最新发电机短路电流计算书
短路电流计算书

最大短路电流计算及计算结果5最大短路电流计算及计算结果5.1基本参数:电力系统短路容量:S "kQ =1444MVA电压系数c 1=1.1(66kV)c 2=1.1(6kV)c 3=1(380/220V)TR11A/B变压器变比:t r(0)=U T1/U T2=10.48TR21~24A/B变压器变比:t r(1)=U T1/U T2=15.005.2计算短路回路中各主要元件的阻抗值1)电力系统电抗:66kV 侧: 3.326kV 侧:0.030240.38kV 侧:0.000122)电力变压器阻抗:编号容量短路电压负载损耗二次侧计算电压阻抗电阻电抗(MVA)(kW)(kV)Z rT (Ω)R rT (Ω)X rT (Ω)TR11A/BS rT 20U k %12.0△P r 89.1U T2 6.30.23810.00880.2380TR21A/B S rT 1.6U k % 6.0△P r 14U T20.40.00600.00090.0059TR22A/B S rT 0.25U k % 4.0△P r 2.91U T20.40.02560.00740.0245TR23A/B S rT 0.25U k % 4.0△P r 2.91U T20.40.02560.00740.0245TR24A/BS rT0.5U k %4.0△P r 4.5U T20.40.01280.00290.0125TR11A/B换算至0.4kV侧:4E-050.00115.3计算电路阻抗值1)对k-2点求短路回路总电抗值R ∑(k-2)=R rT(11)=0.0088X ∑(k-2)=Z Qt2+X rT(11)=0.2682R/X=0.033Z ∑(k-2)=0.26842)对k-3点求短路回路总电抗值R ∑(k-3)=R'rT(11)+R rT(21)=0.0009X ∑(k-3)=Z Qt3+X'rT(11)+X rT(21)=0.0061R/X=0.15Z ∑(k-3)=0.00623)对k-4点求短路回路总电抗值R ∑(k-4)=R'rT(11)+R rT(22)=0.0075X ∑(k-4)=Z Qt3+X'rT(11)+X rT(22)=0.0247R/X=0.304Z ∑(k-4)=0.02584)对k-5点求短路回路总电抗值R ∑(k-5)=R'rT(11)+R rT(23)=0.0075X ∑(k-5)=Z Qt3+X'rT(11)+X rT(23)=0.0247R/X=0.304Z ∑(k-5)=0.02585)对k-6点求短路回路总电抗值R ∑(k-6)=R'rT(11)+R rT(24)=0.0029X ∑(k-6)=Z Qt3+X'rT(11)+X rT(24)=0.0126R/X=0.231Z ∑(k-6)=0.0130设计版次B1Z rT =u k %*U 2T2100S rTR rT =△P r *U 2T2S 2rTX rT = Z 2rT -R 2rTR'rT =R rT=1t 2r X'rT =X rT=1t 2r=="2111kQn Qt S U c Z =∙∙=2)1(2)0("213311r r kq n Qt t t S U c Z =∙=2)0("21221r kqn Qt t S Uc Z最大短路电流计算及计算结果设计版次B15.4针对各短路点计算各三相短路电流和短路容量由于在无限大容量电力系统内,所以三相短路稳态电流等于对称开断电流等于三相短路电流最大初始值,即:I k =I b =I "k 短路电流峰值:k≈1.02+0.98e-3R/XS rM 电动机额定视在功率(MVA)J电动机极数P rM 电动机额定功率(MW)q 对称开断电流系数U rM 电动机额定电压(kV)μ衰减常数I LR /I rM 电动机堵转电流与额定电流之比t min最小延时(s)cosφ电动机功率因数对中压电机,设定t min =0.1s ,q=0.57+0.12ln[P rM /(J/2)],对低压电机,设定t min =0.02s ,q=1.03+0.12ln[P rM /(J/2)],当q>1时,取q=1在没有得到电机详细数据表的情况下,假设低压电动机极数为2,中压电动机极数为4。
短路电流的计算方法 Word 文档

1、短路电流的计算方法:1.1、两相短路电流计算公式:I=∑R=R1/K+Rb+R2∑X=Xx+X1/K+Xb+X2式中:I——两相短路电流,A∑R、∑X——短路回路内一相电阻、电抗值的总和,ΩXx——根据三相短路容量计算的系统电抗值,ΩR1、X1——高压电缆的电阻、电抗值,ΩKb——变压器变压比Rb、Xb——变压器的电阻、电抗值,ΩR2、X2——低压电缆的电阻、电抗值,ΩUe——变压器二次侧额定电压,V1.2、三相短路电流计算公式:I=1.15 I2、电缆线路短路保护2.1、1200V及以下电网中电磁式过电流继电器的整定2.1.1、保护干线装置公式:Iz≥IQe+Kx∑Ie式中:IQe——最大容量电动机额定起动电流,A,为电动机额定电流的6.0~7.0倍。
∑Ie——其余电动机额定电流之和,AKx——需用系数,取0.5~1.0,一般取1.0。
2.1.2、校验公式:≥1.5若线路上串联两台以上开关(其间无分支线路),则上一级开关整定值,也应按下一级开关保护范围最远点的两相短路电流来校验,校验灵敏度应满足1.2~1.5的要求,以保证双重保护的可靠性。
若校验不满足时,应采取以下措施:1.加大干线或支线电缆截面。
2.设法减少低压电缆线路的长度。
3.采用相敏保护器或软起动等新技术提高灵敏度。
4.更换大容量变压器或采取变压器并联。
5.增设分段保护开关。
6.采用移动变电站或移动变压器。
2.2、电子保护器的整定:2.2.1、电磁起动器中电子保护器过流整定公式:Iz≤Ie当运行中电流超过Iz时视为过载,电子保护器延时动作;当运行中电流达到8Iz时视为短路,电子保护器瞬时动作。
2.2.2、校验公式:≥1.2若校验不满足时,应采取以下措施:1.加大干线或支线电缆截面。
2.设法减少低压电缆线路的长度。
3.采用相敏保护器或软起动等新技术提高灵敏度。
4.更换大容量变压器或采取变压器并联。
5.增设分段保护开关。
6.采用移动变电站或移动变压器。
短路计算书

3333有限公司目录发变组系统短路计算说明 (2)第一部分设备参数表 (3)表1、#1发电机参数表 (3)表2、#2发电机参数表 (4)表3、#1主变参数表 (5)表4、#2主变参数表 (6)表5、110K V系统参数表 (6)表6、各电压等级的基准值 (6)第二部分发变组系统短路电流计算阻抗图 (7)2.1、301II站母联开关断开情况下,短路计算阻抗图 (7)2.2、301II站母联开关闭合情况下,短路计算阻抗图 (8)第三部分三相短路电流计算 (9)3.1、301II站母联开关断开情况下各故障点短路电流计算 (9)3.1.1、当d1点(110kV母线)发生三相短路 (9)3.1.2、当d2点(1#发电机出口)发生三相短路 (11)3.1.3、当d3点(2#发电机出口)发生三相短路 (17)3.2、301II站母联开关闭合情况下各故障点短路电流计算 (23)3.2.1、当d4点(110kV母线)发生三相短路 (23)3.2.2、当d5点(10.5kV I段母线段)发生三相短路 (29)3.2.3、当d6点(10.5kV II段母线段)发生三相短路 (31)第四部分两相相间短路电流计算 (33)4.1、301II站母联开关断开情况下各故障点短路电流计算 (34)4.1.1、当d1点(110kV母线)发生两相短路 (34)4.1.2、当d2点(1#发电机出口)发生两相短路 (35)4.1.3、当d3点(2#发电机出口)发生两相短路 (38)4.2、301II站母联开关闭合情况下各故障点短路电流计算 (41)4.2.1、当d4点(110kV母线)发生两相短路 (41)4.2.2、当d5点(10.5kV I段母线)发生两相短路 (44)4.2.3、当d6点(10.5kV II段母线)发生两相短路 (45)发变组系统短路计算说明计算步骤及方法参考《电力系统分析》(何仰赞等著,华中理工大学出版社)以及《电力系统继电保护与安全自动装置整定计算》(崔家佩等著,中国电力出版社),使用的设备参数均来自其技术协议及出厂试验报告。
近端短路的一台发电机馈电的三相短路电流初始值I″k的计算

三、近端短路的一台发电机馈电的三相短路电流初始值I″k的计算1.按公式计算靠近发电机端或有限电源容量的网络发生短路的主要特点是:电源母线上的电压在短路发生后的整个过渡过程不能维持恒定,短路电流交流分量随之变化,见图4-1 (b),电源的内阻抗不能忽略不计。
图4-1 短路电流波形图(a)远端短路时的电流波形图;(b)近端短路的电流波形图I″k—对称短路电流初始值; ip—短路电流峰值; Ik—稳态短路电流iDC—短路电流直流分量; A—直流分量iDC的初始值短路电流的变化与发电机的电参数及电压自动调整装置的特性有关。
工程设计中常采用运算曲线法计算短路过程某一时刻的短路电流交流分量。
因为同步电机的转子绕组(等效阻尼绕组及励磁绕组)的磁链在突然短路瞬间不能突变,与转子绕组的磁链成正比的超瞬态电动势E″,在突然短路瞬间仍保持短路前的数值,因此短路电流交流分量的起始值,即超瞬态短路电流有效值I″k可利用公式直接计算对于汽轮发电机(4-17)或(4-18)对于水轮发电机(4-19)式中Ij——基准电流,kA;E″——发电机超瞬态电动势,工程计算中可以认为E″≈UrG,kV;UrG——发电机额定电压,kV,UrG=1.05Un;Un——系统标称电压,kV;X″d——发电机超瞬态电抗,Ω;Xw——自发电机出口至短路点间的短路电路电抗,Ω;X″*d、X*w——以发电机额定总容量SnΣ为基准容量的X″d和Xw的标幺值;K——考虑到水轮发电机的超瞬态电抗X″d值比较大而引入的计算系数,见表4-14。
表4-14 水轮发电机的计算系数K值2.按发电机运算曲线计算用运算曲线(图4-4~图4-12) 或查相对应的发电机运算曲线数字表(表4-15~表4 -18)计算交流分量是十分简便的。
由于在制定运算曲线时计及了同步电机的过渡过程和负荷对交流分量的影响,因而也是比较准确的。
用运算曲线计算交流分量的步骤如下:图4-4 汽轮发电机运算曲线(一) (Xc=0.12~0.5,t=0~1s)图4-5 汽轮发电机运算曲线(二) (Xc=0.12~0.5,t=1~4s)图4-6 汽轮发电机运算曲线(三) (Xc=0.5~3.45,t=0~0.2s)图4-7 汽轮发电机运算曲线(四) (Xc=0.5~3.45,t=0.2、0.6s)图4-8 汽轮发电机运算曲线(五) (Xc=0.5~3.45,t=0.6~4s)图4-9 水轮发电机运算曲线(一) (Xc=0.5~3.5,t=0、0.1s)图4-10 水轮发电机运算曲线(二) (Xc=0.18~0.56,t=0~0.4s)图4-11 水轮发电机运算曲线(三) (Xc=0.18~0.56,t=0.4~4s)图4-12 水轮发电机运算曲线(四)(Xc=0.5~3.5,t=0.1~4s)(1) 网络简化。
短路电流的简便估算法

短路电流的简便估算法沈 坚在工程设计中,我们经常需要确定变压器的阻抗值是否满足电气设备的开断水平,这就需要进行短路电流计算。
《电力工程电气设计手册》中叙述的计算方法虽然计算结果比较准确,但是计算过程比较复杂。
我们可以通过变压器、发电机的额定电流除以短路电压百分值或次暂态电抗百分值,快速得到短路电流的估算值。
以下分三种情况介绍计算方法和算例。
一.由发电机提供的短路电流I"I"X √(Ue为额定电压,X’’d为发电机次暂态电抗值)将X d X/、S Pe/cos 和S √3UeIe 代入上式,经化简可得:I Ie/X(Ie为额定电流,X为发电机电抗百分值)算例:某600MW发电机的额定电流为18525A,X为20.49%,求发电机供的短路电流值。
解:I Ie/X=18525/0.2049=90.41kA二.双卷变压器低压侧的短路电流I"I"X √(Ue为额定电压,X’’d为变压器电抗值)将Xd和Se √ 代入上式,经化简可得:I Ie/(Ie为额定电流,为变压器短路电压百分值)算例:某双卷变压器容量为2500KVA, 变比为10/0.4‐0.23kV, 短路电压百分值为10%,变压器低压侧额定电流为3798A。
求变压器低压侧的短路电流。
解:I Ie/ =3798/0.10=37.98 kA对于380V系统,当考虑电动机反馈电流时,计算结果应乘以1.3的修正系数;对于10KV或6KV系统,不用乘以修正系数。
即:37.98X1.3=49.374 kA。
若按《火力发电厂厂用电设计技术规定》附录N的计算方法,短路电流计算值为48.8 kA。
由此看出,用估算法计算出的短路电流值比较接近真实值。
三.分裂变压器低压侧的短路电流I"先按高低压绕组容量的比例,把以高压绕组额定容量为基准的半穿越短路电抗折算为低压分裂绕组的电抗值,再根据上述双卷变压器的短路电流的估算法。
高压短路电流计算书

高压短路电流计算书1.计算依据《工业与民用配电设计手册》第三版(中国电力出版社)第四章p123~p152页2.假定条件(1)假定短路电流是由不衰减的交流分量和以初始值A衰减到零的直流分量组成,可认为远端短路的对称电流初始值I”k和稳态短路电流I k是相等的,即称为远端短路;(2)高压短路只计及各元件(发电机、变压器、电抗器、线路等)的电抗,不计电阻。
3.计算方法标幺制4.已知条件(用户输入)总电抗标幺值X*= 10基准容量S j= 100(MVA)系统标称电压U n=10(kV)= 5.5(kA)基准电流I j= j√3∗1.05∗U峰值系数K p= 1.85.计算流程短路容量:S k=S j/X* (MVA)三相短路电流初始值:I”k(3)=I j/X*(kA)三相短路稳态电流有效值:I k(3)= I”k(3)(kA)三相短路峰值电流:i p(3)=K p∗√2∗I”k(3)(kA)三相短路全电流最大有效值:I p(3)= I”k(3)∗√1+2(K p−1)2(kA)两相不接地短路电流初始值:I”k(2)=0.866*I”k(3)(kA) =两相不接地短路稳态电流有效值:I k(2)=0.866*I k(3)(kA)两相不接地短路峰值电流:i p(2)=0.866*i p(3)(kA)两相不接地短路全电流最大有效值:I p(2)=0.866*I p(3)(kA)6.输出结果短路容量:S k(MVA) = 10 (MVA)三相短路电流初始值:I”k(3)(kA) = 0.55(kA)三相短路稳态电流有效值:I k(3)(kA) = 0.55(kA)三相短路峰值电流:i p(3)(kA) = 1.4( kA)三相短路全电流最大有效值:I p(3)(kA) = 0.83 (kA)两相不接地短路电流初始值:I”k(2)(kA) = 0.48(kA)两相不接地短路稳态电流有效值:I k(2)(kA) = 0.48 (kA)两相不接地短路峰值电流:i p(2)(kA) =1.21( kA)两相不接地短路全电流最大有效值:I p(2)(kA) =0.72(kA)。
电网短路电流计算(发电机并网)
短路电流计算书(发电机并网)一、原始数据系统阻抗标么值为0.0122(最大运行方式),0.0428(最小运行方式) 取基准容量MVA S j 100=,基准电压N av j U U U 05.1==(对应于各电压等级10.5kV ,0.4kV ) 电气设备参数如下:(1) 发电机G1~G2:MW P e 7=,,8.0cos =φ MVA P G e e 75.8cos /==φ,13%''=d X(2) 主变压器1T~2TMVA S S T T 921==,9%=k U(3) 辅助变压器 3T~4T MVA S S T T 243==,9%=k U (4) 厂用变压器5T~8T MVA S S S S T T T T 28765====,9%=k U 三、各元件阻抗参数计算发电机(G1~G2): φcos /100''e j dG P S X X ⨯= =⨯==8.0/71001001321G G X X 1.4857 主变压器(1T~2T ): ejk T S S U X ⨯=100% 19100100921=⨯==T T X X 辅助变压器(5T ): ejk T S S U X ⨯=100% 5.42100100943=⨯==T T X X 厂用变压器(3T~4T ):ejk T S S U X ⨯=100% 5.42100100943=⨯==T T X X四、电气主接线图五、阻抗系统图六、短路电流计算(1)求计算电抗及查表求电流标幺值t I *对于无限大容量系统:01CI I X **∞*== 对于发电机(有限容量系统):先求计算电抗**Gejs m jS X X S =⨯,再查表得到电流标幺值t I *(2)计算短路电流、冲击电流和短路容量对于无限容量系统:电流基准值b S I =短路电流0"b I I I I *∞==⨯ 短路容量"j C CS S X*=对于发电机(有限容量系统):电流基准值(归算到短路点)Gb I =短路电流t t Gb I I I *=⨯短路容量""C av S U I =冲击电流''2I K i sh sh =,在实用计算中,当短路发生在发电机电压母线时,取9.1=sh K ;短路发生在发电厂高压侧母线时,取85.1=sh K ;在其他地点短路时,取8.1=sh K .全电流系数2)1(21-+sh K1.1系统S 出口6.6KV 母线k1 点短路 (1)系统及其等值网络的化简各电源的计算电抗如下: 最大运行方式:2175.01008.0/74857.2.1131/=⨯=⨯=j G G js S S X X 2175.01008.0/74857.2.2142/=⨯=⨯=j G G js S S X X 0122.01/==X X S js最小运行方式:2175.01008.0/74857.2.1131/=⨯=⨯=j G G js S S X X 2175.01008.0/74857.2.2142/=⨯=⨯=j G G js S S X X 0428.01/==X X S js1) 系统S 供给K1点的短路电流:最大运行方式:短路电流周期分量起始值: )(2265.1350122.013531001''kA X I I I S=⨯⨯===∞起始短路容量: )(7213.81960122.01001"MVA X S S j S===短路电流冲击值: )(3543.3632265.1359.122''kA I K i S sh sh =⨯⨯==式中,因为短路发生在发电机电压母线,取9.1=sh K 最小运行方式:短路电流周期分量起始值:)(5415.380428.0135310012''kA X I I I S=⨯⨯===∞起始短路容量:)(4486.23360428.010012"MVA X S S j S ===短路电流冲击值:)(5612.1035415.389.122''kA I K i S sh sh =⨯⨯==式中,因为短路发生在发电机电压母线,取9.1=sh K 2) 发电机G1供给K1点的短路电流: 最大运行方式:根据1/G js X 的值,可以从汽轮发电机计算曲线数字表中查得各电流的标幺值为发电机G1:==0*"*I I 4.75,=∞*I 3.0 换算到35kV 的发电机额定电流为 )(1443.035311kA S I G b G =⨯=所以短路电流周期分量起始值:)(6856.01443.075.41"*''1kA I I I b G G =⨯==稳态短路电流有效值:)(6854.01443.075.41*1kA I I I b G G =⨯==∞∞起始短路容量:)(5623.416856.03533''1''1MVA I U S G av G =⨯⨯== 短路电流冲击值:)(8422.16856.09.122"11kAI K i G sh G sh =⨯⨯==∙最小运行方式:计算过程和结果与最大运行方式相同。
发电机继电保护毕业设计短路计算
(注:2#、3#、4#机组各相关电气元件参数同上)
5、低压厂用工作变:SG-1600/10 6.3 Ud%=10.5
6、双调线和双北线与系统相连,系统侧等值参数:
解:设
1#发电机: =0.165
1#主变压器: =0.145 0.039
发电机出口短路:
备用变压器:
一号厂用变:
发电机额定电流: (KV)
电流互感器变比:
因此电流互感器变比取:2000
根据上述标幺值计Biblioteka ,得等值阻抗图,如下图3.1所示:
1#厂用变压器等值变换
图3.1由三角形变成星行
因此得3.2如下等值电路图
计算书
3短路计算
3.1标幺值计算
原始数据:
1、一号发电机F1:QFSN-300 =20KV = 16.5%COS =0.95
2、一号主变B1: SFP7-370000/220(242 2 2.5%)kv/20kv =370MW Ud%=14.5
YN/ -11
3、一号厂用工作变10B: SFP7-40000/20 40/25-25MVA (20 2 2.5%)KV/6.3-6.3 Ud1-2%=
短路电流计算书
短路电流计算书一.短路电流计算的目的电力系统短路电流计算的主要目的是:1)电气主接线比选2)选择导体和电气3)确定中性点接地方式4)计算软导线的短路摇摆5)确定分裂导线间隔棒的间距6)验算接地装置的接触电压和跨步电压7)选择继电保护装置和进行整定计算二.基本的假定条件和一般规定1.假定条件短路电流实用计算中,采用以下假定条件和原则:1)正常工作时,三相系统对称运行。
2)所有电源的电动势相位角相同。
3)系统的同步电机和异步电机均为理想电机,不考虑电机磁饱和,磁滞涡流及导体集肤效应等影响;转子结构完全对称;定子三相绕组空间位置相差120o电气角度。
4)电力系统各元件磁路不饱和,即带铁芯的电气设备电抗值不随电流大小发生变化。
5)电力系统所有电源都在额定负荷下运行,其中50%负荷在高压母线上,50%在系统侧。
6)同步电机都具有自动调整励磁装置(包括强行励磁)。
7)短路发生在短路电流为最大值的瞬间。
8)不考虑短路点的电弧阻抗和变压器的励磁电流。
9)除计算短路电流的衰减时间常数和低压网络的短路电流外,元件的电阻都忽略不计。
10)元件的计算参数均取其额定值,不考虑参数的误差和调整范围。
11)输电线路的电容略去不计。
12)用概率统计法制定短路电流运算曲线。
2.一般规定1)验算导体和电器动稳定,热稳定以及电器开断电流所用的短路电路,应按本工程的设计规划计算,并考虑电力系统的远景规划(一般为本期工程建成后5-10年).确定短路电流时,应按可能发生最大短路电流的正常接线方式,而不是按仅在切换过程中可能并列运行的接线方式。
2)选择导体和电器用的短路电流,在电气连接的网络中,应考虑具有反馈作用的异步电动机的影响和电容补偿装置放电电流的影响。
3)选择导体和电器时,对不带电抗器回路的计算短路点,应选择在正常接线方式时短路电力为最大的地点。
对带电抗器的6-10kV出线与厂用分支线回路,除其母线与母线间隔开关之间隔板前的引线和套管的计算短路点应该选择在电抗器前外,其余导体和电气的计算短路点一般选择在电抗器后。
(完整版)短路电流的计算方法
第七章短路电流计算Short Circuit Current Calculation§7-1 概述General Description一、短路的原因、类型及后果The cause, type and sequence of short circuit1、短路:是指一切不正常的相与相之间或相与地(对于中性点接地的系统)发生通路的情况。
2、短路的原因:⑴元件损坏如绝缘材料的自然老化,设计、安装及维护不良等所造成的设备缺陷发展成短路.⑵气象条件恶化如雷击造成的闪络放电或避雷器动作;大风造成架空线断线或导线覆冰引起电杆倒塌等.⑶违规操作如运行人员带负荷拉刀闸;线路或设备检修后未拆除接地线就加电压.⑷其他原因如挖沟损伤电缆,鸟兽跨接在裸露的载流部分等.3、三相系统中短路的类型:⑴基本形式: )3(k—三相短路;)2(k—两相短路;)1(k—单相接地短路;)1,1(k—两相接地短路;⑵对称短路:短路后,各相电流、电压仍对称,如三相短路;不对称短路:短路后,各相电流、电压不对称;如两相短路、单相短路和两相接地短路.注:单相短路占绝大多数;三相短路的机会较少,但后果较严重。
4、短路的危害后果随着短路类型、发生地点和持续时间的不同,短路的后果可能只破坏局部地区的正常供电,也可能威胁整个系统的安全运行。
短路的危险后果一般有以下几个方面。
(1)电动力效应短路点附近支路中出现比正常值大许多倍的电流,在导体间产生很大的机械应力,可能使导体和它们的支架遭到破坏。
(2)发热短路电流使设备发热增加,短路持续时间较长时,设备可能过热以致损坏。
(3)故障点往往有电弧产生,可能烧坏故障元件,也可能殃及周围设备. (4) 电压大幅下降,对用户影响很大. (5) 如果短路发生地点离电源不远而又持续时间较长,则可能使并列运行的发电厂失去同步,破坏系统的稳定,造成大片停电。
这是短路故障的最严重后果。
(6) 不对称短路会对附近的通讯系统产生影响。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
2.119
发电机定子电阻(22℃) Ra
Stator Winding Resistance(22℃)
0.0018Ω/相
发电机直轴超瞬态时间常数Td"
Sub-Transient Time CONST
0.014S
发电机直轴瞬态时间常数Td'
Transient Time CONST
DIR .AXIS Subtransient
0.108
发电机直轴瞬态电抗Xd'
DIR .AXIS Transient
0.157
发电机直轴电抗Xd
DIR .AXIS Synchronous
1.767
发电机定子电阻(22℃) Ra
Stator Winding Resistance(22℃)
0.059Ω/相
发电机短路电流计算书
发电机型号
Generator Type
UCM274C
额定输出功率
Rating
80KVA
额定电压
Voltage
400V
发电机直轴超瞬态电抗Xd"
DIR .AXIS Subtransient
0.108
发电机直轴瞬态电抗Xd'
DIR .AXIS Transient
0.157
发电机直轴电抗Xd
发电机直轴超瞬态时间常数Td"
Sub-Transient Time CONST
0.01S
发电机直轴瞬态时间常数Td'
Transient Time COure Time CONST
0.007S
稳态短路电流
Sustained Short Circuit Current
0.028S
发电机电枢时间常数Td
Armature Time CONST
0.007S
稳态短路电流
Sustained Short Circuit Current
430Amps@50HZ
发电机型号
Generator Type
UCM274C
额定输出功率
Rating
80KVA
额定电压
Voltage
400V
发电机直轴超瞬态电抗Xd"
DIR .AXIS Synchronous
1.767
发电机定子电阻(22℃) Ra
Stator Winding Resistance(22℃)
0.059Ω/相
发电机直轴超瞬态时间常数Td"
Sub-Transient Time CONST
0.01S
发电机直轴瞬态时间常数Td'
Transient Time CONST
430Amps@50HZ
发电机型号
Generator Type
LVM634F1
额定输出功率
Rating
1000KVA
额定电压
Voltage
400V
发电机直轴超瞬态电抗Xd"
DIR .AXIS Subtransient
0.082
发电机直轴瞬态电抗Xd'
DIR .AXIS Transient
0.113
发电机直轴电抗Xd
0.103S
发电机电枢时间常数Td
Armature Time CONST
0.035S
稳态短路电流
Sustained Short Circuit Current
4480Amps@50HZ