威图空调中文报警故障描述

合集下载

威图空调操作说明书

威图空调操作说明书

Compact 机柜空调Compact Cooling Unit目录目录 (2)1应用场合 (4)2技术参数 (4)3壁挂式安装 (4)4安全须知 (4)5操作和控制方式 (4)5.1控制器控制 (4)5.1.1控制器的操作 (4)5.1.2参数列表 (5)5.1.3参数设置 (6)5.1.4设定目标温度 (6)5.1.5设定温度范围 (6)5.1.6屏幕显示 (6)5.1.7按键显示 (7)5.1.8开机与关机 (7)5.2报警说明 (7)5.3报警信息及系统状态 (8)5.4强制制冷 (8)6过滤网 (8)7技术信息 (8)7.1.1空调的运行 (8)7.1.2冷凝水的排放 (8)8使用说明 (8)8.1空调的安装 (8)8.1.1空调的外部式安装 (9)8.1.2空调的半嵌入式安装 (9)8.2电源连接 (10)8.2.1连接要点 (10)8.2.2过压保护和电源线载荷 (10)9检验和维修 (11)9.1概述 119.1.1用压缩空气清吹 (11)10存放和处理 (13)11供货范围和保修 (13)2威图机柜空调装配说明书ContentsContents (3)1Application (14)2Technical data (14)3Assembly (14)4Safety notes (14)5Commencing operation and controlbehavior (14)5.1Controller control (14)5.1.1Operation of the controller (14)5.1.2Editable parameters (15)5.1.3Parameter navigation (15)5.1.4Setting the target temperature (16)5.1.5Setting the temperature range (16)5.1.6Controller display (16)5.1.7Display buttons (16)5.1.8Compressor: On / Off (17)5.2Alarm parameters (17)5.3Evaluating system messages (17)5.4Forced cooling (17)6Filter mats (17)7Technical informations (18)7.1.1Operation of the cooling unit (18)7.1.2Condensate discharge (18)8Handling instructions (18)8.1Fitting the cooling unit (18)8.1.1External mounting of the cooling unit (19)8.1.2Partial internal mounting of the coolingunit (accessories not included) (19)8.2Electrical connection (20)8.2.1Connection data (20)8.2.2Overvoltage protection and power lineload (20)9Inspection and maintenance (21)9.1Compressed air cleaning (21)10Storage and disposal (23)11Scope of supply and guarantee (23)Rittal cooling unit assembly and operating instructions31 应用场合4威图机柜空调装配说明书1应用场合控制机柜空调是被设计并用于把控制柜的空气冷却同时把柜内热量排出柜外,从而保护温度敏感部件。

空调故障代码大全

空调故障代码大全

空调故障代码大全本文档将介绍常见的空调故障代码及其解释。

了解这些代码将有助于您更快地识别和解决空调故障。

以下是故障代码列表:1. E0 故障代码- 描述:传感器故障- 解释:空调传感器出现故障,可能是无法正常感知空气温度或湿度。

2. E1 故障代码- 描述:压缩机过载- 解释:空调压缩机受到过载,可能是由于高温、高压或系统内部问题引起。

3. E2 故障代码- 描述:回风传感器故障- 解释:空调回风传感器出现故障,可能导致无法准确检测室内空气质量。

4. E3 故障代码- 描述:电源电压异常- 解释:空调电源电压异常,可能是由于供电问题或电路故障引起。

5. E4 故障代码- 描述:室内风机受阻- 解释:空调室内风机受到阻塞或有其他物体影响其正常运转。

6. E5 故障代码- 描述:室内传感器故障- 解释:空调室内传感器出现故障,可能导致无法准确检测室内空气温度或湿度。

7. E6 故障代码- 描述:通信故障- 解释:空调与控制器之间的通信出现故障,可能是连接问题或控制器本身的故障。

8. E7 故障代码- 描述:电流过载- 解释:空调电流超出额定值,可能是由于过载或电路故障引起。

9. E8 故障代码- 描述:压力保护- 解释:空调系统出现压力异常,可能是由于过高或过低的压力引起。

10. E9 故障代码- 描述:冷凝器高温保护- 解释:空调冷凝器温度过高,可能是由于长时间运行或冷凝器故障引起。

请注意,此列表仅包含常见的故障代码,并且故障代码的具体含义可能因空调型号和品牌而有所不同。

如果您的空调出现故障,建议您查看产品说明书或与厂家联系以获取最准确的解释和修复方法。

希望以上信息对您有所帮助!。

机房空调常见报警速查表及故障说明

机房空调常见报警速查表及故障说明

机房空调常见报警速查表及故障说明机房空调常见报警速查表及故障说明当报警发生时,请记录报警信息,按表格中对应的各项编码操作。

故障级别说明A级严重故障报警该报警严重影响设备运行或对机房造成严重后果。

B级一般故障报警该类报警短时间不会影响机房的温湿度。

C级提示性故障报警该类报警不影响空调运行,只起提示作用。

故障排除步骤:代码GG1按复位键2次将报警消声并复位G2记清报警内容后打电话报修G3用户可在电话指导下简单处理此故障G4报警复位后进行观察G5由专业技术人员进行维修G6该报警复位后可正常运行G7无需维修可自行复位报警原因说明:代号SS1.漏水报警1.排水不畅造成外溢。

2.蒸发器结冰造成漏水。

3.上水管路及电磁阀失灵造成漏水。

S2.高压报警1.室外机散热片脏堵,2.氟量过多:现象为室外机风扇长时间运转,高压不在15-18bar之间波动,而是接近24bar(24bar 为高压报警点)3.室外机散热环境不佳,通风不畅。

4.室外机不转。

S3低压报警1.空气过滤网脏堵。

2.制冷剂不足,冬天气温低时,可能发生类似情况。

3.若高压高低压低,则为管道堵塞。

S4.加湿报警1.室内高湿或低湿报警:a.空调刚开机时,容易发生类似报警。

b.空调房间门窗密闭不严,大量湿空气进入机房内。

C.加湿罐故障。

2.加湿罐故障:a.供水管道内没水。

b.加湿罐未接上水管。

c.加湿罐老化,长期末清洗,结垢严重。

d.上水阀脏堵。

e菜单设置错误。

S5.控制器设定值与实际差距较大1.温湿度设定值太高或太低。

2.其它参数设定不合理。

3.传感器没有进行校对。

S6.失风报警控制器显示有风机符号,但失风报警消不掉,此时打开空调确认:1.风机过流保护或风机烧坏。

2.风机反转。

3.室内机过滤网脏堵。

S7.供电环境较恶略1.电压不稳,超出规定范围。

2.经常停电。

S8.电气元件老化1电池没电。

2显示屏幕抽丝。

3黑屏现象。

4无法完成启动自查。

S9电加热过热报警1.室内机过滤网脏堵。

E-control系统故障中英文对照

E-control系统故障中英文对照

E-control系统故障中英⽂对照故障代码英⽂表述中⽂含义0016Never crank synced at start启动时曲轴与凸轮轴不能同步0091FP low voltage燃⽓压⼒低电压0092FP high voltage燃⽓压⼒⾼电压0107MAP low voltage MAP电压低0108MAP high pressure MAP压⼒⾼0111IAT higher than expected 1IAT⾼于期望值10112IAT low voltage IAT电压低0113IAT high voltage IAT电压⾼0116ECT higher than expected 1ECT⾼于期望值10117ECT/CHT low voltage ECT/CHT电压低0118ECT/CHT high voltage ECT/CHT电压⾼0121TPS1 lower than TPS2TPS1低于TPS20122TPS1 low voltage TPS1电压低0123TPS1 high voltage TPS1电压⾼0127IAT higher than expected 2IAT⾼于期望值20129BP low pressure 背压低0134EGO1 open / lazy EGO1断开0140EGO3 open / lazy EGO2断开0154EGO2 open / lazy EGO3断开0160EGO4 open / lazy EGO4断开0217ECT higher than expected 2ECT⾼于期望值20219Max govern speed override最⼤调速转速超速0221TPS1 higher than TPS2TPS1⾼于TPS20222TPS2 low voltage TPS2电压低0223TPS2 high voltage TPS2电压⾼0234TIP control overboost TIP控制过增压0236TIP active TIP波动0237TIP low voltage TIP低电压0238TIP high voltage TIP⾼电压0261Injector 1 open or short to ground1号喷嘴断开或短接地0262Injector 1 coil shorted1号喷嘴短路0264Injector 2 open or short to ground2号喷嘴断开或短接地0265Injector 2 coil shorted2号喷嘴短路0267Injector 3 open or short to ground2号喷嘴断开或短接地0268Injector 3 coil shorted2号喷嘴短路0270Injector 4 open or short to ground2号喷嘴断开或短接地0271Injector 4 coil shorted2号喷嘴短路0273Injector 5 open or short to ground2号喷嘴断开或短接地0274Injector 5 coil shorted2号喷嘴短路0276Injector 6 open or short to ground2号喷嘴断开或短接地0277Injector 6 coil shorted2号喷嘴短路0279Injector 7 open or short to ground2号喷嘴断开或短接地0280Injector 7 coil shorted2号喷嘴短路0282Injector 8 open or short to ground2号喷嘴断开或短接地0283Injector 8 coil shorted2号喷嘴短路0285Injector 9 open or short to ground2号喷嘴断开或短接地0286Injector 9 coil shorted2号喷嘴短路0288Injector 10 open or short to ground2号喷嘴断开或短接地0289Injector 10 coil shorted2号喷嘴短路0299TIP control underboost TIP控制未增压0336Crank sync noise曲轴输出信号⼲扰0337Crank loss曲轴信号丢失0341Cam sync noise凸轮轴输出信号⼲扰0342Cam loss凸轮轴信号丢失0502Roadspeed input loss of signal0524Oil pressure low机油压⼒低0562voltage low电瓶电压低0563voltage high电瓶电压⾼0615Start relay coil open启动继电器线圈断开0616Start relay ground short启动继电器接地短路0617Start relay coil short to power启动继电器线圈短接到电源06425VE1 low voltage5V电源1电压低06435VE1 high voltage5V电源1电压⾼0650MIL open MIL故障指⽰灯断开0650MIL open MIL断路06525VE2 low voltage5V电源2电压低06535VE2 high voltage5V电源2电压⾼0685Relay coil open电源继电器线圈断开0686Relay ground short电源继电器接地短路0687Relay coil short to power电源继电器线圈短接到电源1111RPM above fuel rev limit level1112RPM above spark rev limit level1121FPP1/2 simultaneous voltages out-of-range(redundancy)FPP1或FPP2同步电压超出范围1122FPP1/2 do not match each other or IVS(redundancy)FPP1和FPP2互相不匹配或不与IVS匹配1131WGP voltage high WGP电压⾼1132WGP voltage low WGP电压低1153CL high NG天然⽓闭环修正系数⾼1154CL low NG天然⽓闭环修正系数低1163AL high NG天然⽓⾃适应学习系数⾼1164AL low NG天然⽓⾃适应学习系数低1166Catalyst inactive on NG天然⽓催化剂不起作⽤1171MegaJector delivery pressure higher than expected EPR出⽓压⼒⾼于期望值1172MegaJector delivery pressure lower than expected EPR出⽓压⼒低于期望值1173MegaJector comm lost EPR通讯丢失1174MegaJector voltage supply high EPR供给电压⾼1175MegaJector voltage supply low EPR供给电压低1176MegaJector internal actuator fault detection EPR内部驱动出现故障1177MegaJector internal circuitry fault detection EPR内部电路出现故障1178MegaJector internal comm fault detection EPR内部通讯出现故障1521CHT higher than expected 1CHT⾼于期望值11522CHT higher than expected 2CHT⾼于期望值21531Gov1/2/3 interlock failure16115VE1/2 simultaneous out-of-range5V电源1和5V电源2同时超出范围1631PWM1-Gauge1 open / ground short1632PWM1-Gauge1 short to power1633PWM2-Gauge2 open / ground short1634PWM2-Gauge2 short to power1635PWM3-Gauge3 open / ground short1636PWM3-Gauge3 short to power1637PWM4 open / ground short PWM4断开或接地短路1638PWM4 short to power PWM4短接到电源1639PWM5 open / ground short PWM5断开或接地短路1640PWM5 short to power PWM5短接到电源1641Buzzer control ground short蜂鸣器控制线接地短路1642Buzzer open蜂鸣器断开1643Buzzer control short to power蜂鸣器控制线短接到电源1643Buzzer control short to power蜂鸣器控制线短接到电源1644MIL control ground short MIL接地短路1645MIL control short to power MIL短接到电源1654Default First Flash Code初始默认闪码(在实际中,初始闪码为2111Unable to reach lower TPS不能实现TPS低信号2112Unable to reach higher TPS不能实现TPS⾼信号2115FPP1 higher than IVS limit FPP1⾼于怠速确认范围2116FPP2 higher than IVS limit FPP2⾼于怠速确认范围2120FPP1 invalid voltage and FPP2 disagrees with IVS(redundancy) FPP1电压⽆效并且FPP2与IVS不⼀致2121FPP1 lower than FPP2FPP1低于FPP22122FPP1 voltage high FPP1电压⾼2123FPP1 voltage low FPP1电压低2125FPP2 invalid voltage and FPP1 disagrees with IVS(redundancy)FPP2电压⽆效并且FPP1与IVS不⼀致2126FPP1 higher than FPP2FPP1⾼于FPP22127FPP2 voltage low FPP2电压低2128FPP2 voltage high FPP2电压⾼2130IVS stuck at-idle, FPP1/2 match2131IVS stuck off-idle, FPP1/2 match2135TPS1/2 simultaneous voltages out of range TPS1和TPS2同步电压超出范围2139FPP1 lower than IVS limit FPP1低于IVS范围2140FPP2 lower than IVS limit FPP2低于IVS范围2229BP high pressure背压⾼2300Spark coil 1 primary open or short to ground1号点⽕线圈初级线路断开或短接地2301Spark coil 1 primary shorted1号点⽕线圈初级线路短路2303Spark coil 2 primary open or short to ground2号点⽕线圈初级线路断开或短接地2304Spark coil 2 primary shorted2号点⽕线圈初级线路短路2306Spark coil 3 primary open or short to ground3号点⽕线圈初级线路断开或短接地2307Spark coil 3 primary shorted3号点⽕线圈初级线路短路2309Spark coil 4 primary open or short to ground4号点⽕线圈初级线路断开或短接地2310Spark coil 4 primary shorted4号点⽕线圈初级线路短路2312Spark coil 5 primary open or short to ground5号点⽕线圈初级线路断开或短接地2313Spark coil 5 primary shorted5号点⽕线圈初级线路短路2315Spark coil 6 primary open or short to ground6号点⽕线圈初级线路断开或短接地2316Spark coil 6 primary shorted6号点⽕线圈初级线路短路2318Spark coil 7 primary open or short to ground7号点⽕线圈初级线路断开或短接地2319Spark coil 7 primary shorted7号点⽕线圈初级线路短路2321Spark coil 8 primary open or short to ground8号点⽕线圈初级线路断开或短接地2322Spark coil 8 primary shorted8号点⽕线圈初级线路短路2324Spark coil 9 primary open or short to ground9号点⽕线圈初级线路断开或短接地2325Spark coil 9 primary shorted9号点⽕线圈初级线路短路2327Spark coil 10 primary open or short to ground10号点⽕线圈初级线路断开或短接地2328Spark coil 10 primary shorted10号点⽕线圈初级线路短路2428Exhaust gas temperature high排⽓温度⾼2618Tach output ground short Tach输出信号接地短路2619Tach output short to power Tach输出信号短接到电源。

空调常见故障代码介绍空调常见故障代码解决方法【详解】

空调常见故障代码介绍空调常见故障代码解决方法【详解】

空调常见故障代码介绍空调常见故障代码解决方法【详解】无论是什么品牌的空调,在使用的时候出现故障是在所难免的,而在空调出现故障的时候,一般都会显示相对应的一些故障代码,来告诉我们故障的具体原因,帮助我们可以更好的辨别故障,方便更快的解决这个问题。

而小编今天为了大家可以更好的了解空调故障代码方面的情况,就来为大家介绍下现在比较常见的一些空调故障代码,希望大家可以作为参考进行了解,在我们以后使用空调的时候可以更好的辨别故障原因,并更快速的加以解决。

A1为室内机印刷电路板不良,A3排水水位系统异常。

A7摆动电机锁定,C4热交换器温度感应器系统异常。

C9吸入空气温度感应器系统异常,E0保护装置动作。

室外机E3高压异常。

室外机 E4低压异常。

室外F3排水管温度异常。

室外机H3高压开关故障。

室外机H9外气温度感应器系统异常。

室外机J3排出管温度感应器系统异常。

室外机 J6热交换器温度感应器系统异常。

故障代码故障原因A6风扇系统故障,风扇电机有问题。

C4室外管温热敏电阻有故障,C9室外微风热敏电阻有故障。

U4室内机与室外控制线接触不良或接错。

U5室内机与遥控器接触不良。

E5过载可压缩机超负荷运行。

E3高压过高使压力继电器断开保护,H3高压控制器本身有故障。

H9室外温度传感器本身有问题。

J6热交换器的感温器有故障。

P3电气箱内的感温器有故障。

错误代码e5表示:室外机压缩机瞬时电流过大,解释是接地不好或压缩机短路,估计室外机有漏电的可能性。

看内外热交是否过脏,内外风机是否异常,拔掉压缩机连接线看是否还显示故障代码,否则查变频板。

大家在购买空调使用的时候,故障问题是在所难免的,而小编在上面为大家介绍的这些空调故障代码的情况,大家一定要仔细了解这方面的情况。

在以后如果大家在使用空调的时候遇到故障的话,大家可以根据空调提示的故障代码来判定故障的原因,从而让我们大家在实际排除故障的时候可以节约更多的时间,以免影响我们大家的日常空调使用效果。

中英文故障对照表

中英文故障对照表

Err070 变桨3限位开关未在安全状态
Err071 快速停止超时-高速 Err072 快速停止超时-低速 Err073 完全停止超时-高速
(* Pitch 3 limiting switch not active in safety_o k state *) (* 2*) (* Fast stop timeout high speed *) (* 2*) (* Fast stop timeout low speed *) (* 2*) (* Full stop timeout high speed *) (* 2*)
Err063 变桨2基准位置错误 Err064 变桨3基准位置错误 Err065 变桨1限位开关未在初始状态
(* Pitch2 referenc e position ing error *) (* 0*) (* Pitch3 referenc e position ing error *) (* 0*) (* Pitch 1 limiting switch not active in stop_ok state *) (* 2*)
Err056 变桨1位置延时故障 Err057 变桨2位置延时故障 Err058 变桨3位置延时故障 Err059 变桨位置没有同步变慢
(* Pitch1 position error delayed *) (* 0*) (* Pitch2 position error delayed *) (* 0*) (* Pitch3 position error delayed *) (* 0*) (* Pitch position s not synchron ous slow *) (* 0*)
Err082 轮毂速度波动误差限度
Err083 保留 Err084 保留 Err085 保留 Err086 保留 Err087 保留

专用空调的报警、故障分析及检修

专用空调的报警、故障分析及检修

专用空调的报警、故障分析及检修1.更换过滤器机组的回风过滤器应该是定期更换的,这个报警是提醒用户现在必须更换过滤器,当过滤器太脏时,空气经过过滤器的压力损耗就大,机组上的一个压力开关就会闭合而触发报警,开关压力可根据开关掣上的贴纸指示来调节。

2.压缩机过载保护装在压缩机内的安全开关,当压缩机过载时会断开,使压缩机停止工作。

每台压缩机都装有三相过载保护器。

压缩机过载报警后,视不同类型而定,可以手动复位或自动复位。

过载保护装置都被安装在压缩机的接线盒里。

3.用户报警用户报警文本可通过程序在液晶显示屏上设置,这种用户报警可以在订货时由用户指定,而附加装置和导线等需要预先安装,报警文本可以被编入按英文字母顺序排列的报警清单中,或由用户自己设定。

如果由用户自动设定,那么必须告诉用户的维修人员有关的报警功能和正确的操作方法。

4.高压保护机组的每台压缩机上均装有一个压力开关,用来监察压缩机的排气压力,当排气压力大于高压设定值时,压力开关会使压缩机的继电接触器离开,并发出一个输入信号给控制系统。

当报警发生后,可以按面板上的键来消除报警声,但必须手动复位该压力开关去消除报警。

高压报警发生后,对于风冷式系统,应检查冷凝器的电源是否关掉,冷凝器的风机有否故障,压缩机的高压控制压力开关是否有故障,维修用的手动阀是否关闭,冷凝器盘管是否脏堵,制冷剂管路是否堵塞,制冷剂是否过多等。

同时,还必须弄清当压缩机接触器吸合时,与其联动的冷凝器控制电动辅助触点是否有接合。

5.高低湿报警高低湿报警说明回风湿度已超过高低湿报警设定点。

检查所有设定点是否合适,检查制冷系统运作是否正常(制冷系统当除湿工作的)。

6.高低温报警该报警说明回风温度已超过了高低温报警设定点,这时应检查所有设定点是否合适,房间的热负荷是否超过了机组的能力(即配备的机组冷量是否太小),检查所有制冷部件的运行情况,包括压缩机和各种阀门等。

7.加湿器故障红外线加湿器:该报警是由安装在加湿水盘上的高水位浮球开关触发的,这个浮球开关是经常关闭的,打开后即报警。

RITTAL威图空调中文说明书

RITTAL威图空调中文说明书

RITTAL威图空调中文说明书随着现代科技的发展,各行各业都需要使用大量的电子设备来支撑日常工作。

在这些设备中,空调是必不可少的一种辅助设备。

它可以有效的降温,保持设备的稳定运行。

而在空调厂家中,RITTAL威图空调是备受大家推崇的品牌之一。

由于RITTAL威图空调的使用说明书全部是德文的,不熟悉德文的使用者想要自主维护和操作是很困难的。

因此,这个时候中文版的RITTAL威图空调说明书就变得尤为重要。

一、RITTAL威图空调产品介绍RITTAL威图空调是一种高效、节能的冷却设备。

它采用先进的制冷技术,能够在较短的时间内将设备温度快速降低至合适的运行温度范围。

此外,RITTAL威图空调还具有多项优良特性,如智能控制、噪音小、运行平稳等。

在智能控制方面,RITTAL威图空调还配备了多个传感器,不仅能够准确测量室内温度和湿度,还能够对各种运行参数进行自动调整。

二、RITTAL威图空调中文说明书概述RITTAL威图空调的中文说明书本着“易懂、易用”原则进行编写,内容全面、详尽。

该说明书主要分为以下几个部分:1. 产品概述:该部分介绍了RITTAL威图空调的各项性能及技术指标,如制冷制热能力、工作电源、温度控制范围等。

2. 安装使用说明:该部分详细描述了RITTAL威图空调的安装及使用方法,包括了室内外机的组装、电源接线、布线等重要步骤。

同时还有各种常见问题的解答。

3. 维护保养说明:该部分详细介绍了RITTAL威图空调的日常维护保养方法,包括了清洗过滤网、更换制冷剂、定期检修等内容。

同时还介绍了常见故障及解决方法。

4. 特殊功能介绍:该部分对RITTAL威图空调一些特殊功用的实现方法进行了介绍,如定时开关机、智能温度调节等。

5. 附录:该部分包含了各种重要的安全提示、通用电气设备符号表及布线图等内容。

还包括了RITTAL威图空调在不同温度条件下的性能变化曲线、机器外观图等。

三、为什么需要中文版的RITTAL威图空调说明书由于RITTAL威图空调的使用说明书全部为德文,加上里面所需的专业术语较多,对于普通用户而言,阅读起来会感到非常困难。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

开路或者短路
A17
相位监视

不正确的相位/缺相
A18
EPPOM 错误
A19
LAN/主从机
主从机没有连接
A20
电压下降
故障显示没有说明
E0
信号显示
连接问题(显示和控制板) 电缆故障或插座连接松动
故障显示A03,A06,和A07,手动重新设置。要这样做,请同时按上下踺5秒钟。
清洁或在必要时更换 清洁或在必要时更换 空调能独立启动 由制冷工程师更换 更换 更换 更换 更换 更换 更换两相
设置或检查连接电缆 结果被储存在日志文件中 通过开关电源重新进行设置 电路板的更换
检查冷凝水排放;必要时修理软管中的异物
A09
冷凝风扇
卡死或者坏了
A10
蒸发风扇
卡死或者坏了
A11
压缩机
压缩机过载(内部线圈保护)
压缩机坏掉(通过测量线圈阻值)
A12
冷凝器温度传感器
开路或者短路
A13
周围环境温度传感器
开路或者短路
A14
冰点温度传感器
开路或者短路
A15
冷凝物温度警告
开路或者短路
A16
内部温度传感器
A05
结冰
根据操作模式,结冰显示
增加柜内问地的正常值
周围环境温度太高
空调高压超过限制
冷凝器脏
清洗
A06
PSA(高压开关)监视器
冷凝滤网脏 冷凝风扇坏
清洗或者更换 更换
膨胀阀坏
由制冷工程师维修
PSA(高压开关)监视器坏
有制冷工程师更换
A07
蒸发器
冷却故障
由制冷工程师维修
A08
冷凝水报警
空调只有内部分冷凝物蒸发
控制显示屏及系统分析
报警号
系统消息
引起原因
诊断方法
A01
打开柜门
开关门位置不正确
检查门的转换位置,如必要,检查连接状况
A02
柜内温度太高
制冷能力太低或者较小空调的顺序错误消息从A03 到A07
检查制冷能力
A03
过滤监视
过滤网脏
清洗或者更换
A04
周围温度太高/太低
周围环境温度允许范围(10℃到60℃
提升或者降低周围温度(例如:加热或者使房间通风