s Input–Resistance thermometer (2, 3, 4 wire circuit)–Thermocouples–Resistance remote signalling unit (0...5000 Ω)–Voltages, mV (–125...1200 mV)s Output–2 wire technique–4...20 mA, digital signals Electrical isolation (I/O)s 1 oder 2 independent channelss Digital low drift processing of measurement values s Customer specific linearizations Continuous sensor and self-monitoring–Parameter saved permanently in EEPROM–Monitoring of data integrety every 10 s s Substitution strategy in case of error (NE43)sApprovals for explosion protection–intrinsically safeEEx [ia] ib IIC T6, mount in zone 1II 3 G EEx n A II T6, mount in zone 2s Input functionality (absolute, differential, average value) s EMC acc. to EN 50082-2 and NE 21, CE conformables Parameterization–PC software application SMART VISION or–Parasofts 5 years warrantyTS 102 / TS 102-Ex Rail mountedtemperature transmitters,programmable,Pt 100 (RTD), thermocouples,electrical isolation10/11-8.50 ENPage 2 of 611.01OutputOutput signal (temperature linear) 4...20 mA Residual ripple (peak-to-peak)< 0.2 %Current consumption < 3.5 mA Max. output current22 mAParameterizable current error signal Underranging 3.5 mA Overranging 22 mA Manual value 3.5...22 mA Dampingt 63 = 0...30 sInputResistance (temperature linear)Resistance thermometer Pt 100, Pt 200...Pt 1000Ni 100, Ni 500min. span 20 K (15 K)Resistance 0...500 Ω/0...5000 Ωmin. span 5 Ω/50 ΩMeasuring current 300 µA Sensor short-circuit < 5 Ω (for RTD)Sensor break > 1.5 M ΩInput filter 50/60 HzThermocouples Types B, E, J, K, L, N, R, S, T, U Voltages –125 mV...125 mV –125 mV...1200 mV Min. span2 mV/50 mV Sensor monitoring current 70 nA Input filter50/60 HzInternal reference junctionPt 100, via software switchable (no jumper necessary)Power supply (at transmitter terminals/poling protected)(2 wire methode: power supply wires = signal wires))Supply voltageU s = 11.5...30 V DC for explosion protection application U i = 11.5...29.4 V DC Influence of supply voltage < 0.05 %/10 V Max. residual ripple≤ 1 % U S (< 500 Hz)Maximum loadR k Ω()Usmax Usmin –()22----------------------------------------------=Input elementMeasuring rangeMin. measuring span Standard SensorIEC 584-1Thermocouple Type B Thermocouple Type E Thermocouple Type J Thermocouple Type K Thermocouple Type R Thermocouple Type S Thermocouple Type T Thermocouple Type N 250...+1820 °C (+482...+3308 °F)–250...+1000 °C (–418...+1832 °F)–210...+1200 °C (–346...+2192 °F)–250...+1372 °C (–418...+2502 °F)–50...+1768 °C (–58...+3215 °F)–50...+1768 °C (–58...+3215 °F)–200...+400 °C (–328...+752 °F)–200...+1350 °C (–328...+2462 °F)235 °C (423 °F)30 °C ( 54 °F)37 °C ( 67 °F)54 °C (98 °F)171 °C (308 °F)193 °C (348 °F)50 °C ( 90 °F)60 °C (108 °F)DIN 43710Thermocouple Type L Thermocouple Type U–200...+900 °C (–76...+482 °F)–200...+600 °C (–328...+1112 °F)36 °C ( 65 °F)40 °C ( 72 °F)IEC 7511)2, 3 and 4 wire Resistance thermometer Pt 100Resistance thermometer Pt 1000–200...+850 °C (–328...+1562 °F)–200...+850 °C (–328...+1562 °F) 20°C ( 36 °F)15 °C ( 27 °F)DIN 437602)2, 3 and 4 wire Resistance thermometer Ni 100Resistance thermometer Ni 500–60...+250 °C (–76...+482 °F)–60...+250 °C (–76...+482 °F) 8 °C ( 15 °F)15 °C ( 27 °F)Resistance Ω0...500 Ω / 0...5000 Ω 5 Ω / 50 ΩVoltagemV–125 mV...+125 mV –125 mV...+1200 mV2 mV 50 mV1)IEC 751 a = 0.00385;2)Edison Curve No. 7General characteristicsOutput signal refreshment ratePt1000.4 s,(input signal change < 0.25 K/s) Thermocouples0.2 s,(input signal change < 2.5 K/s) Vibration resistanceVibration in operation 2 g acc. to DIN IEC 68 part 2-6 Electrical isolation (I/O) 1.5 kV AC (60 s)Long-term stability≤ 0.1 % p.a.Environment conditionsAmbient temperature range(–40)-20...85 °CTransport and storage temperature–40...100 °CRelative humidity< 100 %(100 % humidity with isolated terminals only)Condensation permittedMechanical constructionDimensions cf. dimensional drawing Weight250 gHousing material PolyamidClass of combustibility V0 acc. to UL 94Type of protection IP 20 DIN 40050)Class of protection 2 (IEC 348)Overvoltages catagory IIColor (Epoxy)light grey (RAL 9002) Electrical connectionTerminals, pluggable 2.5 mm2, screw terminalsCharacteristics at rated conditions1)(acc. to IEC 770, related to 25 °C)Measuring error incl. characteristic deviationPt 100/resistance measurement< 0.2 % or < 0.2 K/< 80 mΩWichever value is greater Thermocouple/mV< 0.2 % or < 10 µVWichever value is greater Additional influence of theinternal reference junction Pt 100 DIN IEC 751 Cl. BInfluencesInfluence effect of temperaturePt 100/resistance measurement2)ME (Ω)< (0.08 % + × 0.008 %) / 10KMS (Ω)Thermocouple/mV3)ME (mV)0.014 K< (0.08 % + × 0.01 % + × 100 %) / 10 KMS (mV)MS (K)Percentage related to measuring span MS = ME – MAMA = lower range value, ME = upper range value Explosion protectionIntrinsically safeZone 1EEx [ia] ib IIC T6EC certificate PTB No. Ex-97.D.2221 Temperature class T6/T5/T4< 50 °C/65 °C/85 °CZone 2II 3 G EEx n A II T6 Conformity declaration PTB 99 ATEX 2123 X Temperature class T6/T5/T4< 50 °C/65 °C/85 °CElectromagnetic compatibility (EMC)Pt 100: measuring range 0...100 °C, span 100 KAcc. to NAMUR NE 21 recommendationIn case of an input signal change > 0.25 K/s for Pt100 or > 2.5 K/s for thermocouples a measured value plausibility check is perfor-med.Supply circuit Output [ib]Input [ia]Max. voltage U i = 29.4 V U o = 5.6 VShort-circuit current I i = 130 mA I o = 145 mA4)Max. power P i = 0.8 W P o = 20 mWInternal inductance L i = 220 µH L o = 1 mHInternal capacitance C i = 15 nF C o = 1.55 µFType of test Degree Influence IECburst to signal/data lines2 kV< 0.5 %1000-4-4static dischargecontact discharge to:contact plateterminals for supplyterminals for sensors8 kV6 kV3.75kV< 1.0 %< 1.0 %< 1.0 %1000-4-2radiated field80 MHz...1 GHz10 V/m< 1.0 %1000-4-3coupling150 kHz - 80 MHz10 V< 1.0 %1000-4-61)Percentage related to set measuring span2)Pt 100 (0...400 °C): Effect of temperature influence< (0.08 % + 0.013 %)/10 K = 0.093 %/10 K3)Type K (0...1000 °C): Effect of temperature influence< (0.08 % + 0.01 % + 0.014 %)/10 K = 0.104 %/10 K4) Load current for connected transmitter [ia] < 1.5 mA11.01Page 3 of 6Communication/parameterizationParameterSensor type, measuring range, error signalling, general characteristics (i. e. TAG number), damping, signal simulation of outputSoftware-ToolsSMART VISION or Parasoft Software SMART VISION or Parasoft(optional)2-channel devices: programming channel 2 (terminals 41 and 42)Page 4 of 611.0111.01Page 5 of 6ABB Automation Products GmbH Borsigstrasse 2D-63755 AlzenauPhone +49(0)60 23 92 - 0Fax +49(0)60 23 92 - 33 00Subject to technical changes.Printed in the Fed. Rep. of Germany Data sheet 10/11-8.50 EN 11.01Connection diagramsDimensional diagram (dimensions in mm)。

现场传感器调试与安装

现场传感器调试与安装

• 模拟量输出-AO • (如调节阀控制、风门调节等) • BAS发出设备开0,25%,50%,75%,100% 的命令 • 使用万用表测量DDC输出及反馈值; • 判断控制阀门开度与控制信号是否一致; • 响应正确为合格
谢谢!
现场调试及传感器安装
1.1.1 调试指南
• (一)、调试应具备的条件 • (1)、受BAS监控的设备必须先手动调试 通过; • (2)、各设备机房必须有良好的照明和正 确的电源; • (3)、当涉及与其他有关厂家机电设备接 口时,厂家必须有人配合;
(二)、调试工具
• • • • (1)、手提电脑; (2)、对讲机若干; (3)、万用表; (4)、常用电工工具若干;
水管式压差传感器安装图
第七类:流量计
• 一般有转子流量计、插入式电磁流量计、涡街 式流量计及超声波流量计等,考虑到设备的性 价比,BA系统实际需要情况,一般用插入式 电磁流量计,通常选用DWM2000。 • 调试时请注意以下几点: • 安装位置,需安装在水平直管上,在流量计的 上游需有10倍管径的直管,在流量计的下游需 有5倍管径的直管,如无足够的直管将直接影 响流量计的精度,另水管上的安装位置及套管 安装深度如下图所示;
• 此种传感器如H-SBC-SDT,常用于新风温度、 送风温度及回风温度等,水管型的有H-SBCSDT -150/200,常用于冷冻冷却水系统及热 交换系统,在调试前可先用万表测量其电 阻值,与标准的电阻温度对照表比较,读 出此传感器的温度值与标准温度计测得的 值比较,判断是否在精度范围内,以决定 是否更换此传感器。
第四类:风管式压力开关
• 如609系列压力开关,通常用过滤网压差报警 及风机压差运行状态的判断。 • 用于过滤网压差报警时压力开关的设定:开启 空调机组让其全速运行,调节压差设定至刚好 能动作的位置,把此设定值放大2倍即为压差 报警设定。 • 风机压差开关的设定:开启空调机组让其全速 运行,调节压差设定至刚好能动作的位置,把 此设定值调整至此点的1/3处,再开/关风机数 次检验,压差开关是否相应动作。

银河电气CSA200-G060T01电流传感器使用说明书

银河电气CSA200-G060T01电流传感器使用说明书

CSA200-G060T01电流传感器使用说明书V1.1本手册为湖南银河电气有限公司产品电流传感器用户手册,本手册为用户提供安装调试、操作使用及日常维护的有关注意事项,在安装、使用前请仔细阅读。

本手册随产品一起提供,请妥善保管、以备查阅和维护使用。

声明我们非常认真的整理此手册,但我们对本手册的内容不保证完全正确。

因为我们的产品一直在持续的改良及更新,故我方保留随时修改本手册的内容而不另行通知的权利。

同时我们对不正确使用本手册所包含内容而导致的直接、间接、有意、无意的损坏及隐患概不负责。

安全操作知识◆产品使用前,请您务必仔细阅读用户手册。

◆需对产品进行搬动时,请您务必先断电并将与之相连的所有连接线缆等拔掉。

◆如果发现机壳、稳固件、电源线、连接线缆,或相连的设备有任何损坏,请您立即将装置与电源断开。

◆如果对设备的安全运行存在疑虑,应立即关闭设备和相应附件,并在最快时间内与本公司技术支持部门取得联系,沟通解决。

1.产品概述CSA200-G060T01是一种能在原边、副边完全隔离条件下测量直流、交流、脉冲以及各种不规则波形的电流传感器,它主要用于要求准确度高的计量检定和计量校准领域,以及要求高灵敏度、高稳定性和高可靠性的电能质量分析、功率分析仪、医疗、航空航天、导弹、舰艇等领域。

2.技术特点●极高的准确度●极好的线性度●极高的稳定性●极高的灵敏度●极高的分辨率●极低的温度漂移●极低的失调电流●极低的插入损耗●抗干扰能力强●响应速度快●极低的噪声●极小的角差●宽频带●模拟量输出3.应用场合●计量检定与校准●实验室电流测量●仪器仪表(如功率分析仪)●医疗设备(如核磁共振MRI)●电池组检测●电力控制●电源●舰船●新能源●轨道交通●航空航天●工业测量4.电气性能项目符号测试条件数值单位最小标称最大原边额定电流I PN-- -- ±20 -- Adc测量范围I PM1分钟/小时-- -- ±24 Adc 工作电压V c全范围-- ±12 -- Vdc 电流消耗I c I PM范围内±10 ±50 ±100 mA 电流变比K N输入:输出500:1 -- 额定输出电流I SN原边额定电流--±40--mA测量电阻R M Vc:±12,I:±20 Adc 0 -- 150 ΩPN5.精度-动态参数项目符号测试条件数值单位最小标称最大精度X e输入直流,@25±20℃-- -- 0.05 %线性度εL-- -- -- 100 ppm 零点失调电流I o25℃-- -- 15 uA 零点失调电流I oT全工作温度范围内-- -- 30 uA 频带宽度(- 3 dB) F -- 0 -- 100 kHz 6.一般特性项目符号测试条件数值单位最小标称最大工作温度范围T A-- -40 -- +85 ℃存储温度范围T S-- -45 -- +90 ℃质量m 58±5 g7.安全特性项目符号测试条件数值单位最小标称最大耐受电压原、副边之间副边与外壳之间V d50Hz,1min 5 kV瞬态隔离耐压原、副边之间V w50us 10 kV 相比漏电起痕指数CTI IEC-60112 275 V 8.外形尺寸及端口定义8.1、外形尺寸(单位:mm)图1 外形图外形图说明:外形尺寸、安装定位尺寸公差按照GB/T1804-2000 C级标准执行。

MLS Series 流动级别传感器安装和操作手册说明书

MLS Series 流动级别传感器安装和操作手册说明书

MLS SeriesLiquid Level SwitchesInstallation and Operations Manual00-02-0730In order to consistently bring you the highest quality full featured products, we reserve the right to change our specifications and designs at any time. The latest version of this manual can be found at .CAUTION: MLS Series parts are not interchangeable with otherMurphy liquid level products. Damage caused by using incorrectparts is not covered by our Limited Warranty.Please read the following information before installing. A visualinspection for damage during shipping is recommended beforemounting.BEFORE BEGINNING INSTALLATION OF THIS MURPHYPRODUCT:Disconnect all electrical power to the machine.Make sure the machine cannot operate during installation.Follow all safety warnings of the machine manufacturer.Read and follow all installation instructions.OBSERVE all pressure and electrical ratings and requirements forthe devices and the operating environment.BE SURE all pressure HAS BEEN REMOVED from the vesselbefore opening any pressure connections.Please contact FW MURPHY immediately if you have anyquestions.Table of ContentsProduct Information (1)Features (1)MLS-020, MLS-015 (1)Pressure Vessel Installation: MLS-020 and MLS-015 (2)Direct Installation into the Wall of the Pressure Vessel (2)Installation with a Weld Collar (3)Installation Using Murphy External Float Chamber (3)Electrical Wiring (4)Replacement Parts (4)15000531: MLS Float (4)Accessories (4)15050375: Weld Collar (4)15051098: External Float Chamber (5)15700799: Series 100 External Float Chamber (5)Specifications (6)MLS Series (6)Approximate Shipping Weights and Dimensions (6)(THIS PAGE INTENTIONALLY LEFT BLANK)Product InformationFeaturesClean Magnet Design virtually eliminates iron filing accumulation onto the magnetSeal-Free ConstructionDesigned for harsh gas compressor scrubber applicationsCF8 (304) cast stainless steel body and 304 stainless steel floatMLS Series rated for 2000 psi (13.8 MPa) [138 bar] working pressureElectric model only availableImproved design provides better dependability with reduced number of moving partsAll models screw directly into the scrubber or can be mounted via external float chamberCSA C/US Class 1, Div. 1, Grp. B, C & D locationsCanadian Registration Number: 0F01476.2MLS-020, MLS-015MLS Series Liquid Level Switches with 2” NPT and 1-1/2” NPT mounting are float activated to operate an electrical SPDT reed switch for alarm or shutdown of an engine or electric motor. The MLS Series connects directly into the scrubber wall and can be used with a Murphy weld collar (P/N 15050375) or Murphy external float chamber (P/N 15700799).Thread Table - Table 1Model No Thread “A”MLS-015 1-½”NPTMLS-020 2”NPT NOTE: Refer to Table 2 for clearances.Pressure Vessel Installation: MLS-020 and MLS-015Direct Installation into the Wall of the Pressure VesselCAUTION: Determine that the float travel is not obstructed by the coupling in the vessel wall, internal baffles, etc.Refer to tables 1 and 2 for application data. INSTALLATION BY QUALIFIED PERSONNEL ONLY.1.Make certain the float is tightly screwed onto the counter-balance.2.Before installing the level switch, use of a pipe thread sealant is recommended. Screw the unit directly into the threaded connection in the wall of the pressure vessel.3.Verify that the electrical connection is positioned at the bottom.NOTE: The word TOP is cast into the top of the body. M4.Make the electrical wiring connections according to appropriate wiring diagrams for the alarm or shutdown system to be used. The electrical connection is 1/2”-14 NPT.5.Ensure all electrical connections are insulated and the cover is fully installed before reconnecting electrical power.6.Verify all pressure connections are tight before pressurizing the system.Float Clearance Reference TablesTable 2 Pipe Data Nom. Size(inches) O.D. (inches) Schedule Number Wall Thickness (inches) Inside Diameter(inches) 2.5 2.875 40STD 0.203 2.469 3 3.5 40STD 0.216 3.068 3 3.5 80XS 0.3 2.9 4 4.5 40STD 0.237 4.026 4 4.5 80XS 0.3373.826Installation with a Weld Collar1.The weld collar, P/N 15050375, must be welded into the wall ofthe pressure vessel according to code standards and goodwelding practices.2.Follow above instructions for installation directly into the wall ofthe pressure vessel.Installation Using Murphy External Float Chamber1.Install the Murphy float chamber 15051098 or 15700799 on the outside wall of thepressure vessel using 1” NPT piping. Position the 2” NPT threaded connection at the height where you want the level switch to operate.The 2” NPT threaded connection must bepositioned away from the tank wall.NOTE: If using Float Chamber15051098, best practices recommend asurface mount installation.2. A tee and bleed valve are typically installed at thebottom of the lower 1 inch pipe riser to allowdraining of the float chamber for servicing orreplacement.NOTE: A typical installation withblocking and bleed valves is shown atright.3.Install the MLS-020 in the 2” NPT connection ofthe float chamber. BE SURE float travel is notrestricted and that the float is tight onto thecounter-balance.4.To complete the installation and wiring, follow the instructions for mounting directlyinto wall of the vessel and for wiring.Electrical WiringSwitch Rating: 30VDC/VAC @ 75 mAReplacement PartsOrder by part number designation.15000531: MLS FloatStainless Steel Float, MLS Series (not interchangeable with any other Murphy Level Switch Float)Accessories15050375: Weld CollarOperating Pressure: 2000 psi (13.8 MPa) [138 bar].Operating Temperature: 400︒F (204︒C).15051098: External Float ChamberOperating pressure: 2000 psi (13.8 MPa) [138 bar] Operating temperature: 400︒F (204︒C). 15700799: Series 100 External Float ChamberOperating pressure: 2000 psi (13.8 MPa) [138 bar] Operating temperature: 400︒F (204︒C).SpecificationsMLS SeriesProcess connection: 2” NPT (MLS-020)1-1/2” NPT (MLS-015)Fluid Density (SG): 0.50Pressure Rating: 2000 psig (13.8 MPa)[138 bar] Materials:Body: ASTM A351 CF8 (304 SS)Cover: ASTM A351 CF8 (304 SS)Other Wetted Parts: 304 or 316 SSMeets NACE MR0175 for direct exposure to H2S Process Temperature: -20 to 300︒F (-29 to 149︒C) Electrical: 30VAC/VDC 75mA Form C SPDT Approximate Shipping Weights and Dimensions All models: 5.5lbs (2.49 kg);Dimensions: 14 x 5 x 3.5 in. (356 x 127 x 89 mm)THIS PAGE INTENTIONALY LEFT BLANK.。

FT742 (4-20mA)风传感器用户手册说明书

FT742 (4-20mA)风传感器用户手册说明书

FT TECHNOLOGIES LTD 18 CHURCH ROAD TEDDINGTONMIDDLESEX, TW11 8PD电话: +44 (0)20 8943 0801 传真: +44 (0)20 8943 3283 网址: E-MAIL: ***************.ukA4277-1-CN2017年1月. FT 和 Acu-Res (声共振)标识为FT Technologies 公司注册商标 The FT and Acu-Res logos are registered trademarks of FT Technologies Ltd. Copyright © 2017 FT Technologies Ltd. All rights reserved.FT742 - 模拟型 (4-20mA)风传感器手册管状直接安装方式目录产品标识 (3)Safety Instructions (4)安全须知 (5)1简介 (6)1.1产品概述 (6)1.2产品版本型号与标识 (6)1.3使用范围 (6)1.4声明 (7)2功能描述 (8)2.1技术性能 (8)2.2电流回路 (9)2.2.1电流回路特征 (9)2.2.2均值滤波器特征 (9)2.2.3风速回路 (9)2.2.4风向回路 (10)2.2.5调整风向基准 (11)2.2.6错误检测 (12)2.3加热器设置 (13)2.4低能耗运行 (13)3机械和电气安装 (14)3.1连接器细节 (21)3.2电缆细节 (21)3.3雷击、浪涌与电磁干扰(EMI)防护 (21)4服务、设置与测试 (23)4.1检测 (23)4.2故障查找与故障排除 (24)4.3退货条款 (25)4.4Acu Test 测评套装 (26)4.4.1Acu Test电脑测试评估软件 (26)4.4.2FT055 测试电缆 (27)产品标识本使用手册及相关设备将使用以下标识。

ph传感器操作手册

ph传感器操作手册

pH传感器操作说明书中国区代理商:上海卯林机电设备有限公司地址:上海市闵行区外环路352号D205室电话:传真:email:网址:目录1. 安全预防措施 (3)1.1 健康与安全 (3)1.2 环境保护 (3)1.3 化学品 (3)2 pH传感器 (4)2.1 测量原理 (4)2.2 技术规格 (4)2.3 耐压型pH流通池 (4)3 设置 (5)3.1 安装 (5)3.1.1 传感器安装 (5)3.1.2 耐压型密闭式流通池 (5)3.1.3 敞开式流通池 (6)4. 传感器接线 (7)4.1 ph传感器输入接线.........。

. (7)5. 传感器调试 (8)5.1 开始使用前的准备 (8)5.2 安装 (8)5.3 校准与标准化 (8)5.3.1 校准 (9)5.3.2 标准化 (10)5.3.3 高级维护选项 (10)6. 传感器维修 (11)6 .1 传感器清洗 (11)6.2 传感器保存 (11)7. 维修 (12)1. 安全预防措施●在打开、设置或操作这台仪器之前,请阅读整个手册。

●在维护或更换零件之前确保电源断开。

●在维护或更换零件之前确保仪表没有外部的压力(比如气压或液压)。

●不遵守这些预防措施可能导致人体受伤或损坏设备。

●1.1 健康与安全在接/拆电源线和传感器信号线的时候,确保仪器已经断电。

pH传感器是用来测量水中pH浓度的,所以取放传感器的时候,请带好合适的PPE。

1.2 环境保护此传感器是玻璃结构,它封装有塑料壳体和银/卤化银配件。

使用它的请考虑环境的影响,当到了使用寿命的时候,请根据当地的法律法规进行回收,请勿随意抛弃。

1.3 化学品连接到Crius@控制器的传感器会接触到一些危险的化学品,拿放传感器的时候请要万分小心。

注意(CAUTION)当使用此设备时,必须遵守现场的突发情况和个人安全防护准则PPE: 防护服,防护手套,护目镜示例2. pH传感器2.1 测量原理当使用电极时,pH被以电位的方式进行测量。

银河电气CSA500-G060T01 电流传感器使用说明书

银河电气CSA500-G060T01 电流传感器使用说明书

CSA500-G060T01电流传感器使用说明书V1.1本手册为湖南银河电气有限公司产品电流传感器用户手册,本手册为用户提供安装调试、操作使用及日常维护的有关注意事项,在安装、使用前请仔细阅读。

本手册随产品一起提供,请妥善保管、以备查阅和维护使用。

声明我们非常认真的整理此手册,但我们对本手册的内容不保证完全正确。

因为我们的产品一直在持续的改良及更新,故我方保留随时修改本手册的内容而不另行通知的权利。

同时我们对不正确使用本手册所包含内容而导致的直接、间接、有意、无意的损坏及隐患概不负责。

安全操作知识◆产品使用前,请您务必仔细阅读用户手册。

◆需对产品进行搬动时,请您务必先断电并将与之相连的所有连接线缆等拔掉。

◆如果发现机壳、稳固件、电源线、连接线缆,或相连的设备有任何损坏,请您立即将装置与电源断开。

◆如果对设备的安全运行存在疑虑,应立即关闭设备和相应附件,并在最快时间内与本公司技术支持部门取得联系,沟通解决。

1.产品概述CSA500-G060T01是一种能在原边、副边完全隔离条件下测量直流、交流、脉冲以及各种不规则波形的电流传感器,它主要用于要求准确度高的计量检定和计量校准领域,以及要求高灵敏度、高稳定性和高可靠性的电能质量分析、功率分析仪、医疗、航空航天、导弹、舰艇等领域。

2.技术特点●极高的准确度●极好的线性度●极高的稳定性●极高的灵敏度●极高的分辨率●极低的温度漂移●极低的失调电流●极低的插入损耗●抗干扰能力强●响应速度快●极低的噪声●极小的角差●宽频带●模拟量输出3.应用场合●计量检定与校准●实验室电流测量●仪器仪表(如功率分析仪)●医疗设备(如核磁共振MRI)●电池组检测●电力控制●电源●舰船●新能源●轨道交通●航空航天●工业测量4.电气性能项目符号测试条件数值单位最小标称最大原边额定电流I PN-- -- ±50 -- Adc 测量范围I PM1分钟/小时-- -- ±60 Adc 工作电压V c全范围-- ±12 -- Vdc 电流消耗I c I PM范围内±10 ±60 ±80 mA 电流变比K N输入:输出1000:1 -- 额定输出电流I SN原边额定电流--±50--mA 测量电阻R M Vc:±12,I PN:±50 Adc 0 -- 100 Ω5.精度-动态参数项目符号测试条件数值单位最小标称最大精度X e输入直流,@25±20℃-- -- 0.05 % 线性度εL-- -- -- 50 ppm 零点失调电流I o25℃-- -- 15 uA 零点失调电流I oT全工作温度范围内-- -- 30 uA 响应时间t r-- -- -- 1 us 电流跟随速度di/dt -- 100 -- -- A/us 频带宽度(- 3 dB) F -- 0 -- 100 kHz6.一般特性项目符号测试条件数值单位最小标称最大工作温度范围T A-- -40 -- +85 ℃存储温度范围T S-- -45 -- +90 ℃质量m 58±5 g7.安全特性项目符号测试条件数值单位最小标称最大耐受电压原、副边之间副边与外壳之间V d50Hz,1min 5 kV瞬态隔离耐压原、副边之间V w50us 10 kV 相比漏电起痕指数CTI IEC-60112 275 V8.外形尺寸及端口定义8.1、外形尺寸(单位:mm)图1 外形图外形图说明:外形尺寸、安装定位尺寸公差按照GB/T1804-2000 C级标准执行。

安科瑞BA系列交流电流传感器安装使用说明书

安科瑞BA系列交流电流传感器安装使用说明书

022BA系列交流电流传感器安装使用说明书V1.4安科瑞电气股份有限公司联系方式:188****5116(微信同号)申明版权所有,未经本公司之书面许可,此手册中任何段落,章节内容均不得被摘抄、拷贝或以任何其它形式复制、传播,否则一切后果由违者自负。

本公司保留一切法律权利。

本公司保留对本手册所描述之产品规格进行修改的权利,恕不另行通知。

订货前,请垂询当地代理商以获悉本产品的最新规格。

目录1产品概述 (1)2型号说明 (1)3通用技术条件 (2)4产品规格 (2)4.1BA05-AI交流电流传感器 (2)4.2BA10-AI交流电流传感器 (3)4.3BA20-AI交流电流传感器 (3)4.4BA50-AI交流电流传感器 (4)5外型及安装 (4)5.1外形及穿孔尺寸 (2)5.1.1BA05-AI交流电流传感器 (4)5.1.2BA10-AI交流电流传感器 (5)5.1.3BA20-AI交流电流传感器 (5)5.1.4BA50-AI交流电流传感器 (5)5.2安装方法 (6)5.3应用实例 (7)6BA50L交流剩余电流传感器 (8)6.1BA50L-AI/I(V)交流剩余电流传感器 (8)6.2BA50L-AI变流剩余电流传感器外型及安装 (8)6.3应用实例 (9)6.3.1单相回路 (9)6.3.2三相三线回路 (10)6.3.3三相四线回路 (11)7接线方式 (12)8订货范例 (13)BA系列产品应用电磁感应原理,对电网中的交流电流进行实时测量,采用恒流和线性补偿技术,将其隔离变换为标准的直流信号输出。

24伏或12伏安全电压供电,可广泛用于工业自动化领域。

BA50L为变流剩余电流互感器主要检测用电系统的漏电流,能随时掌握电气线路和设备的情况,防止因漏电而发生的火灾等事故。

2型号说明BA—/—类型:无——平均值测量T——真有效值测量输出:I——直流电流V——直流电压输入:AI——交流电流穿孔尺寸:(单位:mm)05-φ510-φ1020-φ2050-φ50产品系列代号3通用技术条件电源电压DC12V或24V 功耗≤1W绝缘电阻>100MΩ耐压强度输入/输出、电源之间2.0KV/1min,50Hz 温度系数-10℃~+55℃时,≤400ppm/℃环境温度工作:-10℃~+55℃储存:-25℃~+70℃湿度≤93%RH,不结露,无腐蚀性气体场所海拔≤2000m安装方式TS35导轨,或用螺钉固定柜体上4.1BA05-AI交流电流传感器BA05-AI/I(V)单相交流电流传感器(平均值法测量)BA05-AI/I(V)-T单相交流电流传感器(真有效值法测量)技术参数指标精度等级0.5级输入标称值电流AC0.5A、5A、10A等AC0~(0.5~10A)过载持续1.2倍,瞬时电流10倍/5秒吸收功率≤1VA频响25Hz~800Hz(平均值),25~5kHz(真有效值),特别适合工频场合输出标称值DC4~20mA,或0~20mA,0~5V,0~10V等负载电阻电流输出时≤500Ω,电压输出时≥1KΩ响应时间平均值≤350ms,真有效值≤150ms4.2BA10-AI交流电流传感器BA10-AI/I(V)单相交流电流传感器(平均值法测量)BA10-AI/I(V)-T单相交流电流传感器(真有效值法测量)技术参数指标精度等级0.5级输入标称值电流AC8A、25A、50A等AC0~(8~50)A过载持续1.2倍,瞬时电流10倍/1s秒吸收功率≤1VA频响25Hz~800Hz(平均值),25~5kHz(真有效值),特别适合工频场合输出标称值DC4~20mA,或0~20mA,0~5V,0~10V等负载电阻电流输出时≤500Ω,电压输出时≥1KΩ响应时间平均值≤350ms,真有效值≤150ms4.3BA20-AI交流电流传感器BA20-AI/I(V)交流电流传感器(平均值法测量)BA20-AI/I(V)-T交流电流传感器(真有效值法测量)技术参数指标精度等级0.5级输入标称值电流AC40A、100A、200A等AC0~(40~200)A过载持续1.2倍,瞬时电流10倍/1S吸收功率≤1VA频响25Hz~800Hz(平均值),25~5kHz(真有效值),特别适合工频场合输出标称值DC4~20mA,或0~20mA,0~5V,0~10V等负载电阻电流输出时≤500Ω,电压输出时≥1KΩ响应时间平均值≤350ms,真有效值≤150msBA50-AI/I(V)单相交流电流传感器(平均值法测量)BA50-AI/I(V)-T 单相交流电流传感器(真有效值法测量)技术参数指标精度等级0.5级输入标称值电流AC 60A、300A 、600A等AC 0~(60~600)A过载持续1.2倍,瞬时电流10倍/1S吸收功率≤1VA频响25Hz~800Hz(平均值),25~5kHz(真有效值),特别适合工频场合输出标称值DC4~20mA,或0~20mA,0~5V,0~10V 等负载电阻电流输出时≤500Ω,电压输出时≥1KΩ响应时间平均值≤350ms,真有效值≤150ms5外形及安装5.1外形及穿孔尺寸5.1.1BA05-AI 交流电流传感器5.1.2BA10-AI 交流电流传感器5.1.4BA50-AI交流电流传感器5.2安装方法安装方式可选择导轨安装或螺钉固定安装,具体操作如下:a、导轨安装选择适合的地方安装标准DIN35mm导轨,将BA传感器安装到导轨上即可;b、螺丝固定安装在柜体底板上,选择适合的地方开两个与所安装传感器固定孔位置相对应的螺纹孔;将传感器放置后安装定位螺钉(顺时针)。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

目录流量计 (1)压力传感器 (14)温度传感器 (17)氧化锆分析仪 (19)射频导纳物位传感器 (24)火焰检测器 (27)称重传感器 (30)流量计(一)涡轮、涡街流量计一、连接方式:法兰卡装式、法兰式、插入式二、为了确保仪表的测量准确度,涡街流量传感器在管线上安装必须正确地选择安装点,具体要求:1、渐缩管的安装:对于大管径小流量须缩管安装,传感器上游应有不小于15D的等径直管段,下游应有不小于5D的等径直管段。

2、渐扩管的安装:对于小管径大流量需扩管安装,传感器上游应有不小于18D的等径直管段,下游应有不小于5D的等径直管段。

3、弯管的安装:若传感器安装点的上游有90弯头或T形接头,传感器上游应有不小于15D的等径直管段,下游应有不小于5D的等径直管段。

4、不同平面两个弯管的安装:传感器上游应有不小于25D的等径直管段,下游应有不小于5D的等径直管段。

5、流量调节阀或压力调节阀尽量安装在传感器的下游5D以远处,若必须安装在传感器的上游,传感器上游应有不小于25D的等径直管段,下游应有不小于5D的等径直管段。

6、传感器上游有活塞式或柱塞式泵或有活塞式或罗茨鼓风机、压缩机,传感器上游应有不小于20D的等径直管段,下游应有不小于5D的等径直管段。

三、接线方式:1、无显示电流输出型(4-20Ma)2、现场显示电流输出型(4-20mA)(二)超声波流量计1 选择探头安装位置1.1 安装位置应满足的条件(1)工作场所没有过多灰尘和腐蚀性气体;(2)直管段长度:上游侧10D以上,下游侧5D以上(当流速较低时,可适当降低直管段要求):(3)上游侧30D以内不得有扰动因素(如泵、阀门等);(4)流体必须充满管道,不能含有气泡或过量杂质;(5)安装探头的管道不应有强烈的机械振动;(6)安装探头的管道周围需要足够空间。

5. 安装点的温度、压力应在传感器可工作的范围以内。

6. 充分考虑管内壁结垢状况:尽量选择无结垢的管道进行安装,如不能满足时,可把结垢考虑为衬里以求较好的测量精度7. 两个传感器必须安装在管道轴面的水平方向上,并且在轴线水平位置±45o范围内安装,以防止上部有不满管、气泡或下部有沉淀等现象影响传感器正常测量。

如果受安装地点空间的限制而不能水平对称安装时,可在保证管内上部分无气泡的条件下,垂直或有倾角地安装传感器。

传感器安装点示例:1.2 注意要点(1)对于水平管路,探头应安装在水平中心线的±45°之内(如图1所示);(2)对于竖直管路,探头可安装在外圆周的任何位置;(3)应避免将探头安装在管道的变形部位、法兰或焊接部位。

2 选择探头安装方法探头采用V法和Z法安装:V法(常用的方法)一般情况下,V法是比较标准的安装方法,使用方便,测量准确,安装时两传感器水平对齐,其中心线与管道轴线水平即可,可测管径范围为DN15mm-DN400mm。

下列情况使用Z法:1)安装空间有限;2)被测流体中含有少量杂质;3)接收波较弱(比如用水泥做衬里)。

选择安装方法的依据:一般来说,D>300mm的管道采用Z法安装。

Z法(最常用的方法)当管道很粗或由于液体中存在悬浮物、管内壁结垢太厚或衬里太厚等原因,造成V法安装信号弱,机器不能正常工作时,就需要选用Z法安装。

Z法的特点是超声波在管道中直接传输,没有反射(称为单声程),信号衰耗小。

Z法可测管径范围为100mm至6000mm。

现场实际安装时,建议200mm以上的管道都要选用Z法(这样测得的信号最大)。

3 探头安装表面的处理在安装之前,首先清除管道表面的铁锈、污垢等(管道表面有防护层时,应先剥去防护层),使管壁表面平滑无污物。

清理范围应达到探头安装距离L+200mm宽度的整个圆周。

4、安装距离由仪器自动算出,参见说明书。

5 在管道上安装探头(1)打磨安装点,打磨面积约为探头面积的3倍;(2)清除探头发射面和管道安装表面的油污;(3)将耦合剂涂满探头的整个发射表面,不要形成气泡;(4)在管道表面涂上硅脂;(5)把探头牢牢地贴在管壁上,用布带或钢带固定探头(注意:两探头的发射方向必须相对)。

二、KL-TUF/TUC-2000系列超声波流量计/热量表采用了窗口化软件设计,所有输入参数、仪器设置和显示测量结果统一细分为100多个不同的显示窗口(有时也称为菜单),这些显示窗口标记为M00,M01………M+9。

进入某个显示窗口的快捷方法是键入MENU 键,然后键入两位数字表示的窗口号码。

例如欲进入35号窗口,则键入MENU 3 5 键在相邻窗口(例如M39和M41是M40的相邻窗口)之间移动,使用▲/+ 或▼/- 键。

窗口按下列规律安排:●00~09 号窗口是显示窗口,能显示瞬时流量、正累积流量、负累积流量、净累积流量、瞬时流速、日期时间、模拟输入当前量、当前工作状态、今日流量。

●10~29 号窗口是初始参数操作窗口,在这些窗口中输入诸如管道外径、管壁厚度、流体种类、传感器类型、传感器安装方法等参数,显示安装距离、参数固化等。

●30~38 号窗口是流量单位选择和累积器选项操作窗口,在这些窗口中,可以选择工作单位系,可选择流量计工作单位诸如立方米、公升等、可以打开或关闭各累积器或是对其进行“清零”操作。

●40~49 号窗口包括流量修正操作窗口和网络标识地址码(46 号)、密码保护(47 号)、线性度折线修正(48 号)等。

●50~89 号窗口包括定时输出、RS485 输出、继电器输出、电流环输出、批量控制器、LCD 显示器、日期时间、频率信号输出、报警输出、模拟输入、日月年累积器、热量测量等功能的设置和操作。

●90~94 号窗口为流量计检查窗口。

90 号窗口显示信号强度和信号质量Q值;91 号窗口显示信号传输时间比;92 号窗口显示通过测量估计的流体声速;93 号窗口显示测量的信号传输总的时间和时间差;94 号窗口显示雷诺数和仪器自动修正系数。

●95 号窗口是进入此窗口就启动了流量计的循环显示功能,顺序为M95→M00→M01→M02→M03→M04→M05→M06→M07→M08→M09→M90 →M95 时间间隔为8 秒。

●+0~+9 号窗口是附加的一些次常用功能窗口,包括上断电时间记录、总工作时间、总上电次数等。

甚至还包括一个单精度函数计算器。

还有一些窗口是有关硬件调试操作的,只用于厂家调试。

详细的说明请见“怎样使用”和“命令/显示窗口详解”章节。

§4. 2菜单一览表三、接线方式:传感器接线图:压力传感器一、安装方式:采用引压管+仪表阀+传感器二、安装要求:使用JYB压力变送器对压力进行测量,变送器应尽量安装在温度梯度和温度波动小的地方,同时要避免振动和冲击。

三、安装位置:JYB压力变送器可直接安装在测量点上。

连接螺纹:1/2或者M20X1.50为确保JYB压力变送器接头密封,应先在接头处卷上密封胶带,然后拧紧变送器。

四、安装方式:1、液体测量:测量液体流量时,取压口应开在流程管道的侧面。

以避免渣滓的沉淀。

同时变送器要安装在取压口的旁边或下面,以便气泡排入流程管道之内2、气体测量:测量气体流量时,取压口应开在流程管道的顶端或侧面。

并且变送器应装在流程管道的旁边或上面,以便积聚的液体容易注流程管道之内3、蒸汽测量:测量蒸气流量时,取压口应开在流程管道的侧面,并且变送器安装在取压口的下面,以便冷聚液能充满在导压管里。

应当注意,在测量蒸汽或其它高温介质时,其温度不应超过变送器的使用极限温度被测介质为蒸汽时,导压管中要充满水,以防止蒸汽直接和变送器接这样变送器工作时,其容积是很微不足道的,不需要加装冷凝管。

五、接线方式:六、注意事项:1. 防止变送器与腐蚀或高温(≥90℃)的介质直接接触2. 要防止渣滓在导压管内沉积3. 导压管要尽可能短4. 负压计两边导压管内的液柱压头应保持平衡5. 导压管应安装在温度梯度和温度波动小的地方6. 防止引压管内结晶或低温结冰六、减少误差的方法如下:1) 导压管应尽可能短些2) 当测量液体或蒸汽时,导压管应向上连到流程工艺管道,其斜度应小于1/123) 对于汽体测量时,导压管应向下连到流程工艺管道,其斜度应小于1/124) 液体导压管道的布设要避免中间出高点,气体导压管道的布设要避免中间出低点,5) 负压计两导压管应保持相同的温度6) 为避免摩檫影响,导压管的口径应足够大7) 充满液体导压管中应无气体存在8) 当使用隔离液时,负压计两边导压管的液体应相同9) 采用洁净剂时,洁净剂连接处应靠近工艺管道取压口,洁净剂所经过的管路其长度和口径应相同,应避免洁净剂通过变送器温度传感器一、安装方式:传感器+接头(法兰或螺纹)二、安装注意事项:1、传感器能够插入到待测量的温场中心位置,使传感器感温部位通常处于管道轴线部位。

2、高温测量一般垂直安装,如侧装要考虑高温会使保护管变形损坏,加强保护管或者设备加装保护支架。

3、有搅拌扰动场合的测量,一般要有加强管,传感器从加强管内插入到测量部位;如要求响应时间快一些,传感器部位(即保护管端部)可以露出少许。

4、流速场合的测量(如管道),不但要考虑流体的冲击力,还要考虑流体产生的涡流振动破坏。

要求保护管不但要有一定的结构强度,安装方法也很重要,如顺着流向斜式安装,或在管道拐弯直角处迎流向插入安装。

5、产品在压力环境中使用,使用单位应遵照国家相关安全要求进行压力试验,确认合格并满足使用要求方可安装使用。

三、接线方式:氧化锆分析仪对于气体分析仪器,安装方式的正确与否对仪器的正常测量具有很大的影响,下面针对仪器的几个组成部分详细说明:一、ISG-C检测器(氧探头)检测器结构,见图3,氧传感器安装在检测器头部,用四条不锈钢螺钉固定。

检测器设有两条气路:标准气入口、参比气入口。

从标准气入口通入不同的标准气样,即可由转换器对系统进行在线的标定操作。

图中所注“标气入口”即为校准操作时使用。

如不进行校准操作,请务必将“标准气入口”堵死,以防止空气泄漏进去,引起测量误差。

其“参比气入口”在任何时间都要开放,保持与大气的畅通。

氧化锆检测器结构图(以检测器标准长度400mm为例)检测器接线盒内共有8根引线端子,接线方式见图,检测器安装有温度传感器(AD590),所以由检测器向转换器传送热电偶信号时不必使用补偿导线。

检测器标准长度有六种:180mm,400mm,600mm,800mm,1000mm,1200mm 注意:1、氧探头内部安装由四条陶瓷引管、一个石英玻璃管、氧传感器等易部件,因此在搬运和安装时请切勿发生剧烈磕碰!2、氧探头顶端的金属过滤器能够有效的防止烟尘等杂质,切勿将其取下,以免引起传感器的堵塞。

3、在进行氧探头的端子连线时,请注意不要将电缆的外胶皮放入端子的压片下,由于仪器对氧探头内部的电炉进行时时在线控温,引线接触不良会引起控温电路或加热变压器的损坏。