神港FC系列说明书

合集下载

IFP-100神港 通讯模块手册

IFP-100神港 通讯模块手册

PROFIBUS通信转换器IFP-100使用说明书警告在进行配线或检查作业前,应先断开仪表电源。

在未断电的情况下作业,将可能因电击导致人身重大伤害事故!IFP-1001. 简介1.1 IFP-100简介------------------------------------------------------------------------------- 3 1.2 系统配置----------------------------------------------------------------------------------- 32. 型号2.1 型号----------------------------------------------------------------------------------------- 3 2.2 型号铭牌的表示方法-------------------------------------------------------------------- 33.各部位名称和功能--------------------------------------------------------------- 34. 设定------------------------------------------------------------------------------- 45. 安装5.1 场所选择----------------------------------------------------------------------------------- 5 5.2 外形尺寸图-------------------------------------------------------------------------------- 5 5.3 圆形插座安装----------------------------------------------------------------------------- 66. 导线连接6.1 接线端排列-------------------------------------------------------------------------------- 7 6.2 导线连接实例----------------------------------------------------------------------------- 77. 通信数据7.1数据形式------------------------------------------------------------------------------------ 9 7.2数据结构------------------------------------------------------------------------------------ 9 7.3数据设定过程-------------------------------------------------------------------------------- 12 7.4读数据过程-------------------------------------------------------------------------------- 12 7.5数据传送------------------------------------------------------------------------------------- 128. 规格--------------------------------------------------------------------------------- 139. 故障排除--------------------------------------------------------------------------141. 简介1.1 IFP-100简介IFP-100 是一种通信转换器,用来连接PROFIBUS主机单元(SIEMENS PLC,等),作为PROFIBUS-DP从机单元,进行数据交换。

FC11阀门定位器说明书V1.0

FC11阀门定位器说明书V1.0

产品的不断升级可能导致部分数据的变化,如有改动恕不另行通知电动阀门智能定位器/阀门操作器(电子式伺服控制器)产 品 说 明 书(V1.0)通 用 型目录一、 概述 (1)二、 电气性能指标 (1)三、 主要技术指标 (2)四、 操作显示面板 (3)五、 接线方法 (4)六、 产品使用方法 (5)七、 产品输入输出信号标定 (6)八、 出厂恢复与辅助设置 (7)九、 错误代码列表 (8)十、 用户软件操作流程图 (8)符-oh-。

U5等于-oh-状体下才能进入到U6、U7手动转角标定。

当U5在数字密码状态时,按下键递减数据,可回到-oh-状态。

当按住▲或▼键不动时,数据以恒定的速度快速递增和递减。

U0-U13按▲或▼键修改设置参数堵转测试:当发给执行器动作指令时,若在xx.x 秒都没有动作,将发出-E4-(或-E5-)错误代码,并停止xx.x 秒后,向动作指令的反方向动作2秒,然后再向动作指令的方向动作xx.x 秒,若故障消除,则清除错误代码且解除报警状态,继续工作。

若没有解除,则再停止xx.x 秒后,向动作指令的反方向动作2秒,然后再向动作指令的方向动作xx.x 秒。

如此往复动作3回合,都没有消除故障,则永远出现-E4-(或-E5-)错误代码和报警,等待人为断电故障排查。

3、故障报警:当产品有报警接口,且出现故障代码时,报警继电器由常开转为常闭。

代码消失,报警继电器恢复常开,完全与故障代码同步。

注意:无效回差时间(传动误差)较大时,应将堵转时间设定大些避免误报警!执行器电机连接线脱接、过热保护、执行器传动齿轮间隙大、电位器安装时传动齿轮之间间隙大、电位器脱接或质量不良等因素,都会产生堵转处理程序,所以出现此故障,请先排查执行器问题。

补充说明:1、U0-U4菜单的功能可在线调试,可定位器处于自动控制状态,当某参数发生改变时,定位器能根据新参数实时调控。

2、在U5菜单时,U5与-oh -交替显示。

FC300操作说明书

FC300操作说明书
! 如何安装 ................................................................... 11
" 如何开始 .................................................................. 11 " 附件包 (≤ 7.5 kW) ............................................................. 12 " 机械安装 .................................................................. 14 " 电气安装 .................................................................. 16 " 拆除外接电缆的挡板 ........................................................ 16 " 主电源连接和接地 .......................................................... 17 " 电动机连接 ................................................................ 19 " 保险丝 .................................................................... 21 " 访问控制端子 .............................................................. 23 " 电气安装,控制端子 ........................................................ 23 " 连接示例 .................................................................. 24 " 启动/停止 ................................................................. 24 " 脉冲启动/停止 ............................................................. 25 " 加速/减速 ................................................................. 25 " 电位器参考值 .............................................................. 25 " 电气安装,控制电缆 ........................................................ 26 " 开关 S201、S202 和 S801 ........................................................ 27 " 最终设置与测试 ............................................................ 28 " 其他连接 .................................................................. 30 " 继电器选件 MCB 105 ............................................................ 30 " 机械制动控制 .............................................................. 33 " 电动机热保护 .............................................................. 33

FC系列中文操作说明(神港)

FC系列中文操作说明(神港)
运行和维护的注意事项
注意
• PID自整定(AT)的执行,请在试运行时实施。 • 为防止触电及发生调节仪故障,通电中请勿触及端子。 • 在实施端子锁紧或清洁作业时,必须在调节仪电源关闭的情况下执行。
通电期间作业,可能因触电而产生重大人身伤害。 • 在清洁时,请用柔软的干布。 • 应避免用硬物撞击和刮擦显示器。
功能
1
控制方式制 PID 控制 PD 控制 ON/OFF 控制
加热/冷却 3
加热(反作用)动作 冷却(正作用)动作
报警 1
无待机动作
待机
4
待机动作
报警 2
无待机动作
待机
5
待机动作
/
6
输入传感器
7*
K, J, R, B, N, PL- , Pt100, JPt100 S, E, T, C, 4 ~ 20mA, 0 ~ 20mA,
FC 系列数字显示调节仪 使用说明书
目次
前言
1 简介……………………………………………………………………………………………………………(1)
2 各部分名称和功能……………………………………………………………………………………………(2) 3 设定……………………………………………………………………………………………………………(3) 3.1 拔出内部组件 ………………………………………………………………………………………………(3) 3.2 开关设定 ……………………………………………………………………………………………………(4) 3.3 插入内部组件 ………………………………………………………………………………………………(5) 4 操作……………………………………………………………………………………………………………(6) 4.1 操作流程图………………………………………………………………………………………………….(6) 4.2 操作……………………………………………………………………………………………………………(8)

FC操作手册版

FC操作手册版
2)显示屏上的图标予以警情(防区类型)指示。
3)信号LED指示接收到无线报警触发信号,状态LED动态指示报警进程。
3.7
在布防状态下,主机会自动进行电话掉线检测,一旦检测到电话掉线会立即启动现场高音警笛连续鸣笛。在撤防状态下,一旦检测到电话掉线后,主机间断性地提示“电话掉线”约60秒,在此期间如果电话线恢复或进行撤防操作,则停止提示音,否则提示音结束后立即开启现场高音警笛默认为5分钟。
FC-300报警主机




FC-300操作说明
一、功能简介
1、全程语音提示功能:所有本地或远程操作、报警信息、事件记录查看等都有语音提示。
2、用户界面:液晶图文显示操作步骤、工作状态、报警流程,使用直观方便。
3、三十二个无线防区:每个无线防区都可自动学习对码,也可通过键盘手动输入地址编码,本产品主机兼容我公司出品的任何一款无线探测器,便于用户扩充无线防区。
3.5
主机使用安定宝Contact ID通讯协议向接警中心发送报警信息,若主机接收到接警中心的确认信号,则以此报警成功,否则主机会重复报警(最多5次重拨中心电话)。报警信息由接警中心电脑软件进行显示及报警处理。
3.6
只有设置为盗警、延时周界警情的防区才受处出布防、在家布防、撤防操作的控制,其它的防区类型均处于24小时报警有效状态。
紧急呼救:按遥控器的紧急呼救按钮,或按键盘上的【紧急/旁路】键3秒,主机会发出报警信号,10秒后您事先设置好的接警手机会被拨通。按撤防键消除报警。
四、用户设置
4.1
输入【1234】【旁路】【1】【确认】
1234旁路 1#年 月 日 #
4.2
【1234】 【旁路】 【2】 【确认】 输入4位用户密码 【确认】

日本神港 JC-33A 系列通用控制器操作说明书

日本神港 JC-33A 系列通用控制器操作说明书

日本神港JC-33A系列通用控制器操作说明书日本神港(SHINKO)株式会社拥有五十余年温度控制的丰富经验,在工业控制仪表领域以其独特的科研与开发为先导,推出了JC-33A系列通用型通用控制仪表,它采用了最先进的加热冷却双PID算法,无超调,无欠调,输入用户自由组态,双设定值,手自动功能,通讯功能,回路断线报警,JC系列仪表已通过ISO9001质量认证,广泛应用于橡胶,实验仪器,空调,纺织,汽车,食品,电缆电线等工业的温度,湿度,压力,液位元等控制。

(1)PV测量值显示 (9)TX/RX通讯指示红色LED显示实际测量值 当处于通讯状态时,黄色LED亮(2)SV设定值显示 (10)A1报警1指示 绿色LED显示实际设定值或手动输出值 当报警1动作时,红色LED亮(3)设定值1指示 (11)A2/L2报警指示当使用设定值1时,绿色LED亮 当报警2动作或回路断线时,(4)设定值2显示 红色LED亮当使用设定值2时,黄色LED亮 (12)增加键(5)输出1指示 按此键增加数值当输出1工作时,绿色LED亮 (13)减少键(6)输出2指示 按此键减少数值当输出2工作时,黄色LED亮 (14)方式键(7)HB加热器断线报警 按此键并配合其它键使用可进入各级菜单当发生加热器断线或传感器断线时, (15)OUT/OFF键红色LED亮 按此键一秒钟可关闭仪表输出 ;(8)AT自整定指示 按三秒钟可输出百分比当处于自整定状态时,黄色LED亮(1) 仪表选型JC □- □ 3 A- □/ M, □JC SERIES D JCD (W96×H96×D100mm ) R JCR (W48×H96×D100mm ) 尺寸 SJCS (W48×H48×D100mm ) 1适用于JCD ,JCR 机种 序 号 2仅适用于JCS-23-A □/□机种 控制动作 3PID 控制(控制方式可以选择) 警报1(A1) A多种动作系统(动作方式可选择) RRelay 继电器接点,1a 1b (JCS:1a) SDC 电压输出(驱动SSR 用):12+20V 控制输出(O U T ) ADC 电流输出:4~20mA M多种范围输入系统(输入种类热电偶、电阻体可选择) ADC 电流输入:0~20mA ,4~20mA (JCS 可于M 入力中选择此入力) 入 力 V DC 电压输入:0~1V ,0~10V ,1~5V(JCS 可于M 入力中选择0~1V )A2 警报2(A2)(动作方式可选择) W(5A)等级:5A W(10A)等级:10AW(20A)等级:20AW(50A)加热器 断线警报 等级:50A DR Relay 继电器接点:1aDS DC 电压输出(驱动SSR 用): 12+20V 最大40mA DA 控制输出 加热、 冷却控制 (JCS 无)DC 电流输出:4~20mA 负荷电阻:最大550ΩC5 串行通信 RS-485LA 回路断线警报SM 设定值记忆外部切换功能(仅JCS 为附加特殊功能)BK 黑色IP 防尘·防滴(IP54)特殊功能(需指定) TC 外壳接线端子防护<注>:特殊功能并非每一机种均可指定采用,请参照各别机种详细目录。

神钢C-10VF 取扱说明书(中国)


■ 阅读“使用说明书”后,务必妥善保管,以便使用本产品的人员能够随时阅读。 ■ 使用的产品转让或出借时,务必将“使用说明书”随附于产品本体的醒目位置,以便新的所有者了解安全 正确的使用方法。 ■ 本“安全注意事项”所记载的危险、警告、注意并未涵盖所有情况。请仔细阅读使用说明书,并始终将安 全放在第一位。
2/31
危险
不能用于压电方式的零件供料机。 请勿在放置可燃物、易燃物等危险品的场所使用。 本产品并非防爆型。可能会起火或燃烧。 安装产品时,务必进行可靠夹持和固定。 否则,可能会因产品翻倒、掉落、异常动作等造成人员受伤。 请勿在本产品上淋水。淋水、清洗或在水中使用,均可能会因异常动作造成人员受伤、触电、火灾等。 因配线作业等拆下护罩作业前,应切断输入电源。 外壳内有高电压,非常危险。
昕芙旎雅株式会社
前言
衷心感谢您选用 C10 系列控制器。 为正确使用本控制器,使用前请务必阅读本使用说明书。 本说明书也适用于维护时参阅,请妥善保管。 另外,请将其交给最终用户。


前言......................................................................................................................................................1 安全注意事项 .......................................................................................................................................2 配线......................................................................................................................................................5 面板基本操作 .......................................................................................................................................7

DCL说明书


(7) 窗口 说 明
窗口编号 内容 设 定值1(SV1)
1-1
说明
*此窗 口设 置第 一个 设定值 *设 置 范围 :传 感器 下限~传 感器 上限 *出厂 值为0
AT自整 定 2-1
*此 窗口设 置仪 表自 整定 功能 *当 处 于自 整定 期间,仪 表AT指示 灯闪 亮
*自 整 定结 束后,P,I, D,A RW参 数自 动 存 储
附: 在 高 低 温 控 制中,左边的DCL测试高 温区温度,右边的DCL测试低温区温度 再 温 湿 度 控 制 中,左边的DCL测试温度,右边的DCL 测试湿度
DCL: 左边
右边
通 信 协 议 :Modbus RTU协议 通信地址: 1
通 信 速 率 :9600bps 校验 选 择:Modbus RTU方式 停止位: 1
(5)D C L - 3 3 A操 作 流程图
按键
P V/ SV显 示
控制输出关闭功能 按 键1秒钟
输出 手动 操作 按 键3秒 钟
+
[主 设置 方式] 2-1[子设置 方式]
设 定 值1(SV1) AT自 整 定
+ 3秒
+隐藏 键 3秒
3
-1[辅助 设置方 式1]
设定之锁定功能
[辅传助感设器置选方择 式2 ]4
W(50A) C5
互 感 器 电 流 :50 A RS -485通 讯
(2) 输 入范 围(用 户在仪表 内自由选择)
输入类型
输入范围
K
- 2 0 0 ~ 1 3 7 0摄 氏 度
- 1 9 9 . 9~ 4 0 0. 0摄 氏 度
J
- 2 0 0 ~ 10 0 0摄 氏 度

神港JC系列通讯说明书

神港JC系列通讯说明书COMMUNICATION INSTRUCTION MANUALJCS, JCM, JCR, JCD-33A, C5No.JC3CE6 2005.04 To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual.WarningTurn the power supply to the instrument off before wiring or checking it.Working or touching the terminal with the power switched on may result in severe injury or death due to Electric Shock.1. System configurationRS-485 multi-drop connection communication (C5 option) (Fig. 1-1)(Fig. 1-2)Please use the IF-400 (sold separately) as a communication converter. 2. WiringWhen using communication converter IF-400 ? 9-pin Dsub connector: Connection: (Communication speed: 2400, 4800, 9600, 19200bps)Host computerConnection: (Communication speed: 2400, 4800, 9600, 19200bps)Shield wireConnect only one side of the shield wire to the FG terminal so that current cannot flow to the shield wire.(If both sides of the shield wire are connected to the FG terminal, the circuit will be closed between the shield wire and the ground. As a result, current will run through the shield wire and this may cause noise.)Be sure to ground the FG terminal. Terminator (Terminal resistor)Do not connect terminator with the communication line because each JC -33A has built-in pull-up and pull-down resistors instead of a terminator.-33AIt is necessary to set the instrument number individually to the JC -33A when communicating byconnecting plural units in serial communication (C5 option).Select a communication speed of the JC -33A in accordance with that of the host computer. ? For the instrument number setting and communication speed, refer to the instruction manual for JC -33A.4. Communication procedureCommunication starts with command transmission from the host computer (hereafter Master) and ends with the response of the JC -33A (hereafter Slave).Response with datathe master sends the reading command, the slaveresponds with the corresponding set value or current ?Acknowledgementthe master sends the setting command, the slaveresponds by sending the acknowledgement after theprocessing is terminated. ? Negative acknowledgement the master sends non-existent command or value out of the setting range, the slave returns the negative ? No responseaddress is set, or when there is a communication error(framing error or checksum error), or when LRC or CRCdiscrepancy is detected.Host computerCommunication timing of the RS-485 (C5 option)Slave sideWhen the slave starts transmission through RS-485 communication line, the slave is arranged so as to provide an idle status (mark status) transmission period of 1 or more characters before sending the response to ensure the synchronization on the receiving side.The slave is arranged so as to disconnect the transmitter from the communication line within a1 character transmission period after sending the response.Master side (Notice on programming)Set the program so that the master can disconnect the transmitter from the communication line withina 1 character transmission period after sending the command in preparation for reception of theresponse from the slave.To avoid the collision of transmissions between the master and the slave, send the next command after carefully checking that the master received the response.5. Shinko protocol5.1 Transmission modeShinko protocol is composed of ASCII codes.Hexadecimal (0 to 9, A to F), which is divided into high order (4-bit) and low order (4-bit) out of 8-bit binary data in command is transmitted as ASCII characters.Data format Start bit : 1 bitData bit : 7 bitsP arity : EvenS top bit : 1 bitError detection: Checksum5.2 Command configurationAll commands are composed of ASCII. The data (set value, decimal number) is represented withhexadecimal number, and ASCII code is used.The negative numbers are represented with 2's complement.(1) Setting command(2) Reading command(3) Response with data(5) Negative acknowledgementHeader: Control code to represent the beginning of the command or the response.ASCII codes are used.Setting command, Reading command : 02H fixedResponse with data, Acknowledgement : 06H fixedNegative acknowledgement : 15H fixed Number ofcharactersNumber ofcharactersNumber ofcharacters Number ofcharactersNumber ofcharactersAddress (Instrument number): Numbers by which the master discerns each slave. Instrument number 0 to 94 (00H to 5EH) and Global address 95 (7FH) The numbers (20H to 7EH) are used by giving 20H of bias, because 00H to 1FH are used for control code.95 (7FH) is called Global address , which is used when the same command is sent to all the slaves connected. However, the response is not returned.Sub address : 20H fixedCommand type : Code to discern Setting command (50H) and Reading command (20H) Data item : Data classification of the command object Composed of hexadecimal 4 digits (Refer to the Communication command table) Data : The contents of data (set value) depend on the setting command Composed of hexadecimal 4 digits (Refer to the Communication command table) Checksum : 2-character data to detect communication errors Delimiter : Control code to represent the end of command 03H fixed Error code : Represents an error type. Composed of hexadecimal 1 digit. 1 (31H)-----Non-existent command 2 (32H)-----Not used 3 (33H)-----Setting outside the setting range 4 (34H)-----Status unable to set (e.g. AT is performing) 5 (35H)-----During setting mode by keypad operation5.3 Checksum calculationChecksum is used to detect receiving errors in the command or data.Set the program for the master side as well to calculate the checksum of the response data from the slaves so that the communication errors can be checked. The ASCII code (hexadecimal) corresponding to the characters which range from the address to that before the checksum is converted to binary notation, and the total value is calculated.The lower 2-digit of the total value are converted to 2’s complements, and then to hexadecimal figures, that is, ASCII code for the checksum. Refer to the following example procedure. Checksum calculation example Main set value: 600 (0258H) Address (instrument number): 0 (20H)1’s complement: Reverse each binary bit. 0 will become 1 and vice ve rsa. ? 2’s complement: Add 1 to 1’s complements.20H50H0010 00000101 00001101 11111+[1's complement][2's complement][Hexadecimal][ASCII]5.4 Contents of the commandNotes on the setting command and reading commandPossible to set the set value by setting command of the communication function even when the set value is locked.Although the options are not applied, setting the items forthe options is possible by the setting command. However, they will not function.The memory can store up to 1,000,000 (one million) entries.If the number of settings exceeds the limit, the data will not be saved. So frequent transmission via communication is not recommended.When connecting plural slaves, the address (instrument number) must not be duplicated.When sending a command by Global address [95 (7FH)], the same command is sent to all the slaves connected. However, the response is not returned.The instrument number and communication speed of the slave cannot be set by communication function.Setting commandThe settable range is the same as that by key operation.For the communication command, refer to the communication command table of this manual. ? All commands are composed of ASCII.The data (set value, decimal) is converted to hexadecimal figures, and ASCII is used.A negative number is represented by 2's complement. When the data (set value) has a decimal point, a whole number without a decimal point is used. Reading commandAll commands are composed of ASCII.The data (set value, decimal) is converted to hexadecimal figures, and ASCII is used.A negative number is represented by 2's complement. When the data (set value) has a decimal point, the response is returned as a whole number without a decimal point.6. Modbus protocol6.1 Transmission modeThere are 2 transmission modes (ASCII and RTU) in Modbus protocol. 6.2 ASCII modeHexadecimal (0 to 9, A to F), which is divided into high order (4-bit) and low order (4-bit) out of 8-bit binary data in command is transmitted as ASCII characters. Data format Start bit : 1 bit Data bit : 7 bits P arity : Even/Odd/No parity (Selectable) S top bit : 1 bit/2 bits (Selectable) Error detection : LRC (Longitudinal Redundancy Check) Data interval : 1 second or less (1) Message configurationASCII mode message is configured to start by [: (colon)(3AH)] and end by [CR (carriage return) (0DH) + LF (Line feed)(0AH)]. (See Fig. 6.2-1)(2) Slave addressSlave address is an individual instrument number on the slave side and is set within the range 00H to 5FH (0 to 95).The master identifies slaves by the slave address of the requested message.The slave informs the master which slave is responding to the master by placing its own address in the response message.[Slave address 00H (broadcast address) can identify all the slaves. However slaves do not respond.] (3) Function code The function code is the command code for the slave to undertake the following action types (T able 6.2-1). (Table 6.2-1) Function code Contents 03 (03H) Reading the set value and information from slaves 06 (06H) Setting to slavesFunction code is used to discern whether the response is normal (acknowledgement) or if any error (negative acknowledgement) is occurred when the slave returns the response message to the master. When acknowledgement isreturned, the slave simply returns the original function code.When negative acknowledgement is returned, the MSB of the original function code is set as 1 for the response.Slave address FunctioncodeDataError check LRC Delimiter (CR)Header (:)Delimiter (LF)(For example, when the master sends request message setting 10H to function code by mistake, slave returns 90H by setting the MSB to 1, because the former is an illegal function.) For negative acknowledgement, exception code (Table 6.2-2) below is set to the data of response message and returned to the master in order to inform it that what kind of error has occurred. (Table 6.2-2)Exception code Contents1 (01H) Illegal function (Non-existent function)2 (02H) Illegal data address (Non-existent data address)3 (03H)Illegal data value (Value out of the setting range)17 (11H)Illegal setting (Unsettable status)18 (12H) Illegal setting (During setting mode by key operation, etc)(4) DataData depends on the function code.A request message from the master is composed of data item, number of data and setting data.A response message from the slave is composed of numberof bytes, data and exception codein negative acknowledgement. Effective range of data is –32768 to 32767 (8000H to 7FFFH).(5) Error check of ASCII modeAfter calculating LRC (Longitudinal Redundancy Check) from the slave address to the end of data, the calculated 8-bit data is converted to two ASCII characters and are appended to the end of message.Create a message in RTU mode.Add all the values from the slave address to the end of data. This is assumed as X.Make a complement for X (bit reverse). This is assumed as X.Add a value of 1 to X. This is assumed as X.Set X as an LRC to the end of the message.Convert the whole message to ASCII characters.Reading (Instrument number 1, SV)A request message from the masterThe number of data means the data item to be read, and it is fixed as (30H 30H 30H 31H).A response message from the slave in normal status (When SV=100)(Fig.6.2-3) The number of response bytes means the number of bytes of the data which has been read,and it is fixed as (30H 32H).A response message from the slave in exception (error) status (When data item is mistaken)The function code MSB is set to 1 for the response message in exception (error) status (83H).The exception code (02H: Non-existent data address) isreturned as contents of error.Setting (Instrument number 1, SV=100)A request message from the master(Fig.6.2-5)A response message from the slave in normal status(Fig.6.2-6)SlaveaddressFunctioncodeData itemError checkLRCDelimiterHeader(30H 31H)Number ofdata(3AH)1224422(30H 33H)(30H 30H 30H 31H)(30H 30H 30H 31H)(46H 41H)(0DH 0AH)Number of charactersSlaveaddressFunctioncodeNumber ofresponse bytesError checkLRCDelimiterHeader Data1222422(3AH)(30H 31H)(30H 33H)(30H 32H)(30H 30H 36H 34H)(39H 36H)(0DH 0AH)Number ofcharacters(0DH 0AH)SlaveaddressFunctioncodeExceptioncodeError checkLRCDelimiterHeader122222Number ofcharacters(3AH)(30H 31H)(38H 33H)(30H 32H)(37H 41H)SlaveaddressFunctioncodeData itemError checkLRCDelimiterHeader(30H 31H)Data(3AH)1224422Number ofcharacters(30H 36H)(30H 30H 30H 31H)(30H 30H 36H 34H)(39H 34H)(0DH 0AH)SlaveaddressFunctioncodeData itemError checkLRCDelimiter Header Data1224422Number ofcharacters (3AH)(30H 31H)(30H 36H)(30H 30H 30H 31H)(30H 30H 36H 34H)(39H 34H)(0DH 0AH)A response message from the slave in exception(error) status (When a value out of the setting range is set)(Fig. 6.2-7)The function code MSB is set to 1 for the response message in exception (error) status (86H). The exception code (03H: Value out of the setting range) is returned as contents of error.6.3 RTU mode8-bit binary data in command is transmitted as it is. Data format Start bit : 1 bit Data bit : 8 bits Parity : Even/Odd/No parity (Selectable) Stop bit : 1 bit/2 bits (Selectable) Error detection : CRC-16 (Cyclic Redundancy Check) Data interval : 3.5 characters transmission time or less (1) Message configurationRTU mode is configured to start after idle time is processed for more than 3.5 character transmission and end after idle time is processed for more than 3.5 character transmission. (See Fig.6.3-1) (Fig. 6.3-1) (2) Slave addressSlave address is an individual instrument number on the slave side and is set within the range 00H to 5FH (0 to 95).The master identifies slaves by the slave address of the requested message.The slave informs the master which slave is responding to the master by placing its own address in the response message.[Slave address 00H (broadcast address) can identify all the slaves. However slaves do not respond.] (3) Function code The function code is the command code for the slave to undertake the following action types (T able 6.3-1). (Table 6.3-1) Function code Contents 03 (03H) Reading the set value and information from slaves 06 (06H) Setting to slavesFunction code is used to discern whether the response is normal (acknowledgement) or if any error (negative acknowledgement) is occurred when the slave returns the response message to the master. When acknowledgement is returned, the slave simply returns the original function code.When negative acknowledgement is returned, the MSB of the original function code is set as 1 for the response.(For example, when the master sends request message setting 10H to function code by mistake, slave returns 90H bysetting the MSB to 1, because the former is an illegal function.) For negative acknowledgement, exception code (Table 6.3-2) below is set to the data of response message and returned to the master in order to inform it that what kind of error has occurred. (Table 6.3-2)Exception code Contents 1 (01H) Illegal function (Non-existent function) 2 (02H) Illegal data address (Non-existent data address) 3 (03H) Illegal data value (Value out of the setting range) 17 (11H) Illegal setting (Unsettable status) 18 (12H) Illegal setting (During setting mode by keypad operation, etc) (4) Data Data depends on the function code.A request message from the master side is composed of data item, number of data and setting data. A response message from the slave side is composed of number of bytes, data and exception code in negative acknowledgement. Effective range of data is –32768 to 32767 (8000H to 7FFFH). (5) Error check of RTU modeAfter calculating CRC-16 (Cyclic Redundancy Check) from the slave address to the end of data, the calculated 16-bit data is appended to the end of message in sequence from low order to high order.3.5 idle characters Slave address Function codeData Error check CRC 3.5 idlecharacters Slave addressFunction codeException codeError checkLRCDelimiterHeader2Number ofcharacters 22221(3AH)(30H 31H)(38H 36H)(30H 33H)(37H 36H)(0DH 0AH)How to calculate CRCIn the CRC system, the information is divided by the polynomial series. The remainder is added to the end of the information and transmitted. The generation of polynomial series is as follows.16 + X 15+ X 2 + 1)Initialize the CRC-16 data (assumed as X) (FFFFH).Calculate exclusive OR (XOR) with the 1st data and X. This is assumed as X.Shift X one bit to the right. This is assumed as X.When a carry is generated as a result of the shift, XOR is calculated by X ofand the fixeduntil shifting 8 times.up to the last data.Set X as CRC-16 to the end of message in sequence from low order to high order. RTU modeReading (Instrument number 1, SV) ? Request message from the masterThe number of data means the data item to be read, and it is fixed as 0001H. ? Response message from the slave in normal status (When SV=100)(Fig. 6.3-3)The number of response byte means number of bytes of the data which has been read, and it is fixed as 02H.Response message from the slave in exception (error) status (When non-existent data item is sent)The function code MSB is set to 1 for the response message in exception (error) status (83H). The exception code (02H: Non-existent data address) is returned as contents of error. Setting (Instrument number 1, SV=100) ? Request message from the masterResponse message from the slave in normal statusResponse message from the slave in exception (error) status (When a value out of the setting range is set)The function code MSB is set to 1 for the response message in exception (error) status (86H). The exception code (03H: Value out of the setting range) is returned as contents of error.3.5 idle charactersSlave address Function code Data itemError check CRC 3.5 idle characters(01H)(03H)(0001H)Number of data (0001H)(D5CAH)11222Number of characters3.5 idle charactersSlave address Function code Number of response bytesError check CRC 3.5 idle characters(01H)(03H)(02H)Data(0064H)(B9AFH)11122characters3.5 idle charactersSlave address Function code Exception code Error check CRC 3.5 idle characters(01H)(83H)(02H)(C0F1H)1112Number of characters3.5 idle charactersSlave address Function code Data item Error check CRC 3.5 idle characters(01H)(06H)(0001H)Data (0064H)(D9E1H)11222characters 3.5 idle charactersSlave address Function code Data item Error check CRC 3.5 idle characters(01H)(06H)(0001H)Data(0064H)(D9E1H)112223.5 idle characters Slave address Function code Exception code Error check CRC 3.5 idle characters(01H)(86H)(03H)(0261H)1112characters7. Communication command tableWhen the data (set value) has a decimal point, remove the decimal point and represent it as a whole number, then express it in hexadecimal figures.Shinko command type ModbusfunctioncodeData item Data20H/50H 03H/06H 0001H: SV1 Set value20H/50H 03H/06H 0002H: Not used20H/50H 03H/06H 0003H: AT/Auto-reset setting 0000H: Cancel 0001H: Perform 20H/50H 03H/06H 0004H: OUT1 proportional band setting Set value20H/50H 03H/06H 0005H: OUT2 proportional band setting Set value20H/50H 03H/06H 0006H: Integral time setting Set value20H/50H 03H/06H 0007H: Derivative time setting Set value 20H/50H 03H/06H 0008H: OUT1 proportional cycle setting Set value20H/50H 03H/06H 0009H: OUT2 proportional cycle setting Set value20H/50H 03H/06H 000AH: Not used20H/50H 03H/06H 000BH: A1 setting Set value20H/50H 03H/06H 000CH: A2 setting Set value20H/50H 03H/06H 000DH: Not used20H/50H 03H/06H 000EH: Not used20H/50H 03H/06H 000FH: HB (Heater burnout alarm)settingSet value20H/50H 03H/06H 0010H: LA (Loop break alarm) timesettingSet value20H/50H 03H/06H 0011H: LA (Loop break alarm) spansettingSet value20H/50H 03H/06H 0012H: Set value lock selection (*1) 0000H: Unlock 0001H: Lock 10002H: Lock 2 0003H: Lock 3 20H/50H 03H/06H 0013H: SV high limit setting Set value20H/50H 03H/06H 0014H: SV low limit setting Set value20H/50H 03H/06H 0015H: Sensor correction value setting Set value20H/50H 03H/06H 0016H: Overlap/Dead band setting Set value20H/50H 03H/06H 0017H: Not used20H/50H 03H/06H 0018H: Scaling high limit setting Set value 20H/50H 03H/06H 0019H: Scaling low limit setting Set value 20H/50H 03H/06H 001AH: Decimal point place selection 0000H: XXXX (No decimal point)0001H: XXX.X (1 digit after decimalpoint)0002H: XX.XX (2 digits after decimalpoint)0003H: X.XXX (3 digits after decimalpoint)20H/50H 03H/06H 001BH: PV filter time constant setting Set value20H/50H 03H/06H 001CH: OUT1 high limit setting Set value 20H/50H 03H/06H 001DH: OUT1 low limit setting Set value 20H/50H 03H/06H 001EH: OUT1 ON/OFF actionhysteresis settingSet value20H/50H 03H/06H 001FH: OUT2 action mode selection 0000H: Air cooling0001H: Oil cooling0002H: Water cooling20H/50H 03H/06H 0020H: OUT2 high limit setting Set value 20H/50H 03H/06H 0021H: OUT2 low limit setting Set value 20H/50H 03H/06H 0022H: OUT2 ON/OFF action hysteresis settingSet value20H/50H 03H/06H 0023H: A1 action selection (*2)0024H: A2 action selection (*2) 0000H: No alarm action0001H: High limit alarm0002H: Low limit alarm0003H: High/Low limits alarm 0004H: High/Low limit range alarm 0005H: Process high alarm0006H: Process low alarm0007H: High limit alarm with standby 0008H: Low limit alarm with standby 0009H: H/L limits alarm w/standby[–200 to 1370400.0[–200 to 1000176017601820800400.013001390[0 to 2315[–199.9 to 850.0[–199.9 to 500.08505002500750.0[–320 to 1800320033001500750.023002500[0 to 4200[–199.9 to 999.9[–199.9 to 900.0[–300 to 15009004 to 20mA DC[–1999 to 9999]20H/50H 03H/06H 0048H: ARW (anti-reset windup) settingSet value20H/50H 03H/06H 006FH: Key Lock selection 0000H:Key enabled0001H: Key Lock50H 06H0070H:Key operation change flagclearing 0000H:No action 0001H: All clearing20H 03H 0080H: PV reading Present PV (input value)20H 03H 0081H: OUT1 MV reading Set value20H 03H 0082H: OUT2 MV reading Set value20H 03H 0083H: Not used20H 03H 0084H: Not used20H 03H 0085H: OUT status reading 0000 0000 0000 0000 215to 2020 digit: OUT10: OFF 1: ON21 digit: OUT20: OFF 1: ON22digit: A1 output0: OFF 1: ON23 digit: A2 output0: OFF 1: ON24 digit: Not used (Always 0)25 digit: Not used (Always 0)26 digit: HB (Heater burnout alarm)output0: OFF 1: ON(When sensor burnout, 0: OFF)27 digit: LA (Loop break alarm)output0: OFF 1: ON28 digit: Overscale0: OFF 1: ON29 digit: Underscale0: OFF 1: ON210 digit: OUT/OFF selection0: OUT 1: OFF211 digit: AT/Auto-reset0: OFF 1: ON212 digit: OUT/OFF key functions election0: OUT/OFF 1: Auto/Manual213 digit: Not used (Always 0)214 digit: Auto/Manual control0: Automatic 1: Manual215 digit: Change in key operation0: No 1: Yes20H 03H 0086H: Not used20H 03H 0087H: Not used20H 03H 00A0H: Not used20H 03H 00A1H: Instrument information reading 0000 0000 0000 0000215to 2020 digit: Not used (Always 0)21 digit: Cooling action0: Not applied 1: Applied22 digit: A1 function0: Not applied 1: Applied23 digit: A2 function0: Not applied 1: Applied24 digit: Not used (Always 0)25 digit: Not used (Always 0)26 digit: HB (Heater burnout alarm)0: Not applied 1: Applied27 digit: LA (Loop break alarm)0: Not applied 1: Applied28 to 215 digit: Not used (Always 0)This is why the set value reverts to the one before Lock 3 when power is turned OFF.(*2) When alarm action type is changed, the alarm set value reverts to the default value and alarm output status is also initialized.NoticeWhen data setting is changed by front keypad operation, the data that is related to the changed item is also changed automatically as shown in Example 1 below.However, when the data setting is changed by communication function, the related data does not change as shown in Example 2 below. (Only the changed data is altered.) (Example 1) SV high limit: 1370SV: 1000When SV high limit is changed to 800 by the front keypad operation, both SV high limit and SV are changed to 800.(Example 2) SV high limit: 1370SV: 1000When SV high limit is changed to 800 by communication function, SV high limit is changed to 800, however, SV ismaintained at the same temperature 1000.8. SpecificationsC able length : Maximum communication distance 1.2km Cable resistance: Within 50 (Terminator is not necessary or 120 or more on one side.)Communication line : EIA RS-485 Communication method : Half-duplexCommunication speed : 9600bps (2400, 4800, 9600, 19200bps) Selectable by keypad Synchronous system : Start-stop synchronous Code form : ASCII, binary Error correction : Command request repeat system Error detection : Parity check, Checksum (LRC), CRC Data format Start bit : 1 Data bit : 7, 8 Parity : Even, Odd, No parity Stop bit : 1, 29. TroubleshootingIf any malfunctions occur, refer to the following items after checking the power supply to the master and the slave.Problem: Communication failureCheck the followingThe connection or wiring of communication cable is not secure.Burnout or imperfect contact on the communication cable and the connector. Communication speed of the slave does not coincide with that of the master.The data bit, parity and stop bit of the master do not accord with those of the slave. The instrument number of the slave does not coincide with that of the command. The instrument numbers are duplicated in multiple slaves.Make sure that the program is appropriate for the transmission timing.Problem: Although communication is occurring, the response is 'NAK'.Check the followingCheck that a non-existent command code has not been sent.The setting command data exceeds the setting range of the slave.The controller cannot be set when functions such as AT are performing. The operation mode is under the front keypad operation setting mode.For further inquiries, please consult our agency or the shop where you purchased the unit.SHINKO TECHNOS CO.,LTD.OVERSEAS DIVISION::::Reg. Office Mail Address URL E-mail1-2-48, Ina, Minoo, Osaka, Japan P.O.Box 17, Minoo, Osaka, Japan http://www.shinko-technos.co.jp overseas@shinko-technos.co.jpTel :Fax:81-72-721-278181-72-724-1760。

FCR-13A-A M神港SHINKO神港温控器代理


深圳温控器
相关阅读: /Controlproduct/view/id/363.shtml
3
等成效可供挑选。●文件组号可由外部设定,可设定7种技术法度典范,编号后便当的移 用。通过进程面板可设定当地或长途控制编制,在按键上可发动键庇护成效,安定、靠 得住。●抗干扰性:对于外表常常操作在工矿企业中,考虑到电网电压及作业现象的鄙 俗,在外表的软、硬件规划上均采用了需求编制,大猛行进了外表的抗干扰性、不变性 ,使之对作业现象的恳求下降为零,存在更广泛的操作价值。●摹拟变换输出成效:可 将实际值、设定值、控制输出值中任一量摹拟变换为DC4~20mA或DC0~1V,传输到 其它设备,满意无法进行数字通讯的体系恳求。●手动/自动编制切换:外表存在手动成 效,可酬报调剂输出值。并在切换进程中完成安稳过渡,不发生扰动。●外形尺度:S48×48×110mm;R-48×96×110mm;D-96×96×110mm(W×H×D)●选型:· 控 制输出:+
FCR-13A-A M神港SHINKO神港温 控器代理
深圳温控器 相关阅读: /Controlproduct/view/id/363.shtml
1
FC简纯挚真智能可编程调剂仪●单组可编程7步自力PID控制●简略可程式控制成效。● 供应多种输入暗号记号与多成效挑选。●供应1组多种动作警报输出的规范装备●外表精 度0.2%●采样周期0.125秒●模糊控制,PID自整定●可通迅,4路自力报警●通过进程 ISO-9001认证及CE、UL等安规合用于热措置、流量、压力等控制。FC系列智能数显调 剂仪:●FC系列智能数显调剂仪是一种高精度,高报价的通用型单回路控制器,存在独 霸精练,自在输入,双四位显现,模糊抗干扰PID自整定,多组PID参数设定,7段可编 程以及RS485或RS232C串行通讯口,外表的精度等第为0.2级,采样周期125ms。●智 能输入:用户可在独霸面板上自在挑选热电偶、热电阻、直流电压、直流电流的输入类 型。输入量程可随意设定。●疾速呼应、行进前辈控制:外表的基赋功Controlproduct/view/id/363.shtml
  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

_
设定值
MODE
PV / SV显示方式 实测温度 主设定值
PV / SV显示方式 实测温度 主设定值
+ MODE 约3秒 设定值锁定选择
选择项
MODE
主设定值上限设定 设定值
MODE
主设定值下限设定 设定值
MODE
传感器补偿设定 设定值
MODE
重叠区/死区设定 设定值
MODE
10
远程/本地选择 方式
输出关闭显示选择 选择项
MODE
14
主设定值上升速率设定 设定值
MODE
PV 上显示 OFF 无任何显示 只在 PV 上显示测量值
主设定值下降速率设定 设定值
MODE
输入异常时输出选择 选择
MODE
PV/SV显示方式 实测温度 主设定值
PV/SV显示方式 实测温度 主设定值
+ 约3秒 程序控制切换
MODE
仪表地址设定 设定值
MODE
波特率选择 选择项
MODE
通信协议选择 选择项
MODE
PV / SV显示方式 实测温度 主设定值
PV / SV显示方式 实测温度 主设定值
+ + MODE 约3秒 刻度范围上限设定
设定值
MODE
刻度范围下限设定 设定值
MODE
小数点位置选择 选择项
MODE
××××. ×××.× ××.××
选择项
约1秒 OUT OFF
OUT OFF
16
PV/SV显示方式 实测温度 主设定值
MODE 约3秒 输出操作值显示方式 实测温度 操作值
MODE
MODE
(定值控制) (程序控制)
步剩余时间显示 实测温度 步剩余时间
MODE
17
OUT OFF
OUT OFF
OUT OFF
OUT OFF
106(特选功能TC)
报警4动作延迟时间设定
开输出/关输出设定模式 开输出时间设定
(约3秒)
程序模式
(约3秒)
定值控制/程序控制选择
关输出时间设定
第1步时间设定
第2步时间设定
第3步时间设定
外部设定输入上限设定 外部设定输入下限设定
第4步时间设定 第5步时间设定 第6步时间设定
变送输出动作选择
第7步时间设定
变送输出上限设定
MODE
主设定值 设定值
MODE
PV / SV显示方式 实测温度 主设定值
+ MODE
存储文件号选择 设定值
MODE
自整定执行/取消 选择项
MODE
MODE
(当执行时)
8
SV
自整定取消
SV
主比例带设定 设定值
MODE
冷却比例带设定
_
设定值
MODE
积分时间设定 设定值
MODE
微分时间设定 设定值
MODE
MODE
传感器补偿值设定
MODE
远程/本地选择
MODE
仪表号设定
MODE
通信速度选择
MODE
29
辅助功能设定模式2
(约3秒)
刻度范围上限设定
刻度范围下限设定
小数点位置选择
PV 滤波时间常数设定 报警3动作方式选择
报警4动作方式选择
报警1动作间距设定
报警3动作间距设定
报警4动作间距设定
报警1动作延迟时间设定 报警3动作延迟时间设定
×.×××
PV滤波时间常数 设定值
MODE
11
主输出上限设定 设定值
MODE
主输出下限设定 设定值
MODE
主输出开/关动作间距 设定值
MODE
冷却动作方式选择 选择项
MODE
冷却输出上限设定 设定值
MODE
冷却输出下限设定 设定值
MODE
冷却输出开/关间距 设定值
MODE
报警3动作方式选择 选择项
29 30
1
PV
PV明显大于SV
※ 在控制范围内 SV

SV明显大于PV
AT启动点 AT启动点
时间
2
3
4
5
仪表通电,预热 2s PV/SV 显示方式
选择
6
7


PV显示器 SV显示器
PV显示器 SV显示器

. .
刻度范围 上限值

. . .
刻度范围 上限值
PV / SV显示方式 实测温度 主设定值


20
FCR
三相
~ 地
开/关
报警 单 元电 源
加热器 电炉
报警 单元 热电偶
21

22
23
1 10000
24
25
26
1000 500
0
单相 地
电炉
报警单元 热电偶
27
(调节仪1)
(调节仪2)
28
附录:FC□-15A操作流程图
仪表通电,预热2S PV/SV 显示方式
主设定
MODE
SV设定
选择项
MODE
MODE
(定值控制)
(程序控制)
定值控制 程序控制
第1步时间设定
_
设定值
MODE
15
第2步时间设定
_
设定值
MODE
第3步时间设定
_
设定值
MODE
第4步时间设定
_
设定值
MODE
第5步时间设定
_
设定值
MODE
第6步时间设定
_
设定值
MODE
第7步时间设定
_
设定值
MODE
PV/SV显示方式 实测温度 主设定值
OUT1比例周期设定 设定值
MODE
OUT2比例周期设定
_
设定值
MODE
手动复位值设定 设定值
MODE
报警1值设定 设定值
MODE
报警2值设定 设定值
MODE
报警3值设定 设定值
MODE
报警4值设定 设定值
MODE
9
加热器断线报警设定 设定值
MODE
回路断线报警时间
_
设定值
MODE
回路断线报警幅度
积分时间设定
M OD E
微分时间设定
M OD E
开/关输出死区设定
M OD E
报警1值设定
M OD E
报警3值设定
M OD E
报警4值设定
MODE
回路异常报警时间设定
MODE
回路异常报警幅度设定
MODE
M OD E (约3秒) 辅助功能设定模式1
设定值锁定选择
MODE
SV上限设定
MODE
SV下限设定
18
106(特选功能 TC) 106(特选功能 TC)
19
100~240V AC 或24V AC/DC
OUT2 (DR,DS,DA)/ A2/程序组结束/ LA/P24
A1/程序组结束
OUT1 (S/M 或 A/M)
TA 或 TV EA 或 EV
W 或 W3
EA 或 EV 或
或 或
OUT1

或 或
MODE
13
报警1延迟时间设定 设定值
MODE
报警2延迟时间设定 设定值
MODE
报警3延迟时间设定 设定值
MODE
报警4延迟时间设定 设定值
MODE
外部设ቤተ መጻሕፍቲ ባይዱ输入上限 设定值
MODE
外部设定输入下限 设定值
MODE
变送输出选择 选择项
MODE
变送输出上限设定 设定值
MODE
变送输出下限设定 设定值
MODE
PV/SV显示方式 实测温度 主设定值
手动控制 实测温度 手操值
OUT OFF
键可暂停控制动作或关闭多台仪表中未用的已通电仪表的控制输出。
PV/SV显示方式
实测温度 主设定值 约1秒 OUT
OFF
[任何模式,如处于冷却动作方式选择时]
控制输出关闭功能
约1秒 OUT OFF
冷却动作方式选择
(*) (不亮)
M OD E
手动控制
OUT OFF
(约1秒)
控制输出OFF功能
定值控制的场合,控制输出OFF功能 程序控制的场合,启动程序控制
MODE (约3秒)
MODE
开输出/关输出操作量显示
步剩余时间显示
M OD E
MODE
基本参数设定 设定值存储文件号选择
M OD E
自整定执行/取消
M OD E
比例带设定
M OD E
MODE
12
报警4动作方式选择 选择项
MODE
报警1常开/常闭选择 选择项
MODE
报警2常开/常闭选择 选择项
MODE
报警3常开/常闭选择 选择项
MODE
报警4常开/常闭选择 选择项
MODE
报警1动作间距 设定值
MODE
报警2动作间距 设定值
MODE
报警3动作间距 设定值
MODE
报警4动作间距 设定值
变送输出下限设定
控制输出关闭时显示选择
操作量演算周期设定
SV 上升速率设定
SV 下降速率设定
过冲抑制功能选择
2008. 07 30
相关文档
最新文档