约克 YORK 彩屏YK离心操作说明书

约克 YORK 彩屏YK离心操作说明书
约克 YORK 彩屏YK离心操作说明书

M AX E TM

CENTRIFUGAL LIQUID CHILLERS

Supersedes: NOTHING Form 160.73-O2 (1202) MODEL YK (STYLE F)

R-134a COOLING ONLY

WITH OPTIVIEW TM CONTROL CENTER

FOR ELECTRO-MECHANICAL STARTER,

SOLID STATE STARTER & VARIABLE SPEED DRIVE

00611VIP

LDO5842

YORK INTERNATIONAL

FORM 160.73-O2(1202)

2

This equipment is a relatively complicated apparatus. During installation, operation, maintenance or service, individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, oils, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and respon-sibility of operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property

IMPORTANT!

READ BEFORE PROCEEDING!

GENERAL SAFETY GUIDELINES

in which it is situated, as well as severe personal in-jury or death to themselves and people at the site.This document is intended for use by owner-authorized operating/service personnel. It is expected that this in-dividual possesses independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and under-stood this document and any referenced materials. This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question.

SAFETY SYMBOLS

The following symbols are used in this document to alert the reader to areas of potential hazard:

WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or se-rious injury.

DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

CAUTION identifies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollution. Usually an instruction will be given, together with a brief explanation.

External wiring, unless specified as an optional connection in the manufacturer’s product line, is NOT to be connected inside the micro panel cabinet. Devices such as relays, switches, transducers and controls may NOT be installed inside the micro panel. NO external wiring is allowed to be run through the micro panel. All wiring must be in accordance with YORK’s published specifications and must be performed ONLY by qualified YORK personnel. YORK will not be responsible for damages/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this will void the manufacturer’s warranty and cause serious damage to property or injury to persons.

NOTE is used to highlight additional information which may be helpful to you.

FORM 160.73-O2(1202)

YORK INTERNATIONAL

3

CHANGEABILITY OF THIS DOCUMENT

It is the responsibility of operating/service personnel as to the applicability of these documents to the equip-ment in question. If there is any question in the mind of operating/service personnel as to the applicability of these documents, then, prior to working on the equipment, they should verify with the owner whether the equipment has been modified and if current literature is available.

DESIGN LEVEL (F)

POWER SUPPLY – for 60 Hz 5 for 50 Hz COMPRESSOR CODE H4, H5, H6, H7, H8, J1, J2, J3, J4, P1, P2, P3, P4, P5, P6, P7 CONDENSER CODE

AB, AC, AD, BB, BC, BD, CF, CG, CH, DF, DG, DH, EB, EC, ED, FA, FB, FC, FD, GB, GC, GD, HB, HC, HD, JB, JC, JD, TB, TC, TD, VB, VC, VD EVAPORATOR CODE

AB, AC, AD, BB, BC, BD, CF, CG, CH, DF, DG, DH MODEL EB, FB, FC, FD, GB, GC, GD, GF, GH, HB, HC, HF, HH, JF, JG, JH, TF, TG, TH, VF, VH, WF, WH

NOMENCLATURE

YK CB CB P6 – CM F

MOTOR CODE 60 Hz 50 Hz CH CX 5CE 5CT CJ CY 5CF 5CU CK CZ 5CG 5CV CL CA 5CH 5CW CM CB 5CI 5CX CN DA 5CJ 5DA CP DB 5CK 5DB CR DC 5CL 5DC CS DD 5CM 5DD CT DE 5CN 5DE CU DF 5CO 5DF CV DH 5CP 5DG CW DJ 5CQ 5DH CF CG 5CR 5OJ 5CS

-uct improvement, the information contained in this doc-ument is subject to change without notice. While YORK makes no commitment to update or provide current information automatically to the manual owner, that in-formation, if applicable, can be obtained by contacting the nearest YORK Applied Systems Service office.

REFERENCE INSTRUCTIONS

DESCRIPTION FORM NO. SOLID STATE STARTER (MOD “B”) – OPERATION & MAINTENANCE 160.00-O2 VARIABLE SPEED DRIVE – OPERATION 160.00-O1 VARIABLE SPEED DRIVE – SERVICE INSTRUCTIONS 160.00-M1 INSTALLATION 160.73-N1 OPTIVIEW CONTROL CENTER - SERVICE INSTRUCTIONS 160-54-M1 WIRING DIAGRAM – UNIT WITH ELECTRO-MECHANICAL STARTER 160.73-PW1 WIRING DIAGRAM – UNIT WITH MOD “A” SOLID STATE STARTER 160.73-PW2 WIRING DIAGRAM – UNIT WITH VARIABLE SPEED DRIVE 160.73-PW3 RENEWAL PARTS – UNIT 160.73-RP4 RENEWAL PARTS – OPTIVIEW CONTROL CENTER 160.54-RP1 OPTIVIEW? PANEL - OPERATION & MAINTENANCE 160.54.O1

FORM 160.73-O2(1202)

4SECTION 1 Description of System and Fundamentals of Operation (6)

System Operating Procedures......................................................................

9

System Components Description (1)

5

Operational Maintenance (21)

Troubleshooting (23)

SECTION 6Maintenance (25)

SECTION 7Preventive Maintenance (34)

TABLE OF CONTENTS

YORK INTERNATIONAL

FORM 160.73-O2(1202)

LIST OF FIGURES

FIG. 1 – MODEL YK MAXE TM CHILLER (6)

DETAIL A – COMPRESSOR PREROTATION

VANES (7)

FIG. 2 – REFRIGERANT FLOW-THROUGH CHILLER (8)

FIG. 3 – OIL LEVEL INDICATOR LABEL (9)

FIG. 4 – CHILLER STARTING SEQUENCE &

SHUTDOWN SEQUENCE

(EM STARTER & SOLID STATE STARTER) (10)

FIG. 5 – CHILLER STARTING SEQUENCE &

SHUTDOWN SEQUENCE

(VARIABLE SPEED DRIVE) (11)

FIG. 6 – LIQUID CHILLER LOG SHEETS (12)

FIG. 7 – SYSTEM COMPONENTS (15)

FIG. 8 – SCHEMATIC DRAWING (YK) COMPRESSOR

LUBRICATION SYSTEM (16)

FIG. 9 – OIL RETURN SYSTEM (21)

FIG. 10 – CHARGING OIL RESERVOIR WITH OIL (22)

FIG. 11– EVACUATION OF CHILLER (25)

FIG. 12 – SATURATION CURVE (27)

FIG. 13 – DIAGRAM - MEGGING MOTOR WINDINGS (29)

FIG. 14 – MOTOR STATOR TEMPERATURE &

INSULATION RESISTANCE (30)

YORK INTERNATIONAL5

FORM 160.73-O2(1202)

6

electro-mechanical starter, YORK Solid State Starter

(optional), or Variable Speed Drive (optional).

In operation, a liquid (water or brine to be chilled)

flows through the evaporator, where boiling refrigerant

absorbs heat from the liquid. The chilled liquid is then

piped to fan coil units or other air conditioning terminal

units, where it flows through finned coils, absorbing heat

from the air. The warmed liquid is then returned to the

chiller to complete the chilled liquid circuit.

The refrigerant vapor, which is produced by the boil-

ing action in the evaporator, flows to the compressor

where the rotating impeller increases its pressure and

temperature and discharges it into the condenser. Water

flowing through the condenser tubes absorbs heat from

the refrigerant vapor, causing it to condense. The con-

denser water is supplied to the chiller from an external

SECTION 1

DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION

00116vip CONDENSER

CONTROL

CENTER

COMPRESSOR

MOTOR

EVAPORATOR

FIG. 1 – MODEL YK MAXE TM CHILLER

SYSTEM OPERATION DESCRIPTION (SEE FIG. 2)

The YORK Model YK MaxE TM Chiller is commonly ap-

plied to large air conditioning systems, but may be used on

other applications. The chiller consists of an open motor

mounted to a compressor (with integral speed increasing

gears), condenser, evaporator and variable flow control.

The chiller is controlled by a modern state of the art Mi-

crocomputer Control Center that monitors its operation.

The Control Center is programmed by the operator to suit

job specifications. Automatic timed start-ups and shut-

downs are also programmable to suit nighttime, week-

ends, and holidays. The operating status, temperatures,

pressures, and other information pertinent to operation

of the chiller are automatically displayed and read on a

graphic display. Other displays can be observed by press-

ing the keys as labeled on the Control Center. The chiller

with the OptiView Control Center is compatible with an

YORK INTERNATIONAL

FORM 160.73-O2(1202)

YORK INTERNATIONAL

7

1

source, usually a cooling tower. The condensed refrig-erant drains from the condenser into the liquid return line, where the variable orifice meters the flow of liquid refrigerant to the evaporator to complete the refrigerant circuit.

7619A(D)

DETAIL A –

COMPRESSOR PREROTATION VANES

Description of System and Fundamentals of Operation

The major components of a chiller are selected to handle the refrigerant, which would be evaporated at full load design conditions. However, most systems will be called upon to deliver full load capacity for only a relatively small part of the time the unit is in operation.

CAPACITY CONTROL

The major components of a chiller are selected for full load capacities, therefore capacity must be controlled to maintain a constant chilled liquid temperature leaving the evaporator. Prerotation vanes (PRV), located at the entrance to the compressor impeller, compensate for variation in load (See Detail A).

The position of these vanes is automatically controlled through a lever arm attached to an electric motor located outside the compressor housing. The automatic adjust-ment of the vane position in effect provides the perfor-mance of many different compressors to match various load conditions from full load with vanes wide open to minimum load with vanes completely closed.

YORK INTERNATIONAL

FORM 160.73-O2(1202)

8

FIG. 2 – REFRIGERANT FLOW-THRU CHILLER PREROTATION VANES (See Detail A)

SUCTION

EVAPORATOR

ELIMINATOR

OIL COOLER

LD00924

FLOW CONTROL ORIFICE

SUB-COOLER

CONDENSER

DISCHARGE BAFFLE

DISCHARGE

COMPRESSOR

FORM 160.73-O2(1202)

YORK INTERNATIONAL

9

START-UP PROCEDURE

Pre-Starting

Prior to starting the chiller, observe the OptiView Control Center. Make sure the display reads SYSTEM READY TO START .

To pre-start the chiller, use the following procedure: 1.Oil Heater – The oil heater must be energized for 12 hours prior to starting the chiller.

2.Prior to start, the clock must be programmed for the proper day and time. Any setpoints which are desired to be changed may be programmed. All Control Cen-ter setpoints should be programmed before the chiller is started. (Refer to Form 160.54-O1).

Vent any air from the chiller water boxes prior to starting the water pumps. Failure to do so will result in pass baffle damage.

START-UP

1.If the chilled water pump is manually operated, start the pump. The Control Center will not allow the chiller to start unless chilled liquid flow is established through the unit. (A field supplied chilled water flow switch is required.) If the chilled liquid pump is wired to the Microcomputer Control Center the pump will automatically start, therefore, this step is not neces-sary.

System Operating Procedures

SECTION 2

SYSTEM OPERATING PROCEDURES

OIL HEATERS

If the oil heater is de-energized during a shutdown period, it must be energized for 12 hours prior to starting com-pressor, or remove all oil and recharge compressor with new oil. (See “Oil Charging Procedure”, page 22.)

OIL HEATER OPERATION

The oil heater operation is controlled by the OptiView? Control Center. The heater is turned on and off to main-tain the oil temperature to a value 50°F (10°C) above the condenser saturation temperature. This is the target value and if the oil temperature falls to 4°F (-15.5°C) or more below the target, the heater is turned on. It is turned off when the oil temperature increases to 3°F (-16°C) above the target value.

If the target value is greater than 160°F (71°C), the target defaults to 160°F (71°C). If the target value is less than 110°F (43.3°C), it defaults to 110°F (43.3°C). To prevent overheating of the oil in the event of a con-trol center component failure, the oil heater thermostat (1HTR) is set to open at 180°F (82°C).

CHECKING THE OIL LEVEL IN THE OIL RESERVOIR

Proper operating oil level – During operation, the oil level should fall to the “Operating Range” identified on the vertical oil level indicator label. See Figure 3.

? If the oil level during operation is in the “Over

Full” region of the oil level indicator, oil should be removed from the oil reservoir, This reduces the oil level to the “Operating Range”.

? If the oil level during operation is in the “Low Oil”

region of the oil level indicator, oil should be added to the oil reservoir. (See “Oil Charging Procedure”, page 22)

Comply with EPA and Local regu-lations when removing or disposing

of Refrigeration System oil!

FIG. 3 – OIL LEVEL INDICATOR LABEL

LD08647

YORK INTERNATIONAL

FORM 160.73-O2(1202)

10

2.To start the chiller, press the COMPRESSOR START switch. This switch will automatically spring return to the RUN position. (If the unit was previously started, press the STOP/RESET side of the COMPRESSOR switch and then press the START side of the switch to start the chiller.) When the start switch is energized, the Control Center is placed in an operating mode and any malfunction will be noted by messages on a graphic display.

Any malfunctions which occur during STOP/RESET are also displayed.

When the chiller is shut down, the prerotation vanes will close automatically to prevent loading the compressor on start-up.

When the chiller starts to operate, the following au-tomatic sequences are initiated: (Refer to Fig. 4 & 5, “Chiller Starting & Shutdown Sequence Chart”.)

1.The OptiView Control Center display message will

read SYSTEM PRELUBE for the first 50 seconds of the starting sequence.

2.The oil pump will start to circulate oil for a 50 second pre-run to establish oil flow and adequate lubrication to all bearings, gears, and rotating surfaces within the compressor.

The high and low oil pressure transducers (OP) and the oil temperature sensor (RT3) will sense any mal-function in the lubrication system.

3.The anti-recycle timer software function will operate after the 50 seconds of pre-run time. At this time, the timer will be initiated and will run for 30 minutes after the compressor starts. If the chiller shuts down during this period of time, it cannot be started until the timer completes the 30 minute cycle.

4.The chilled liquid pump contacts will close, start-ing the chilled liquid pump, to allow liquid flow through the evaporator when the COMPRESSOR start switch is energized.

5.After the first 50 seconds of operation, the com-pressor will start.

6.For display messages and information pertaining to the operation of the OptiView? Control Center, refer to Form 160.54-O1.

FIG. 4 – CHILLER STARTING SEQUENCE & SHUTDOWN SEQUENCE (EM STARTER & SOLID STATE STARTER)LD04040

** NOT FOR ALL SHUTDOWNS. REFER TO “DISPLAY MES-SAGES” SECTION OF THIS MANUAL.

FORM 160.73-O2(1202)

YORK

INTERNATIONAL

11

2

FIG. 5 – CHILLER STARTING SEQUENCE & SHUTDOWN SEQUENCE (VARIABLE SPEED DRIVE)

LD04130

CHILLER OPERATION

After the compressor reaches its operating speed, the Prerotation Vanes will begin to open under the control of the Microprocessor Board which senses the leaving chilled liquid temperature. The unit capacity will vary to maintain the leaving CHILLED LIQUID TEMPERA-TURE setpoint. The Prerotation Vanes are modulated by an actuator under the control of the Microprocessor Board. The vane control routine employs proportional plus derivative (rate) control action. A drop in chilled liquid temperature will cause the actuator to close the Prerotation Vanes to decrease chiller capacity. When the chilled liquid temperature rises, the actuator will open the Prerotation Vanes to increase the capacity of the chiller.

However, the current draw (amperes) by the compressor motor cannot exceed the setting of the % CURRENT LIMIT at any time during the unit operation, since the Microcomputer Control Center 40 to 100% three-phase peak current limit software function, plus the 3-phase 100% solid state overload current limiter (CM-2), on Electro-Mechanical Starter applications, or the Solid State Starter current Limit function will override the temperature control function and prevent the Prerotation Vanes from opening beyond the % CURRENT LIMIT setting.

** NOT FOR ALL SHUTDOWNS. REFER TO “DISPLAY MES-SAGES” SECTION OF THIS MANUAL.

System Operating Procedures

If the load continues to decrease, after the Prerotation Vanes are entirely closed, the chiller will be shut down by the Leaving Chilled Liquid – Low Temperature Control.

CONDENSER WATER TEMPERATURE CONTROL

The YORK MaxE TM chiller is designed to use less power by taking advantage of lower than design temperatures that are naturally produced by cooling towers throughout the operating year. Exact control of condenser water such as a cooling tower bypass, is not necessary for most installations. The chiller requires only that the minimum condenser water temperature be no lower than the value

determined by referring to the formula below:

where:

ECWT = Entering Condensing Water Temperature LCWT = Leaving Chilled Water Temperature

C Range = Condensing water temperature range at the given load condition.

Min. ECWT = LCWT – C RANGE + 17oF Min. ECWT = LCWT – C RANGE + 9.4oC

YORK INTERNATIONAL

FORM 160.73-O2(1202)

12

OPERATING INSPECTIONS – See Section 2

By following a regular inspection using the display readings of the Microcomputer Control Center, and maintenance procedure, the operator will avoid serious operating difficulty. The following list of inspections and procedures should be used as a guide.Daily

1.Check OptiView? Control Center displays.

2.If the compressor is in operation, check the bearing oil pressure on the SYSTEM Screen. Also check the oil level in the oil reservoir. Operating oil level should be between the upper and lower sight glasses. Drain or add oil if necessary.

3.Check entering and leaving condenser water pressure and temperatures for comparison with job design conditions. Condenser water temperatures can be checked on the SYSTEM Screen.

4.Check the entering and leaving chilled liquid tem-peratures and evaporator pressure for comparison with job design conditions on the SYSTEM Screen.

5.Check the condenser saturation temperature (based upon condenser pressure sensed by the condenser transducer) on the SYSTEM Screen.

6.Check the compressor discharge temperature on the SYSTEM Screen. During normal operation discharge temperature should not exceed 220°F (104°C).

At start-up, the entering condenser water temperature may be as much as 25°F (14°C) colder than the standby return chilled water temperature. Cooling tower fan cycling will normally provide adequate control of the entering condenser water temperature on most instal-lations.

OPERATING LOG SHEET

A permanent daily record of system operating conditions (temperatures and pressures) recorded at regular inter-vals throughout each 24 hour operating period should be kept.

An optional status printer is available for this purpose or Fig. 6 shows a log sheet used by YORK Personnel for recording test data on chiller systems. It is available from the factory in pads of 50 sheets each under Form 160.44-F7 and may be obtained through the nearest YORK office. Automatic data logging is possible by connecting the optional printer and programming the DATA LOGGER function.

An accurate record of readings serves as a valuable reference for operating the system. Readings taken when a system is newly installed will establish normal conditions with which to compare later readings.For example, an increase in condenser approach temperature (condenser temperature minus leaving condenser water temperature) may be an indication of dirty condenser tubes.

FIG. 6 – LIQUID CHILLER LOG SHEETS *NOTE: These items can be printed by an electronic printer connected to the Microboard and pressing the PRINT

key on the Keypad, or automatically using the Data Logger feature.

LD00467

23889A

FORM 160.73-O2(1202)

YORK INTERNATIONAL132

7.Check the compressor motor current on the SYSTEM

Screen.

8.Check for any signs of dirty or fouled condenser

tubes. (The temperature difference between water leaving condenser and saturated condensing tem-perature should not exceed the difference recorded for a new unit by more than 4°F, 2.2°C). Weekly

1.Check the refrigerant charge. (See “Checking The

Refrigerant Charge”, page 28.)

2.Leak check the entire chiller.

Quarterly

1.Perform chemical analysis of oil.

Semi-Annually (or more often as required)

1.Change and inspect compressor oil filter element.

2.Oil return system.

a.Change dehydrator.

b.Check nozzle of eductor for foreign particles.

3.Check controls and safety cutouts.

Annually (more often if necessary)

If quarterly inspection indicates oil is

fine, replacing the oil is not necessary.

1.Drain and replace the oil in the compressor oil sump.

(See “Oil Charging Procedure” page 22.)

2.Evaporator and Condenser.

a.Inspect and clean water strainers.

b.Inspect and clean tubes as required.

c.Inspect end sheets.

https://www.360docs.net/doc/321766021.html,pressor Drive Motor (See motor manufacturers

maintenance and service instruction supplied with unit)

a.Clean air passages and windings per manufac-

turers instructions. b.Meg motor windings – See Fig. 13 for details.

c.Lubricate per motor manufacturer recommenda-

tions.

4.Inspect and service electrical components as necessary.

5.Perform refrigerant analysis.

NEED FOR MAINTENANCE OR SERVICE

If the system is malfunctioning in any manner or the unit is stopped by one of the safety controls, consult the “Operation Analysis Chart”, (Table 1), pages 23 and 24 of this instruction. After consulting this chart, if you are unable to make the proper repairs or adjust-ments to start the compressor or the particular trouble continues to hinder the performance of the unit, please call the nearest YORK District Office. Failure to report constant troubles could damage the unit and increase the cost of repairs.

STOPPING THE SYSTEM

The Optiview? Control Center can be programmed to start and stop automatically (maximum, once each day) whenever desired. Refer to Form 160.54-O1. To stop the chiller, proceed as follows:

1.Push the COMPRESSOR STOP/RESET switch.

The compressor will stop automatically. The oil pump will continue to run for coastdown period.

The oil pump will then stop automatically.

2.Stop the chilled water pump (if not wired into the

Microcomputer Control Center, in which case it will shut off automatically simultaneously with the oil pump.) (The actual water pump contact operation is dependent upon the position of Microboard jumper J54.)

3.Open the switch to the cooling tower fan motors, if

used.

4.The compressor sump oil heater is energized when

the unit is stopped.

PROLONGED SHUTDOWN

If the chiller is to be shut down for an extended period of time (for example, over the winter season), the following paragraphs outline the procedure to be followed.

1.Test all system joints for refrigerant leaks with a

System Operating Procedures

FORM 160.73-O2(1202)

14leak detector. If any leaks are found, they should be repaired before allowing the system to stand for a long period of time.

During long idle periods, the tightness of the system should be checked periodically.

2.If freezing temperatures are encountered while the

system is idle, carefully drain the cooling water from the cooling tower, condenser, condenser pump, and the chilled water system-chilled water pump and coils.

Open the drains on the evaporator and condenser liquid heads to assure complete drainage. (If a Vari-

able Speed Drive, drain its water cooling system. If Solid State Starter. drain water from starter cooling loop.)

3.On the SETUP Screen, disable the clock. This con-

serves the battery.

4.Open the main disconnect switches to the compressor

motor, condenser water pump and the chilled water pump. Open the 115 volt circuit to the Control Cen-ter.

YORK INTERNATIONAL

FORM 160.73-O2(1202)

YORK INTERNATIONAL

15

SECTION 3

SYSTEM COMPONENTS DESCRIPTION

MOTOR

EVAPORATOR

COMPRESSOR

SUCTION

DUAL RELIEF VALVES

SIGHT GLASS

VARIABLE SPEED

OIL PUMP CONTROL

BOX REFRIGERANT CHARGING VALVE

00611vip

FRONT VIEW

FIG. 7 – SYSTEM COMPONENTS

OPTIVIEW CONTROL

CENTER

3

YORK INTERNATIONAL

FORM 160.73-O2(1202)

16

FIG. 7 – SYSTEM COMPONENTS (CONT’D)

28778A

DISCHARGE LINE

OIL COOLER

OIL RESERVOIR

PUMP

REAR VIEW

System Components Description

FORM 160.73-O2(1202)

YORK INTERNATIONAL

17

GENERAL

The YORK Model YK MaxE TM Centrifugal Liquid Chiller is completely factory-packaged including evapo-rator, condenser, compressor, motor, lubrication system, OptiView Control Center, and all interconnecting unit piping and wiring.

COMPRESSOR

The compressor is a single-stage centrifugal type pow-ered by an open-drive electric motor.

The rotor assembly consists of a heat-treated alloy steel drive shaft and impeller shaft with a cast aluminum, fully shrouded impeller. The impeller is designed for bal-anced thrust and is dynamically balanced and over-speed tested. The inserted type journal and thrust bearings are fabricated of aluminum alloy. Single helical gears with crowned teeth are designed so that more than one tooth is in contact at all times. Gears are integrally assembled in the compressor rotor support and are film lubricated. Each gear is individually mounted in its own journal and thrust bearings.

The open-drive compressor shaft seal is a double bellows cartridge style with ceramic internal and atmospheric seal faces. The seal is oil-flooded at all times and is pressure-lubricated during operation.

CAPACITY CONTROL

Prerotation vanes (PRV) modulate chiller capac-ity from 100% to as low as 15% of design for normal air conditioning applications. Operation is by an external, electric PRV actuator which automatically controls the vane position to main-tain a constant leaving chilled liquid temperature.

COMPRESSOR LUBRICATION SYSTEM (See Fig. 8)

The chiller lubrication system consists of the oil pump, oil filter, oil cooler and all interconnecting oil piping and passages. There are main points within the motor-compressor which must be supplied with forced lubri-cation as follows:

https://www.360docs.net/doc/321766021.html,pressor Drive Shaft (Low Speed) a.Shaft seal.

b.Front and rear journal bearings – one on each side of driving gear.

c.Low speed thrust bearing (forward and reverse). https://www.360docs.net/doc/321766021.html,pressor Driven Shaft (High Speed)

a.Forward and reverse high speed thrust bearing.

b.Two journal bearings. 3.Speed Increasing Gears

a.Meshing surfaces of drive and pinion gear teeth.To provide the required amount of oil under the nec-essary pressure to properly lubricate these parts, a motor driven submersible oil pump is located in a remote oil sump.

Upon pressing of the COMPRESSOR START switch on the Control Center, the oil pump is immediately energized. After a 50 second pre-lube period, the com-pressor motor will start. The oil pump will continue to run during the entire operation of the compressor, and for 150 seconds during compressor coastdown.The submerged oil pump takes suction from the sur-rounding oil and discharges it to the oil cooler where heat is rejected. The oil flows from the oil cooler to the oil filter. The oil leaves the filter and flows to the emergency oil reservoir where it is distributed to the compressor bearings. The oil lubricates the compressor rotating components and is returned to the oil sump.

There is an emergency oil reservoir located at the highest point in the lubrication system internally in the compressor. It provides an oil supply to the various bearings and gears in the event of a system shutdown due to power failure. The reservoir, located on the top of the compressor, allows the oil to be distributed through the passages by gravity flow, thus providing necessary lubrication during the compressor coastdown.

3

FORM 160.73-O2(1202)

18LOW SPEED GEAR REAR BEARING

DOUBLE

BELLOWS

SHAFT SEAL

FIG. 8 – SCHEMATIC DRAWING – (YK) COMPRESSOR LUBRICATION SYSTEM LD08577 System Components Description

YORK INTERNATIONAL

FORM 160.73-O2(1202)

YORK INTERNATIONAL

19

OIL PUMP For normal operation, the oil pump should operate at all times during chiller operation.

On shutdown of the system for any reason, the oil pump operates and continues to run for 150 seconds. The sys-tem cannot restart during that time interval.

OIL HEATER

During long idle periods, the oil in the compressor oil reservoir tends to absorb as much refrigerant as it can hold, depending upon the temperature of the oil and the pressure in the reservoir. As the oil temperature is lowered, the amount of refrigerant absorbed will be increased. If the quantity of refrigerant in the oil be-comes excessive, violent oil foaming will result as the pressure within the system is lowered on starting. This foaming is caused by refrigerant boiling out of the oil as the pressure is lowered. If this foam reaches the oil pump suction, the bearing oil pressure will fluctuate with possible temporary loss of lubrication, causing the oil pressure safety cutout to actuate and stop the system. See “Control Center” Form 160.54-O1.

MOTOR DRIVELINE

The compressor motor is an open-drip-proof, squirrel cage, induction type constructed to YORK design spec-ifications. 60 hertz motors operate at 3570 rpm. 50 hertz motors operate at 2975 rpm.

The open motor is provided with a D-flange, cast iron adapter mounted to the compressor and supported by a motor support.

Motor drive shaft is directly connected to the compressor shaft with a flexible disc coupling. This coupling has all metal construction with no wearing parts to assure long life, and no lubrication requirements to provide low maintenance.

For units utilizing remote Electro-Mechanical starters, a terminal box is provided for field connected conduit. Motor terminals are brought through the motor casing into the terminal box. Jumpers are furnished for three-lead type of starting. Motor terminal lugs are not fur-nished. Overload/overcurrent transformers are furnished with all units.

HEAT EXCHANGERS

Evaporator and condenser shells are fabricated from rolled carbon steel plates with fusion welded seams. Heat exchanger tubes are internally enhanced type.The evaporator is a shell and tube, flooded type heat exchanger. A distributor trough provides uniform distribution of refrigerant over the entire shell length. Stainless steel mesh eliminators or suction baffles are located above the tube bundle to prevent liquid refrig-erant carryover into the compressor. A 2" liquid level sight glass is located on the side of the shell to aid in determining proper refrigerant charge. The evaporator shell contains dual refrigerant relief valves.

The condenser is a shell and tube type, with a discharge gas baffle to prevent direct high velocity impingement on the tubes. A separate subcooler is located in the con-denser to enhance performance. Dual refrigerant relief valves are located on condenser shells with optional isolation refrigerant isolation valves.

The removable compact water boxes are fabricated of steel. The design working pressure is 150 PSIG (1034 kPa) and the boxes are tested at 225 PSIG (1551 kPa). Integral steel water baffles provide the required pass arrangements. Stub-out water nozzle connections with Victaulic grooves are welded to the water boxes. These nozzle connections are suitable for Victaulic couplings, welding or flanges, and are capped for shipment. Plugged 3/4" drain and vent connections are provided in each water box.

REFRIGERANT FLOW CONTROL

Refrigerant flow to the evaporator is controlled by a variable orifice.

A level sensor senses the refrigerant level in the con-denser and outputs an analog voltage to the Microboard that represents this level (0% = empty; 100% = full). Under program control, the Microboard modulates a variable orifice to control the condenser refrigerant level to a programmed setpoint. Other setpoints affect the control sensitivity and response. These setpoints must be entered at chiller commissioning by a qualified ser-vice technician. Only a qualified service technician may modify these settings.

3

YORK INTERNATIONAL

FORM 160.73-O2(1202)

20

While the chiller is shut down, the orifice will be in the fully open position causing the sensed level to be ap-proximately 0%. When the chiller is started, after the vane motor end switch (VMS) opens when entering SYSTEM RUN , if actual level is less than the level setpoint, a linearly increasing ramp is applied to the level setpoint. This ramp causes the setpoint to go from the initial refrigerant level (approximately 0%) to the programmed setpoint over a period of 15 minutes. If the actual level is greater than the setpoint when the VMS opens, there is no pulldown period, it immediately begins to control to the programmed setpoint.While the chiller is running, the refrigerant level is nor-mally controlled to the level setpoint. However, anytime the vanes fully close (VMS closes), normal level control is terminated, any refrigerant level setpoint pulldown in effect is cancelled and the outputs to the level control will be opposite that which is supplied to the vane motor (i.e., when a close pulse is applied to the vane motor, an open pulse is applied to the level control, etc.). When the VMS opens, if the refrigerant level is less than the level setpoint, a refrigerant level setpoint pulldown is initiated as described above. Otherwise, the level is controlled to the programmed setpoint.

OPTIONAL SERVICE ISOLATION VALVES

If your chiller is equipped with optional service isolation valves on the discharge and liquid line, these valves must remain open during operation. These valves are used for isolating the refrigerant charge in either the evaporator or condenser to allow service access to the system. A refrigerant pump-out unit will be required to isolate the refrigerant.

Isolation of the refrigerant in this sys-tem must be performed by a qualified service technician.

OPTIONAL HOT GAS BYPASS

Hot gas bypass is optional and is used to eliminate compressor surge during light load or high head op-eration. The OptiView control panel will automatically modulate the hot gas valve open and closed as required. Adjustment of the hot gas control valve must be per-formed by a qualified service technician following the Hot Gas Set-up procedure.

Changes in chilled water flow will require readjustment of the hot gas control to insure proper operation.

OTIVIEW CONTROL CENTER (See Section 2)

The OptiView Control Center is factory-mounted, wired and tested. The electronic panel automatically controls the operation of the unit in meeting system cooling re-quirements while minimizing energy usage. For detailed information on the Control Center, refer to “Section 2” of this manual.

SOLID STATE STARTER (Optional)

The Solid State Starter is a reduced voltage starter that controls and maintains a constant current flow to the motor during start-up. It is mounted on the chiller. Power and control wiring between the starter and chiller are factory installed. Available for 380-600 volts, the starter enclosure is NEMA-1 with a hinged access door with lock and key. Electrical lugs for incoming power wiring are provided.

VARIABLE SPEED DRIVE (Optional)

A 460V – 3-Ph – 60/50 Hz Variable Speed Drive can be factory packaged with the chiller. It is designed to vary the compressor motor speed and prerotation vane position by controlling the frequency and voltage of the electrical power to the motor. Operational informa-tion is contained in Form 160.00-O1. The control logic automatically adjusts motor speed and compressor pre-rotation vane position for maximum part load efficiency by analyzing information fed to it by sensors located throughout the chiller.

System Components Description

约克离心机导叶故障处理.PDF

c. 导 叶 马 达 顺 d. 如果不能重合(如下图),可松开两个 约克(无锡)空调冷冻设备有限公司 YK 离心压缩机现场故障分析及解决 ——PRV 机构调节方法 维修指南 版本:0.0版 编号:YW-SERV-0506 发布日期:2005-10-10 共 2 页 1. 背景 YK 压缩机在机组运行过程中有时出现一些导叶机构故障,如:导叶马达断轴,或导叶启闭不到位。 2. 故障可能的原因 造成以上所述故障的可能原因是:导叶马达存在质量问题, 或导叶机构(即 PRV 机构)的调节不到位。 现针对PRV 机构调节不到位的问题,根据现场实际情况,按以下步骤进行调节。 3. 解决方案 3.1为了防止由于PRV 机构调节不到位造成的导叶马达断轴问题,可在停机时,在不打开压缩机的情况下作以下检查及操作: a. 拆开外曲柄与外连杆的连接螺栓 b. 在导叶马达位于于行程上止点(PRV 叶片全闭)时,使外柄处于PRV 叶片完全关闭的位置(可手动拉动外柄), 检查外柄和外连杆连接处是否重合。 时针旋转至停(下止点-PRV 全开),手动拉动外柄使其处于PRV 叶片全开的位置,检查外柄和外连杆连接处是否重合。 外连杆螺栓,适当调短外连杆。

FORM NO. e.调短外连杆后,逆时针扳动外柄,使PRV叶片全闭,然后将电机逆时针旋转至停(上止点-PRV全关),松开控制轴长螺栓(不要拧出)。连接外柄与外连杆,然后适当拧紧控制轴长螺栓。 f.重复c步骤的操作,保证PRV g.拆开外柄与外连杆, 紧所有螺栓、螺母。 3.2 如果导叶马达已损坏,更换新的马达之后,可按3.1所述的方法进行操作。 3.3如果以上操作仍不能解决问题,则需要调节压缩机内部的限位螺钉。PRV全开及全闭时,两个限位螺钉与蜗壳内壁应分别保持微小间隙~1mm。因为涉及压缩机内部零件,请按YK压缩机维修手册操作,由有离心压缩机维修经验的工程师操作。 说明: 1.以上所有操作应在明确了故障现象,并排除了其他可能的原因之后才能进行。 2.操作时应使用合适的工具,并按规定的力矩上紧所有紧固件。 3.如按此文件所述方法操作后,仍不能排除故障,应及时向维修主管或工厂反映,以便得到更多的支持。 4.压缩机在出厂前,已完成PRV机构的调节。鉴于PRV机构调节比较复杂,因此在开机调试时,或PRV机构无明显异常的情况下,建议不要对PRV机构进行任何拆 解、改动,有任何疑问可及时联系维修主管或联系工厂。 2Page 2 of 2

约克离心机配件中英文对照

约克YK、YT离心式冷水机组常用配件号码中英语对照约克YK、YT离心式冷水机组常用配件: 011-00434-000 冷冻"F"油 011-00533-000 冷冻"K"油 013-02987-000 VSD冷冻液 026-13508-000 干燥过滤器 026-14777-007 干燥过滤器 026-32386-000 油过滤器 026-37563-000 干燥过滤器 029-16764-000 干燥过滤器 331-02430-601 YK(F)主板 031-00947-000 电流控制板 024-30468-002 油泵变频板 031-01080-000 电源板C型机 031-01743-002 输入输出板 364-51806-000 止推传感器 371-01450-003 触发板 331-01771-000 彩色显示板 029-22452-000 高速止推板 022-09570-000 角阀 022-10079-000 安全阀 029-22454-000 轴封轴承 025-17175-001 导叶马达 024-27248-000 浮筒开关 025-33730-000 马达执行器 025-38178-000 电子执行器 025-33288-000 温度传感器 025-32924-000 排气传感器 025-34535-001 压力探测器 025-37831-000 温度传感器 025-34159-000 温度传感器 025-28678-001 油压传感器 025-29148-002 压力传感器 025-29148-004 压力传感器 225-30406-001 压力控制器

YORK螺约克杆机离心机YS,YK,YT主板故障常见

判断YORK约克螺杆机离心机YS、YK、YT主板常见故障私人日志 2010-03-17 19:57:48| 分类:约克机|字号大中小订阅 YSYKYT主板常见故障判断 一、元件功能介绍 Control Panel 由主板、I/O板、电源、显示器、键盘及CM-2板(机电式启动用)或ACCB(自适应容量控制板,VSD用)组成。 1. 主板 主板包括操作软件,微处理器及模拟量输入。其中EPROM包括启动自检程序,BRAM 为保存数据的电池,FLASH贮存整个操作程序。启动失败时,可检查EPROM、BRAM和FLASH CARD。FLASH版本描述,C.MLM.nn —(01=YK、02=YT、03=YS、04=YK(P)、05=YR) 跳线设定 JP2、JP3、JP4、JP5、JP7、JP8根据不同显示器品牌,按照显示器标签描述设定 JP34 冷媒型式设定。 YS、YK机组IN:选择R22,OUT:选择R134a YT机组IN:选择R11,OUT:选择R123 JP35 冷水/盐水程序设定, IN:冷水工况

OUT:盐水工况 JP37 压缩机电机启动器类型 IN:机电式或固态启动器 OUT:VSD,同时JP39必须为IN。 JP39 固态启动器类型 IN:A型 OUT:B型 JP41、JP42—高速止推轴承近程式传感探头型号IN:+12DC OUT:+24DC SW1设定 SW1-2 油泵型式ON:变频油泵OFF:定速油泵SW1-3预润滑时间ON:增强型预润滑,时间180S OFF:标准预润滑,时间150S SW1-4软件自检 SW1-5重启动设定ON:自动启动OFF:手动启动SW1-6反重复启动计时ON:反重复启动计时,OFF:反重复启动计时失效

约克离心机解锁程序

近发传感器校验程序 压缩机制造完成后在约克工厂安装好近发传感器和电势计,或是现场安装,或是在现场重装压缩机,按到已预定好的位置。这个值需作为“参考位置”按步骤操作。这个值直到压缩机重装或近发传感器和电势计已被更换才改变。 注意:“参考位置”值必须在微电脑控制中心运作,如微电路板或RTC (U16)被现场替换,要按下列程序重新输入: 1)把“压缩机开关”移到“停止/复位”位置 2)按“存取代码”,显示“输入存取代码” 3)1380回车 4)出现“进入授权编程模式” 5)按“编程”,显示“编程模式,选择设定值” 6)按“模式”键,显示“现运行的模式” 7)按“日期推进/滚动屏幕”键,直到出现“选择维修操作模式”。每按一次此键,就会出现不同模式 8)回车,出现“编程模式,选择设定值” 9)按“存取代码”,显示“进入编程无效” 10)按“模式”键,出现“维修模式”;如不出现,重新从第1步开始。11)按“存取代码”键,出现“输入存取代码” 12)1397回车

13)显示“进入授权编程” 14)按“编程”建,显示“编程模式,选择设定值” 15)按“显示资料”键  “近发传感器采用程序”显示2秒  “启动油泵”显示2秒,油泵自动打开  显示“油压XXX PSIG25,最低程序”,直到油压超过25.0PSIG(可按油槽键,如需要可关闭油泵,转到编程模式下/瞬捷信息)  显示“按回车校验近发传感器” 16)按回车,显示“实际位置=XX MILS;参考位置=YY MILS”17)阅读下列步骤并按步骤执行 a 如第一次作为轴承式样改新安装近发传感器,或压缩机重新调整,或是现场更换近发传感器部件和电势计,按“*”键。这就会把“参考位置”值YY当作“实际位置”值输入,这就建立了参考位置。 注意:在微机记录此数据以备将来之需。 或是 b 如果参考位置已建立,微电路板或RTC U16才被更换,确定原记录在微机内的“参考位置”值,使用回车,输入此值。因为是数值输入,

约克空调-故障解决方法技术资料

故障的分析与解决方法—离心机故障的分析与解决方法—离心机 电机温度过高 1、电机冷却系统管路是否有异常现象 2、确认短时间内开机次数是否太频繁 轴承温度过高 1、油加热器的动作是否正常 2、油位是否太低 3、供油管路上的阀是否全开 油温过低 1、油加热器供电是否正常 2、油加热器继电器是否有故障 3、油位是否适当 排气温度过高 1、确认是否有启动太频繁的情况 2、冷却水量及水温是否适当 3、冷凝器铜管是否太脏 4、系统内是否有空气 冷凝器压力过高 1、冷却水进水温度是否太高 油位太低 1、油箱出口阀是否被关闭 2、油过滤器是否堵脏 3、油温是否太低

冷冻(却)水流量大小 1、水泵运行是否正常 2、所有水阀开启的位置是否适当 3、泵体内是否有空气 冷冻水出水温度太高 1、出水温度设定值太高 2、机组已满负荷运行,是否实际负荷大于机组容量 3、制冷剂是否不足 4、冷却水进水温度是否过高 5、蒸发器的分离板和垫片是否有漏造成旁通 约克离心机故障停机或运行中的英文翻译 约克离心机运行停止显示器的实际 运行停止显示器的实际 MON 10:00 AML0W WATER TEMP-AUTOSTAT 停止的日期停止的时间原因再启动方法 *原因说明是星期一上午10:00点冷水出口温度比设定值低2.2度所以冷冻机停止,冷水出口温度上升就重新自动启动. 2. MON X X:X X AM-FLOW SWITCH-AUTOSTAT *冷水流量开关开放时冷冻机停止运行,冷水流量开关最少2秒就停止运行,检验好冷水流量开关以后25秒中START SEQUENCE INITIATED后可以继续运行 3. MON X X:X X AM-SYSTEM CYCLING-AUTOSTAT *因数字输入板的远控/手动输入连接的远控命令冷冻机停止 4. MON X X:X X AM-POWER FAILURE-AUTOSTAT *停电时冷冻机自动停止,电源连接以后自动启动MICRO BOARD是工厂里设定为手动

约克离心机VSD经济性分析

VSD 变频驱动离心式冷水机组经济性分析 一 VSD 变频驱动离心式冷水机组介绍 自1979年,约克开始给离心机组配备专用变频调速装置,至今已有二十多年,2000台以上机组的工程经验,节能效果显著,广受用户青睐。自1997年下半年开始,约克推出了适应中国市场的50Hz 变频离心机。下图是约克VSD 变频驱动离心式冷水机组的外形图: 从机组外型图上可直观地看出:VSD 变速驱动装置直接安装在机组上,VSD 机组的外形尺寸,水管连接尺寸,连接形式等完全与恒速离心式冷水机组相同。 二 VSD 变频驱动离心式冷水机相比恒速离心机,主要具有下列几方面的优势: 独特控制逻辑,大大提高部分负荷性能指标 众所周知,冷水机组99%以上的时间运行在部分负荷工况。通常,恒速离心机通过调节导流叶片开度来调节机组输出冷量,最高效率点通常在70%~80%负荷左右,负荷降低,单位冷量能耗增加较显著。而约克变频离心机采用自适用控制逻辑,同步调节电机转速和导流叶片开度,来调节机组输出冷量,最高效率点在40%~50%负荷左右,而且负荷降

低,单位冷吨能耗增加缓慢。约克变频离心机几千个工程的应用表明:同容量工程,变频离心机节能显著,年运行费用节省30%左右。 另一方面,变频离心机提高了电源功率因数,优化机组启动性能,提高机组效率。 ●控制离心式冷水机组避开喘振点,提高机组可靠性 配置VSD的离心机组,在低负荷状态运行时,同时调节导流叶片开度和电机转速,调节机组运行状态,可控制离心机组迅速避开喘振点,避免喘振对机组的伤害,确保机组运行安全。 ●优化机组启动性能,延长设备寿命 恒速离心机通常配置星三角启动器,一次启动电流高达满负荷电流的200~250%,二次启动电流甚至可能高达满负荷电流(FLA)的500%,而变频离心机的VSD变频驱动装置对机组实现软启动,启动电流不会超过机组满负荷电流(FLA)的100%,这减少了设备的电流冲击,冷水机组没有启动时间间隔的限制,机组可频繁启停,可最大限度的节能,最大限度的提高冷冻水出水温度的控制精度,即提高空调舒适性。同时,启动电流降低,可降低电器设备投资,延长设备寿命。 ●部分负荷低转速运行,降低噪音 约克变频离心机大部分时间运行在部分负荷工况,低转速运行,降低了电机噪音,且降低冷媒的排气速度,气流噪音降低。约克300TR冷水机组现场测试的结果表明:30%负荷状态下运行时,VSD离心机组的噪音相比恒速离心机组降低8dBA。 ●变频驱动装置直接安装在机组上,节省安装费用 常规恒速离心机的星三角启动器单独安装在机房地面,通常需配备控制变压器、电流表及电压表等,需现场安装接线。而变频离心机不需要另外的启动器等电器设备,其驱动装置可由工厂直接安装在机组上,不需现场接线,节省机房面积,节省安装费用。 ●经UL认证,配备先进,性能可靠 约克变频装置的外壳为NEMA-1设计,整个装置和机组都得到UL(保险商实验室)认证,性能可靠。 约克先进的滤波系统也是约克变频装置的突出特点。它是唯一符合IEEE592-1992(电气与电子协会)标准的变频装置滤波系统。滤波系统的引入会使机组的功率因数提高至0.98。 三约克VSD变频驱动离心式冷水机组能耗分析 建筑物大楼的空调冷负荷一天中存在不同时刻的负荷差别,一年中存在不同季节的负荷差别,而中央空调冷水机组冷量匹配往往能满足建筑物的最大负荷需求,致使中央空调冷水机组在99%左右的运行时间内,都运行在部分负荷状态,正是基于这一点,给约克

水冷离心式冷水机组考察报告(精)

水冷离心式冷水机组考察报告 2013年 3月 15日,天气 23-28℃,根据公司领导安排参加水冷离心式冷水机组运行情况考察。参加考察人员有:成本管理中心蔡经理、陈文、酒管公司贺小虎、张德生、机电管理部罗国庆,本次主要考察约克和麦克维尔公司在三亚地区已投入运行机组情况。 一 . 约克水冷离心式冷水机组 1. 三亚大东海银泰度假酒店, 业主单位是湘投瑞达置业有限公司, 酒店于 2003年开业, 选用一台 800RT 和两台 450RT 美国进口水冷离心式冷水机组, 机房设备已运行 10年时间。该酒店制冷机房位于主楼地下一层与配电室相邻,制冷机房因后期增加洗衣房空调设备导致面积过小,设备布置显得凌乱。 1.1由于酒店管理公司设备管理到位, 机组外观整洁, 无尘土。在机身未发现有油迹, 仅在设备供油管道接头处, 发现小面积油迹, 机组下侧地面有小面积的黑色油迹。 1.2通过与酒店工作人员了解, 该酒店四台水冷离心式冷水机组的日常维修养护委托约克公司负责。 1.3约克机组采用开式电机结构, 风冷形式, 导致电机两端处均有进风格栅, 发现进风格栅处有少量积尘。 1.4现场发现机房内有三瓶 50KG 钢瓶 134A 制冷剂及四桶机组专用润滑油,其中还有一台机组电机与压缩机轴封箱被拆卸, 通过酒店工作人员了解, 该机组轴封损坏需要更换,厂家还未将轴封零件送至三亚。 1.5通过现场对机组运行状态观察,机身有轻微振动,油泵、供油管路有轻微振动。 1.6机房墙体和天棚采用玻璃棉作隔音处理,隔音降噪效果差,在距离机房 8米的地方均能听见机组运行噪音。 2. 三亚美高梅度假五星级酒店,业主单位是中粮集团,酒店于 2011年 11月开业,选用 3台 800RT 和 1台 450RT 水冷离心式冷水机组,机房设备运行不到两年时间。

水冷离心式冷水机组考察报告

水冷离心式冷水机组考察报告 2013年3月15日,天气23-28℃,根据公司领导安排参加水冷离心式冷水机组运行情况考察。参加考察人员有:成本管理中心蔡经理、陈文、酒管公司贺小虎、张德生、 机电管理部罗国庆,本次主要考察约克和麦克维尔公司在三亚地区已投入运行机组情况。 一.约克水冷离心式冷水机组 1. 三亚大东海银泰度假酒店, 业主单位是湘投瑞达置业有限公司, 酒店于2003年开业, 选用一台800RT和两台450RT 美国进口水冷离心式冷水机组, 机房设备已运行10年 时间。该酒店制冷机房位于主楼地下一层与配电室相邻,制冷机房因后期增加洗衣房空调设备导致面积过小,设备布置显得凌乱。 1.1由于酒店管理公司设备管理到位, 机组外观整洁, 无尘土。 在机身未发现有油迹, 仅在设备供油管道接头处, 发现小面积油迹, 机组下侧地面有小面积的黑色油迹。1.2通过与酒店工作人员了解, 该酒店四台水冷离心式冷水机组的日常维修养护委托约克公司负责。 1.3约克机组采用开式电机结构, 风冷形式, 导致电机两端处均有进风格栅, 发现进风格栅处有少量积尘。 1.4现场发现机房内有三瓶50KG钢瓶134A 制冷剂及四桶机组专用润滑油,其中还有一台机组电机与压缩机轴封箱被拆卸, 通过酒店工作人员了解, 该机组轴封损坏需要更换,厂家还未将轴封零件送至三亚。 1.5通过现场对机组运行状态观察,机身有轻微振动,油泵、供油管路有轻微振动。1.6机房墙体和天棚采用玻璃棉作隔音处理,隔音降噪效果差,在距离机房8米的地方均能听见机组运行噪音。

2. 三亚美高梅度假五星级酒店,业主单位是中粮集团,酒店于2011年 11月开业,选用3台800RT和1台450RT 水冷离心式冷水机组,机房设备运行不到两年时间。该 酒店制冷机房位于地下二层,机房空间宽敞大气,设备间距大,为设备检修维护留 空间。 2.1机房采用玻璃加矿棉板作隔音处理, 隔音效果一般, 在机房外面 3米处能听见设 备运行声音。 2.2通过对机器油路检查发现, 部分管件连接处有少量油迹。 通过酒店工作人员了解, 该酒店四台机组的日常养护委托由约克公司负责。 2.3机房四台离心机组电机配置变频器, 但未配置谐波过滤器, 业主单位忽视变频器谐波的危害, 大功率变频器谐波的危害性是业界公认, 不配加谐波过滤器将产生的危害: 变频器谐波降低电力设备使用寿命、使变压器的铜损增加。增加铁损,影响绝缘能力、引起变压器绕组及线间电容之间的共振;变频器输出谐波使电机额外升温,产生机械震动、噪音及过电流;变频器谐波会使电力电容发生过载、过热甚至损坏电容器;变频器谐波电流会使开关设备在启动瞬间产生很高的电流变化率,破坏绝缘;变频器谐波将使继电保护和自动装置出现误动作,并使仪表和电能计量出现较大误差;变频器谐波对附近的通信系统产生干扰,轻者出现噪声,降低通信质量,重者丢失信息,电器工况变坏等。 3. 约克考察小结 约克公司成立于1874年美国约克郡,至今已有139年发展历史,产品 应用范围广泛, 从主机到末端主要分为民用、商用及工业冷冻设备三大类。 1995年在中国无锡设制造工厂,主要产品为水冷离心式冷水机组、水冷螺杆式 机组、工业用机组。

相关主题
相关文档
最新文档