继电保护纵连差动保护整定计算

继电保护纵连差动保护整定计算
继电保护纵连差动保护整定计算

(一)纵连差动保护

1、线路最大负荷电流

max N f I I ?=

=315(A ) ∴选择变比为300/5的电流互感器

CT 二次侧电流 2N I =315*5/300=5.25(A)

最小不平衡电流

20.1umb SS N I K I ==0.1*0.5*5.25=0.263(A)

∴最小动作电流

dz k umb I I I =?=1.3*0.263=0.342(A)

2、

基准值

12d d I I ==

=1000/(

)=5.02(KA ) 母线左侧K1短路电流

*110.554 6.9

k I =+=0.134 KA *11k k d I I I =?=6.72.68(A)

母线右侧K2短路电流

*210.5540.496

k I =+=0.952 KA *22k k d I I I =?=4.78 KA

∴躲过外部短路的最大平衡电流

10.1k ump ss

AT I I K n ==0.1*0.5*4.78/60=3.98 A 外部短路最大短路电流

160k k I I =

≈80 A 最大动作电流

dz k ump I K I =?=1.3*3.98=5.17 A ∴最大制动电流

0.580(80)res I =--=80 A

斜率

5.170.342800.263K -==-0.06

3、

灵敏度校验:(最小运行方式下线路出口两相短路)

(1)K1点短路(母线右侧)

A 点电流

*A k d I I =

=*5.02*1

1.09=4 KA

二次侧

260A

A I I ==66.47 KA

B 点电流

*2B k d I I I =

=2*5.02*1

0.554 6.9+=0.583 KA

二次侧

260B

B I I ==9.72 A

制动电流

220.5res B A I I I =-=28.37 A 差动电流

22cd B A I I I =+=76.19 A 2()*op res N dz I I I K I =--=(28.37-5.25)*0.06+0.342=1.729

A ∴1cd

m op

I K I ==44.06

∴满足要求

(1)K2点短路(母线左侧)

A 点电流

*2A k d I I I =

=2*5.02*1

1.090.554+=

2.63 KA

二次侧

260A

A I I ==43.83 KA

B 点电流

*2B k d I I I =

=2*5.02*16.09=0.709 KA 二次侧

260

B B I I ==11.82 A 制动电流 220.5res B A I I I =-=16 A 差动电流

22cd B A I I I =+=55.65 A 2()*op res N dz I I I K I =--=(16-5.25)*0.06+0.342=0.987 A ∴1cd m op I K I ==56.38 ∴满足要求