西门子发电机出口断路器 技术条件范本3AH3818-7
发电机出口断路器选型

发电机出⼝断路器选型发电机出⼝真空断路器的选型近⼏年来, 真空断路器在中压输配电领域得到了飞速发展, 占据了该领域的绝对市场优势. 同时针对于发电机出⼝应⽤场合, 也有了长⾜的进步, 特别是近年来国内中⼩型⽔电站 (发电机组单机容量<=100MW) 原有少油出⼝断路器SN4改造项⽬, 真空断路器以压倒性的优势取代了SF6断路器. 综合其原因主要有以下⼏点:1. 可靠安全的机械和电⽓性能2. 较长的机械和电⽓操作寿命3. 最⾼的经济性,节省投资4. 节省空间,电⽹改造的最佳⽅案5. 彻底免维护6. 较短的交货期7. ⽆潜在的腐蚀和有毒的⽓体分解物德国西门⼦公司于1988年向国内提供了⾸例应⽤, 安装于云南卢布⾰⽔电站, 型号为3AH3, 额定容量为12kV/6,300A/40kA.但发电机出⼝场合不同于⼀般的中压配电应⽤, 就断路器型式试验⽽⾔, 国内试验站⽆论是西⾼所, 沈⾼所,以及北京电科院, 由于受到试验设备限制, 所执⾏的标准均为GB1984或者DL402. ⽆法对国际通⽤的IEEE/ANSI std C37.013?以对称电流为基础的交流⾼压发电机断路器标准?规定的试验项⽬进⾏验证, 就国内相应标准⽽⾔, 则为DL427以及GB/T14824. 以下列举其与GB1984/DL402的主要区别;1. 主触头极限温升2.ANSI/IEEE C37.013触头表⾯允许温升 K 温度极限值 oC银, 银合⾦或等同物65 105铜30 70GB1984/DL402触头表⾯允许温升 K 温度极限值 oC银, 银合⾦或等同物75 115铜35 753. 额定电流下导电连接处的极限温升ANSI/IEEE C37.013触头表⾯允许温升 K 温度极限值 oC银, 银合⾦或等同物65 105铜30 70GB1984/DL402- 1 -触头表⾯允许温升 K 温度极限值 oC银, 银合⾦或等同物75 115铜50 904. 多相短路⾮对称开断能⼒ANSI/IEEE C37.013当X/R=50,发电机断路器主触头分离时间为4周波时,⾮对称开断能⼒与对称开断能⼒的⽐值保守估计为1.32, 系统源故障时, 直流分量保守值为50%; 发电机源侧短路时则可超过100%.GB1984/DL402以分闸时间为3周波计算, 则直流分量试验值通常为30%左右5. 额定固有暂态恢复电压 (TRV) 及上升速率 (RRRV)ANSI/IEEE C37.013系统源故障变压器额定容量 (MVA) TRV (kV) RRRV (kV/us)<100 1.84U 3.5101~200 1.84U 4.0202~400 1.84U 4.5发电机源故障发电机额定容量 (MVA) TRV (kV) RRRV (kV/us)<100 1.84U 1.6101~200 1.84U 1.8202~400 1.84U 2.0失步开断变压器额定容量 (MVA) TRV (kV) RRRV (kV/us)<100 2.6U 3.3101~200 2.6U 4.1202~400 2.6U 4.7U----发电机断路器额定最⾼电压变压器额定容量 (MVA) TRV (kV) RRRV (kV/us)<100 2.6U 3.3101~200 2.6U 4.1202~400 2.6U 4.7GB1984/DL402额定电压试验⽅式TRV (kV) RRRV (kV/us)19.7 0.24(100%Isc)7.2kV 411.8 0.34(100%Isc)12 4纵观⽬前国内应⽤的国际知名品牌以及国产真空断路器, 就发电机应⽤场合来说, 基本情况如下:ABB公司由于其真空断路器受到额定容量限制 (最⼤⾄50kA/3150A), 很少涉⾜于此领域;ALSTOM公司由于其真空断路器技术参数存在缺陷 (如直流分量仅为20%, 分闸时间较长等), ⽆法满⾜应⽤要求;国产品牌如北开, 天⽔等, 其发电机出⼝断路器为新开发产品, 产品技术稳定性有待考验, 试验标准⽆法满⾜ANSI/IEEE标准要求参数, 国内使⽤业绩鲜见, 在此类极具重要性的场合, ⽬前不推荐作为使⽤产品;西门⼦公司于80年代末向全球市场推⼴发电机出⼝真空断路器以来, ⾄今已有超过1,500台在全世界范围内安全运⾏.国内业绩⾃1995年后不完全统计已经达到234台, 其中⼤部分运⾏于⽔电⼚, 其成熟性和稳定性得到了⼀致公认.3AH系列真空断路器是西门⼦公司90年代中期推向全球市场的新型产品. 它以原有3AF真空断路器 (机电寿命30,000次)为原形, 在其基础上采⽤了新型的真空灭弧室 (截流值标准从5A控制到了3A以内为重要特征之⼀), 并且对原有弹簧操作机构作了进⼀步精简 ,提⾼了零部件配合加⼯和配合精度以及采⽤了新型的耐磨损材料. 保留了其⼀贯动作可靠的特点, 并且⾸先在全球对真空断路器提出了免维护概念. 免维护概念的倡导是西门⼦公司作为在中压开关领域领导者的⼀个重要标志. 其主要特点如下:1. 世界领先的截流值⽔平 <3A对于真空断路器⽽⾔, 截流值是体现其性能⽔平的重要标志之⼀. 它直接影响真空断路器对于开断⼩电感电流负载的过电压⽔平 (截流过电压U=k*I*rootL/C, 其中k为衰减系数, rootL/C为系统波阻抗, I为截流值, 前⾯两项参数由系统本⾝所决定, ⽽截流值I则取决于不同制造⽔平的真空断路器).西门⼦承偌在切合空载变压器等⼩电感电流负荷情况下, 过电压倍数可限制在2.1p.u以下, 从⽽保证不会产⽣危害其他电⽓设备的危险过电压.附:试验报告TVS 2448 及总结陈述.2. 可满⾜极⾼的RRRV试验报告TVM2/2867E清楚表明了西门⼦真空断路器17.5KkV/63kA成功通过了TRV (<=30kV), RRRV(11kV/us), 短路电流50kA以及 TRV (>30kV), RRRV(18kV/us), 短路电流63kA的型式试验, 试验标准为IEEE C37.013-1989.由于采⽤相同的触头材料, 所以以上试验报告中RRRV值适⽤于其他型号所有西门⼦真空断路器.瞬态恢复电压上升率 (RRRV)同样具有重要意义, 当介质强度恢复速度低于瞬态恢复电压上升速率时, 断路器断⼝就会发⽣复燃. 尤其在发电机出⼝短路等场合开断时, RRRV值可达4.0kV/us, 若此时断路器断⼝介质恢复不能满⾜RRRV的要求, 断路器就有可能发⽣⾼频重燃, 以致产⽣危害极⼤的⾼频重燃过电压.3. 可满⾜对于直流分量的要求西门⼦3AH38 (17.5/63kA)型真空断路器在开断额定短路电流63kA时, 直流分量可达76%;3AH3AH3028/3128/3178/3228型真空断路器在开断额定短路电流63kA时, 直流分量可达60%;3AH3057/3117/3167/3217型真空断路器在开断额定短路电流50kA时, 直流分量可达60%;3AH1116//1166/1216型真空断路器在开断额定短路电流40kA时, 直流分量可达60%;以上断路器完全能满⾜此类应⽤场合的要求.4. 极⾼的额定短路开断次数西门⼦3AH38 (17.5/63kA)/3228型真空断路器在开断额定短路电流63kA时, 开断次数达30次;3AH3AH3028/3128/3178型真空断路器在开断额定短路电流63kA时, 开断次数达50次;3AH3057/3117/3167/3217型真空断路器在开断额定短路电流50kA时, 开断次数达50次;3AH1116//1166/1216型真空断路器在开断额定短路电流40kA时, 开断次数达50次;以上所有断路器机电寿命均为10,000次5. ⼴泛⽽可靠的运⾏业绩⽆论是起始于80年代末90年代初的初期应⽤ (东北电⽹红⽯⽔电站等), 还是最近⼏年在⼴西, ⼴东, 福建, 四川等地⼤量的⽔电站运⾏业绩, 都表明了西门⼦3AH真空断路器性能是极其可靠⽽出⾊.6. 完善的售后服务体系.西门⼦(中国)有限公司在上海设有输配电集团中压开关元件技术⽀持部, 经德国总部多次培训的资深专业⼯程师可随时向⽤户提供⼀流的服务, ⼀旦应⽤户需要, 可在最短时间内赶赴⾄现场解决问题.售后服务热线:021-********综上所述, 作为及其重要的发电机出⼝场合, 产品选型必须极其谨慎, 否则, ⼀旦出现机组停机现象, 损失将不可估量. 西门⼦真空断路器以其卓越的性能, 能够完全胜任其应⽤.附:1. 直流分量浅析对于断路器开断短路电流的考核, 严格意义上应分为对称短路电流以及⾮对称短路电流. 对称短路电流仅局限于短路电流的周期分量, ⾮对称短路电流为周期分量以及直流分量之和.GB1984以及DL403标准针对断路器型式短路开断试验有如下要求:试验⽅式1~4 (主要考核对称短路电流开断能⼒)中, 开断电流的直流分量不得超过20%.原因如下:在开断电流周期分量相等的情况下, ⾮周期分量 (直流分量)的存在, 虽然有可能提⾼触头分离瞬间的短路电流瞬间值, 但它在某种程度上却有利于的开断. 这是因为, 当短路电流中存在⾮周期分量时, 不管是电弧在⼤半波过零或⼩半波过零时熄灭, 断⼝所受的瞬态⼯频恢复电压均⽐⽆周期分量时要⼩.电⼒系统三相短路电流, 最严酷情况下冲击电流计算结果如下:ia= -Ipmcosωt + Ipme-t/Ta根据短路电流波形, 短路电流的最⼤值即短路冲击电流将在短路发⽣后半波时出现, 当f=50Hz时, 其值为0.01秒, 可得冲击电流计算式为:(1+e-0.01/Ta) Ipm=kim Ipm通常情况下, 当短路发⽣于发电机出⼝时, 取kim= 1.9; 于电⼚电站中⼼时, 取kim= 1.85; 于其他地点短路时, 取kim= 1.8, 此时峰值电流为1.8*Root2*Isc=2.55Isc.其中Ta=L/R, 电⽹固定参数;由以上⽅程式可得, 三相短路电流的全电流取决于周期分量以及⾮周期分量, 其中⾮周期分量⼜取决于触头分离时刻以及电⽹固定参数 Ta因此1. GB1984以及DL402⼜有如下规定:对于时间间隔τ (断路器最⼩分闸时间+10ms)不⼤于70ms的断路器必须进⾏⽅式5试验 (包括⽅式1~4).试验⽅式5应以100%的额定短路电流, 直流分量等于τ值所对应的规定值.对于⽤在直流分量可能⼤于 GB1984以及DL402中相应规定值的场合 (如发电机出⼝以及发电站中⼼附近) 的断路器, 试验应由制造⼚协商.2. TRV及RRRV浅析断路器⽤以开断短路电流时, 开断过程中出现的电弧可能在交流电流过零时⾃然熄灭. 由于电弧⼀经形成,断⼝间的介质就会因电弧放电⽽强烈游离, 因此在电流过零电弧⾃然熄灭后, 断⼝间的绝缘不能⽴即恢复.当断⼝恢复电压⾼于介质强度时, 电弧就会复燃.电流过零后断⼝绝缘性能即介质强度的恢复, 以及在断⼝两端出现的外施电压即恢复电压是影响断路器开断性能的两个重要因素.短路故障电路⼤多为电感电阻性电路, 电流过零时电路中断, 电源电压全部加在触头 (弧隙) 两端, 弧隙上的电压恢复过程将是由电弧电压上升到电源电压的这样⼀个过渡过程. 在实际电路中, 弧隙间总有电容的存在, 弧隙电压不可能突变, 电压恢复过程将是是带有周期性的振荡过程.电压恢复过程中, ⾸先出现在弧隙两端的是具有瞬态特性的电压, 称为瞬态恢复电压, 瞬态恢复电压存在的时间很短, 通常为⼏⼗微秒⾄⼏毫秒. 瞬态恢复电压消失后, 弧隙两端出现的是由⼯频电源决定的电压, 即⼯频恢复电压. 从灭弧⾓度看, 瞬态恢复电压具有决定性的意义. 其电压变化取决于:⼯频恢复电压⼤⼩;电路中电感, 电容和电阻的数值以及它们的分布情况;断路器的电弧特性, 即断路器弧后的断⼝电阻;瞬态恢复电压中含有⾼频振荡, 其振荡频率取决于线路电感及电源侧对地电容, 其电压幅值最⼤可达⼯频恢复电压的1.4~1.5倍, 即所谓的振幅系数.当断路器开断三相接地故障时, 还必须考虑⾸开相系数的影响, 通常情况下, 取⾸开相系数为1.5.因此额定瞬态恢复电压(TRV)计算如下:Uc=1.4x1.5x(root2/root3)xUn;1.4------振幅系数1.5-----⾸开相系数Un-----断路器额定电压瞬态恢复电压上升率 (RRRV)同样具有重要意义, 当介质强度恢复速度低于瞬态恢复电压上升速率时, 断路器断⼝就会发⽣复燃. 尤其在发电机出⼝短路等场合开断时, RRRV值可达4.0kV/us, 若此时断路器断⼝介质恢复不能满⾜RRRV的要求, 断路器就有可能发⽣⾼频重燃, 以致产⽣危害极⼤的⾼频重燃过电压.额定电压⼀定时, RRRV值取决于系统固有振荡频率.。
真空断路器使用及维护说明

西门子3AH3真空断路器、SIEMENS3AH3真空断路器技术参数:品牌:西门子真空断路器型号:3AH3极数:3额定绝缘电压:2000功能:3AH3用于切合大容量负载免维护型断路器。
3AH3—免维护断路器,用于高断路能力,电压范围在7.2 kv 和36 kv 之间。
它具有10000次操作周期的使用寿命。
原理:该断路器开断容量大,并能够进行切合操作10000次且免维护,是适用于发电机和工业场合的理想断路器。
3AH3标准型真空断路器可以用在短路电流高达72KA,额定电压高达40.5KV的发电机和工业系统中;满足IEC标准中的试验规范。
3AH真空断路器由上海西门子开关有限公司严格按照ISO9002质量保证体系的要求控制原材料的采购、生产和检验。
断路器的真空灭弧室采用一次封排技术制造,触头材料为Cr-Cu合金,经电弧冶炼而成。
触头采用先进的设计形状和结构,具有极高的耐电弧能力和很小的弧压降。
因此,在保证开断额定短路电流的前提下,灭弧室的体积可以具有较小的尺寸。
西门子的这种新型真空灭弧室,还具有截流值小的特点。
因此,断路器在开断变压器等一类感性负载时,不会出现危害的操作过电压,真空灭弧室与弹簧操动的优良机械特性配合,还使3AH真空断路器能够多次成功地合、分电容器组,而不会出现重燃过电压。
断路器的操动机构采用弹簧储能,可以手动储能,也可以电动储能。
在该机构中各个零部件都是经过精密加工,装配而成。
而且,关键部件和材料用特殊的工艺制造。
这样,确保了整个操动机构具有很小的摩擦力,各零件之间配合精确,动作可靠。
真空断路器作用:(1)正常工作状态时的分合闸操作(控制用);(2)故障状态时的保护操作(保护用);断路器-互感器-继电保护;负荷开关-熔断器保护;(3)设备的隔离;3AH断路器适用于:快速负荷转移、同步;自动重新合闸电流达到31.5 KA;以恢复电压非常高的上升初始速度断开短路电流;电机和发电机的开关;变压器和电抗器的开关;高架线路和电缆的开关;电容器的开关;电弧炉的开关;滤波电路的开关。
西门子 3AH 真空断路器 说明书

3AH上海西门子开关有限公司2杰出的真空开关技术现在,真空已成为中压断路器领域中成本-效益最佳的灭弧介质。
使用最优化的真空开关技术,我们的产品在各方面都呈现了超常规的优良特性。
最显著的优点●稳定的绝缘性能-在真空环境下,没有分解物,由于严格地密封,外界环境对其无影响。
●恒定的触头接触电阻-由于真空下无氧化,能保持触头表面的清洁。
因此,在设备的整个寿命周期内,触头接触电阻一直维持在较小水平。
●开断次数高-额定电流开断最高达30,000次,短路电流开断次数可高达100次。
一万次操作次数内免维护在正常条件下,3AH 断路器在10000次操作内是免维护的,即在前10000次操作或前10年运行无需润滑和机械调整,两个条件以先到为准。
触头磨损很小,电弧电压只有20到200V 。
燃弧时间最大仅15ms ,触头间隙间的能量消耗很小。
灭弧原理当触头分离时,被遮断的电流产生金属蒸汽,电流通过金属蒸汽通道维持至下一电流零点,电弧在过零处被遮断。
金属蒸汽在数微秒内丧失导电性能-这样触头间隙的介质强度能迅速地重新恢复。
根据不同的开断容量,可以选择多种触头形状及尺寸大小。
●横向磁场触头:在这种结构中,电流在约小于10kA 时呈扩散状。
电流更大则呈集聚状绕触头旋转。
●纵向磁场触头:在此结构中,电弧始终保持扩散状,即使电流高达72kA 也是这样。
3AH 真空断路器——真空开关技术的结晶●德国西门子公司最新设计●配用新一代西门子真空灭弧室,更适合中国电力系统的技术标准和运行条件●理想的触头材料和形状,保证较小的截流值和终身稳定的接触电阻●所有零部件全部满足西门子德国质量标准●完备的型式试验●机电寿命高●在正常条件下,10000次操作次数内免维护●零部件少,结构紧凑合理,确保操作更可靠,更安全●理想的感性和容性负荷的开断特性横向及纵向磁场中的电弧3高质量的3AH 真空断路器西门子真空断路器3AH 系列系结合多年的产品设计和运行经验,基于原3AF 真空断路器并针对中国电力系统绝缘要求而进行改进开发和生产的新一代产品。
优选西门子真空断路器讲解

Electrical antipumping
马达操作储能机构
motor operated stored energy mechanism
11常开+11常闭辅助开关
auxiliary switch 11 NO + 11 NC
二次侧64芯接插件
terminal connection via 64 pole pin plug
原装进口(西门子柏林开关厂)
3AH系 列
3AH SERIES
3AH4-频繁操作型断路器
3AH3-大容量断路 器
3AH5-小容量断路 器
西门子3AH3系列真空断路器供货范围
50kA及以上开断可提供4500A断路器
西门子3AH4系列真空断路器供货范围
西门子真空断路器-特殊应用的首选
炼钢厂的电弧炉 3AH2/4真空断路器
3AH3真空断路器操动机构
3AH3 VCB operating mechansim
齿轮箱 位置开关 合闸弹簧
电机 储能指示 位置指示
计数器
辅助开关
合闸按钮 合闸线圈 分闸按钮 分励脱扣器
耐用且极可靠 易于维护 部件少 长的使用寿命
产品细节决定品质
3AH5真空断路器操动机构
齿轮箱 位置开关 合闸弹簧
二次侧64芯接插件
terminal connection via 64 pole pin plug
ห้องสมุดไป่ตู้
可选择配置
Optional equipment:
附加脱扣线圈(最多二个 )
Additional shunt release (Max. one)
28芯端子排
Terminal strip connection
西门子3AC最小油电路断路器中级电压服务技术简介说明书

Retrofit Solution for SIEMENS 3AC make minimum oil circuit breakerThe foremost advantage of retrofittinga circuit breaker in switchgear is thatthe required specifications are metwith the latest technology at only apartial cost of replacing the equipment.This becomes more evident whenthe associated costs of civil works,cabling and downtime are considered.Retrofitting helps in saving up to 60percent of the cost of new equipment.Typically, retrofitting constitutesreplacement of vital equipment havingsimilar or advanced features, for lifeextension, reduced maintenance andimproved functionality. This includesupgradation and modernization ofbasic equipment and allied parts. Theretrofitted switchgear offers far greatersystem, reliability, long term safety andlong term availability of spares withminimal investment and downtime.Siemens 3AC breakerABB is a full system provider forretrofit solutions, from the proposaland design, through the manufacturingand testing, up to the installation andcommissioning.1V Y N 000006 R e v . 00, e n - C o p y r i g h t © 2014 A B B . A l l r i g h t s r e s e r v e d .For more information please contact Service department at: ABB India LimitedPPMV – Retrofit & Services Plot No. 79, Street No. 17,MIDC Estate,Satpur Nashik,Maharashtra, India – 422007Tel: +91 253-2201200Fax: +91 253-2351260Email:******************.com ABB VD4 retrofit of Siemens 3AC breakerNOTE:We reserve the right to make changes in the course of technical development.Benefits Reliability– Significant life time extension– Lower maintenance requirements – Long time availability of spare parts Safety– Strong fault risk reduction– Additional embedded safety features – Improved operator protection Technology– Latest generation apparatus– Designed according to IEC 62271-100 Standard – Tested and certified products Project– Short implementation time for replacement – Minimum shutdown of the switchboard – Smooth site activity Investment– Limited capital investment– Minimization of further maintenance costs – Warranty on the conversion workFactsThese circuit breakers are widely present in the networks and ABB can provide the relevant retrofitting solutions across the globe. This equipment has been in service for many decades and retrofitting could significantly extend the operational life of the switchgear. The use of well proven VD4 Vacuum circuit breaker enhances the reliability of the switchgear. The retrofit circuit breakers can be fitted with Surge Arresters or Potential Transformers on request. Many types of existing circuitbreakers can be identified by looking at the rating plates Viz. 3AC-10NTechnical dataA full range of retrofit solutions have been developed based on ABB vacuum and gas circuit breakers. Fused vacuum contactor is also available for replacing Motor Starter Units.ABB proposal provides the best fit for purpose apparatus for each switchgear unit, depending of the complete network, equipment conditions and the specific feeder operational characteristics.The following basic details are necessary for providing standard retrofit solutions:– Height, width and depth of the circuit breaker compartment – GA, cross section and schematic drawing of the existing panel– Height, width and depth of the panel – Control & motor voltage – Feeder details。
西门子 3AE-SION真空断路器 说明书

概述
高质量的 3AE-SION 真空断路器
3AE-SION真空断路器是西门子结合三十多年的真空产品设计和运行经验并针对中国电力市场开发和生产的最新的一代产品。 融合了德国的最新科技,代表了真空开关的最新发展方向。
· 紧凑型设计适用于 7.2-24kV 的任何开关柜,电气参数最大 40kA、4000A。 · 模块化设计使安装简单化,接线灵活化,可选的相距及极距满足各种特殊需要。 · 机电寿命可达到 30,000 次,在正常工况下,10,000 次操作次数内免维护。 · 革新的绝缘设计和新材料的应用提高了绝缘强度,断路器采用了大爬距绝缘设计,配用最新开发的大爬距真空灭弧室,
1)
275/310 275/310 275/310 275/310 210/310 275/310
1250
1600 110 40 2000 2500 3150 40001)
210/310 275/310 275/310 275/310 275/310 275/310
4
3AE-SION
!"
!"#
3AE1175-2(12kV/31.5kA/1250A) 210mm ! 275mm
3
西门子 3AE-SION 真空断路器
供货范围
额定 型号 电压 (kV) 3AE1104-1 3AE1114-1 3AE1164-1 3AE1174-1 3AE1104-2 3AE1114-2 3AE1164-2 3AE1174-2 3AE1184-3 3AE1584-3 3AE1584-4 3AE1584-6 3AE1105-1 3AE1115-1 3AE1165-1 3AE1175-1 3AE1105-2 3AE1115-2 3AE1165-2 3AE1175-2 3AE1185-3 3AE1585-3 3AE1585-4 3AE1585-6 3AE1585-7 3AE1585-8 3AE1186-2 3AE1586-2 3AE1186-3 3AE1586-3 3AE1586-4 3AE1586-6 3AE1586-7 3AE1586-8
太平湾电站发电机出口西门子开关选型设计

刘 长 江
( 太平 湾发 电厂 , 辽 宁 丹 东 1 8 0 ) 1 0 0
[ 摘要] 针 对发 电机 出口断路 器( N 一0 / 4 S 1 G) t中存在 的 问题 ,提 出在参 数 匹配 的情 况 下用 西 门子真 空断路 器  ̄ 替代 S 1G 的方案 。通过计算三相短路 电流 ,选 出发 电机 出口断路 器重要 技 术参数 ,并对安装 中出 N 一0
9 5
恢复电压 上升率 /k  ̄ ) (V/s 对地及断口间冲击耐压/ V k 出厂真空度 /a br
< 1 l 哪 × 0 < 1 1 叫 × 0
操作 1万次 内真空度/ a br
() 点短 路 时 ,太 平湾 电站二 号 机分 支 线 三 相 短 2
路计算结果见表 2 。
( ) 弧 室 、导 电杆 和 静触 头在 大 修 时更 换 频 繁 。 4消 ( ) 论 证 ,达不 到 5k 5经 8 A额 定 开 断 容量 。
图 1 太平湾 电站电气主接线 图
Байду номын сангаас
x'
 ̄o2 15 - 3
选 取 基 准 电压 — Up 1 0 一 1 . k ,基 准 一 .5 05V
表2 太平湾 电站二号机分支线三相短路计算结果 ( 点短E 如 国
5 安装中出现 的技术 问题及解 决措施
针对安装 中出现 的技术 问题 ,采取 了如下解决 措
施。
() 1 开关 进 出 口双槽 型铝母 线 更 换 问题 。 0 3 H3真 空 开 关 相 间 距 离 为 2 5 A 7mm, 而 S 4 N— 1G 开关 相 间距 离 为 60 0 0mm。
发电机出口断路器技术协议【精选】

附件1技术规范1总则1.1本技术协议适用于阜阳华润电力有限公司2X 600MW超临界机组的的发电机出口断路器,它提出了该设备的功能设计、结构、性能、安装和试验等方面的技术要求。
1.2买方在本技术协议中提出了最低限度的技术要求,并未规定所有的技术要求和适用的标准,卖方应提供一套满足本技术协议和所列标准要求的高质量产品及其相应服务。
1.3卖方如对本协议书有偏差(无论多少或微小)都必须清楚地以书面形式提出,否则买方将认为卖方完全接受和同意本协议书的要求。
1.4卖方提供的设备性能参数以本技术协议书为主。
如买、卖双方发生异议,以最能满足买方现场要求的原则协商解决。
2工程概况见第一卷合同须知3设计和运行条件3.1系统概况和相关设备3.1阜阳华润电力有限公司2 X600MW工程,本期安装额定容量为600MW勺汽轮发电机_2_台,发电机出口设断路器。
3.2 安装地点:户内3.2工程主要原始资料本期工程地处安徽省阜阳市北部,距市区约9.5km。
厂址地形:厂址场地开阔、地形平坦,自然标高29.8m-29.5m。
西北坡向东南,厂址范围东西长约3km,南北宽约2-4km,场地留有扩建。
厂区场地设计标高暂定为30.90m,主厂房零米标高为31.20m (黄海高程)。
3.2.1气象资料电厂厂址多年主要气象要素如下:历年平均大气压历年平均气温历年极端最高气温1012.8hPa 15.0 C41.4 C历年极端最低气温-20.4 C历年最高日降雨量220.2mm多年平均年降雨量907.75mm历年平均绝对湿度14.6hPa历年最大绝对湿度41.5hPa历年最小绝对湿度0.1hPa历年平均蒸发量1586.5mm历年平均风速 2.8m/s最大积雪深度41cm最大冻土深度13cm历年平均雷暴日数31.9 天历年最多雷暴日数57天历年实测十分钟平均最大风速24.0m/s瞬间最大风速32.0 m/s历年平均相对湿度73%历年最小相对湿度1%覆冰厚度10mm3.2.2 厂区地震基本烈度:厂址范围内没有地震断裂通过,地震烈度为7 度,在50 年超概率 10%的条件下,地震动水平峰值加速度为 1.257 m/s2 。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
三相真空断路器(3AH3818-7)
1 使用环境条件
1.1 环境温度
上限+40℃
下限-25℃
1.2 日温差15K
1.3 海拔高度<1000m 1.4 安装地点户内
1.5 20℃时相对湿度
日平均≤95%
月平均<90%
1.6 抗震强度
水平加速度0.3 g
垂直加速度0.3 g
2 断路器技术条件
2.1 额定电压17.5 kV 2.3 额定电流3,150 A
2.4 额定短路开断电流
a. 系统源测
对称分量63kA
直流分量75%
瞬态恢复电压32.2kV
瞬态恢复电压上升速率>=4.5kV/us
b. 发电机源测
对称分量31.5kA
直流分量130%
瞬态恢复电压32.2kV
瞬态恢复电压上升速率>=1.6kV/us 2.5 额定失步开断电流
对称短路开断电流直流分量31.5kA <20%
非对称短路开断电流
直流分量
振幅系数
首开相系数
瞬态恢复电压
恢复电压上升陡度31.5kA
>=60%
1.5
1.5
46kV
>=3.2Kv/us
2.6 工频耐受电压
相间, 对地50 kV
断口间50 kV
3.2.7 雷电冲击耐受电压
相间, 对地95 kV
断口间110 kV
2.8 热稳定电流63 kA/3s
2.9 额定动稳定电流175 kA
2.10 额定关合电流175 kA
2.11 合闸时间<=80ms
2.12 分闸时间
一级分励脱扣<=65ms
二级分励脱扣<=45ms
2.13 燃弧时间<=15ms
2.14 分合闸不同期性
合闸 2 ms
分闸 2 ms
2.15 额定操作顺序O-180s-CO-180s-CO 2.16 操作机构弹簧操动机构
(可通过电动和手动储能) 2.17.1 分合闸线圈电压DC220V
2.17.2 储能电机电压DC220V
2.17.3 辅助开关12NO+12NC
2.18 冷却方式自然风冷
2.19 维修周期
2.20.1 时间断路器在IEC60056标准所规定的正
常运行环境下终身免维护
2.20.2 机械操作次数10,000次
2.20.3 负荷电流开断次数
3150A 10,000次
2.20.4 开断短路电流次数
63kA 50kA 30次50次
2.21 额定频率50 Hz
2.22 小电感电流开断能力操作过电压小于2.5p.u
2.23 噪音水平(距断路器2m处) <=115dB
3. 基本要求
3.1 发电机断路器由一台真空断路器安装使用,由电气指令实现合分闸操作,断路器应
为自然冷却。
3.2 温升
断路器的各个部件的温升应符合美国标准ANSI C37.013-1989中的要求值,在环
境温度40°C额定持续电流时,主触头的最热点和其他连续载流件的温升都不超过
65K。
3.3 操作机构
3.3.1 弹簧操作机构
3.3.2 操作机构应能使断路器三相同时分、合闸,并有防跳措施。
3.3.3 操作机构的功能要求和接线应按照供方标准并提供该标准。
3.3.4 操作机构应配备不少于下列设备
1.机械操作计数器
2.每台独立的断路器具有手动操作跳、合闸装置
3.机械位置指示器(识别断路器在分、合闸位置)
4.弹簧储能状态指示器
5.两个独立的分闸线圈
3.3.5 储能电动机功率为500W,
电动机工作电压波动范围: 85~110%
3.3.6 合闸线圈工作电压波动范围:85~110%
3.3.7 合闸线圈工作电压波动范围:70~110%
3.3.8 在DC220V,合分闸线圈功率140W, 动作电流小于2.5A
3.4 辅助设备
3.4.1 一个接地端子
3.4.2 由于截流值低(2-3A),无须考虑过电压保护