基于MatLab的抑制变压器励磁涌流仿真研究_陈仁云
基于MatLab的电力变压器建模和仿真分析(1)

2.4.2 仿真参数介绍及波形 ................................................................................... 32 2.5 仿真三相变压器 T3 的内部故障 ................................................................... 38 2.5.1 仿真 T3 相间短路(AB 相)的模型如图 .................................................. 38 2.5.2 模型参数介绍及波形 ................................................................................... 38 2.5.3 仿真 T3 匝间短路的模型如图 .................................................................... 42 2.5.4 模型参数介绍及波形 ................................................................................... 42 第三章 变压器仿真波形分析 ............................................................................... 45 3.1 对励磁涌流进行 FFT 分析 ............................................................................. 45 3.2 对外部故障进行 FFT 分析 ............................................................................. 46 3.3 对内部故障进行 FFT 分析 ............................................................................. 47 总结 ......................................................................................................................... 49 参考文献 ................................................................................................................. 50 附录:外文翻译 1 .................................................................................................. 51 外文翻译 2 .............................................................................................................. 56 指导教师评语表 ..................................................................................................... 60
变压器空载合闸励磁涌流抑制技术研究

变压器空载合闸励磁涌流抑制技术研究随着海洋石油越来越多的依托海底电缆电力组网进行边际油田开发,对电力组网的供电可靠性要求越来越高。
通常电力变压器空载合闸时会产生较大的励磁涌流,容易造成变压器差动保护装置和敏感电力电子元器件的误动作,影响电力系统的安全稳定运行等。
针对这一问题,本文运用MATLAB软件对相控开关模型进行仿真和對串并联电阻数学模型进行分析,得出加装相控开关能够明显的抑制投切大容量变压器时产生的涌流。
通过串并联电阻能够加快冲击电流的衰减速度,使得变压器保护装置可以躲过涌流引起的误动作时间。
标签:变压器;空载合闸;励磁涌流;MATLAB一、项目概述中国海洋石油某油田由一艘浮式储油轮和两个井口平台组成。
储油轮作为油田的供电中心,共设置三台透平发电机组,单台机组的额定容量为4632kW,额定功率因数0.8;两个井口平台只设置有应急发电机,正常生产用电由储油轮通过两台4000kV A,6.3/10.5kV的升压变压器升压,然后通过两根海缆(3x50mm2)分别向井口平台供电,至井口海缆长度分别为3km和4.8km,井口平台再通过两台并列运行的4000kV A,10.5kV/0.4kV的降压变压器为平台上用电设施供电。
平台电力系统黑启动时,储油轮上仅有一台透平发电机为井口平台供电,空载投入6.3/10.5kV升压变压器产生励磁涌流导致单台机组关停脱网,必须开启两台透平发电机组才能承受励磁涌流冲击,因此严重影响了油田供电恢复的效率,必须对变压器采取励磁涌流抑制措施,降低对电网的冲击。
二、变压器励磁涌流解决方案1.变压器励磁涌流变压器原边绕组接在交流电源上而副绕组开路时的运行方式叫做空载运行。
变压器二次侧空载时,副绕组流过的电流为0;一次侧流过的电流称为励磁电流,该励磁电流流过一次绕组产生主磁通。
当变压器空载关合上口断路器时,由于合闸相位的随机性以及变压器剩磁的影响,使得铁芯磁通迅速趋于饱和,从而产生幅值很大、频率很高的励磁涌流。
变压器低压侧并联电容器的励磁涌流抑制方法研究

电子测量变压器低压侧并联电容器的励磁涌流抑制方法研究杜力民,曾耀吾(国网湖南省电力公司怀化供电分公司,湖南怀化,418000 )摘要:变压器空载合闸时,由于线圈绕组剩磁及铁芯非线性特性作用,导致变压器产生很大的励磁涌流。
励磁涌流会经常导致差动保护误 动作,从而影响电力系统的运行可靠性及运行质量。
建立并分析变压器低压侧并联电容器数学模型,在MATLAB/SIMUUNK中建立变压器 空载合闸的仿真模型,分析仿真结果与理论分析相符。
为深入研究抑制变压器励磁涌流提供了一定的依据。
关键词:变压器;空载合闸;励磁涌流;MATLAB/SIMUUNK;电容器0前言变压器空载投入运行或切除外部故障后重新恢复运行 过程时,绕组线圈中的剩磁所产生的磁场与流过线圈电流产 生的磁场会相互作用,两者将导致铁芯中的磁通量瞬间增 大,变压器铁芯将迅速达到饱和状态,变压器铁芯一旦达到 饱和状态,励磁电抗值将急剧减小,因而产生很大的励磁电 流,此过程称为励磁涌流。
当变压器不带负荷合闸时,在低压侧并联接入一个电容 器可以抑制变压器铁芯的饱和,阻止励磁电抗迅速变小。
变 压器铁芯未能达到饱和状态,则励磁阻抗不会急剧减小,此 过程中产生的励磁电流不会急剧增大。
1变压器低压侧并联电容器的数学模型通过对变压器数学模型分析可得出其高压绕组与低压 绕组电阻的T型等效电路图[1],如图1 (a)所示。
图中Lla 为一次侧高压漏电感,L2a为二次侧低压绕组折算到一次侧 高压侧的漏电感,LM为励磁电感,r i为一次侧绕组电阻,4为二次侧绕组折算到_次侧的电阻。
Lla、L2a与LM相比,可以忽略不计。
因此,为了便于计算分析,忽略Lla、L2a,同时铁心损耗比较小,不在数学模型中提现。
在以上假设条 件下,可以得到简化后的等效电路图如图1 (b)所示。
如果在变压器二次侧并联一个电容器,如图2所示,当电容器大小为某一值时,励磁电感与其在工频下发生并联 谐振,此时励磁阻抗相对于无穷大,以达到抑制励磁电流急 剧增大的目的。
计及剩磁的变压器励磁涌流的仿真研究

TRANSFORMER
Vol.46 No.11 November 2009
计及剩磁的变压器励磁涌流的仿真研究
黄 金,方春恩,李天辉,王凤翔
(西华大学电气信息学院,四川 成都 610039)
摘要:根据变压器的工作原理,推导出了剩磁的计算公式,并通过 ATP-EMTP 的仿真阐述了抑制励磁涌流的控制
为了验证这三个策略的有效性, 先看看随机合 闸时产生的励磁涌流,如图 4 所示。
600 340 80
励 磁 涌 流/A
-180 -440
-700
0
0.2
0.4
0.6
0.8
1
时 间/s 图 4 随机合闸时产生的励磁涌流
Fig.4 Magnetizing inrush current during random close
第 46 卷
准 B相
C相
+准r
A相
O
A
t
-准r
合A相 P Q
图 5 A 相合闸后 B 相、C 相绕组的磁通变化趋势
Fig.5 Magnetic flux curves in phase B and C after close of phase A
励 磁 电 流/A
相、C 相)的最佳合闸时刻。 按这个要求关合断路器 就能够有效地避免铁心磁通过饱和, 从而抑制励磁 涌流,这个控制策略称为快速合闸策略。运用该策略 消除涌流(见图 4)后的励磁电流波形如图 6 所示, 显然快速合闸策略已经成功地把励磁涌流消除了。
铁心磁通
励磁电流 t (a) 对 称 的 铁 心 磁 通
铁心磁通 准
磁化特性
I
基于MATLAB的三相变压器励磁涌流仿真分析

基于MATLAB的三相变压器励磁涌流仿真分析崔芳芳【摘要】利用MATLAB中的电力系统模块库PSB,建立三相变压器空载模型及短路模型.在此模型基础上对变压器空载合闸和短路故障切除后电压恢复时的励磁涌流进行了仿真,并对此仿真结果进行了分析.仿真结果与理论分析相吻合,表明利用MATLAB/PSB能够有效地实现对变压器励磁涌流的仿真,为变压器保护的算法研究提供基础.【期刊名称】《安徽电气工程职业技术学院学报》【年(卷),期】2010(015)001【总页数】5页(P60-64)【关键词】变压器;电力系统模块库;仿真;励磁涌流;FFT分析【作者】崔芳芳【作者单位】浙江舟山电力局,浙江,舟山,316000【正文语种】中文【中图分类】TM7430 引言当变压器空载合闸或外部故障切除后电压恢复时,由于铁芯饱和会产生很大的励磁涌流,在最不利的情形下,可达到正常励磁电流的上百倍,或者说可达到变压器额定电流的 5~7倍。
这一大大超过正常励磁电流的空载合闸电流称为励磁涌流。
励磁涌流的大小和衰减时间与外加电压的相位、铁芯中剩磁的大小和方向、电源容量的大小、回路的阻抗、变压器容量的大小和铁芯饱和程度、铁芯的剩磁以及合闸时的相角等因素有关[1]。
同时,在变压器空载合闸这一瞬变过程中,电流、电压的波形也会发生畸变,产生谐波;在一定的条件下,还可能会引起电力系统谐振,产生过电压。
本文利用 MATLAB软件,在变压器各种运行情况下进行计算机仿真,并对所产生励磁涌流的特点进行分析。
1 MATLAB/PSB简介MATLAB是 Mathwork公司推出的一套高效率的数值计算和可视化软件,适用于多种学科的大型仿真与计算。
它集数值分析、矩阵计算、信号处理和图形显示于一体,构成了一个方便的、界面友好的用户环境,对许多专门的领域都开发了功能强大的模块集成工具箱。
其中提供了专用电力系统模块 PSB(Power System Block),它是一种针对电气系统的可视化建模与仿真工具。
基于MatlabSimulink的变压器运行仿真分析

基于Matlab/Simulink的变压器运行仿真分析作者:田震来源:《科技创新与应用》2019年第26期摘; 要:文章简单介绍了变压器运行原理,在理论基础上,运用Matlab/Simulink中电气系统模块库中的仿真模型,对常见的双绕组三相变压器在空载合闸过程中产生励磁涌流的工况进行仿真建模,并通过模型获得了空载合闸时电流电压变化曲线及其变化规律,研究结果对提高变压器运行的可靠性、减少事故发生率具有一定的指导意义。
关键词:变压器;Matlab;仿真;励磁涌流中图分类号:TM407; ; ; ; 文献标志码:A; ; ; ; ;文章编号:2095-2945(2019)26-0009-03Abstract: In this paper, the principle and mechanism of transformer operation are briefly introduced. On the basis of theory, the simulation model of electrical system module library in Matlab/Simulink is used. In this paper, the simulation modeling of the excitation inrush current produced by the common double-winding three-phase transformer in the process of no-load closing is carried out, and the current and voltage variation curve and its variation law during no-load closing are obtained through the model. The research results have certain guiding significance to improve the reliability of transformer operation and reduce the incidence of accidents.Keywords: transformer; Matlab; simulation; excitation inrush current引言在電力系统运行中,变压器是重要设备之一,能够保证整个系统连续的、可靠的稳定运行,但它也是容易发生电力系统各种事故最多的设备之一,为了更好地研究变压器的结构特点和保护运行方式,对变压器进行仿真显得十分必要。
基于MATLAB的励磁控制系统仿真分析

基于MATLAB的励磁控制系统仿真分析摘要:近些年来,电力系统发展迅速,基本形成了高电压、大机组、超远距离输送的模式。
因此,保证电力系统的安全、稳定、高效运行成为了研究的热点与难点。
同步发电机励磁控制系统是同步发电机控制系统的核心。
经过长年的研究证明,实现对同步发电机励磁的合理有效控制,是实现电力系统稳定运行要求的最快捷、最有效、最廉价的方法。
同步发电机的励磁系统一般由励磁功率单元和励磁调节器两个部分组成。
本文从同步发电机励磁控制系统原理入手,在深入学习PID控制与模糊控制理论之后,将两者结合起来,提出了基于模糊PID同步发电机励磁控制策略,并对其进行了基于MATLAB的励磁控制系统仿真分析。
关键字:同步发电机;励磁控制系统;MATLAB建模;PID控制;模糊控制1发电机励磁系统的作用维持发电机或其他控制点(例如发电厂高压侧母线)的电压在给定水平维持电压水平是励磁控制系统的主要的任务,有以下 3 个主要原因:第一,保证电力系统运行设备的安全。
电力系统中的运行设备都有其额定运行电压和高运行电压。
保持发电机端电压在容许水平上,是保证发电机及电力系统设备安全运行的基本条件之一,这就要求发电机励磁系统不但能够在静态下,而且能在大扰动后的稳态下保证发电机电压在给定的容许水平上。
发电机运行规程规定,大型同步发电机运行电压不得高于额定值的 110%。
第二,保证发电机运行的经济性。
发电机在额定值附近运行是经济的。
如果发电机电压下降,则输出相同的功率所需的定子电流将增加,从而使损耗增加。
规程规定大型发电机运行电压不得低于额定值的 90%;当发电机电压低于 95%时,发电机应限负荷运行。
其他电力设备也有此问题。
第三,提高维持发电机电压能力的要求和提高电力系统稳定的要求在许多方面是一致的。
励磁控制系统对静态稳定、动态稳定和暂态稳定的改善,都有显著的作用,而且是为简单、经济而有效的措施。
2同步发电机励磁系统建模2.1 发电机模型和励磁系统同步发电机是电力系统中物理过程最复杂的的元件,既有机械运动过程又有电磁暂态过程,并且包含变量众多。
变压器励磁涌流识别及抑制的仿真研究设计

变压器励磁涌流识别及抑制的仿真研究设计变压器励磁涌流识别及抑制的仿真研究摘要本文对变压器励磁涌流问题进行了深入的研究,从最基本的变压器磁路和电路结构出发,详细阐述变压器励磁涌流产生的基本原理,它的存在对常用的变压器保护性能的影响,以及如何在变压器保护中减弱和消除它的影响。
文章在综述了励磁涌流的产生机理后,分析了励磁涌流的产生过程和波形特点,探讨利用电流作判据和现代数字信号处理技术与智能理论作涌流分析等识别励磁涌流进行了比较,并指出各种方法的优缺点。
并对一些新的判别技术进行简单介绍和展望。
此外,本文还介绍了目前使用得较为广泛、有效的几种抑制变压器励磁涌流的方法,并详细介绍了其中的选相投切技术的基本原理,分析了变压器空载投切的暂态过程,同时分析了快速合闸策略、延迟合闸策略、同步合闸策略以及相控投切策略这四种控制策略。
最后在仿真软件中搭建变压器模型,对单相变压器励磁涌流和三相变压器励磁涌流进行了PSCAD和MatLab仿真,同时还对带合闸电阻的单相变压器励磁涌流和中性点串电阻的三相变压器励磁涌流进行了对比仿真试验。
通过对比分析,证明这两种方法的正确性和可行性。
关键词:励磁涌流选相投切技术PSCAD MatLab 仿真31Research for Identification and Inhibition ofTransformer Inrush Current Via SimulationABSTRACTIn this paper, issues of transformer inrush current is studied in some depth, The research will be begin from the analyzing basic structure of the magnetic circuit and circuit structure of transformer, and the more detailed principle of inrush current generated is stated, Further, the negative affection on differential protection of transformer by inrush current, and how to weaken and even eliminate its impact is also described in the paper.This paper reviews the inrush current after the formation mechanism, analysis of inrush current and waveform characteristics of the production process, Explore the use of current as the criterion for identification inrush current and the use of modern digital signal processing technology and intelligent theory of the inrush current surge of identification methods are analyzed and compared with the advantages and disadvantages of each method, and a number of The new identification technology brief and outlook.In addition, this article also describes the current use was more extensive and effective inhibition of transformer inrush current of several methods and gave details of the election in which controlled switching technology the basic principle, analysis of transformer no-load switching transient process, while discussed rapid closing strategy discussed, delayed closing strategy, simultaneous closing strategy, and switching control strategy with the four control strategies.Last build transformer model, single-phase transformer inrush current and three-phase transformer inrush current simulation with PSCAD,while also closing resistor with a single-phase transformer inrush current and neutral series resistor to simulate three-phase transformer inrush current compared test. By comparison, the two methods from which to prove the correctness and feasibility.31KEYWORDS:Inrush Current Controlled Switching PSCAD MatLab simulation31目录第一章绪论 (1)1.1课题的研究背景与意义 (1)1.2变压器励磁涌流研究的现状 (2)1.3本文的主要工作 (2)第二章变压器励磁涌流分析 (4)2.1变压器励磁涌流的产生及特点 (4)2.1.1单相变压器的励磁涌流 (4)2.1.2三相变压器的励磁涌流 (7)2.2励磁涌流的危害 (8)2.3空载合闸时变压器磁通的变化 (9)2.3.1合闸瞬间电压为最大值时的磁通变化 (9)2.3.2合闸瞬间电压为零时的磁通变化 (10)2.4本章小结 (11)第三章变压器励磁涌流的识别 (12)3.1短路故障电流及其特征 (12)3.2利用电流波形特征识别励磁涌流的方法 (13)3.2.1二次谐波制动原理 (13)3.2.2间断角闭锁原理 (14)3.2.3波形对称原理 (15)3.2.4采样值差动 (15)3.2.5波形比较法 (16)3.2.6波形上下对称系数法 (16)3.2.714周波面积法 (16)3.2.8波形正弦度特征法 (18)3.3数字信号原理的识别方法 (19)3.3.1波形相关性分析法 (19)3.3.2数学形态法 (20)3.3.3误差估计法 (20)313.4磁通特性识别法 (21)3.5等值电路法 (22)3.6功率差动法 (22)3.7变压器回路方程法 (23)3.8励磁涌流识别中现代信号处理技术与智能技术的应用 (23)3.8.1模糊逻辑的多判据法 (23)3.8.2神经网路法 (23)3.8.3联合时频分析法 (24)3.9本章小结 (25)第四章几种常用的抑制励磁涌流的方法 (27)4.1空载变压器选相投切 (27)4.2内插接地电阻 (27)4.3改变变压器绕组的分布 (28)4.4在变压器低压侧并联电容器 (28)4.5本章小结 (29)第五章选相分合闸的基本原理与控制策略 (30)5.1选相分合闸投切技术的基本原理 (30)5.2选相分合闸投切三相变压器 (30)5.2.1快速合闸策略 (31)5.2.2延迟合闸策略 (32)5.2.3同时合闸策略 (33)5.2.4相控投切策略 (33)5.3本章小结 (33)第六章系统仿真 (34)6.1PSCAD/EMTDC在电力系统仿真中的应用 (34)6.2单相变压器励磁涌流仿真分析 (34)6.2.1无合闸电阻的单相变压器励磁涌流仿真 (35)6.2.2带合闸电阻的单相变压器励磁涌流仿真 (37)6.3三相变压器励磁涌流仿真 (38)6.3.1中性点直接接地的三相变压器励磁涌流仿真 (40)316.3.2中性点串电阻三相变压器的励磁涌流仿真 (41)6.3.3 选相分合闸三相变压器的励磁涌流仿真 (43)6.4本章小结 (43)总结 (45)参考文献 (46)致谢 (48)附录 (49)31第一章绪论1.1课题的研究背景与意义随着我国经济近些年来的迅速发展,人们对电力的需求日益增长。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
图2
Fig.2
合闸初相角对励磁涌流的影响
Influence of Initial Closing Angle to Magneting Inrush Current
所用三相变压器模型为三相三柱式变压器,绕组连 额定容量为 300 kVA, 额定电压为 接方式为 Yn/△,
由于合闸时电压的初相角对励磁涌流的影响很 大,因此在这里对在不同合闸初相角下进行合闸产 生的励磁涌流的最大值进行了统计。如图 3 所示。
1) 并联合闸电阻,通过合闸电阻承受冲击电
流, 在冲击电流衰减到一定范围后再切除合闸电阻。
2) 内插电阻法,在三相变压器的中性点处联
接一个接地电阻,以承受这种不平衡电流,从而使 得变压器的励磁涌流得以衰减。
3) 变压器选相分合闸技术,利用电压与磁通
的相位关系,通过控制开关合闸时间来达到抑制励 磁涌流的目的[5]。
Simulation Study of Transformer Magnetizing Inrush Based on MatLab
CHEN Renyun1, LIANG Jiaolan2
(1. Hechi Power Supply Bureau, Guangxi Power Grid Co., Hechi, Guangxi 547000, China; 2. Jinchengjiang Power Supply Company, Guangxi Power Grid Co., Hechi, Guangxi 547000, China) Abstract: Three common methods to suppress the inrush current, interpolation resistance method, parallel switch in resistance method and phase identificated switch on/off technique, are taken in MatLab/Simulink simulation to construct the models of three-phase transformers, the impacts of original switch phase angle and earth resistance on no-load transformer switching are analyzed. Simulation results shows the attenuation is the fastest while adopting the interpolation resistance method; whereas the attenuation effect is the best while adopting the phase identificated switch on/off technique, but it required coordination by interpolation resistance method to improved the time accurac and to reduce the operation difficulty. Key words: MatLab; magneting inrush current; Parallel switch in resistance method; interpolation resistance method; phase identificated switch in/off technique
2012 年 第 6 卷 第 3 期 2012,Vol. 6,No. 3
南方电网技术 SOUTHERN POWER SYSTEM TECHNOLOGY 中图分类号:TM401+.1
研究与分析 Study & Analysis 文献标志码:A
文章编号:1674-0629(2012)03-0086-04
图6
Fig.6
中性点串电阻的变压器空载合闸波形图
66.7 %。励磁涌流在 0.06 s 即可衰减到稳定值,比
不带合闸电阻的断路器合闸方案衰减速度快了
Waveform Figure of No-Load Transformer Closing with Neutral Impedance
从图 7 可以看出,中性点串电阻对励磁涌流的 削弱作用在一定范围内是随着阻值的升高而增加 的。 阻值为 25 Ω 的中性点电阻, 就可使励磁涌流峰 值削减超过一半,在阻值为 200 Ω 时,励磁涌流的 峰值削减率为 66.7%。该方法的抑制作用有限,需 要与其他涌流抑制策略相结合使用,但若要达到
(a) 合闸初相角为 0°时的变压器空载合闸波形 (a) Waveform of No-Load Transformer Closing with Initial Angle 0°
I
i 1
n
max n
I max
i 1
n
I max
i 1
(i=1, 2, 3, …, n-1, n) 。 (2)
图1
Fig.1
变压器空载合闸系统连接图
由图 3 可知,在(0~0.5π)区间,合闸初相角 越大,励磁涌流越小。
Connection Diagram of No-Load Transforቤተ መጻሕፍቲ ባይዱer Closing
88
南方电网技术
第6卷
电源初相角为 90°时合闸空载变压器产生的励 磁涌流最小,甚至可以忽略。考虑到实际上变压器 会存在一定的剩磁, 即使在电压峰值时合上断路器, 也可能会产生很大的励磁涌流峰值,对变压器产生 冲击。鉴于此,提出了带合闸电阻的断路器合闸方 案。具体接线如图 4 所示。
m cos t m cos r 。 (1)
1 变压器励磁涌流产生的原因及危害
当变压器合闸时,在外电压的作用下,其一次 侧绕组的磁场将会发生变化,该绕组在磁路中将产 生单极性的偏磁[2]。为抵消外磁场的变化,铁心线 圈可能会流过很大的励磁电流。如果变压器原来就 有剩磁并且偏磁的极性和剩磁的极性相同时,这种 饱和程度会更加严重,从而大幅度降低变压器绕组 的励磁电抗,引起很大的励磁涌流。
R 来抑制冲击电流,待冲击电流衰减到额定电流之
这样就能有效的抑制了励磁 内时再将合上开关 K2, 涌流,并且加快了合闸励磁涌流的衰减速度。 图 5 为仿真所得的波形图。由实验结果可知, 带合闸电阻的断路器合闸方案的最大励磁涌流峰值 约为 13 A,相比不带合闸电阻的断路器合闸方案最 大励磁涌流峰值下降了 26 A,励磁涌流削减率约为
I max 无抑制策略或抑制策略效果不明显下的变 采用效果更好的抑制策略 压器励磁涌流峰值; I max
下的变压器励磁涌流峰值;n 为实验次数。 3.1 并联合闸电阻的变压器励磁涌流仿真 不带合闸电阻的系统连接图如图 1 所示。仿真
(b) 合闸初相角为 90°时的变压器空载合闸波形 (b) Waveform of No-Load Transformer Closing with Initial Angle 90°
2 几种常用的抑制励磁涌流的方法
目前主要有两种抑制励磁涌流的方法,一是通 过变压器外部控制削减励磁涌流。二是通过内部控
第3期
陈仁云,等:基于 MatLab 的抑制变压器励磁涌流仿真研究
87
制即通过改变变压器的内部结构达到削弱励磁涌流 的目的 。这些方法的实现方式分别为:
[4]
因为励磁涌流的大小和合闸初相角有关,考虑 到合闸时间的分散性,进行了多次合闸操作,找出 每次合闸的最大励磁涌流峰值。 为了简化仿真操作, 把合闸的初相角设置为 0°和 90°分别进行比较。 励磁涌流实验波形图如图 2 所示。 发现当 0 时合闸,励磁涌流最大峰值为 39 A,约为额定电流 的 6 倍, 合闸 0.35 s 后励磁涌流衰减到一个稳定值。 在其他条件不变的情况下, 90 时,涌流最大峰 值为 10.8 A,相比变压器额定电流,可以断定电压 初相角为 90°时,空载变压器合闸不会产生励磁涌 流,与之前的理论分析相符。
图4
带合闸电阻的变压器空载合闸电路
速度加快,因此串联中性点电阻的方法能有效限制 励磁涌流,对合闸冲击电流的快速衰减十分有利。
Fig.4 Circuit of No-Load Transformer Closing with Closing Resistance
在变压器合闸时,先合上 K1,用适当的电阻器
的关系曲线,就可以根据变压器的饱和磁通选取合 适的 R 值。 3.2 内插电阻法的变压器励磁涌流仿真 电源和变压器参数不变,取内插接地电阻为 50
Ω,在最严重的情况下合闸(合闸初相角为 0°)用 MatLab 对中性点串电阻的变压器励磁涌流进行仿
真,验证其实用性和可行性。 由图 6 仿真实验结果发现, 串联中性点电阻后, 变压器励磁涌流的幅值不但由 39 A 减小到 15 A, 合闸时的涌流削减率最大可达 61.5%,而且衰减的
25/0.6 kV,绕组的电阻标幺值为 0.01,漏感抗标幺
值为 0.02,仿真计算采用 ode23t 数字积分方式。由 上述数据可以算得高压侧额定电流为 6.93 A。
图3
Fig.3
不同合闸初相角下的涌流最大值
Maximum Inrush Current Under Different Initial Closing Angle
4) 改变变压器绕组的分布,通过改变变压器
的结构增加暂态等效电感来抑制励磁涌流。由于需 要改变变压器的结构,它的发展受到限制[6]。
5) 变压器低压侧并联电容器,这种方法通过
抑制变压器磁通达到饱和从而抑制了励磁涌流[7]。
3 变压器励磁涌流仿真分析
为了检测各种方法抑制励磁涌流的幅值和有效 性,利用 MatLab 建立仿真分析的系统模型,通过 励磁涌流的削减率对抑制涌流的策略进行对比仿 真。定义励磁涌流削减率为