M S S er i esM a n ua lm ot o rp r ot e ct o rsCK1-xx contacts must mount flush on the right side of the MS132; these devices are supplementary and not required for use in UL 508 Type E &F applicationsSK4-11 contacts are required for UL 508 Type E applications using types MS4xx; included when purchasing types MS4xx-xxEHKF1-11HK4-11HK1-11 HKS4-20SK1-11 CK1-11 SK4-11AA1-24UA1-24AA4-24AccessoriesFor Types MS116, MS132, MS45x, MS49xM S S e r i e s M a n u a l m o t o rp r o t e c t o r sActuation tablesFor Types MS116, MS132, MS45x, MS49xX = Indicates closed state O = Indicates open stateFor connection diagrams, see page 4.17.1 + I>> indicator window = red.M S S er i e s M a n u a l m o t o r pr o t e c t o r sThe DX495 terminal is included when purchasing type MS49x-xxE devices.PS1-2-0-65PS1-3-1-100S1-M3-25KA450DX495AccessoriesFor Types MS116, MS132, MS45x, MS49xM S S e r i e s M a n u a l m o t o rp r o t e c t o r s 4AccessoriesFor Types MS116, MS132ABB Manual motor protectors can also be connected to the SMISSLINE power distribution bus system, which provides a versatile and flexible means of distributing power to a wide variety ofelectrical devices. For complete system information, see Section 24.The 9 mm wide additional housing is needed when an odd number of combi modules are plugged on the socket; required to fill space into a full module (18 mm).The 9 mm wide additional housing must also be used when a side-mount auxiliary contact isused.SMISSLINE busbar combi modules for types MS116 / MS132 +M S S er i esM a n ua lm ot o rp r ot e ct o rsLocking accessoriesDoor mount kits - Type 12 & IP 65Max. 3 padlocks with bail diameter Ø 4…6.5 mmThrough-door hardware - Types 1, 3R, 12 and IP 64Max. 3 padlocks with bail diameter Ø 5…8 mmFor coded shaft couplers, the “On” position is dependent on the mounting orientation of the MMPMust have handle, shaft coupler and shaft for through-door operation. Drive spindles can replace both shaft coupler and shaft.Enclosures - Type 12 & IP 65Type MS116 devices trip to the “Off” positionMax. 3 padlocks with bail diameter Ø 4…6.5 mmFor UL enclosure type ratings, contact technical support.SA1 SA2DMS132-GMSHD-LY MSHD-LTY1SAM101923R00021SAM101924R00131SAM201920R1000IB132-GAccessoriesFor Types MS116, MS132, MS45x, MS49xM S S e r i e s M a n u a l m o t o rp r o t e c t o r sAccessoriesFor Types MS116, MS132, MS45x, MS49xMS132 + PSR SoftstarterMS132 + AF ContactorBEA16-4BEA16-3M S S er i e s M a n u a l m o t o r pr o t e c t o r sCurrent limitersThe sum of all load currents including inrush currents shall not exceed the maximum permissible load of the S803W.1 Also suitable for Tap Conductor protection.2 Requires the use of a line-side feeder terminal S1-M3-xx; see accessories section.3MCCB interrupting rating must be equal to or greater than the rating of the device.MS132 Short circuit current ratings using S803W current limiters (kA)Catalog numberUL 508 - Motor controllers, manual (NLRV)UL 508 - Combination motor controllers (NKJH)Circuit breakerGroup motor installation 1Self-protected Type E 2Self-protected Type F 2240V 480V600V480Y/ 277V600Y/ 347V480Y/ 277V600Y/ 347VType F contactorsMS132-0.16MCCB, 400Amax.3656565476547AF26…AF38MS132-0.25656565476547AF26…AF38MS132-0.4656565476547AF26…AF38MS132-0.63656565476547AF26…AF38MS132-1.0656565476547AF26…AF38MS132-1.6656565476547AF26…AF38MS132-2.5656565476547AF26…AF38MS132-4.0656565476547AF26…AF38MS132-6.3656565186547AF26…AF38MS132-10656565186547AF26…AF38MS132-12656565-65-AF26…AF38MS132-16656565-65-AF26…AF38MS132-20656565-65-AF26…AF38MS132-25656565-65-AF26…AF38MS132-32656565-65-AF26…AF38S803W-SCL32-SRt i m e [s ]n x I Maximum loadAccessories For Type MS132Rated for use with the type MS132, the S803W current limiters can provide selective coordination for individual downstream SCPDs, and can be utilized in combination up to 65 kA at 600 v ac. For more information, see Section 17 - S800 Series.M S S e r i e s M a n u a l m o t o rp r o t e c t o r sConnection diagramsFor Types MS116, MS132, MS45x, MS49xConnection diagramsAccessories for use with Type MS116, MS132 & MS4xx1 L1 5 L38676I >>I >I D1D2<U C1C2423288423434781321221466568675857787314133434433417755658557675765665858783 L268AA1...AA4...UA1...UA4...HKF1-11HK4-11HK1-11HKS4-11HKF1-20HK4-20HKF1-02HK4-02SK1-11SK4-11SK1-20SK1-02CK1-11SK4-11CK1-20CK1-02M S S er i esM a n ua lm ot o rp r ot e ct o rsMS116UA1AA1SK1HK1CK1CK1HK1HK1SK1HK1S1-M1-25PS1-..-65BS1-3PS1-..-65S1-M2-25MS132S1-M1-25PS1-..-100BS1-3SA13-phase busbar upto 92 A3-phase busbar upto 65 AHKF1General accessory mounting layoutMS116 & MS132M S S e r i e s M a n u a l m o t o rp r o t e c t o r sMain circuit – Utilization characteristics according to IEC/ENShort-circuit breaking capacity and back-up fusesl CS Rated service short-circuit breaking capacity l CU Rated ultimate short-circuit breaking capacity I CC Prospective short-circuit current at installation location Note: Maximum rated current of the back-up fuses if I CC > I CSType230 V AC 400 V AC 440 V AC 500 V AC 690 V AC I CS kAI CU kAgG, aM AI CS kAI CU kAgG, aM AI CS kAI CU kAgG, aM AI CS kAI CU kAgG, aM AI CS kAI CU kAgG, aM AMS116-0.16No back-up fuse required up to I CC = 50 kANo back-up fuse required up to I CC = 30 kAMS116-0.25MS116-0.4MS116-0.63MS116-1.0MS116-1.6MS116-2.51010251010255525MS116-4.0662566252225MS116-6.3666366632240MS116-10666366632250MS116-12 252580252580666366632250MS116-16161680161680666344632263MS116-201015-1015-36-34-22-MS116-251015-1015-36-34-22-MS116-321010-1010-36-34-22-MS116-10: No need for back-up fuse in networks with a prospective current of up to 50 kA at 400 V .MS116-16: No need for back-up fuse in networks with a prospective current of up to 16 kA at 400 V . With an appropriate 80 A type gG fuse the device can be used in a network with a prospective current of up to 100 kA.MS116-32: No need for back-up fuse in networks with a prospective current of up to 15 kA at 400 V .Technical data - IEC/EN MS116M S S er i e s M a n u a l m o t o r pr o t e c t o r s TypeMS116StandardsUL 508, CSA 22.2 No. 14Maximum operational voltage 600 V ACManual motor controller ratings See table "UL 508 – Manual motor controller"Trip rating 125 % FLAMotor ratings Horse powerSee table "Motor rating, three phase"Full load amps (FLA)See table "Motor rating, three phase"Locked rotor amps (LRA)See table "Motor rating, three phase"Motor rating, three phasehp Horse power FLA Full load amps LRALocked rotor ampsType110-120 V AC 220-240 V AC 440-480 V AC 550-600 V AC hpFLALRAhpFLALRAhpFLALRAhpFLALRAMS116-0.16-0.160.96-0.160.96-0.160.96-0.160.96MS116-0.25-0.25 1.5-0.25 1.5-0.25 1.5-0.25 1.5MS116-0.4-0.4 2.4-0.4 2.4-0.4 2.4-0.4 2.4MS116-0.63-0.63 3.78-0.63 3.78-0.63 3.78-0.63 3.78MS116-1.0- 1.0 6.0- 1.0 6.0 1.0 6.01/20.98MS116-1.6- 1.69.6- 1.69.63/4 1.612.53/4 1.310MS116-2.5- 2.515.01/2 2.2201 2.1151-1/2 2.416MS116-4.0- 4.016.01 4.2302 3.4253 3.925.6MS116-6.31/2 4.4401-1/2 6.4403 4.8325 6.136.8MS116-1018.46039.66457.6467-1/2950.8MS116-121-1/2128039.6647-1/21163.5101164.8MS116-16213.6100515.292101481101164.8MS116-20319.2128515.292101481151793MS116-25319.21287-1/22212715211162022116MS116-32530.4184102816220271452527146Technical data - UL/CSA MS1161 Suitable as motor disconnect only when provided with padlock SA1 or SA3...Main circuit – Utilization characteristics according to UL/CSAM S S e r i e s M a n u a l m o t o rp r o t e c t o r sGeneral technical dataMain circuit – Connecting characteristicsTechnical data MS116M S S er i e s M a n u a l m o t o r pr o t e c t o r s Type MS132StandardsIEC/EN 60947–2, IEC/EN 60947-4-1, IEC/EN 60947-1Rated operational voltage U e 690 V AC / 250 V DC Rated frequency DC, 50/60 HzTrip class10 (10A for MS132-0.16)Number of poles 3Duty time100 %Rated impulse withstand voltage U imp 6 kVRated insulation voltage U i 690 V ACRated operational current I eSee ordering details Rated instantaneous short-circuit current setting I i See ordering detailsRated service short-circuit breaking capacity I cs See table "Short-circuit breaking capacity and back-up fuses"Rated ultimate short-circuit breaking capacity I cuSee table "Short-circuit breaking capacity and back-up fuses"Short-circuit breaking capacity and back-up fusesl CS Rated service short-circuit breaking capacity l CU Rated ultimate short-circuit breaking capacity I CC Prospective short-circuit current at installation location Note: Maximum rated current of the back-up fuses if I CC > I CSType230 V AC 400 V AC 440 V AC 500 V AC 690 V AC I CS kAI CU kAgG, aM AI CS kAI CU kAgG, aM AI CS kAI CU kAgG, aM AI CS kAI CU kAgG, aM AI CS kAI CU kAgG, aM AMS132-0.16No back-up fuse required up to I CC = 100 kAMS132-0.25MS132-0.4MS132-0.63MS132-1.0MS132-1.6MS132-2.5MS132-4.02020*2020*33*MS132-6.32020*2020*33*MS132-102020*2020*33*MS132-122020*2020*33*MS132-162020*2020*33*MS132-202020*2020*33*MS132-25505010050501002020*1010*33*MS132-32255012525501252020*1010*33*MS132-16: No need for back-up fuse in networks with a prospective current of up to 100 kA at 400 V .MS132-32: No need for back-up fuse in networks with a prospective current of up to 50 kA at 400 V . With an approbiate 125 A type gG fuse the device can be used in a network with a prospective current of up to 100 kA * not available yetTechnical data - IEC/EN MS132Main circuit – Utilization characteristics according to IEC/ENM S S e r i e s M a n u a l m o t o rp r o t e c t o r sMain circuit – Utilization characteristics according to UL/CSAMotor rating, three phasehp Horse power FLA Full load amps LRALocked rotor ampsType110-120 V AC 220-240 V AC 440-480 V AC 550-600 V AC hpFLALRAhpFLALRAhpFLALRAhpFLALRAMS132-0.16-0.160.96-0.160.96 - 0.160.96 - 0.160.96MS132-0.25-0.25 1.5-0.25 1.5 - 0.25 1.5 - 0.25 1.5MS132-0.4-0.4 2.4-0.4 2.4 - 0.4 2.4 - 0.4 2.4MS132-0.63-0.63 3.78-0.63 3.78 - 0.63 3.78 - 0.63 3.78MS132-1.0- 1.0 6.0- 1.0 6.0 - 1.0 6.0 1/2 1.0 6.0MS132-1.6- 1.69.6- 1.69.6 3/4 1.69.6 3/4 1.69.6MS132-2.5- 2.515.01/2 2.515.01 2.515.0 1-1/2 2.515.0MS132-4.0- 4.024.01 4.024.02 4.024.03 3.926.0MS132-6.31/2 6.337.81-1/2 6.337.83 4.832.056.137.0MS132-103/410.060.039.664.057.646.0 7-1/2 9.051.0MS132-121-1/212.072.039.664.0 7-1/2 11.064.01011.065.0MS132-16216.084.0515.292.01014.081.01011.065.0MS132-20319.2128.0515.292.01014.081.01517.093.0MS132-25319.2128.07-1/222.0127.01521.0116.02022.0116.0MS132-32530.4184.01028.0162.02027.0145.02527.0146.0Technical data - UL/CSA MS1324M SS er i esM an ua lm ot o rp r ot e ct o rsType MS132 Pollution degree3Phase loss sensitive YesAmbient air temperatureOperation Open - compensated without derating-25 ... +60 °COpen-25 ... +70 °CEnclosed (IB132)0 ... +40 °CStorage-50 ... +80 °CAmbient air temperature compensation ContinuousMaximum operating altitude permissible2000 mResistance to shock acc. to IEC 60068-2-2725 g / 11 msResistance to vibrations acc. to IEC 60068-2-6 5 g / 3 ... 150 HzMounting position Position 1-6 (optional for single mounting) Mounting DIN-rail (EN 60715)Group mounting On requestMinimum distance to otherunits same typeHorizontal0 mmVertical150 mmMinimum distance toelectrical conductive boardHorizontal, up to 400 V0 mmHorizontal, up to 690 V> 1.5 mmVertical75 mmDegree of protection Enclosure / terminals IP20Main circuit – Connecting characteristicsTechnical dataMS132General technical dataM S S e r i e s M a n u a l m o t o rp r o t e c t o r sTechnical dataMS116 & MS132 AccessoriesGeneral technical dataTypeUA1AA1Standards IEC/EN 60947-1, UL 508/60947-4-1A, CAN/CSA C22.2 No.14/60947-4-1-07Pick-up value % of Uc ≥ 85≥ 70Drop-out value% of Uc 35…70-Power consumption Pick-upVA 9HoldingVA 3Ambient air temperatureOperation -20…+55 °C Storage-50…+80 °CM S S er i e s M a n u a l m o t o r pr o t e c t o r s Contact utilization characteristics per IECTypeHKF1-xxHK1-xxHK1-20LSK1-xxCK1-xxStandardsIEC/EN 60947-5-1 Rated operational voltage U e250 V AC/690 V AC/250 V DC 600 V DC Conventional free-air thermal current I th 5 A 6 ARated frequency50/60 Hz Rated impulse withstand voltage U imp 6 kVA Rated insulation voltage U i 230 V 690 V Pollution degree3Ambient air temperature Operation -20…+55 °C Storage -50…+80 °C Resistance to shock acc. to IEC 60068-2-2725 g / 11 ms Resistance to vibrations acc. to IEC 60068-2-6 2 g / 5…150 HzNumber of poles1 N.C. + 1 N.O. or2 N.O. or 2 N.C.2 leading N.O.1 N.C. + 1 N.O. or2 N.O. or 2 N.C.I e / Rated operational current AC-15 acc. to IEC/EN 60947-5-1 for utilization category24 V , 50/60 Hz 36 120 V , 50/60 Hz 36230 V , 50/60 Hz 1.54 400 V , 50/60 Hz -3 690 V , 50/60 Hz -1 I e / Rated operational current DC-13 acc. to IEC/EN 60947-5-1 for utilization category24 V 1.02 125 V 0.270.55 250 V 0.100.27 600 V -0.15Minimum switching capacity 17 V / 5 mA Short-circuit protective device 10 A Type gG Duty time 100 % MountingFront of MMS Right side of MMSMounting positions 1-6Mechanical durability 100000 cycles Electrical durability100000 cyclesContact utilization characteristics per UL/CSATypeHKF1-xxHK1-xxHK1-20LSK1-xxCK1-xxStandardsUL 508/60947-4-1A, CAN/CSA C22.2 No.14/60947-4-1-07 Rated voltage UL/CSA 240 V AC/ 250 V DC 600 V AC/ 600 V DC Pilot dutyB300, Q300B600, Q600AC thermal rated current 5AC maximum volt-ampere making 3600AC maximum volt-ampere breaking 360DC thermal rated current 2.5DC maximum volt-ampere make/break 69Connecting characteristicsTypeHKF1-xxHK1-xxHK1-20LSK1-xxCK1-xxConnecting capacitySolid 1 or 2 x 1...1.5 mm² Flexible 1 or 2 x 0.75...1.5 mm² Flexible with non-insulated ferrule 1 or 2 x 0.75...1.5 mm² Flexible with insulated ferrule 1 or 2 x 0.75...1.5 mm² Stranded acc. to UL/CSA 1 or 2 x AWG 16-14 Flexible acc. to UL/CSA 1 or 2 x AWG 16-14 Stripping length 8 mmTightening torques 0.8...1.2 Nm / 7...10.3 Ib.in Connection screwPozidriv 2 / M3Technical dataMS116 & MS132 AccessoriesM S S e r i e s M a n u a l m o t o rp r o t e c t o r sMain circuit – Utilization characteristics according to IEC/ENShort-circuit breaking capacity and back-up fusesl CS Rated service short-circuit breaking capacity l CU Rated ultimate short-circuit breaking capacity I CC Prospective short-circuit current at installation location Note: Maximum rated current of the back-up fuses if I CC > I CS Type240 V AC 400 V AC 440 V AC 500 V AC 690 V AC I CS kAI CU kAgG, aM AI CS kAI CU kAgG, aM AI CS kAI CU kAgG, aM AI CS kAI CU kA gG, aM A I CS kA I CU kA gG, aM A Short-circuit protection MS45xMS45x-40No back-up fuse required up to I CC = 100 kA255016015501255101002463MS45x-45255016015501255101002463MS45x-50255016015501255101002480MS45x: No need for back-up fuse in networks with a prospective current of up to 50 kA at 400 V.With an appropriate 160 A type gG fuse the device can be used in a network with a prospective current of up to 100 kA.Short-circuit protection MS49xMS49x-40No back-up fuse required up toI CC = 100 kA 255012520501256121253663MS49x-50255012520501256121253680MS49x-63255016020501606121603680MS49x-75255016020501606816035100MS49x-90255016020501606816035125MS49x-100255016020501606816035125MS49x-40: No need for back-up fuse in networks with a prospective current of up to 50 kA at 400 V. With an appropriate 125 A type gG fuse the device can be used in a network with a prospective current of up to 100 kA.MS49x-100: No need for back-up fuse in networks with a prospective current of up to 50 kA at 400 V. With an appropriate 160 A type gG fuse the device can be used in a network with a prospective current of up to 100 kA.Technical data - IEC/EN MS45x & MS49xM S S er i e s M a n u a l m o t o r pr o t e c t o r s Main circuit – Utilization characteristics according to UL/CSAType MS45x, MS49xStandardsUL 508, CSA 22.2 No. 14 Maximum operational voltage 600 V ACManual motor controller ratings See table “UL 508 – Manual motor controller” Trip rating125 % FLAMotor ratings Horsepower See table “Motor rating, three phase” Full load amps (FLA) See table “Motor rating, three phase” Locked rotor amps (LRA)See table “Motor rating, three phase”Motor rating, three phasehp Horsepower FLA Full load amps (FLA)LRA Locked rotor amps (LRA)Type208 V AC 220-240 V AC 440-480 V AC 550-600 V AC hpFLALRAhpFLALRAhpFLALRAhpFLALRATypes MS450 / MS451MS451-16516.7102.0515.292.01014.081.01517.093.0MS451-20516.7102.07.522.092.01521.0116.02022.0116.0MS451-257.524.2140.01028.0127.02027.0145.02527.0146.0MS451-321030.8179.01028.0162.02534.0183.03032.0174.0MS45x-401546.2257.01542.0232.03040.0218.04041.0232.0MS45x-451546.2257.01542.0232.03040.0218.04041.0232.0MS45x-501546.2257.02054.0232.04052.0290.05052.0290.0Types MS495 / MS496MS49x-401546.2257.01542.0232.03040.0218.04041.0232.0MS49x-501546.2257.02054.0232.04052.0290.05052.0290.0MS49x-632059.4321.02568.0290.05065.0363.06062.0348.0MS49x-752574.8404.02568.0365.06077.0435.07577.0434.0MS49x-903088.0481.03080.0435.07596.0543.010099.0580.0MS49x-10040114.0641.040104.0580.07596.0543.010099.0580.0Technical data - UL/CSA MS45x & MS49xM S S e r i e s M a n u a l m o t o rp r o t e c t o r sTechnical data MS45x & MS49xGeneral technical dataMain circuit – Connecting characteristicsM S S er i e s M a n u a l m o t o r pr o t e c t o rs General technical dataTypePS4-xxxS4-M1StandardsIEC/EN 60947-1Rated operational voltage U e 690 V AC Rated operational current I e 108 A Rated frequency50/60 Hz Rated impulse withstand voltage U imp 6 kV Rated insulation voltage U i 690 V AC Pollution degree 3Cross-section10 mm 225 mm 2Ambient air temperature Operation -25... +70°C Storage-50... +80°CGeneral technical dataTypeUA4AA4Standards IEC/EN 60947-1, UL 508/60947-4-1A, CAN/CSA C22.2 No.14/60947-4-1-07Pick-up value % of U c ≥ 85≥ 70Drop-out value% of U c 35 (70)-Power Pick-up VA 20.2Consult factory consumption HoldingVA 7.2Consult factoryTechnical dataMS45x & MS49x AccessoriesM S S e r i e s M a n u a l m o t o rp r o t e c t o r sTechnical dataMS45x & MS49x AccessoriesM S S er i e s M a n u a l m o t o r pr o t e c t o r s 1,5 / 0,06"1,7 / 0,07"14 / 0,55"14 / 90 / 3,54"45 / 1,77"0,55"35 / 1,38"5,5 / 0,22"45 / 1,77"57,8 / 2,3"70 / 2,76"43,5 / 1,71"80,1 / 3,15"27,5 / 1,1"75 / 2,95"MS116-0.16... MS116-16, MS132-0.16…MS132-10MS116-20... MS116-32, MS132-12... MS132-321,5 / 0,06"1,7 / 0,07"27,5 / 1,1"45 / 1,77"57,8 / 2,3"35 / 1,38"5,5 / 0,22"69,8 / 2,75"43,3 / 1,7"79,9 / 3,15"14 / 0,55"14 / 75 / 2,95"97,8 / 3,85"45 / 1,77"0,55"DMS132-xMS116-0.16…MS116-16 or MS132-0.16…MS132-10 + UA1, AA1,SK1, HK1, CK1, HKF1-11MS116-20... MS116-32 or MS132-12... MS132-32 + UA1, AA1, SK1, HK1, CK1, HKF1-11IB132-xApproximate dimensionsM S S e r i e s M a n u a l m o t o rp r o t e c t o r sApproximate dimensionsMS450-40…MS450-50, MS451-16…MS451-50MS495-40…MS495-100, MS496-40…MS496-100。

1000KVA继电保护说明书

1000KVA继电保护说明书

变压器1000kva继电保护说明书一、变压器为1000kva;10kv/0.4kv;△/Y;三相电流比75/5A;1、速断:整定值:供电局提供:<0.2秒(从互感器处加入电流,到开关端口断开测得)2、过流:整定值:供电局提供:<0.5秒(从互感器处加入电流,到开关端口断开测得)过载:整定值:变压器容量105%,一次60.7A,二次4A,延时9秒报预警。

3、零序电流:供电局不提供时,我方作如下规定:取变压器容量的2.5%作为零流的基准值,动作跳闸或报预警,即一次零流1.5A;二次零流0.1A动作跳闸或报预警,延时0.5秒。

本系统室内接地因高压线路很短,互感器前侧接地流经互感器的零流很小,互感器后侧接地流经互感器的零流很大,本装置只对互感器后侧接地有效,前侧端接地只靠供电局线路保护解决,如果0.1A会动作时,应会诊后按0.15A,0.2A,0.25A….. 以0.05A级逐步放大(变压器为△/Y不考虑低压侧零流问题),或重新由测量计算所得。

总之,-次零序电流限止在远小于10A以内。

二、施耐德CCA634+MES114( ,E,F)综保屏编制要求如下:1、速断、过流时:起动A4~A5跳闸,起动A10~A11事故报警,起动A7~A8切断合闸回路。

2、过载发生:起动L5~L6报警。

3、二次零流达到0.1A,延时0.5秒,起动L11~L12跳闸,起动A10~A11事故报警,起动L5~L6报预警(如果在供电局不要求跳闸时,可将2LP事先分断),仅使L5~L6报预警有效。

(由外部2LP确定是跳闸还是仅报预警) 。

4、高温动作K6:也仅起动L5~L6报预警(和零流、过载报预警共用,届时查看对应仪表区分)。

5、超高温动作K7,K1:K7起动A4~A5跳闸,起动A10~A11事故报警,起动A7~A8切断合闸回路;如果不要求跳闸,可将3LP事先分断仅由K1起动L8~L9报预警。

(由外部3LP确定是跳闸还是仅报预警) 。

电力系统继电保护课程设计说明书

电力系统继电保护课程设计说明书

目录课程设计任务书......................................................................................... 错误!未定义书签。

课程设计选题之一 .. (4)1概述 (6)1.1继电保护的任务 (7)1.2继电保护整定计算的基本任务 (7)1.3本设计继电保护内容 (7)2保护配置原则及结果 (7)2.1 110kV电网继电保护配置原则 (8)2.2本区域电网的运行方式说明 (8)2.3本区域电网继电保护配置方案 (9)3 整定计算 (10)3.1 发电机、变压器、线路的参数的计算 (10)3.2正序、零序网路图 (13)3.3线路距离保护的整定计算 (14)4 结论 (20)5 参考文献 (21)课程设计选题之一(一)已知条件1、110kV系统接线简图如图所示。

发电厂甲变电所(二)参数选择与具体任务(1)各线路的负荷自起动系数5.1K;其它参数按书上选择。

=ss(2)发电厂各发电机组的次暂态电抗均为''X=0.129(按自身额定容量的标么值);d功率因数为均为0.85。

最大发电容量为机组同时投运,最小发电容量为退出一台发电机组。

假设发电机正、负电抗相等,等于次暂态电抗。

(3)各变电所引出线上的后备保护动作时间如图示,后备保护的时限级差△t=0.5s;线路保护需整定两侧保护动作值,保护包括接地保护和相间保护。

(4)线路的正序电抗每公里均为0.4Ω/kM;负序阻抗等于正序阻抗;零序阻抗为1.2Ω/kM;线路阻抗角为80º。

(5)电压互感器的变比1.0/=n kV,线路电流互感器变比可根据线路最大负110TV荷电流选择,负荷阻抗角为30º。

(6)系统最大及最小的正序、零序等值阻抗都已折算到100MVA标准容量下,系统S中性点接地。

变压器的短路电压百分比按本变压器额定容量给出,具体参数见任务安排表。

1600KVA变压器

1600KVA变压器

变压器招标文件(技术部分)一.总则1、总体要求1.1.本招标文件适用于成都市华西海圻永安项目工程的变压器及高低压配电柜设备。

它提出设备的功能设计、结构、性能、安装、试验和检修等方面的技术要求。

1.2.招标方在本招标文件中提出了最低限度的技术要求,并未对一切技术细节做出规定,也未充分引述有关标准和规范的条文,投标方应提供符合民用建筑标准和本招标书的优质产品及其相应服务。

同时必须满足国家有关安全、环保等强制性标准和规范的要求。

1.3.本招标文件中设备交货期为:年月日前甲方安装场地交货投标方应提供:(1)满足本招标文件和所列标准要求的高质量产品及其相应服务。

(2)投标方应提供高质量的设备,这些设备应是技术先进并经过两台三年以上成功运行实践证明是成熟可靠的产品。

投标方应具有5年以上设计、制造同类设备的历史并有3年以上良好的运行经验,在安装调试运行中未发现重大的设备质量问题或已有有效的改进措施。

1.3投标方必须持有权威机关颁发的ISO-9000系列认证书或等同的质量保证体系认证证书。

1.4.如对本招标文件有偏差(包括任何细微偏差,无论多少)都必须清楚地表示在本招标文件的附录“差异表”中。

否则将认为投标方完全响应本招标文件提出的要求。

1.5.投标方须执行本招标文件所列标准。

有矛盾时,按照技术要求严格的条款所述标准执行。

1.6.若投标方所提供的投标文件前后有不一致的地方,应以更有利于设备安装运行、工程质量为原则,由招标方确定。

1.7.合同签订后1周内,按本规范要求,投标方提出合同设备的设计、制造、检验/试验、装配、安装、调试、试运、验收、试验、运行和维护等标准清单给招标方,由招标方确认。

1.8.标识原则、方法和内容在签定技术协议时讨论确定。

1.9.投标方应保证提供的产品符合安全、健康、环保标准的要求。

投标方对成套设备(含辅助系统与设备)负有全部技术及质量责任,包括分包(或采购)的设备和零部件。

1.10.在签订合同之后,招标方有权提出因规范标准和规程发生变化而产生的一些补充要求,在设备投料生产前,投标方应在设计上给予修改。

电力系统继电保护说明书

电力系统继电保护说明书

第一章概述第 1 . 1节电力系统继电保护的作用电力是当今世界使用最为广泛、地位最为重要的能源,电力系统的安全稳定运行对国民经济、人民生活乃至社会稳定都有着极为重大的影响。

电力系统由各种电气元件组成。

这里电气元件是一个常用术语,它泛指电力系统中的各种在电气上的独立看待的电气设备、线路、器具等。

由于自然环境,制造质量运行维护水平等诸方面的原因,电力系统的各种元件在运行中可能出现各种故障或不正常运行状态。

因此,需要有专门的技术为电力系统建立一个安全保障体系,其中最重要的专门技术之一就是继电保护技术。

电力系统继电保护的基本作用是:在全系统范围内,按指定分区实时的检测各种故障和不正常运行状态,快速及时地采取故障隔离或告警等措施,以求最大限度地维持系统的稳定,保持供电的连续性,保障人身的安全,防止或减轻设备的损坏。

第 1 . 2节电力系统继电保护技术与继电保护装置继电保护技术是一个完整的体系,它主要由电力系统的故障分析、继电保护原理及实现、继电保护配置设计、继电保护运行与维护等技术构成,而完成继电保护功能的核心是继电保护装置。

继电保护装置,是指装设于整个电力系统的各个元件上,能在指定区域快速准确地对电气元件发出的各种故障或不正常运行状态作出反应,并按规定时限内动作,时断路器跳闸或发出告警信号的一种反事故自动装置。

继电保护装置的基本任务是:(1)自动、迅速、有选择地将故障元件从电力系统中切除并最大限度地保证其他无故障部分恢复正常运行;(2)能对电气元件的不正常运行状态作出反应,并根据运行维护规范和设备承受能力动作,发出告警信号,或减负荷,或延时跳闸;(3)条件许可时,可采取预定措施,尽快地恢复供电和设备运行。

总之,继电保护技术是电力系统必不可少的组成部分,对保障系统安全运行,保证电能质量,防止故障扩大和事故发生,都有极其重要的作用。

第1.3节继电保护的基本要求对作用于跳闸的继电保护装置,在技术上有四个基本要求,也就是所说的“四性”:选择性、速动性、灵敏性和可靠性。

箱变1250KVA变压器)

箱变1250KVA变压器)

附件一1250KV A、1600KV A干式变压器技术协议四川凯力威置业有限公司二〇一四年三月五日第一部分技术要求1、总则1.1、本设备技术要求适用于10kV预装式(欧式)箱变,技术要求提出了该产品的功能设计、结构、性能、和试验等方面的要求。

1.2、甲方在本技术协议中提出了最低限度的技术要求,并未规定所有的技术要求和适用的标准,未对一切技术细则作出规定,也未充分引述有关标准和规范的条文,乙方应提供一套满足本技术协议和现行有关标准要求的高质量产品及其相应服务,乙方可以提供满足更高的标准的产品。

1.3、如果乙方没有以书面形式对本技术协议的条款提出异议,则意味着乙方提供的设备(或系统)完全满足本技术协议的要求。

1.4、本设备技术协议经甲乙双方确认后作为订货合同的技术附件,与合同正文具有同等的法律效力。

1.5、乙方须执行现行国家标准和行业标准。

应遵循的主要现行标准如下。

本技术规范出版时,所示版本均为有效。

所有标准都会被修订,供需双方应探讨使用下列标准最新版本的可能性。

有矛盾时,按现行的技术要求较高的标准执行。

DL/T 537-2002 《高压 / 低压预装箱式变电站选用导则》DL/T 537-1993 《 6 ~ 35kV 箱式变电站订货技术条件》GB311.1-1997 《高压输变电设备的绝缘配合》GB6450-1986 《干式电力变压器》GB11022-1999 《高压开关设备和控制设备标准的共用技术要求》GB3804-1990 《 3 ~ 63kV 交流负荷开关》GB7328-1987 《电力变压器和电抗器的声级测定》2、使用环境条件2.1、周围空气温度:最高气温:+ 40 ℃最低气温:- 17.5 ℃最高日平均气温:+ 30 ℃最高年平均气温:+ 20 ℃最大日温差: 25K2.2、海拔:不超过 1000m ;2.3、风速:不大于 25m /s ;2.4、环境湿度:月平均值不大于 90% ;日平均值不大于 95% ;2.5、耐地震能力地震烈度: 8 级地面水平加速度: 0.2g;地面垂直加速度: 0.1g ;2.6、安装地点的倾斜度:不大于 3 °2.7、考虑日照、污秽、凝露及自然腐蚀的影响。

1250KVA继电保护说明书

1250KVA继电保护说明书

变压器1250kva继电保护说明书一、变压器为1250kva;10kv/0.4kv;△/Y;三相电流比150/5A;1、速断:整定值:供电局提供:<0.2秒(从互感器处加入电流,到开关端口断开测得)2、过流:整定值:供电局提供:<0.5秒(从互感器处加入电流,到开关端口断开测得)过载:整定值:变压器容量105%,一次75.9A,二次2.5A,延时9秒报预警。

3、零序电流:供电局不提供时,我方作如下规定:取变压器容量的2.5%作为零流的基准值,动作跳闸或报预警,即一次零流1.8A;二次零流0.06A动作跳闸或报预警,延时0.5秒。

本系统室内接地因高压线路很短,互感器前侧接地流经互感器的零流很小,互感器后侧接地流经互感器的零流很大,本装置只对互感器后侧接地有效,前侧端接地只靠供电局线路保护解决,如果0.06A会动作时,应会诊后按0.1A,0.15A,0.2A,0.25A….. 以0.05A级逐步放大(变压器为△/Y不考虑低压侧零流问题),或重新由测量计算所得。

总之,-次零序电流限止在远小于10A以内。

4、压变低压继电器动作报警1YJ--3YJ为70V。

二、施耐德T40 CCA634+MES114( ,E,F)综保屏编制要求如下:1、速断、过流时:起动A4~A5跳闸,起动A10~A11事故报警,起动A7~A8切断合闸回路。

2、过载发生:起动L5~L6报警。

3、二次零流达到0.06A,延时0.5秒,起动L11~L12跳闸,起动A10~A11事故报警,起动L5~L6报预警(如果在供电局不要求跳闸时,可将2LP事先分断),仅使L5~L6报预警有效。

(由外部2LP确定是跳闸还是仅报预警) 。

4、高温动作K6:也仅起动L5~L6报预警(和零流、过载报预警共用,届时查看对应仪表区分)。

5、超高温动作K7,K1:K7起动A4~A5跳闸,起动A10~A11事故报警,起动A7~A8切断合闸回路;如果不要求跳闸,可将3LP事先分断仅由K1起动L8~L9报预警。

继电保护计算及整定

继电保护计算及整定

(3)短路回路的总阻抗 Z=〔(ΣX)2+(ΣR)2〕1/2 (4)短路电流的计算 三相短路电流: Id(3)=Up/(1.732×Z) Up——短路点所在电网的平均电压,V Z——短路点至母线的阻抗 两相短路电流: Id(2) ≈ 0.87 Id(3)
2、低压线路短路电流计算 (1)系统电抗 Xx=Up2/Sd ,Ω Up——低压线路平均电压,KV Sd——母线上短路容量,MVA
继电保护计算及整定
一、高开整定 以下一级所带变压器容量计算
Iz=Ie=Sb/(1.732xUe) Id≥(5-8)Iz
二、移变 1、高压侧 以变压器额定容量为基准计算,过 流、短路整定值比上一级高开适当小 些。
2、低压侧(馈电开关)
Iz=∑Pe/(1.732xUex0.85) Id≥Ioe+Kx∑Ie Ioe——容量最大的电动机的额定电 流,对于有数台电动 机同时启动的工作机械,若其总功率大于单台启动的容量 最大电动机功率,Ioe则为这几台同时启动的电动机的额定 启动电流之和; ∑Ie——其余电动机的额定电流之和 A KX——需用系数(取0.6—抗 XL=xL ,Ω X——输电线路单位长度上的电抗,Ω/km (1.2KV电缆线路取0.07) L——输电线路的长度,km 线路电阻 R=L/D×S ,Ω L——电缆长度,M D——铜芯电缆的电导率,m/(Ω· mm2)(取42.5) S——电缆芯线截面,mm2
(5)短路电流的计算 三相短路电流 Id(3) =Up/1.732×Z Up——短路点所在电网的平均电压, V Z——短路点至母线的阻抗 两相短路电流 Id(2) ≈ 0.87 Id(3)
三、馈电开关 以下级所带总负荷为基准计算,过流、 短路整定值比上一级移变低压侧适当小些。
  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

继电保护说明书
变压器1600KVA+1250KV A2总柜
一、变压器为1600KV A+1250KV A总柜;10kv/0.4kv;△/Y;三相电流比250/5A;
1、速断:整定值:供电局提供:<0.2秒(从互感器处加入电流,到开关端口断开测得)
2、过流:整定值:供电局提供:<0.5秒(从互感器处加入电流,到开关端口断开测得)
过载:整定值:总变压器容量80%,一次130A,二次2.5A,延时9秒报预警。

3、零序电流:供电局不提供时,我方作如下规定:取总变压器容量的2.5%作为零流的
基准值,动作跳闸或报预警,即一次零流4.0A;二次零流0.08A动作跳闸或报预警,延时0.5秒。

本系统室内接地因高压线路很短,互感器前侧接地流经互感器的零流
很小,互感器后侧接地流经互感器的零流很大,本装置只对互感器后侧接地有效,
前侧端接地只靠供电局线路保护解决,如果0.08A会动作时,应会诊后按
0.10A,0.15A,0.2A,0.25A….. 以0.05A级逐步放大(变压器为△/Y不考虑低压侧零
流问题),或重新由测量计算所得。

总之,-次零序电流限止在远小于10A以内。

4、压变低压继电器动作报警1YJ--3YJ为70V。

二、施耐德T40 CCA634+MES114( ,E,F)综保屏编制要求如下:
1、速断、过流时:起动A4~A5跳闸,起动A10~A11事故报警,起动A7~A8切断合
闸回路。

2、过载发生:起动L5~L6报警。

3、二次零流达到0.08A,延时0.5秒,起动L11~L12跳闸,起动A10~A11事故报警,
起动L5~L6报预警(如果在供电局不要求跳闸时,可将2LP事先分断),仅使L5~L6
报预警有效。

(由外部2LP确定是跳闸还是仅报预警) 。

4、高温动作K6:也仅起动L5~L6报预警(和零流、过载报预警共用,届时查看对应仪
表区分)。

5、超高温动作K7,K1:K7起动A4~A5跳闸,起动A10~A11事故报警,起动A7~A8
切断合闸回路;如果不要求跳闸,可将3LP事先分断仅由K1起动L8~L9报预警。

(由
外部3LP确定是跳闸还是仅报预警) 。

6、远程操作:SA远程K9有效时,L2~L3合闸有效,A4~A5分闸有效,内部状态远
程通信有效(本次不考虑远程通信及远程操作,仅作备用,需远程的,甲方追加)。

综合上述:零流动作选择跳闸或报预警由外部2LP确定,方便设备投入零流漂移防误跳和方便调整;超高温信号选择跳闸或者报预警,由外部3LP确定。

在任何情况下零流和超高温动作下,可以有条件关闭跳闸。

但不能关闭报预警,关闭报预警后果严重。

设备资产属于甲方的,甲方有权确定选择跳闸还是报预警,甲方不签字确认的,一律给予跳闸处理,一经投运,甲方在续保期要求零流和超高温动作变更,应以书面提供依据,方可协商解决,甲方也可自行处理,责任与我方无关。

本说明书,也称告知书,一并随图送于甲方存档,并要求调试人员按本说明书操作。

共同遵守电力法规,保你我他各方平安。

上海光大科技(集团)有限公司
设计人员:李新福
2012-6-16。