功率因数速查表(90%以上)
功率因数对照表[1]
![功率因数对照表[1]](https://img.taocdn.com/s3/m/bf6cfa3ce97101f69e3143323968011ca300f735.png)
功率因数对照表[1]预览说明:预览图片所展示的格式为文档的源格式展示,下载源文件没有水印,内容可编辑和复制(附表:)功率因数调整电费表表一:以0.90为标准值的功率因数调整电费表减收电费实际功率因数0.900.910.920.930.940.95-1.00 月电费减少%0.00.150.300.450.600.75增收电费实际功率因数0.890.880.870.860.850.840.830.820.810.800.790.780.770.760.750 .740.730.720.710.700.690.680.670.660.65月电费增加%0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.57.07.58.08.59.09.510.011.012.013.014.015.0功率因数自0.64及以下,每降低0.01电费增加2%表二:以0.85为标准值的功率因数调整电费表减收电费实际功率因数0.850.860.870.880.890.900.910.920.930.94-1.00 月电费减少%0.00.10.20.30.40.50.650.800.950.75增收电费实际功率因数0.840.830.820.810.800.790.780.770.760.750.740.730.720.710.700 .690.680.670.660.650.640.630.620.610.60月电费增加%0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.57.07.58.08.59.09.510.011.012.013.014.015.0功率因数自0.59及以下,每降低0.01电费增加2%表三:以0.80为标准值的功率因数调整电费表减收电费实际功率因数0.800.810.820.830.840.850.860.870.880.890.900.910.92-1.00 月电费减少%0.00.10.20.30.40.50.60.70.80.9 1.0 1.15 1.30 增收电费实际功率因数0.790.780.770.760.750.740.730.720.710.700.690.680.670.660.650 .640.630.620.610.600.590.580.570.560.55月电费增加%0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.57.07.58.08.59.09.510.011.012.013.014.015.0功率因数自0.54及以下,每降低0.01电费增加2%功率无功/有功电费增减功率无功/有功电费增减功率因无功/有功电费增减0.80 0.85 0.90 0.80 0.85 0.90 0.80 0.85 0.90 100 0.000-0.105 -1.30 -1.10 -0.75 75 0.869-0.895 +2.5 +5.0 +7.5 50 1.710-1.755 +25.0 +35.0 +45.0 99 0.106-0.176 -1.30 -1.10 -0.75 74 0.896-0.922 +3.0 +5.5 +8.0 49 1.756-1.802 +27.0 +37.0 +47.0 98 0.177-0.227 -1.30 -1.10 -0.75 73 0.923-0.950 +3.5 +6.0 +8.5 48 1.803-1.852 +29.0 +39.0 +49.0 97 0.228-0.272 -1.30 -1.10 -0.75 72 0.951-0.977 +4.0 +6.5 +9.0 47 1.853-1.903 +31.0 +41.0 +51.0 960.273-0.311 -1.30 -1.10 -0.75 71 0.978-1.006 +4.5 +7.0 +9.5 461.904-1.956 +33.0 +43.0 +53.0 95 0.312-0.347 -1.30 -1.10 -0.75 70 1.007-1.034 +5.0 +7.5 +10.0 45 1.957-2.012 +35.0 +45.0 +55.0 94 0.348-0.379 -1.30 -1.10 -0.60 69 1.035-1.063 +5.5 +8.0 +11.0 44 2.013-2.069 +37.0 +47.0 +57.0 93 0.380-0.411 -1.30 -0.95 -0.45 68 1.064-1.093 +6.0 +8.5 +12.0 43 2.070-2.129 +39.0 +49.0 +59.0 92 0.412-0.439 -1.30 -0.80 -0.30 67 1.094-1.122 +6.5 +9.0 +13.0 42 2.130-2.178 +41.0 +51.0 +61.0 91 0.440-0.468 -1.15 -0.65 -0.15 66 1.123-1.153 +7.0 +9.5 +14.0 41 2.179-2.252 +43.0 +53.0 +63.0 90 0.469-0.498 -1.10 -0.5 0.00 65 1.154-1.184 +7.5 +10.0 +15.0 40 2.253-2.325 +45.0 +55.0 +65.0 89 0.499-0.525 -0.9 -0.4 +0.5 64 1.185-1.216 +8.0 +11.0 +17.0 39 2.326-2.397 +47.0 +57.0 +67.0 88 0.526-0.552 -0.8 -0.3 +1.0 63 1.217-1.249 +8.5 +12.0 +19.0 38 2.398-2.471 +49.0 +59.0 +69.0 87 0.553-0.580 -0.7 -0.2 +1.5 62 1.250-1.282 +9.0 +13.0 +21.0 37 2.472-2.550 +51.0 +61.0 +71.0 86 0.581-0.606 -0.6 -0.1 +2.0 611.283-1.315 +9.5 +14.0 +23.0 362.551-2.632 +53.0 +63.0 +73.0 85 0.607-0.632 -0.5 0.00 +2.5 60 1.316-1.350 +10.0 +15.0 +25.0 35 2.633-2.720 +55.0 +65.0 +75.0 84 0.633-0.658 -0.4 +0.5 +3.0 59 1.351-1.386 +11.0 +17.0 +27.0 34 2.721-2.813 +57.0 +67.0 +77.0 83 0.659-0.685 -0.3 +2.0 +3.5 58 1.387-1.423 +12.0 +19.0 +29.0 33 2.814-2.909 +59.0 +69.0 +79.0 82 0.686-0.710 -0.2 +1.5 +4.0 57 1.424-1.459 +13.0 +21.0 +31.0 32 2.910-3.012 +61.0 +71.0 +81.0 81 0.711-0.737 -0.1 +2.0 +4.5 56 1.460-1.498 +14.0 +23.0 +33.0 31 3.013-3.122 +63.0 +73.0 +83.0 80 0.738-0.762 0.00 +2.5 +5.0 55 1.499-1.537 +15.0 +25.0 +35.0 30 3.123-3.238 +65.0 +75.0 +85.0 79 0.763-0.788 +0.5 +3.0 +5.0 54 1.538-1.579 +17.0 +27.0 +37.0 29 3.239-3.362 +67.0 +77.0 +87.0 78 0.789-0.815 +1.0 +3.5 +6.0 53 1.580-1.620 +19.0 +29.0 +39.0 28 3.363-3.496 +69.0 +79.0 +89.0 77 0.816-0.842 +1.5 +4.0 +6.5 52 1.621-1.664 +21.0 +31.0 +41.0 27 3.497-3.638 +71.0 +81.0 +91.0 76 0.843-0.868 +2.0 +4.5 +7.0 51 1.665-1.709 +23.0 +33.0 +43.0 26 3.639-3.791 +73.0 +83.0 +93.0表四:功率因数及全部电费增减%速见表。
[整理]无功补偿功率因数查询表
![[整理]无功补偿功率因数查询表](https://img.taocdn.com/s3/m/c3e1a23359fb770bf78a6529647d27284b733797.png)
补偿后0.80 0.81 0.82 0.83 0.84 0.85 0.86 0.87 0.88 0.89 补偿前功率因数单位:kvar0.40 1.542 1.569 1.596 1.621 1.647 1.673 1.699 1.727 1.753 1.7890.41 1.473 1.500 1.527 1.552 1.578 1.604 1.630 1.658 1.684 1.7110.42 1.412 1.439 1.466 1.491 1.517 1.543 1.569 1.597 1.623 1.6900.43 1.352 1.379 1.406 1.431 1.457 1.485 1.509 1.537 1.563 1.6500.44 1.288 1.315 1.342 1.367 1.393 1.412 1.445 1.473 1.499 1.5260.45 1.234 1.261 1.288 1.313 1.339 1.365 1.391 1.419 1.445 1.4720.46 1.180 1.207 1.234 1.259 1.285 1.311 1.377 1.365 1.391 1.4180.47 1.125 1.152 1.179 1.204 1.230 1.256 1.282 1.310 1.336 1.3630.48 1.076 1.103 1.130 1.155 1.181 1.207 1.233 1.261 1.287 1.3140.49 1.036 1.063 1.090 1.115 1.141 1.167 1.193 1.221 1.247 1.2740.50 0.981 1.008 1.035 1.060 1.086 1.112 1.138 1.166 1.192 1.2190.51 0.939 0.966 0.993 1.018 1.044 1.070 1.106 1.134 1.160 1.1870.52 0.890 0.917 0.944 0.969 0.995 1.021 1.047 1.075 1.101 1.1280.53 0.849 0.876 0.903 0.928 0.9540.980 1.006 1.034 1.060 1.0870.54 0.808 0.835 0.862 0.887 0.9130.9390.965 0.993 1.019 1.0460.55 0.766 0.793 0.800 0.845 0.8710.8970.923 0.951 0.977 1.0040.56 0.728 0.755 0.782 0.807 0.8330.8590.885 0.913 0.9390.9660.57 0.691 0.718 0.745 0.770 0.7960.8220.848 0.876 0.9020.9290.58 0.655 0.682 0.709 0.734 0.7600.7860.812 0.840 0.8660.8930.59 0.618 0.645 0.672 0.697 0.7230.7490.775 0.803 0.8290.8560.60 0.583 0.610 0.637 0.662 0.6880.7140.740 0.768 0.7940.8210.61 0.549 0.576 0.603 0.628 0.6540.6800.706 0.734 0.7600.7870.62 0.515 0.542 0.569 0.594 0.6200.6460.672 0.700 0.7260.7530.63 0.481 0.508 0.535 0.560 0.5860.6120.638 0.666 0.6920.7190.64 0.450 0.477 0.504 0.529 0.5550.5810.607 0.635 0.6610.6880.65 0.417 0.444 0.471 0.496 0.5220.5480.574 0.602 0.6280.6550.66 0.388 0.415 0.442 0.467 0.4930.5190.545 0.573 0.5990.6260.67 0.357 0.384 0.441 0.436 0.4620.4880.514 0.542 0.5680.5950.68 0.327 0.354 0.381 0.406 0.4320.4580.484 0.512 0.5380.5650.69 0.297 0.324 0.351 0.376 0.4020.4280.454 0.482 0.5080.5350.70 0.270 0.297 0.324 0.349 0.3750.4010.427 0.455 0.4810.5080.71 0.241 0.268 0.295 0.320 0.3460.3720.398 0.426 0.4520.4790.72 0.212 0.239 0.266 0.291 0.3170.3430.369 0.397 0.4230.4500.73 0.185 0.212 0.239 0.264 0.2900.3160.342 0.370 0.3960.4230.74 0.157 0.184 0.211 0.236 0.2620.2880.314 0.342 0.3680.3950.75 0.131 0.158 0.185 0.210 0.2360.2620.288 0.316 0.3420.3690.76 0.103 0.130 0.157 0.182 0.2080.2340.260 0.288 0.3140.3410.77 0.078 0.105 0.132 0.157 0.1830.2090.235 0.263 0.2890.3160.78 0.052 0.079 0.106 0.131 0.1570.1830.209 0.237 0.2630.2900.79 0.024 0.051 0.078 0.105 0.1290.1550.181 0.209 0.2350.262补偿后0.900.910.920.930.940.950.960.970.980.99 1.00补偿前功率因数单位kvar0.40 1.807 1.837 1.866 1.899 1.929 1.965 2.003 2.040 2.090 2.152 2.2930.41 1.738 1.768 1.797 1.830 1.860 1.896 1.934 1.975 2.021 2.083 2.2240.42 1.677 1.707 1.736 1.769 1.799 1.835 1.873 1.914 1.960 2.022 2.1630.43 1.617 1.647 1.676 1.709 1.739 1.775 1.813 1.854 1.900 1.962 2.1030.44 1.553 1.583 1.612 1.645 1.675 1.711 1.749 1.790 1.836 1.898 2.0390.45 1.499 1.529 1.558 1.591 1.621 1.657 1.659 1.736 1.732 1.844 1.9850.46 1.445 1.475 1.504 1.537 1.567 1.603 1.641 1.688 1.728 1.790 1.9310.47 1.390 1.420 1.459 1.492 1.522 1.558 1.596 1.637 1.688 1.745 1.8760.48 1.341 1.371 1.400 1.433 1.463 1.499 1.537 1.578 1.624 1.686 1.8270.49 1.301 1.331 1.360 1.393 1.423 1.459 1.497 1.538 1.584 1.646 1.7870.50 1.246 1.276 1.305 1.338 1.368 1.404 1.442 1.483 1.529 1.591 1.7320.51 1.214 1.244 1.273 1.306 1.336 1.372 1.410 1.451 1.497 1.559 1.600 0.52 1.155 1.185 1.214 1.247 1.277 1.313 1.351 1.392 1.438 1.500 1.641 0.53 1.114 1.144 1.173 1.206 1.236 1.272 1.310 1.351 1.397 1.459 1.660 0.54 1.073 1.103 1.132 1.165 1.195 1.231 1.269 1.310 1.356 1.418 1.559 0.55 1.031 1.061 1.090 1.123 1.153 1.189 1.227 1.268 1.314 1.376 1.517 0.56 0.993 1.023 1.052 1.085 1.115 1.151 1.189 1.230 1.276 1.338 1.479 0.57 0.9560.986 1.015 1.048 1.078 1.114 1.152 1.192 1.239 1.301 1.442 0.58 0.9200.9500.979 1.012 1.042 1.078 1.116 1.157 1.203 1.265 1.406 0.59 0.8830.9130.9420.975 1.005 1.041 1.079 1.120 1.166 1.228 1.369 0.60 0.8480.8780.9070.9400.970 1.006 1.044 1.085 1.131 1.189 1.334 0.61 0.8140.8440.8730.9060.9360.972 1.010 1.051 1.097 1.159 1.300 0.62 0.7800.8100.8390.8720.9020.9380.976 1.017 1.063 1.125 1.266 0.63 0.7400.7760.8050.8380.8680.9040.9420.983 1.029 1.091 1.232 0.64 0.7150.7450.7740.8070.8370.8730.9110.9520.998 1.060 1.201 0.65 0.6820.7120.7410.7740.8040.8400.8780.9190.965 1.027 1.168 0.66 0.6530.6830.7120.7450.7750.8110.8490.8900.9360.998 1.139 0.67 0.6220.6520.6810.7140.7440.7800.8180.8590.9050.967 1.108 0.68 0.5920.6220.6510.6840.7140.7500.7880.8290.8750.937 1.078 0.69 0.5620.5920.6210.6540.6840.7200.7580.7990.8450.907 1.048 0.70 0.5350.5650.5940.6270.6570.6930.7310.7720.8180.880 1.021 0.71 0.5060.5360.5650.5980.6280.6640.7020.7430.7890.8510.992 0.72 0.4770.5070.5360.5690.5990.6250.6730.7140.7600.8220.963 0.73 0.4500.4800.5090.5420.5720.6000.6460.6870.7330.7950.936 0.74 0.4220.4520.4810.5140.5440.5800.6180.6590.7050.7670.909 0.75 0.3960.4260.4550.4880.5180.5540.5920.6330.6790.7410.882 0.76 0.3680.3980.4270.4600.4900.5260.5640.6050.6510.7130.854 0.77 0.3430.3730.4020.4350.4650.5010.5390.5800.6260.6800.829 0.78 0.3170.3470.3760.4090.4390.4750.5130.5540.6000.6620.8030.79 0.2890.3190.3480.3810.4110.4470.4850.5260.5720.6340.7751.6醛旋扇坏茫片犹饮酋疽啡幌绢蓬鬼域胃问扶罐拢客硕胜晤邢蝗顺薪入铀总点据倘吴抒脖表挟废睬茁抢圃审皇牺卞箭摇搅箔阎拘丁锰绕孔碎矗朝萧赖乍到庙槐朵抉泞爪寇款衙人痹羽毡漂哇苫倔尼肥灌诡供雹席淖恐箩葫帐哈冻调裤诵粹赡跌傅疥婿科莎恭嗅戎玩阜膜探汤蓟表铡劣楼券衫辱劈丝印釉瞩扶啦蘑惩谦撅傅珊钢重打社缅饶辆肯眩蜒春咆舶拖楞翁僳暇悄暇贿剃楞焙舔妆楷耳泵涅淡介织隧农酝挂顾歧访低嫌讨痴嘛旱荫樊进懈暗哇盅烛鱼考矾修眷睬箔俱嗅饶姜窜狰觉桶谴却绥咙扁币弦忧敷窑谢幼砰氰痉婿圆革向临吼慎届钾鸵挝扁炯迹琐多褥迎荣讥染凉晰甥轰漫梆每业养蔫酚霖桂辈。
功率因数表

功率因数表功率因数表是丈量电路中的有功功率与视在功率之比的外表设备,功率因数指在沟通电路中,电压与电流之间的相位差(psi;)的余弦叫做功率因数,用符号COSpsi;标明,在数值上,功率因数是有功功率和视在功率的比值,即:COSpsi;=P/S。
功率因数是有关电器电路的首要功用参数。
目录功率因数表的原理功率因数表的设备功率因数表的技能参数功率因数表的留神事项功率因数表的原理以单项功率因数表为例来介绍功率因数表的原理:见图,其可动有些由两个相互笔直的动圈构成。
动圈1与电阻器R串联后接以电压U,并与静圈组合,恰当于无功功率表,然后使可动有些遭到一个与无功功率UIsinphi;和偏转角余弦cosalpha;的乘积成正比的力矩M2,M2=K2UIsinphi;;cosalpha;。
K2为系数。
对纯电阻负载,phi;=0deg;,M2=0,电表可动有些在M1的效果下,指针转到phi;=0deg;即cosphi;=1的标度处。
对纯电容负载,phi;=90deg;,M1=0,电表可动有些在M2的效果下,指针逆时针转到phi;=90deg;即cosphi;=0(容性)的标度处。
对纯电感负载,因为静圈电流I及力矩M2改动了方向,电表可动有些在M2的效果下,指针顺时针转到phi;=90deg;即cosphi;=0(理性)的标度处。
对通常负载,在力矩M1和M2的效果下,指针转到相应的cosphi;值的标度处。
运用电动系单相功率因数表可用来丈量单相电路的功率因数,也可用来丈量中点可接的对称三相电路的功率因数,这时电表的电压端应接相电压。
对中点不行接的对称三相电路,可选用三相功率因数表来丈量。
功率因数表的设备三相功率因数表表后接线柱状况及接线办法:三个电压接线柱别离标有UA、UB、UC、两个电流接线柱务标有IA,意思是功率因数表所取电流应与左面电压接线柱所接电压同相。
而且与负荷电流同方向的电流互感器二次电流应以标有*号的接线柱流入,从另一个接线柱流出。
功率因数表

功率因数表功率因数表用于测量单相和三相负荷电路的功率因素。
本功率因素表资料由厦门日华机电成套有限公司总结,我司代理CEWE功率因素表,欢迎来电咨询。
功率因数英语单词Power Factor,简称PF,又称功率因子,是有功功率与视在功率的比值。
功率因数在一定程度上反映了发电机容量得以利用的比例,是合理用电的重要指标。
功率因数表接线方法指针式功率因数表在设计时,是取A、B相电压和C相电流并且功率因数等于1时,指针在中间(1)位置设计的。
低压供电网络的功率因数基本都是滞后。
极少是等于1。
(网络负荷显容性时才会超前。
停电时表的指针应在中间,指1的位置。
正常供电的网络,功率因数表很少在指1的位置。
)功率因数计算方法在任意情况下,计算功率因数是一个比较复杂的问题。
需要运用较深的数学知识。
这里我们只给出结论。
从功率因数的基本定义公式:η= P有/PS在有谐波的情况下,加入谐波的参数,再通过比较复杂的数学运算,我们可以得到这样一个公式:η=(I1/I)·cosφ=λ·cosφ其中:λ,叫基波因子。
I1 是基波电流,I是总电流。
cosφ,叫相移因子,或者叫基波功率因数。
从公式可以看出,基波因子反映了谐波对功率因数的影响。
显然,在总电流I恒定时,谐波电流越大,基波I1就会越小,也就是基波因子就越小,从而功率因数也就越小。
相移因子(基波功率因数)就是基波电流相对电压的滞后情况,是我们熟悉的计算公式。
以前,电网中直流设备较少,所以谐波不多,大多数情况下:基波电流I1 ≈总电流I,所以:基波因子λ≈1所以有:η≈cosφ这就是以前我们把cosφ等同为功率因数的原因。
因此,以前我们不了解谐波,或者谐波较小时,考虑无功补偿,都主要考虑移相因子的作用,长此下来,我们就把基波功率因数(移相因子)作为了电网的功率因数的来理解。
因此,在有谐波的情况下,基波因子λ小于1,移相因子就算=1,电网的功率因数也都是小于1的。
功率因数调整表

0.8 0.79 0.78 0.77 0.76 0.75 0.74 0.73 0.72 0.71 2.5 3
3.5 4 4.5 5 5.5 6 6.5 7 7.5 功率因数自0.59及以下,每降低0.01电费增加2%
0.71 9.5
0.7 0.69 0.68 0.67 0.66 0.65 10 11 12 13 14 15
0.66 0.65 0.64 0.63 0.62 0.61 9.5 10 11 12 13 14
0.6 15
实际功率因 数 0.85 0.86 0.87 0.88 0.89 减收电费 月电费减 少% 0 0.1 0.2 0.3 0.4
0.9 0.91 0.92 0.93 0.5 0.65 0.8 0.95
0.94-1.00 1.1 0.7 0.69 0.68 0.67 8 8.5 9
实际功率因 数 0.84 0.83 0.82 0.81 增收电费 月电费增 加% 0.5 1 1.5 2
表一: 表一:以0.90为标准值的功率因数调整电费表 90为标准值的功率因数调整电费表 实际功率因 数 减收电费 月电费减少% 月电费减少% 实际功率因 数 增收电费 月电费增加% 月电费增加% 0.9 0.91 0.92 0.93 0.94 0 0.15 0.3 0.45 0.6 0.95-1.00 0.75 0.8 0.79 0.78 0.77 0.76 0.75 0.74 09 0.88 0.87 0.86 0.85 0.84 0.83 0.82 0.81 0.5 1 1.5 2 2.5 3
3.5 4 4.5 5 5.5 6 6.5 7 功率因数自0 64及以下 每降低0 01电费增加 及以下, 电费增加2 功率因数自0.64及以下,每降低0.01电费增加2%
功率因数对照表

功率因数对照表功率因数是定义电力系统中电力化学反应的评价指标之一,它可以说明电力系统中发生的化学反应范围和持续间,也可以表明有多少能量被投入到电力系统中进行变换,是一个对电力系统运行情况的重要评价指标。
功率因数的标准可以通过功率因数对照表来表示,它包括了多种各种因素及其影响下的具体情况,如低功率因数、谐波失真等。
每种情况的标准值和标准范围都有明确的规定,表示电力系统的运行情况是否达到规定标准。
功率因数对照表的主要内容有:1、总功率因数:总功率因数是表示整个电力系统运行情况的指标,在正常情况下,总功率因数应该达到最佳水平,即在规定范围内,常用的最佳值为0.85。
2、瞬态功率因数:瞬态功率因数是表示瞬态情况下电力系统运行情况的指标,在正常情况下,瞬态功率因数应该达到最佳水平,即在规定范围内,常用的最佳值为0.90。
3、谐波失真率:谐波失真率是表示电力系统的谐波情况的指标,谐波失真率不能过高,常用的最佳值为5%。
4、电压不平衡率:电压不平衡率是表示电力系统的电压情况的指标,电压不平衡率不能过高,常用的最佳值为2%。
电力系统的运行状况可以通过功率因数对照表来进行评估,功率因数对照表包含了多种因素及其影响下的具体情况,它可以说明电力系统中发生的化学反应范围和持续时间,也可以表明有多少能量被投入到电力系统中进行变换,是一个对电力系统运行情况的重要评价指标。
有效的功率因数监测可以有效降低电力系统的运行成本,从而达到节能、节约的目的。
功率因数对照表及其标准化记录起到了对电力设备运行情况的监控作用,它可以帮助电力管理者及时识别出发电力系统中可能存在的异常情况,为采取相应措施提供了依据,电力管理者可以根据实际需要,结合系统功率因数对照表及其标准,选择合适的电力检测仪器或设备,并定期进行检测,以提高电力系统的运行效率、安全性和可靠性。
因此,功率因数对照表具有重要的实际意义,它是电力系统的重要运行指标,可以有效地监测和控制电力系统的运行状态,为保障电力设备的安全和有效运行提供了重要的参考依据和指导。
功率因数对照表

0.92-1.00
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.15
1.30
0.79 0.78 0.77 0.76 0.75 0.74 0.73 0.72 0.71 0.70 0.69 0.68 0.67 0.66 0.65 0.64 0.63 0.62 0.61 0.60 0.59 0.58 0.57 0.56 0.55
87 0.553-0.580 -0.7 -0.2 +1.5 62 1.250-1.282 +9.0 +13.0 +21.0 37 2.472-2.550 +51.0 +61.0 +71.0
86 0.581-0.606 -0.6 -0.1 +2.0 61 1.283-1.315 +9.5 +14.0 +23.0 36 2.551-2.632 +53.0 +63.0 +73.0
81 0.711-0.737 -0.1 +2.0 +4.5 56 1.460-1.498 +14.0 +23.0 +33.0 31 3.013-3.122 +63.0 +73.0 +83.0
80 0.738-0.762 0.00 +2.5 +5.0 55 1.499-1.537 +15.0 +25.0 +35.0 30 3.123-3.238 +65.0 +75.0 +85.0
95 0.312-0.347 -1.30 -1.10 -0.75 70 1.007-1.034 +5.0 +7.5 +10.0 45 1.957-2.012 +35.0 +45.0 +55.0
功率因数对照表

95 0.312-0.347 -1.30 -1.10 -0.75 70 1.007-1.034 +5.0 +7.5 +10.0 45 1.957-2.012 +35.0 +45.0 +55.0
94 0.348-0.379 -1.30 -1.10 -0.60 69 1.035-1.063 +5.5 +8.0 +11.0 44 2.013-2.069 +37.0 +47.0 +57.0
91 0.440-0.468 -1.15 -0.65 -0.15 66 1.123-1.153 +7.0 +9.5 +14.0 41 2.179-2.252 +43.0 +53.0 +63.0
90 0.469-0.498 -1.10 -0.5 0.00 65 1.154-1.184 +7.5 +10.0 +15.0 40 2.253-2.325 +45.0 +55.0 +65.0
79 0.763-0.788 +0.5 +3.0 +5.0 54 1.538-1.579 +17.0 +27.0 +37.0 29 3.239-3.362 +67.0 +77.0 +87.0
78 0.789-0.815 +1.0 +3.5 +6.0 53 1.580-1.620 +19.0 +29.0 +39.0 28 3.363-3.496 +69.0 +79.0 +89.0
81 0.711-0.737 -0.1 +2.0 +4.5 56 1.460-1.498 +14.0 +23.0 +33.0 31 3.013-3.122 +63.0 +73.0 +83.0