4" Regul. B74+gauge
stain steel AISI 316 SWAGEL METRIC
AL102 1/2"STI 203071560G E N E R A L A C T U A T O R A N D A C C E S S O R I E S A0713966->69CCI - USA SPDT
-20° /+70°C
1/4"by pass DOUBLE ACTINGLOW VOLUME
stainless steel AISI 316L FC 2130-4M-2S
RSM SUPPLIED 0