SPAJ 142C通用过流及接地保护继电器用户手册及技术说明2SPAJ 142C通用过流及接地保护继电器发布:1997-10-14状态:2002.04.24版本: B (replaces 34 SPAJ 18 EN1)目录特性......................................................................................................................................................2用途......................................................................................................................................................2动作原理..............................................................................................................................................3接线原理图...........................................................................................................................................4接线端子..............................................................................................................................................6模块之间的控制信号............................................................................................................................7信号缩写符说明...................................................................................................................................7动作指示器...........................................................................................................................................8电源与输出继电器模块........................................................................................................................9技术数据..............................................................................................................................................10维护与检修...........................................................................................................................................13备件......................................................................................................................................................13安装尺寸与说明...................................................................................................................................14订货须知..............................................................................................................................................15通用过流及接地保护继电器SPAJ 142C 全套手册包括如下分册:通用过流及接地保护继电器SPAJ 142C D 型继电器模块的一般特性SPCJ 4D29型组合式过电流与接地故障模块特性具定时限或反时限特性的过电流保护具瞬时或定时限特性的电流速断保护具定时限或反时限特性的零序过电流保护具瞬时或定时限特性的零序电流速断保护断路器失灵保护可选择的输出继电器配置灵活的串行通讯功能灵活的功能配置适用于各种不同的应用数字显示整定值、测量值及故障记录值连续的自检功能用途SPAJ 142C 通用过流及接地保护继电器是主要用于电力系统中直接接地、电阻接地或阻抗接地的辐射式电网中,作为有选择性的短路和零序电流接地保护。

ABB综合保护器的实践应用

ABB综合保护器的实践应用

ABB综合保护器的实践应用摘要:主要对ABB综合保护器应用过程中出现的一些问题进行了简单的阐述及应用效果小结,它还有许多功能需要我们进一步的研究,以便将来更好的加以利用。

关键词:综合保护器;过流;保护;程序一引言我厂部分6KV高压柜的原电流保护采用DL-32型电磁继电器,这种继电器容易误动,由于其接线端子绝缘性能变差,容易造成短路导致保护回路误动,影响生产。

因此决定选用新型综合保护继电器予以替代,经过对国内外多种新型综合保护器调研,选择ABB的SPA系列综合保护器,以取代原先使用的分立式保护继电器,在装置大修期间进行实施。

该SPA系列综合保护器为多功能,数字式保护继电器,它集控制、保护、监测于一体,具有可靠性高、设计统一、功能层次完善的特点,代表了当今保护和控制领域的优良品质,它采用了功能强大的微处理器,对测量、采集的数据进行数字式的计算和处理,从而大大抑制了高频干扰和直流暂态分量的影响。

广泛应用于辐射状配电系统与电机保护系统,也能用于线路、变压器和发电机保护的后备保护装置,带定叶限或反时限(IDMT)特性的三相低定值过电流元件,瞬时或定时限功能的三相高定值过电流元件等,提供过流,速断、接地等保护,同时本身带有内部故障自动诊断的连续自检装置。

此外,通过SPA总线的光缆串行通信口,可获得任何继电器的数据,对应于继电器的参数以及测量记录和记录变量,结果等具有功能强大的支持性软件。

建厂投产初期投用的部分6KV高压柜为铠装落地式封闭开关柜,提供过流,速断、接地保护功能的均为感应式传统继电器,已不适应现代保护集成化、智能化、系统化的自动控制要求。

同时原进口的保护继电器已月超老化,其备品备件已难以在市面购置,急需进行更新和替代。

经过对各型综保的选型筛选,以及电网公司中压综合保护器多年的实际使用经验,选用ABB的SPA系列综合保护器,其中电动机配出柜选用SPAM150C型综合保护器、进线与变压器配出柜选用SPAJ140C与SPAJ142C型综合保护器,暂不考虑综保的系统组网问题,全部为现场调试和就地测量、显示和监控。

ABB通用过流及接地保护继电器SPAJ 142C

ABB通用过流及接地保护继电器SPAJ 142C

SPAJ 142C通用过流及接地保护继电器用户手册及技术说明2SPAJ 142C通用过流及接地保护继电器发布:1997-10-14状态:2002.04.24版本: B (replaces 34 SPAJ 18 EN1)目录特性......................................................................................................................................................2用途......................................................................................................................................................2动作原理..............................................................................................................................................3接线原理图...........................................................................................................................................4接线端子..............................................................................................................................................6模块之间的控制信号............................................................................................................................7信号缩写符说明...................................................................................................................................7动作指示器...........................................................................................................................................8电源与输出继电器模块........................................................................................................................9技术数据..............................................................................................................................................10维护与检修...........................................................................................................................................13备件......................................................................................................................................................13安装尺寸与说明...................................................................................................................................14订货须知..............................................................................................................................................15通用过流及接地保护继电器SPAJ 142C 全套手册包括如下分册:通用过流及接地保护继电器SPAJ 142C D 型继电器模块的一般特性SPCJ 4D29型组合式过电流与接地故障模块特性具定时限或反时限特性的过电流保护具瞬时或定时限特性的电流速断保护具定时限或反时限特性的零序过电流保护具瞬时或定时限特性的零序电流速断保护断路器失灵保护可选择的输出继电器配置灵活的串行通讯功能灵活的功能配置适用于各种不同的应用数字显示整定值、测量值及故障记录值连续的自检功能用途SPAJ 142C 通用过流及接地保护继电器是主要用于电力系统中直接接地、电阻接地或阻抗接地的辐射式电网中,作为有选择性的短路和零序电流接地保护。

SPAJ140C

SPAJ140C
•具有定時(Definite Time)特性的保護特性 •可以經由設定直接關閉此功能(SGF)
– 3.配合適當設定可以由電驛外面輸入信號抑制所 有或某種保護功能(SGB) – 4.配合適當設定可以直接操作或由電驛外面輸入 信號,做兩組保護功能設定值的同時切換動作(SGB)
IL2:4,5腳( In=5)或4,6腳(In=1);輸入S相電流 68,69腳,跳脫信號,不適合直接跳CB IL3:7,8腳( In=5)或7,9腳(In=1);輸入T相電流 74,75腳,跳脫或起動信號,可以直 接跳CB Io:25,26腳( In=5)或25,27腳(In=1);輸入零相電流 外面輸入的(BS)電壓信號, 配合參數SGB設定使用 77,78腳,啟動信號,不適合直接跳CB 電驛正常運作時71,72腳開路, 反之71,72腳閉合 通訊埠
0.8 0
12
–電流大小(Tap)與時間參數(Level)
• I>/In 51 級保護之啟動電流設定值的指示器:定時曲線時 0.5~5.0In;反時曲線時0.5~2.5In(Tap) • t>;K 51 級保護之動作時間t>或時間倍數K設定值(Level)。 配合SGF設定,確定此處設定值代表的意義為t>或K,設定範圍: k 0.05 ~ 1;t 0.04 ~ 300s) • I>>/In 50 級保護之啟動電流設定值(Tap) • t>> 50 級保護之動作時間t>>設定值(Level) • Io>/In 51N 保護級之啟動電流設定值(0.1-0.8In)(Tap) • to>;Ko 51N 級保護之動作時間to>或時間倍數K設定值(Level) 配合SGF設定,確定此處設定值代表的意義為to>或Ko • Io>>/In 50N 級保護之啟動設定值(Tap) • to>> 50N 級保護之動作時間to>>設定值(Level)

中压配电产品基础知识5

中压配电产品基础知识5

中压配电产品基础知识第一部分真空断路器一、ABB:型号意义:VD4 12 06 --- 25↓↓↓↓真空断路器名称电压等级额定电流分断能力12:12KV 06:630A 25:25KA额定电流: 06:630A 12:1250A 16:1600A, 20:2000A 25:2500A 31:3150A 40:4000A型号意义:EV12 06 25 210 D↓ ↓ ↓ ↓ ↓真空断路器名称 额定工作电流 额定短路开断电流 相间距离 断路器类型06 :630A 25: 25KA 210mm 手车式<F 固定式>额定工作电流: 06 :630A 12:1250A 16:1600A, 20:2000A 25:2500A 31:3150A 40:4000A型号意义:VS1 – B (ZN63A) 12/ 3150 - 40↓ ↓ ↓ ↓ ↓ ↓真空断路器 常州江南森 产品设计序号 额定电压KV 额定电流A 额定短路四、常熟型号意义:C V 1 - 12 / T □□↓↓↓↓↓↓↓常熟真空断设计额定弹簧操额定额定短路开关路器序号电压KV 作机构电流A 开断电流KA型号意义:RM VS 1-- 12 / 1250 ----- 31.5↓↓↓↓↓↓上海人民电器厂真空断路器设计序号额定电压KV 额定电流 A第二部ABB -VSC 真空接触器型号意义:VSC 7 400A↓↓↓VSC 真空接触器额定电压KV 7:7.2KV 额定电流DTSF系列10KV交流金属全封闭六氟化硫环网开关柜生产厂家:汕头市德通开关有限公司。

1)产品特点:A:免维护。

B:体积小。

C:安全环保。

D:操作方便。

E:扩展能力强。

F:机械寿命长。

G:技术方案灵活多变。

H:配件、附件加装或安装方便。

2)适用场合:广泛应用于10KV额定电流630A的工业及民用电缆环网及供电末端。

特别适用于电力系统中作为接受和分配电能之用:A:开闭所。

B:高层建筑。

SPAJ142C型过电流和接地故障组合继电器-1

SPAJ142C型过电流和接地故障组合继电器-1

SPAJ 142 C型过电流和接地故障组合继电器用户手册和技术说明ABB Network Partner1MRS 750873-MUM EN1997 10 14 发行A版(替换34 SPAJ 18 EN1)检查:PH批准:PH资料中的数据如有改变,恕不通知。

目录性能------------------------------------------------------------------------------------- 3 用途------------------------------------------------------------------------------------- 3 操作说明-------------------------------------------------------------------------------- 3 连接图----------------------------------------------------------------------------------- 5 连接------------------------------------------------------------------------------------- 6 模块之间的控制信号----------------------------------------------------------------- 8 所用信号的缩写----------------------------------------------------------------------- 9 操作指示器----------------------------------------------------------------------------- 10 电源和输出继电器模块-------------------------------------------------------------- 12 技术数据-------------------------------------------------------------------------------- 13 维护和维修----------------------------------------------------------------------------- 17 备件------------------------------------------------------------------------------------- 18 外形尺寸和安装说明----------------------------------------------------------------- 18 订购须知-------------------------------------------------------------------------------- 19SPAJ 142 C型继电器手册包含下列各分手册:对继电器的一般说明1MRS 750873-MUM END-型继电器模块的一般性能1MRS 750066-MUM ENSPCJ 4D29型过电流和接地故障模块1MRS 750119-MUM EN2性能三相低设置的过流装置带有有限时间或反时间(IDMT)的性能。

ABB继电器选型资料

ABB继电器选型资料

开关量输入和输出接点数量
输入/输出接点数量 开关量输入接点 跳闸回路监视输出接点
REF 541 15 2
REF 543 25 2
REF 545 34 2
大容量输出接点(NO 单极)
0
大容量输出接点(NO 双极)
5
信号输出接点(NO)
2
2
3
9
11
2
4
信号输出接点(NO/NC)
5
5
8
装置自检输出接点
1
1
0,IEC 60870-5-103 及 SPA 协议,通讯波特率最大可 量量、控制、报警和参数的详细信息。
至 19.2kbps。这些端口可以方便用户简易快速地接入各
类厂家的后台系统。
REF 541,REF 543 和 REF 545 的差别仅仅在于三者的开
关量输入和输出接点数量不同。
4
二 订货号
REF 54_ KC127AAAA
1
5
三 端子接线图
*) 功率方向 **) 典关 Q1 合 隔离开关 Q1 分
隔离开关 Q2 合 隔离开关 Q2 分 隔离开关 Q3 合 隔离开关 Q3 分
REF 542plus 开关柜保护和测控装置
一概述
在中压开关柜的无论有无后台系统各种应用场合中,均能 使用数字式控制技术的解决方案。开关柜保护和测控装置 REF 542plus 就如同它的前一代产品 REF 542,集成了测 量、监视、保护、控制和自检等功能,同时拥有完善的通 讯规约,REF 542plus 能够方便地集成到 ABB 或其他第三 方后台系统中。上述功能和其他一些电能质量检测功能都 基于可编程环境中,新一代装置特别的灵活性和可扩展性 使得一个装置可实现所有的二次方案,甚至传统的方法无 法实现的方案,它都很容易实现。

电气二次图识图技巧

电气二次图识图技巧

电气二次图识图技巧秦国强一、二次图说明图中所有的回路都没有被供电,所有电器的触点均表示在线圈没有通电或触点未受到机械外力作用、没有发生机械动作时的位置。

对接触器和继电器来说,是在动铁心未被吸合时的位置,即主触点和辅助常开触点是断开的,辅助常闭触点是闭合的;对按钮来说,是在未按下时的位置,即常开触点是断开的,常闭触点是闭合的。

对于阀门电动头来说,48VDC控制回路中各限位开关的触点位置对应于阀门全关状态。

二、电气设备符号在阅读电气原理图时,必须熟悉图中各器件的符号和作用。

常用电气符号见附录一。

电气设备代码见附录二。

三、识图技巧看图方法:先交流,后直流;交流看电源,直流找线圈;抓住触点不放松,一个一个全查清。

(参考《怎样看电气二次回路图》一书)我个人的理解是:直流回路是为了控制交流回路,先看交流回路可以明确整张电气图的主旨。

而且通常来说交流回路比较简单,容易看懂。

交流回路先看电源,再依接线找到设备。

直流回路先看继电器线圈,找到线圈后,再找出与之相应的触点,根据触点的闭合或断开引起回路的变化情况进行分析,直至查清整个控制回路的动作过程。

电气原理图都是“分块”的,即图中接线明显分为几个部分,包括交流主电路、110VDC和48VDC 控制部分、状态指示和报警辅助电路。

拿到图纸后,先看最上边的提示部分(如下图110V直流控制),就可快速、清楚地了解每组接线的作用。

在分析控制回路的逻辑时,很实用的一个办法是采用反向推理。

即先明确回路的控制目标,然后去分析正常工作时的线圈及触点状态和故障出现后的动作逻辑。

从比较简单的接线入手,由易到难,由已经明确的来反推自己有疑问的部分。

举个例子,380V电动机控制二次接线图(如右图)中,继电器K204通常用于报警和状态指示的控制;K204失电时故障灯(黄灯)亮,由此去判定与线圈K204串联的触点的状态就很简单了:K212得电,即试验盒插入;热继电器F4动作;熔断器动作,S301触点1-2断开;上述三种情况使线圈K204串联的常闭触点断开,K204失电,触点1-9闭合,黄灯亮。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

D型继电器模块的一般特性用户手册和技术说明ABB Network Partner211MRS 750066-MUM EN1995 4 12 发行A版(替换34 SPC 3 EN1)检查:JH批准:TK资料中的数据如有改变,恕不通知。

目录前面板布置----------------------------------------------------------------------------- 21 控制按钮-------------------------------------------------------------------------------- 23 显示------------------------------------------------------------------------------------- 23 显示主菜单-------------------------------------------------------------------------- 23 显示子菜单-------------------------------------------------------------------------- 23 选择器开关组SGF、SGB、SGR -------------------------------------------------- 24 设置------------------------------------------------------------------------------------- 25 设置方式----------------------------------------------------------------------------- 25 例1:继电器运行值的设置 ----------------------------------------------------- 28 例2:继电器开关组的设置 ----------------------------------------------------- 30 记录的信息----------------------------------------------------------------------------- 32 断开测试功能-------------------------------------------------------------------------- 33 例3:输出的强制启动 ----------------------------------------------------------- 35 运行的指示----------------------------------------------------------------------------- 37 故障代码-------------------------------------------------------------------------------- 3722控制按钮继电器模块的前面板上有两个按钮。

RESET/STEP按钮用于运行指示器的复位和向前或向后逐步显示主菜单及子菜单。

PROGRAM按钮用来将主菜单的某个位置移至相应的子菜单,用来输入某参数的设置方式,和STEP按钮一起用来存储所设置的值。

在本手册的以下各节中将叙述模块的各种操作。

显示在保护继电器模块的显示器上显示所测量的值、设置的值和记录的数据。

其显示由4位数字组成。

其中右侧的3位绿色数字指示所测量的值、设置的值和记录的数据,而在最左侧的红色数字指示寄存器的代码。

测量和设置的值由在前面板上的邻近的黄色LED指示器来指示。

在显示一个所记录的故障值时,红色数字给出相应寄存器的号。

如果显示功能只作为一个运行的指示器,则只显示红色的数字。

当模块接通保护继电器模块的辅助电压时,开始逐个测试显示的所用线段,所需数据约为15秒钟。

首先各数字的相应线段顺时针逐个发亮,包括小数点在内。

然后每个数字的中央线段逐个发亮。

整个序列进行两次。

在完成测试之后,显示器变暗。

按下STEP按钮可中断此测试过程。

在整个测试过程中较大模块的保护功能处于待机状态。

显示主菜单在正常运行过程中,任何所需数据,即现行测量值、设置值和记录的参数值,均可在主菜单上进行存取。

通过STEP按钮从显示上可逐个访问显示在主菜单上的数据。

当按住STEP 按钮约1秒钟时,显示按顺序向前移动。

当按住STEP按钮约0.5秒钟时,显示按顺序向后移动。

对发暗的显示,只能向前移动。

当一直按住STEP按钮时,显示一直向前移动,在发暗的位置上停留片刻。

除非通过进入暗点来关闭显示,从STEP按钮最后按下的时刻起约5分钟,显示仍保持发亮。

在5分钟结束时,关闭显示。

显示子菜单在子菜单上显示不大重要的和不经常设置的值。

子菜单的数量和继电器模23块的类型有关。

在有关保护继电器模块的说明中将给出子菜单。

按下PROGRAM按约1秒钟可从主菜单进入子菜单。

当松开按钮后在显示上的红色数字开始闪烁,指示已进入子菜单。

按照从主菜单显示转向另一个主菜单时的同样原理,从一个子菜单转入另一个子菜单,或退回主菜单;当按住STEP按钮1秒钟时,显示向前移动,当按住STEP按钮0.5秒钟时,显示向后移动。

当红色显示转暗时,显示重新进入主菜单。

在从用LED指示器指示一测量值或设置值的主菜单转入一子菜单,指示器保持发亮,显示的地址窗开始闪烁。

子菜单的位置只由闪烁的红色地址数显示,在显示上没有任何发亮的设置值的LED指示器。

选择器开关组SGF、SGB、SGR继电器模块在各种场合下应用的运行特性,其设置和选择部分用选择器开关组SG_来进行选择。

开关组为基本的软件,因而实际上在继电器模块的硬件中是找不到的。

当在显示上显示开关组的检验和时,开关组的指示器发亮。

从显示的检验和开始,通过输入的设置方式,可以一个接着一个地设置开关,如同它们就像是真实的具体开关一样。

在设置步骤终了时,显示整个开关组的检验和。

开关组是否已正确地设置好,可用检验和来验证。

图2给出手动进行检验和计算的实例。

当按照此例计算的检验和与继电器模块显示上所显示的检验和相等时,即已正确设置完有关开关组中的开关。

p.4 图6cm图2 选择器开关组SG_计算检验和的实例24在各种继电器模块的手册中详细说明了各种保护继电器模块的选择器开关的功能。

设置大部分起始值和运行时间是由继电器模块前面板上的显示和各个按钮来设置的。

当有关的设置值在显示上显示时,每个设置值均有与其对应的发亮的指示器。

除了设置值的主堆栈之外,D型继电器模块备有第2设置值堆栈。

可由下列3种不同方法来完成主设置和第2设置之间的接通:1)通过串行通信总线上的命令V150,2)通过外部控制信号BS1、BS2或RRES(BS3),3)通过继电器模块的按钮,参看寄存器A的子菜单4。

设置方式一般说来,在要改变大量的设置值时,即在试运行继电器系统时,建议使用装有必要软件的个人计算机的键盘来输入继电器的设置值。

如果没有计算机也没有软件可以使用时,或只需改变不多的设置值时,建议使用下述步骤。

主菜单和子菜单的寄存器含有所有可设置的参数。

按下PROGRAM按钮在从主菜单或子菜单上可访问的所谓设置方式下进行设置,直到整个显示开始闪烁时为止。

这样位置指示在改变之前的参数。

通过按下PROGRAM按钮,编程顺序向前移动一步。

首先,在最右侧的数字开始闪烁,而其余的显示则不闪烁。

通过STEP按钮来设置闪烁的数字。

按下PROGRAM按钮,将闪烁的光标从一个数字移向另一个数字。

在设置号各参数值之后,将小数点放在合适的位置上。

最后,整个显示再次达到闪烁,并准备存储各数据。

通过同时按下按钮STEP和PROGRAM,将一设置数据记录在存储器内。

在记录新数据之前,退出设置方式并不影响设置,原先的值仍然有效。

其次,如进行设置超出特定参数的容许限值将使新值失效,而仍然保持原先的值。

按下PROGRAM按钮可从设置方式退至主菜单或子菜单,直到在显示上的绿色数字停止闪烁时为止。

注!当通过按钮进行人机对话时,在前面板上的显示启动一5分钟的暂停25功能。

因此,在这5分钟期间如没有按下按钮,继电器将自动返回至正电荷状态。

这就是说显示变暗,继电器离开显示方式,在未触及继电器时,继续例行程序或任何程序。

这是用户不知道怎样做时最方便脱开某个状态的方法。

在将继电器模块插入继电器的壳体中之前,必须明确该模块确已正确设置完毕。

如果对此有任何怀疑时,应该用备用的继电器装置或用断开的继电器断开电路来读出设置值。

如果这点也做不到,则可按下PROGRAM按钮,并同时接通继电器模块的电源,将继电器设置为非断开的方式。

这时显示器将显示3个短横“―――”来指示非断开方式。

串行通信启动,并可以访问所有的主菜单和子菜单。

在非断开方式下,避免不必要的断开,并可对各设置进行检验。

在5分钟暂停或进入主菜单显示变暗位置10秒钟之后,将自动进入正常的保护继电器方式。

p.5 图10cm图 3 进入继电器模块的主菜单和子菜单的基本原理26p.6 图图 4 设置SPCJ 4D29型过流和接地故障继电器模块的主菜单和子菜单的部分实例。

按下S T E P按钮,在主菜单上为当前应用的并显示的设置。

主菜单还包括当前的测量值,寄存器1…9,0和A。

主设置值和第2设置值位于子菜单上并在显示上用PROGRAM按钮进行访问。

27例1设置方式的操作。

用手动方式设置过流继电器模块的初始电流值I>的主设置。

主设置的初始值为0.80×In, 第2设置值为1.00×In。

所求的电源初始值为1.05×In。

a)不断按下STEP按钮直到LED接近I>符号发亮时为止,在显示器上出现当前的初始值。

b)按下PROGRAM按钮1秒钟以上,然后松开,进入子菜单,取得主设置值。

至此,红色数字显示一闪烁的数字1,说明第1子菜单位置,绿色数字显示此设置值。

c)按下PROGRAM按钮5秒钟,输入设置方式,直到显示开始出现闪烁时为止。

d)再次按下PROGRAM按钮1秒钟,使最右侧的数字出现闪烁。

e)至此,可更改闪烁的数字。

用STEP按钮设置数字为所要求的值。

f)按下PROGRAM按钮使中间一个绿色的数字出现闪烁。

g)用STEP按钮设置中间的数字。

28h)按下PROGRAM按钮使最左侧的数字出现闪烁。

i)用STEP按钮设置数字。

j)按下PROGRAM按钮使小数点出现闪烁。

k)必要时,用用STEP按钮移动小数点的位置。