《阶梯柱基计算书》

《阶梯柱基计算书》
《阶梯柱基计算书》

阶梯柱基计算书一、示意图

基础类型:阶梯柱基计算形式:程序自动计算

平面:

剖面:

二、基本参数

1.依据规范

《建筑地基基础设计规范》(GB 50007-2002)

《混凝土结构设计规范》(GB 50010-2002)

《简明高层钢筋混凝土结构设计手册(第二版)》2.几何参数:

自动计算所得尺寸:

B1 = 1700 mm, A1 = 1700 mm

H1 = 200 mm, H2 = 200 mm

B = 400 mm, A = 400 mm

B3 = 1900 mm, A3 = 1900 mm

无偏心:

B2 = 1700 mm, A2 = 1700 mm

基础埋深d = 2.00 m

钢筋合力重心到板底距离a s = 80 mm

3.荷载值:

(1)作用在基础顶部的标准值荷载

F gk = 550.06 kN F qk = 328.08 kN

M gxk= 0.00 kN·m M qxk= 0.00 kN·m

M gyk= 18.51 kN·m M qyk = 0.00 kN·m

V gxk = 0.00 kN V qxk = 0.00 kN

V gyk = 0.00 kN V qyk = 0.00 kN

(2)作用在基础底部的弯矩标准值

M xk = M gxk+M qxk = 0.00+0.00 = 0.00 kN·m

M yk = M gyk+M qyk = 18.51+0.00 = 18.51 kN·m

V xk = V gxk+V qxk = 0.00+0.00 = 0.00 kN·m

V yk = V gyk+V qyk = 0.00+0.00 = 0.00 kN·m

绕X轴弯矩: M0xk = M xk-V yk·(H1+H2) = 0.00-0.00×0.40 = 0.00 kN·m

绕Y轴弯矩: M0yk = M yk+V xk·(H1+H2) = 18.51+0.00×0.40 = 18.51 kN·m

(3)作用在基础顶部的基本组合荷载

不变荷载分项系数r g = 1.20 活荷载分项系数r q = 1.40

F = r g·F gk+r q·F qk = 1119.38 kN

M x = r g·M gxk+r q·M qxk= 0.00 kN·m

M y = r g·M gyk+r q·M qyk= 22.21 kN·m

V x = r g·V gxk+r q·V qxk = 0.00 kN

V y = r g·V gyk+r q·V qyk = 0.00 kN

(4)作用在基础底部的弯矩设计值

绕X轴弯矩: M0x = M x-V y·(H1+H2) = 0.00-0.00×0.40 = 0.00 kN·m

绕Y轴弯矩: M0y = M y+V x·(H1+H2) = 22.21+0.00×0.40 = 22.21 kN·m 4.材料信息:

混凝土: C40 钢筋: HRB400(20MnSiV、20MnSiNb、20MnTi) 5.基础几何特性:

底面积:S = (A1+A2)(B1+B2) = 3.40×3.40 = 11.56 m2

绕X轴抵抗矩:Wx = (1/6)(B1+B2)(A1+A2)2= (1/6)×3.40×3.402 = 6.55 m3

绕Y轴抵抗矩:Wy = (1/6)(A1+A2)(B1+B2)2= (1/6)×3.40×3.402 = 6.55 m3三、计算过程

1.修正地基承载力

修正后的地基承载力特征值 f a = 118.00 kPa

2.轴心荷载作用下地基承载力验算

计算公式:

按《建筑地基基础设计规范》(GB 50007-2002)下列公式验算:

p k = (F k+G k)/A (5.2.2-1)

F k = F gk+F qk = 550.06+328.08 = 878.14 kN

G k= 20S·d = 20×11.56×2.00 = 462.40 kN

p k = (F k+G k)/S = (878.14+462.40)/11.56 = 115.96 kPa ≤ f a,满足要求。3.偏心荷载作用下地基承载力验算

计算公式:

按《建筑地基基础设计规范》(GB 50007-2002)下列公式验算:

当e≤b/6时,p kmax = (F k+G k)/A+M k/W (5.2.2-2)

p kmin = (F k+G k)/A-M k/W (5.2.2-3)

当e>b/6时,p kmax = 2(F k+G k)/3la (5.2.2-4) X方向:

偏心距e xk = M0yk/(F k+G k) = 18.51/(878.14+462.40) = 0.01 m

e = e xk = 0.01 m ≤ (B1+B2)/6 = 3.40/6 = 0.57 m

p kmaxX = (F k+G k)/S+M0yk/W y

= (878.14+462.40)/11.56+18.51/6.55 = 118.79 kPa

≤ 1.2×f a = 1.2×118.00 = 141.60 kPa,满足要求。

4.基础抗冲切验算

计算公式:

按《建筑地基基础设计规范》(GB 50007-2002)下列公式验算:

F l≤ 0.7·βhp·f t·a m·h0(8.2.7-1)

F l = p j·A l(8.2.7-3)

a m = (a t+a b)/2 (8.2.7-2)

p jmax,x = F/S+M0y/W y = 1119.38/11.56+22.21/6.55 = 100.22 kPa

p jmin,x = F/S-M0y/W y = 1119.38/11.56-22.21/6.55 = 93.44 kPa

p jmax,y = F/S+M0x/W x = 1119.38/11.56+0.00/6.55 = 96.83 kPa

p jmin,y = F/S-M0x/W x = 1119.38/11.56-0.00/6.55 = 96.83 kPa

p j = p jmax,x+p jmax,y-F/S = 100.22+96.83-96.83 = 100.22 kPa

(1)柱对基础的冲切验算:

H0 = H1+H2-a s = 0.20+0.20-0.08 = 0.32 m

X方向:

A lx = 1/4·(A+2H0+A1+A2)(B1+B2-B-2H0)

= (1/4)×(0.40+2×0.32+3.40)(3.40-0.40-2×0.32)

= 2.62 m2

F lx = p j·A lx= 100.22×2.62 = 262.55 kN

a b = min{A+2H0, A1+A2} = min{0.40+2×0.32, 3.40} = 1.04 m

a mx = (a t+a b)/2 = (A+a b)/2 = (0.40+1.04)/2 = 0.72 m

Flx ≤ 0.7·βhp·f t·a mx·H0= 0.7×1.00×1710.00×0.720×0.320 = 275.79 kN,满足要求。

Y方向:

A ly = 1/4·(B+2H0+B1+B2)(A1+A2-A-2H0)

= (1/4)×(0.40+2×0.32+3.40)(3.40-0.40-2×0.32)

= 2.62 m2

F ly = p j·A ly= 100.22×2.62 = 262.55 kN

a b = min{B+2H0, B1+B2} = min{0.40+2×0.32, 3.40} = 1.04 m

a my = (a t+a b)/2 = (B+a b)/2 = (0.40+1.04)/2 = 0.72 m

Fly ≤ 0.7·βhp·f t·a my·H0= 0.7×1.00×1710.00×0.720×0.320 = 275.79 kN,满足要求。

(2)变阶处基础的冲切验算:

X方向:

A lx= 1/4·(A3+2H0+A1+A2)(B1+B2-B3-2H0)

= (1/4)×(1.90+2×0.12+3.40)(3.40-1.90-2×0.12)

= 1.75 m2

F lx = p j·A lx= 100.22×1.75 = 174.90 kN

a b = min{A3+2H0, A1+A2} = min{1.90+2×0.12, 3.40} = 2.14 m

a mx = (a t+a b)/2 = (A3+a b)/2 = (1.90+2.14)/2 = 2.02 m

Flx ≤ 0.7·βhp·f t·a mx·H0= 0.7×1.00×1710.00×2.020×0.120 = 290.15 kN,满足要求。

Y方向:

A ly= 1/4·(B3+2H0+B1+B2)(A1+A2-A3-2H0)

= (1/4)×(1.90+2×0.12+3.40)(3.40-1.90-2×0.12)

= 1.75 m2

F ly = p j·A ly= 100.22×1.75 = 174.90 kN

a b = min{B3+2H0, B1+B2} = min{1.90+2×0.12, 3.40} = 2.14 m

a my = (a t+a b)/2 = (B3+a b)/2 = (1.90+2.14)/2 = 2.02 m

Fly ≤ 0.7·βhp·f t·a my·H0= 0.7×1.00×1710.00×2.020×0.120 = 290.15 kN,满足要求。

5.基础受压验算

计算公式:《混凝土结构设计规范》(GB 50010-2002)

F l≤ 1.35·βc·βl·f c·A ln(7.8.1-1)

局部荷载设计值:F l = 1119.38 kN

混凝土局部受压面积:A ln = A l= B×A = 0.40×0.40 = 0.16 m2

混凝土受压时计算底面积:A b = min{B+2A, B1+B2}×min{3A, A1+A2} = 1.44 m2混凝土受压时强度提高系数:βl = sq.(A b/A l) = sq.(1.44/0.16) = 3.00

1.35βc·βl·f c·A ln

= 1.35×1.00×3.00×19100.00×0.16

= 12376.80 kN ≥ F l = 1119.38 kN,满足要求。

6.基础受弯计算

计算公式:

按《建筑地基基础设计规范》(GB 50007-2002)下列公式验算:

MⅠ=a12[(2l+a')(p max+p-2G/A)+(p max-p)·l]/12 (8.2.7-4)

MⅡ=(l-a')2(2b+b')(p max+p min-2G/A)/48 (8.2.7-5)

(1)柱根部受弯计算:

G = 1.35G k= 1.35×462.40 = 624.24kN

X方向受弯截面基底反力设计值:

p minx = (F+G)/S-M0y/W y = (1119.38+624.24)/11.56-22.21/6.55 = 147.44 kPa p maxx = (F+G)/S+M0y/W y = (1119.38+624.24)/11.56+22.21/6.55 = 154.22 kPa p nx = p minx+(p maxx-p minx)(2B1+B)/[2(B1+B2)]

= 147.44+(154.22-147.44)×3.80/(2×3.40)

= 151.23 kPa

Ⅰ-Ⅰ截面处弯矩设计值:

MⅠ= [(B1+B2)/2-B/2]2{[2(A1+A2)+A](p maxx+p nx-2G/S)

+(p maxx-p nx)(A1+A2)}/12

= (3.40/2-0.40/2)2((2×3.40+0.40)(154.22+151.23-2×624.24/11.56)+(154.22-151.23)×3.40)/12

= 268.47 kN.m

Ⅱ-Ⅱ截面处弯矩设计值:

MⅡ= (A1+A2-A)2[2(B1+B2)+B](p maxx+p minx-2G/S)/48

= (3.40-0.40)2(2×3.40+0.40)(154.22+147.44-2×624.24/11.56)/48

= 261.45 kN.m

Ⅰ-Ⅰ截面受弯计算:

相对受压区高度:ζ= 0.041222 配筋率:ρ= 0.002187

计算面积:699.86 mm2/m

Ⅱ-Ⅱ截面受弯计算:

相对受压区高度:ζ= 0.040121 配筋率:ρ= 0.002129

计算面积:681.17 mm2/m

(2)变阶处受弯计算:

X方向受弯截面基底反力设计值:

p minx = (F+G)/S-M0y/W y = (1119.38+624.24)/11.56-22.21/6.55 = 147.44 kPa

p maxx = (F+G)/S+M0y/W y = (1119.38+624.24)/11.56+22.21/6.55 = 154.22 kPa

p nx = p minx+(p maxx-p minx)(2B1+B3)/[2(B1+B2)]

= 147.44+(154.22-147.44)×5.30/(2×3.40)

= 152.73 kPa

Ⅰ-Ⅰ截面处弯矩设计值:

MⅠ= [(B1+B2)/2-B3/2]2{[2(A1+A2)+A3](p maxx+p nx-2G/S)

+(p maxx-p nx)(A1+A2)}/12

= (3.40/2-1.90/2)2((2×3.40+1.90)(154.22+152.73-2×624.24/11.56)+(154.22-152.73)×3.40)/12

= 81.37 kN.m

Ⅱ-Ⅱ截面处弯矩设计值:

MⅡ= (A1+A2-A3)2[2(B1+B2)+B3](p maxx+p minx-2G/S)/48

= (3.40-1.90)2(2×3.40+1.90)(154.22+147.44-2×624.24/11.56)/48

= 78.98 kN.m

Ⅰ-Ⅰ截面受弯计算:

相对受压区高度:ζ= 0.091174 配筋率:ρ= 0.004837

计算面积:580.47 mm2/m

Ⅱ-Ⅱ截面受弯计算:

相对受压区高度:ζ= 0.088361 配筋率:ρ= 0.004688

计算面积:562.57 mm2/m

四、计算结果

1.X方向弯矩计算结果:

计算面积:699.86 mm2/m

采用方案:f12@140

实配面积:807.84 mm2/m

2.Y方向弯矩计算结果:

计算面积:681.17 mm2/m

采用方案:f12@140

实配面积:807.84 mm2/m

(注:素材和资料部分来自网络,供参考。请预览后才下载,期待你的好评与关注!)

相关主题
相关文档
最新文档