机柜空调说明书
艾默生DTS8000E50 60Hz系列外挂式机柜空调操作及使用说明书

1 手册提示 (7)2 搬运 (7)2.1 运输 (7)2.2 储运 (7)2.3 开箱 (7)3 供货范围 (8)4 一般信息 (8)5 铭牌 (8)6 安全 (9)7 功能 (9)7.1 配置与功能 (9)7.2 工作原理 (9)7.3 冷凝物 (10)8 技术规格书 (11)8.1电气原理图 (11)8.2备品备件 (13)8.3安装开孔 (14)8.4气流原理 (17)8.5技术参数 (18)9 安装 (25)9.1 概述 (25)9.2 安装工作 (25)9.3 电气连接 (26)10 运行条件 (26)11.2 操作显示器 (27)11.3启动自检模式 (27)11.4 门触点 (28)11.5 设备故障 (28)12 参数查看与设置 (28)13 清洁和维护 (29)13.1 清洁 (29)13.2 维护 (30)14 停止使用 (30)15 故障排除 (30)16 保障条款 (30)附表I (31)1 Hints on the manual (32)2 Handling (32)2.1 Transport (32)2.2 Storage (32)2.3 Unpacking (33)3 Scope of delivery and options (33)4 General Information (33)5 Name plate (33)6 Safety (34)7 Function (34)7.1 Function and configuration (34)7.2 Operating principles (35)8.1 Circuit Diagram (36)8.2 Spare parts (38)8.3 Installation Cut-out (39)8.4 Airflow principle (42)8.5 Technical Data (43)9 Installations (50)9.1 General (50)9.3 Electrical connection (51)10 Operating condition (52)11 Putting into operation and function (52)11.1 General remarks (52)11.2 Operation display (52)11.3 Start-up / Test mode (53)11.4 Door contact (53)11.5 Equipment fault (53)12 Parameters View and Settings (54)13 Cleaning and Maintenance (55)13.1 Cleaning (55)13.2 Maintenance (55)14 When not in used (55)15 Trouble shooting (56)16 Warranty Conditions (56)Appendix I (57)1 手册提示此手册为百能堡电气科技有限公司(以下简称百能堡)提供的门装或侧装螺栓固定,外挂式机柜空调系列的安装运行指南。
whk330机柜空调设置说明

whk330机柜空调设置说明WHK330机柜空调设置说明一、前言WHK330机柜空调是一款专为机房环境设计的空调设备,具有多种功能和设置选项。
本文将详细介绍WHK330机柜空调的设置方法和注意事项,帮助用户更好地使用该设备。
二、基本参数1. 适用范围:19英寸标准机柜;2. 制冷量:3300W;3. 电源:AC220V/50Hz;4. 控制方式:智能化微电脑控制;5. 工作温度范围:18℃~30℃。
三、安装与连接1. 安装位置应选择通风良好、干燥、无尘、无腐蚀性气体和强电磁干扰的场所;2. 确认电源符合要求,接地可靠;3. 确认输入电压与设备标识一致;4. 连接排水管道,排放水箱内积累的水分。
四、开机前准备1. 检查散热器是否有异物或灰尘堵塞;2. 检查进出风口是否畅通;3. 确认冷媒充足。
五、开机操作1. 打开总电源开关;2. 按下机柜空调面板上的“电源”键,机柜空调开始运行;3. 设置温度:按下面板上的“温度+”或“温度-”键,设置所需温度;4. 设置风速:按下面板上的“风速”键,选择所需风速。
六、高级设置1. 定时开关机:按下面板上的“定时”键,可以设置定时开关机时间;2. 睡眠模式:按下面板上的“睡眠”键,可以进入睡眠模式;3. 静音模式:按下面板上的“静音”键,可以进入静音模式;4. 自动清洁功能:长时间使用后,按下面板上的“自清洁”键,可以启动自动清洁功能。
七、注意事项1. 请勿将手插入机柜空调内部维修或清洁;2. 请勿在潮湿环境中使用本产品;3. 请勿在直射阳光照射下使用本产品;4. 请勿将易燃物品放置在机柜空调附近。
八、维护保养1. 定期清洗散热器和过滤网;2. 定期检查冷媒压力和冷媒充足情况;3. 定期检查电源线和接线是否松动;4. 定期检查排水管道是否畅通。
九、结语WHK330机柜空调是一款高效、智能的机房空调设备,使用前请仔细阅读本说明书,并按照要求进行设置和操作,以确保设备正常运行和使用寿命。
机柜空调使用说明书(RA-900W电子版)

图三
冷气机
电 控 箱
冷气机
图四
电控箱
错误
正确
-2-
错误
正确
泠逸工业制冷·安装使用说明书
机柜空调
2、安装方法 (1)当机组在搬运、装卸时,请始终保持设备处于垂直直立状态,不要将设备长期放在露天场所; (2)为使空调器的冷却效果最佳,请将机组直接安装在电气柜的外壁上或顶上(根据用户所选机型来决定), 请勿采用风管的形式进行送风,如若确实需要采用风管送风,请先咨询本公司技术工程师; (3)空调器在安装之前,请先确认好安装位置的强度是否能承载机组,以免造成人员受伤及设备损坏,当 安装在电气柜门上时,最好该扇箱门能固定不动,当需要打开时请先确认好加在门上的重量不会使整个电 气柜倾倒; (4)电气柜上必须开孔,以便使冷风能进入电控箱内,具体的开口尺寸请参见图五; (5)箱体开孔时请严格参照开口尺寸进行,孔口处的毛刺必须清除,以免划伤机组; (6)当长期使用时请注意安装螺栓是否损坏或脱落,若有而未加处理,将有可能导致机器掉落而损坏; (7)侧装式机柜空调的安装方式见下页图; (8)RA-900W 机柜空调安装开孔图见附页图纸;
-6-
泠逸工业制冷·安装使用说明书
机柜空调
菜单设置选项 回差设定 压缩机延时 温度设置下限 温度设置上限 模式选择 温度校正
山特精密空调一体机架空调用户手册说明书

客服热线:400-830-3938/800-830-3938Rack Type Air Conditioner User Manual 一体机架空调用户手册产品防伪为了切实保障您的用电安全,帮助您购买到真正的山特精密空调,请注意以下事项:1. 认准山特注册商标:、、、、。
2. 山特所有产品机身上均贴有“产品序列号”(产品序列号是唯一的,一个产品对应一个序列号);如果您购买到有疑问的山特产品,可通过以下途径向本公司反馈1.客服热线:400-830-3938/800-830-39382.品牌保护邮箱:*************************版权声明山特公司致力于技术创新,不断提供更好的产品和服务满足客户需求,对产品设计、技术规格的更新,恕不另行通知。
产品以实物为准。
请到山特网站w 下载最新版的产品说明书。
版权所有© 2020山特电子(深圳)有限公司1.1F OREWORD (1)1.2A IR CONDITIONER DESCRIPTION (1)1.2.1Principles of function (1)1.2.2Operating Conditions (1)1.3S TANDARDS (2)2.SAFETY NOTICES (2)3.INSTALLATION AND OPERATION (2)3.1M ECHANICAL INSTALLATION (2)3.2E LECTRICAL INSTALLATION (3)3.3P OWER-ON STEPS (4)4.SYSTEM FUNCTION INTRODUCTION4 4.1C OOLING (4)4.2H EATING (O PTION) (5)4.3D OOR ALARM (5)4.4C OMPONENT CONTROL MODE (5)4.5U NIT SEQUENCING CONTROL (OPTION) (5)4.5.1T IME S WITCHING (5)4.5.2T EMPERATURE SWITCH (5)4.5.3B OTH WORKING WITH HIGH TEMPERATURE (5)4.5.4D ISTURBANCE SWITCHING (5)4.6S ELF TESTING (6)4.7H YDROGEN DISCHARGING/EMERGENCY FAN (OPTION) (6)4.8A LARM (6)4.9U NIT MENU STRUCTURE (7)4.9.1Operation interface (7)4.9.2Menu structure (7)5.MAINTENANCE (8)5.1D AILY MAINTENANCE (8)5.2C OMPRESSOR MAINTENANCE (8)5.3C OMMON FAULT (9)1.简介 (15)1.1前言 (15)1.2空调器描述 (15)1.2.1工作原理 (15)1.2.2运行条件 (15)1.3符合标准 (16)2.安全注意事项 (16)3.安装和操作 (17)3.1空调器机械安装 (17)3.2电气安装 (17)3.3开机步骤 (18)4.系统功能介绍 (18)4.1制冷功能 (19)4.2制热功能(选配) (19)4.3门禁功能 (19)4.4器件控制模式 (19)4.5双机切换控制(选配) (19)4.5.1定时切换 (19)4.5.2温度切换 (19)4.5.3高温同开 (19)4.5.4故障切换 (20)4.6自测 (20)4.7排氢/应急风扇(选配) (20)4.8故障 (20)4.9机组菜单结构 (21)4.9.1操作界面 (21)4.9.2菜单结构 (21)5.维护 (22)5.1日常维护表 (22)日常维护表 (22)5.2压缩机维护 (22)5.3故障及恢复措施 (23)常见故障及恢复措施 . E RROR!B OOKMARK NOT DEFINED.6.产品有毒有害物质申明 (29)附录1.维修保证 (30)附录2.合格证 (31)Introduction1.1 ForewordNote: All of the operations of this product shall be performed by professional engineers and technicians.This manual can only be used to guide the installation and operation of EF series of industry cabinet air-conditioners. The manual content includes the functional description and regular maintenance of the unit. In this manual, the safety tips and warning signs are described as follows:DANGER!If the measures described in the following are not strictly observed there is danger to life and health.HAZARD!If the measures described in the following are not strictly observed there is danger to life and health due to electrical shock.CAUTION!If the measures described in the following are not strictly observed material damage may be caused.1.2 Air conditioner descriptionThe EF series outdoor cabinet air conditioner is a cooling product developed for cabinet. This air conditioner’s frequency can be regulated. It has cooling capacity regulating function, and the fans can regulate speed automatically.Function Diagram 1.2.1 Principles of functionThe refrigerant is compressed by compressor (1) into high temperature and high pressure gas; To the condenser (3), and suctioned by the cooling fan (2) from the bottom part into outdoor air, where the heat is forced through the condenser (3) to spread to the surrounding environment in the air, and the refrigerant becomes into a liquid through the throttling element (4), the refrigerant pressure drops, and in the evaporator (6), the refrigerant absorbs the heat inside the control cabinet and evaporates; The hot air is suctioned by the evaporation fan (5) from inside the control cabinet, and through the evaporator, the air is cool and forced to discharge into the inside of the control cabinet. At the same time, the air inside the control cabinet is dehumidified.This series can be used a variety of installations.This is shown in the pictures below:Working Principle Diagram1.2.2 Operating Conditions⚫Power system220VAC±15%,50/60Hz⚫External cycle temperature:-40℃~ 50℃Note: Please read the nameplate parameters on the air conditioner carefully. The actual technicalparameters shall be subject to the nameplate name.1.3 StandardsStandard DescriptionGB/T17626.7-1998EMCGB4706.1Safety of household appliances or similar electric applianceGB4798.1Environmental conditions existing in the application of electric and electronic product –StorageGB4798.2Environmental conditions existing in the application of electric and electronic product –TransportationGB4798.3Environmental conditions existing in the application of electric and electronic product –Use2. Safety noticesThe following safety notices are to be observed in their entirety for the correct use of the equipment: 2.1 Transport⚫Keep the air conditioner in a horizontal state during transportation.⚫If the cabinet needs to be transported, please remove the air conditioner and pack itseparately before transportation.2.2 Storage⚫Storage environment should not exceed 70 °. ⚫Keep the air conditioner in a horizontal state during storage.2.3 Unpacking⚫Prior to and during unpacking make a visual inspection of the air conditioner to seewhether any damage has occurred duringtransport. Especially pay attention to looseparts,dents,visible loss of oil etc.⚫Any damage mast be reported immediately to the forwarding agent (follow the instructionsin“Rules For Damage Claims”).Moreover,thelatest ed ition of the “After sales Service Letterof Commitment”⚫Before disposing of packing material ensure that it does not contain any loose components.2.4 Installation ⚫The site for the enclosure, and hence the arrangement of the air conditioner, is selected so as to ensure good ventilation;⚫The location is free from excessive dirt and moisture;⚫The ambient temperature does not exceed +45℃;⚫The enclosure is sealed on all sides(IP54).Condensation will occur if the enclosure isleakage;⚫Air inlet and outlet are not obstructed on the inside of the enclosure;⚫The duct size outside the air conditioner cabinet should not be less than the limit value in the following figure.⚫Units are only fitted horizontally in thespecified position.Max. Deviation from the true horizontal:2°;⚫Losses from the components installed in the enclosure must not exceed the specificrefrigeration capacity of the air conditioneritself;⚫The customer must not modify the airconditioner in any way.Distance Diagram3. Installation and Operation3.1 Mechanical installationBefore the installation of air conditioner, the fitting surface of cabinet shall be properly opened withvent and screw hole, where the hole size shall refer to the appearance size figure as provided by the manufacturer.CAUTION!If the required cutouts are only made in the switch cabinet just before mounting of the air conditioner, make sure that swarf is not allowed to enter the device hood by using a cover sheet. Mounting:1) Insert the air conditioner into the cabinet alongthe guide rail direction.2) The installation flange of the air conditionerand the installation surface inside the cabinetare fixed, as shown in the figure below:Installation Diagram3.2 Electrical installationCAUTION!As the cabinet air conditioner is connected to the power supply via the circuit protection device, the appropriate circuit protection device and the power cable should be chosen according to the air conditioning nameplate and technical parameters.CAUTION!Too high voltage may lead to damage of cabinet air conditioner. Please follow the voltage requirement marked on the nameplate to switch on the air conditioner.CAUTION!In order to avoid any damaging effects, before turning on the power supply, the cabinet air conditioner must be reliably earthed.Note: The power input port identifier is subject to the specific unit screenprintingReferences to common (copper wire) selection: RatedCurrent≤5A≤10A≤15A≤25A Power linediameter1.0mm1.5mm2.5mm4mmConnecting interface (The power input terminal will be subject to application instructions)Connecting interface:Port DefinitionPowerinputL1/LL:220VAC power input cable L;L1:110VAC power input cable L L2/NN:220VAC power input cable N;L2:110VAC power input cable L PEGrounding wire of the airconditionerAlarm outputNC The first public alarm dry nod (NC) COMThe first public alarm dry nod(COM)NOThe first public alarm dry nod(NO)(Option)1The second public alarm dry nod(COM)(Option)2The second public alarm dry nod(NO) (Option)Signal input 3 N/A4Hydrogen discharge / emergencyfan dry contact (FG) (Option)5Hydrogen discharge / emergencyfan dry contact (NO) (Option)6Hydrogen discharge / emergencyfan dry contact (COM) (Option) 7Door open alarm input (option)8comm unicati on ports +RS485 communication ports (+)(Option)-RS485 communication ports (-)(Option)⚫Alarm output (option):The unit provides alarm output dry contact. Ifthere is no alarm, the dry contact is close.When there is alarm, the dry contact will open.Contact capacity: resistive load5A@30VDC/5A@250VAC.⚫Hydrogen discharge / emergency fan electricity connecting.(option):Note: Contact capacity: max load 2A@-48VDC; 8A@230VAC.➢Hydrogen discharge / emergency fan(AC input) connecting interface diagram;AC input connecting interface diagram➢Hydrogen discharge / emergency fan(DC input) connecting interface diagram;DC input connecting interface diagramDC input connecting interface diagram(FG:optional)3.3 Power-on stepsFirstly make sure the AC voltage is in accordance with the standard, and then close the power input switch. 30s later the internal cycle fan of the unit will be started. After delay time about 3min, the unit select operation mode according to the unit’s. 4. System function introductionAir conditioner running is automatically controlled completely according to the temperature inside the cabinet, and through the inner loop temperature sensor, the controller detects the cabinet return air temperature and the set point for judgment, to control the work of compressor or the fan.4.1 CoolingCooling stop point=cooling start point-cooling sensitivity. When the cabinet internal temperature exceeds the cooling start-up point, the cooling will be started; when the cabinet internal temperature is lower than the cooling stop point, the cooling Parameter Default value Setting rangeCoolSP 25℃[15~50]Cool△T 5℃[1~10]INHT 65℃[20~80]stops.Setting point description:CoolSP:Point when cooling starts.Cool△T:Temperature control sensitivity.INHT:Internal high Temp. alarm point.CAUTION!For the reliable operation of the unit and the maximum energy efficiency, it is recommended that the users should not randomly change the temperature set point. The above set point is not on behalf of the factory settings.4.2 Heating (Option)Heating stop point=heating point+heating sensitivity. When the temperature inside the cabinet is lower than the heating start-up point, the heating will start; when the temperature inside the cabinet is higher than the heating stop point, the heating will stop.Parameters Default value Setting range HeatSP 0℃[-5~15]Heat△T 10℃[1~15]Setting point description:HeatSP:Point when heating starts.Cool△T:Temperature control sensitivity.CAUTION!For the reliable operation of the unit and the maximum energy efficiency, it is recommended that the users should not randomly change the temperature set point. The above set point is not on behalf of the factory settings.4.3 Door alarmTo avoid an increase in condensation, a door operated switch should be used which will switch the air conditioner off when the switch the air conditioner off when the enclosure door is opened. After judging whether the cabinet door is opening or not by the sign sent by the door magnetic switch ,the air conditioner will alarm and stop. CAUTION:When door opened, the door magnetic switch will be triggered to shut down the air conditioner after one minute. After door closed, the door magnetic switch will be released, then the air conditioner will start work after three minutes when the temperature inside is higher than the set point.4.4 Component control mode1) Control modern of internal fan:The inner fan runs in normal speed when system runs normally.2) Control mode of external fan:Air circulation mode: The external fan stops.Cooling mode:The external fan’s running speed depends on the condenser’s temperature. The higher the temperature is, the higher the fan speed is; the lower the temperature is, the lower the fan speed is.3) Control mode of compressor:Air circulation mode: Compressor stops.Cooling mode: The compressor’s running speed depends on the temperature differences between return air and setting value. The higher the difference is, the higher the compressor speed is; the lower the difference is, the lower the compressor speed is.4.5 Unit sequencing control(option)The equipment has linkage function including time switching, disturbance switching, high temperature switching.4.5.1 Time SwitchingTwo air conditioners switch as setting time.4.5.2 Temperature switch1) When cabinet temp reach the setting point cooling point only one air-con will work. When temp lower than cooling stop point, the air-con stops working.2) When cabinet temp reach the setting point high temp point, two air-cons will work together. When temp lower than (high temp point - sensitivity), one air-con stops working, only one air-con will work alone.4.5.3 Both working with hightemperatureWhen one appears high temperature alarm, the other will work at the same time. If high temperature alarm is cleared, one air conditioner will be closed, it will recover to time and temperature switching status.4.5.4 Disturbance switching1) When one air conditioner has a problem, the other will start immediately.2) If the fault that is come up in the switching time is cleared, it do not switch to other until time switch is finished.3) If the fault is not cleared, the other will work all the time.4.6 Self testingThe unit provides the self testing function for on site test and it will automatically goes to self-testing procedure if choosing self-testing function in the system function menu, the procedures are as below:1) If the compressor doesn’t stop, stop thecompressor.2) The internal fan runs for 60 seconds.3) The external fan runs for 60 seconds.4) The compressor runs for 60 seconds with lowlimit speed, meanwhile the external fan runs with 50% full speed.5) The compressor runs for 60 seconds withupper limit speed, meanwhile the external fan runs with full speed.6) If configured with heater, starts heater andruns for 120s.7) If configured with hydrogen discharging fan,starts the fan and runs for 120s.8) The compressor, internal fan & external fan,electric heater, hydrogen discharging fan stops.9) Self-testing procedures finished, the unit worksaccording to the normal logic.4.7 Hydrogendischarging/emergency fan(option)Discharge hydrogen at regular times: according to the requirement for environment inside the cabinet, the hydrogen discharging fan realizes automatic cycle hydrogen discharging and forced ventilation. The interval time of each automatic cycle hydrogen discharging is 24 hours and the discharging time is 5 minutes.2) Forced ventilation:when the compressor does not have cooling capacity (including compressor failure, power failure), the temperature inside the cabinet is higher than the start up point (emergency point + sensitivity) of emergency fan , start the emergency fan.4.8 AlarmThe cabinet air conditioner provides the following alarm information. Please refer to table for the setting point.Diagram for alarm triggeredIf the alarm hasn’t been recovered, t he alarm information will be still on, until the alarm has been eliminated. And you can check the alarm statistics through entering the alarm menu shown as Figure.Sensor Failure4.9 Unit menu structure4.9.1 Operation interfaceThe unit controller adopts the 96x32 LCD, which contains 7 buttons for the setting. The operation interface is as shown in the following figure:ON/OFF:ON/OFF button (press the button 5s), this can be used to turn on/off the unit.: Up button, which is used to increase the setting value or select the previous record/menu.: Down button, which is used to decrease the setting value or select the next record/menu. 4.9.2 Menu structure: Left button, which is used to select the previous bit of the data.: Right button, which is used to select the next bit of the data.ENTER: ENTER button, which is used to confirm the entry.ESC: Quit button, which is used to return to the previous page menu.If there is no keyboard operation for consecutively 60s under any interface after start-up, it will automatically return to the normal display interface. When any button is pressed after the system is powered up, the backlight will turn on. If there is no keyboard operation for consecutively 60s, the backlight will be off.The factory default operation password of the unit is “0001”. To change it, you need to press ENTER on the normal display interface to enter the password input interface, press the LEFT button or RIGHT button to select the bits for change, and press the UP/DOWN button to change the relevant digits, and finally press ENTER button to confirm the change. If the password is incorrect, the interface will display the error message, and the unit setting cannot be changed. If the password is correct, you can enter the main menu and edit the unit setting.Remarks:InT: Internal return temperature sensorTp: Evaporator coil temperature sensorTe: Compressor exhaust pipetemperature sensorCond: Condenser coil temperaturesensorUnit menu structureNote: This diagram is unit menu structure, not the real factory setting.中文EnglishON/OFF ENTER ESC5. MaintenanceTo ensure the normal operation of the airconditioner, please perform regular maintenance for it by referring to Table 5.1.Hazard!All the maintenance should be performed by qualified professionals. Please disconnect thepower and communication & alarm output cables of the air conditioner before any maintenance and do not reconnect them until the maintenance is completed.5.1 Daily maintenanceDaily maintenance table5.2 Compressor maintenanceWhen the compressor is faulted, the solution is replaced with new unit.DISPOSAL :Do not dispose this product as unsorted municipal waste. Collection of such waste separately for special treatment is necessary.City Trash CanCheck item Step descriptionMaintenance cycle Wiring Visually check if the wiring is looseOne year Fan abnormalities Turn the fan to check if it is smooth and if there is any abnormal noiseOne year Drainage pipe Visually check if the drainage mouth is blockedSix monthsCondenser Check the cleanness of the condenser and clean it with compressed airSix monthsFilterCheck visually and clean. If there is dustaccumulation, it can be blown or washed and driedSix months5.3 Common faultCommon fault and recovery measure.can not work5.4 Charge RefrigerantUnits sold outside mainland China do not contain refrigerant. Please refer to the following operations to charge refrigerant on site.1 Tools PreparationTable 5-1Tools preparationTool Illustration FunctionScrewdriver ⚫Dedicated screwdriver is used to remove the anti-theft screws.⚫Flat-blade screwdriver is used to remove the connecting wire from the controller.⚫Phillips screwdriver is used to remove screws from other parts.Diagonal pliers Used to process cables on site and remove the fixed cable ties. Portable vacuumpumpUsed to vacuum on site.Pressure gauge Used to monitor system pressure, maintain pressure, and charge refrigerant for use.Refrigerant R410A refrigerant.Electronic scale Used to charge refrigerant and monitor the weight of the refrigerant charged. Protective gloves Wear gloves when charging refrigerant and vacuuming.Goggles Used to protect the eyes.2 Disassemble the Unit⚫Figure 5-1Disassemble the unitStep 1 Use a small flat-blade screwdriver to remove the air conditioner power cables (L,N, PE). See A in Error! Reference source not found..Step 2 Use a small flat-blade screwdriver to remove the air conditioner signal lines(RS485+, RS485-). See B in Error! Reference source not found..Step 3 Remove the signal line fixed buckles and the drainage pipe binding ties. See C in Error! Reference source not found..Step 4 Open the front door of the cabinet and use a Phillips screwdriver to remove thefour installation screws of the air conditioner. See D in Error! Reference sourcenot found..Step 5 Grasp the two handles on the front panel of the air conditioner and slowly pull out the air conditioner. See E in Error! Reference source not found..Step 6 Use a flat-blade screwdriver to remove the screws of the upper cover and remove the upper cover. Find the refrigerant charging port, as shown in F in Error!Reference source not found..CAUTIONThe charging port is divided into a high-pressure charging port and a low-pressure charging port, and therefrigerant is charged from the low-pressure port. See G in Error! Reference source not found..3 Charge RefrigerantStep 1 Connect the vacuum pump.Use a pressure gauge to connect the high-pressure charging port (red pipe) and low-pressure charging port (blue pipe) of the air conditioner, and the middle pipe is connected to the vacuum pump.⚫Figure 5-2Connect to the vacuum pump(1) Low pressure gauge (2) High pressure gauge (3) Zero adjustment screw(4) Low pressure valve (5) Sight window (6) High pressure valve(7) Low pressure side interface (8) High pressure side interface (9) Vacuum pump or refrigerantinterfaceStep 2 Use a vacuum pump to vacuum the refrigeration system.After confirming that the pipeline connection is completed, turn on the vacuum pump to start vacuuming. Thevacuum degree of the system is required to be below 35Pa.⚫Figure 5-3Power on the vacuum pumpStep 3 Maintain pressure on the system.After the vacuum is completed, power off the vacuum pump, close all the pressure gauges and tighten theconnection between the pressure gauge and the vacuum pump. Keep the pressure of the system for 20-30 minutes and observe whether the pointer of the pressure gauge does not move. If the value of the pressure gauge needleremains unchanged (maintained at -0.1MPa), it proves that the system is well sealed and can be filled withrefrigerant.⚫Figure 5-4Maintain pressureStep 4 Refrigerant charge.After the system pressure is maintained, remove the vacuum pump from the pipeline, and connect the pipeline to the refrigerant tank to charge the refrigerant.1. Move the gas pipe connecting the vacuum pump to the refrigerant tank and tighten it, thenloosen the connection of the middle pipe of the pressure gauge by 4-5 turns.⚫Figure 5-5Connect to the refrigerant tank2. Turn on the switch of the refrigerant tank, let the gas pour into the pipe and rush out from theconnection. The process lasts for about 10 seconds, and then tighten the pressure gaugeconnection so that the air in the pipe is discharged to the outside.3. After exhausting the air from the pipeline, the refrigerant charge is started. Please turn therefrigerant tank upside down when charging, and you must use an electronic scale to ensurethe quality of the refrigerant charged.⚫Figure 5-6Charge refrigerant4. After the refrigerant charging is completed, close the valve on the low pressure port side of thepressure gauge, do not remove the pipeline connection for the time being, and perform thepower-on operation and refrigeration operation.⚫Figure 5-7Close the low pressure charging value4 Power On and Test the Air ConditionerPower on the unit and adjust the cooling point of the unit to below the temperature detected by the indoor sensor. Run the unit for half an hour to see if the cooling of the unit is operating normally.⚫When the ambient temperature reaches the cooling point of the air conditioner, the air conditioner will automatically enter the cooling state when the air conditioner ispowered on for 3 minutes.⚫If the ambient temperature does not meet the cooling conditions, you can turn on the load to make the air conditioner enter the cooling state.After the unit is operating normally, quickly remove the high and low pressure connections. A small amount of refrigerant will be sprayed out during the dismantling process, which is normal. Screw the bonnet back to complete the refrigerant charging.⚫Figure 5-8Remove the refrigerant charging port connection5 Reinstall the Air Conditioner Into the CabinetLift the air conditioner and slowly push it into the cabinet from the front, avoiding the air conditioner limit blocks on the left and right sides of the cabinet until the mounting flange is close to the cabinet column, and then install the air conditioner in the reverse order according to 2 Disassemble the Unit.1. 简介1.1 前言注意:任何针对本产品的操作必须由专业的工程技术人员进行。
HCc机柜空调用户手册-Mini

机柜空调HCc-Mini系列用户手册感谢您购买本产品使用空调前请先阅读使用说明书•本说明书中讲述产品的使用方法及使用的注意事项。
•请将说明书妥善保存,以便必要时查阅。
•如将本商品交给第三者使用时请将说明书一同交付给第三方。
版权所有• 不得翻印重要警告◆错误使用时,会引起危险情况,可能会导致设备损坏。
◆本设备输入电源为220VAC/50Hz或48VDC,接线时请按设备铭牌标示选择接入电源。
◆接线时,请确认电源输入是否处于OFF状态。
◆接线时,切忌将输入电源等接错,否则可能会导致设备损坏。
◆接线时,请使用符合技术规格的线缆。
◆接线时,请使用适当的螺丝刀,过大或过小的螺丝刀都容易导致接插件内部螺丝头损坏。
◆运行前,请确认接线无误后,方可接入电源。
◆运行时,请确认内外循环的进出风口是否通畅。
◆用户若有任何修理的需要,请与厂家联系,在专业技术人员的指导下进行检修。
◆切忌拉扯、扭曲温度传感器、电源线及通讯线,以免产生严重故障。
◆若因控制系统软件存在缺陷而造成的后果,本公司有权利修复缺陷,但没义务承担任何责任。
◆本设备自出厂之日算起,质保期为12个月;若因使用不当而造成的后果,不在质保之列。
◆本设备进出风口、安装尺寸等相关参数,若有改动,恕不另行通知。
目录1产品简介 (3)2空调器结构 (4)3性能参数 (4)4机柜空调的选型方法 (4)5空调器的安装 (5)6空调器控制面板操作说明 (8)7制冷系统 (8)8运行 (9)9故障和处理 (10)10注意事项 (10)11装箱清单 (10)12保修条款 (10)13售后维护与保养 (11)14附注 (11)1 产品简介机柜空调器是通过压缩式制冷来实现吸热制冷的,在机柜密闭的环境下将机柜内设备发出的热量转移到机柜外面。
机柜外面的高温、粉尘等污浊气体不会进入到机柜内部,从而解决了风扇散热所带来的一系列问题。
机柜内部可以始终维持在30℃左右的一个理想温度环境,使电子设备的稳定性得到有效的保证。
海尔 KFR-72LW 06KAP81U1 美悦 3匹柜式变频空调 使用说明书

维 修 板
右
连接管安装提示
1.连接管锥口对准相应阀门接头锥面。
2.用力拧紧连接管螺母,然后用扳手拧紧。
3.拧紧后用防护套件锁紧接头。
根据空调标准GB4706.32要求,
室内侧喇叭口不允许重复使用,如需进 空调室内机采用不可重复使用的
行二次连接时,必须重新加工喇叭口。 连接头,其安装方法与普通连接
室内侧联机后必须加装防护套件,填充 头一样。但是,该连接头一旦被
4.电源线型号:50 机型为RVV,72机型为YZW。 参数:50机型2.5mm2或以上,72机型4.0mm2或以上。 连机线型号:YZW 参数:50机型为4x1.5mm2 或以上;
72机型为4x2.5mm 2 或以上;
接线方法
1.端子的接线方法:
松开接线螺丝,将连机线端子插到端子排和接线螺丝之间,然后拧紧
机线,请用户监督配合。
安装说明
◆ 室内机安装
1.穿墙孔的定位
根据选择的室内机安装位置和管路走向,确定打穿墙孔
的位置。
室内侧
室外侧
2.打穿墙孔
穿墙孔
打一个穿墙孔,外侧稍微向下倾斜。
墙的厚度
室外机安装
(穿墙孔侧视图) 590
安装固定
先将安装支架牢牢固定在墙面上,
以防强风侵袭。固定支架的膨胀
890
螺栓规格要一致,数量≥6个, 直径≥12mm。再把室外机紧固 在支架上,并保持水平。
此框内由厂家印说明书专用号一维码(厂 家生成),宽51*高12mm。此绿框仅用 于定位,实际印刷时删掉。
安装说明
电气安全要求
基本要求
1.电源一定要使用额定电压及空调器专用电路,空调器供电线路中必须 备有足够容量的漏电保护开关和空气开关,空气开关应同时具有磁脱扣 和热脱扣功能,以保证短路和过载都得到保护。需由获得电工资格的人 员,按国家标准规定的布线规则进行布线。 2.空调器可正常运转范围为额定电压220V的90%∽110%。电压过高 过低会影响制冷、制热效果以及寿命,也可能导致噪音过高。 3.空调器与可燃表面间的最小间隙为1.5米。 4.本机有电源线无插头,在固定线路中必须加一个断开装置,且是全极 断开,并触点断开距离至少为3mm。切不可将无插头的电源线,接上 插头直接使用。未随机配套隔离开关的机型,需用户自备漏电保护和空 气开关,空气开关30A以上。注:本机型无随机配套隔离开关。
黑盾机柜av600空调说明书

黑盾机柜av600空调说明书黑盾机柜av600空调说明书:“开/关”键:开关按键在待机时按下开机键就能使空调进入到运行状态,在开机之后,按下空调的关机键,空调就会进入到待机状态。
“模式”键:在进行操作时,按下空调的模式按键,按照“自动→制冷→除湿→送风→制热→自动”循环,就能让空调进入到相应的运行程序中。
“风速”键:能够调整空调内风机的风速,风速按照“自动→低风→中风→高风→自动”方式进行循环。
“风向”键:能够改变空调出风方向,空调导风片的角度选择按照“自动→位置[1]→位置[2]→位置[3]→位置[4]→位置[5]→自动”方式循环。
“摆风”键:按下摆风键,可以将空调摆风设置成连续摆动和点动摆动两种方式。
温度设置键:温度设置键有“温度▼”键、“温度▲”键两种,“温度▼”键设定时按一下温度下降一度,它的控制范围在:16℃—31℃;“温度▲”键按一下温度上升一度,它的控制范围在:16℃—31℃。
“睡眠”键:“睡眠”键按下后在显示器中显示睡眠模式的设定,在睡眠区域中会显示出符号,同时室内的风速也会转变为低风,8个小时之后睡眠结束,睡眠符号也会取消,空调又恢复到原来的风速进行运行。
在使用黑盾机柜av600空调说明书的时候,在空调遥控器上按下“功能”按键大相对应的上下扫风功能中,这时功能灯就会开始进行闪烁,再次按下了上下键之后,空调的指示等亮起就代表空调已经打开,指示灯灭就代表这一功能关闭。
在遥控器上的模式按键中用户可以选择相应的程序,空调的模式按键能够实现制冷、制热、自动、除湿等功能。
如果用户在按下了自动功能按键之后,空调就会自动进行温度、风速的调节,用户在关闭了空调的自动功能之后就能自己进行空调温度的上下调节了。
温度合适调节。
一般在使用空调的时候将空调温度设定合适就能有效的实现空调省电的目的,在夏季空调最佳的温度调节范围是在26℃-28℃,而冬季空调温度最佳调节范围实在18℃-22℃。
空调温度每增加一度,它的耗电量就会增加10%。
黑盾ac1000机柜空调操作说明书

黑盾ac1000机柜空调操作说明书黑盾AC1000机柜空调操作说明书一、产品介绍黑盾AC1000机柜空调是一款专为机房、数据中心等场所设计的高效节能空调设备。
该空调采用先进的制冷技术和智能控制系统,具备出色的制冷效果和稳定可靠的运行性能,能够确保机房设备的正常运行温度,保护设备的安全性和稳定性。
二、安装准备1. 确保机柜空调的安装位置符合要求,避免遮挡和堵塞;2. 检查机柜空调的供电电压和频率是否与现场电源匹配;3. 准备好所需的安装工具和配件,如螺丝刀、螺丝、密封胶等。
三、安装步骤1. 将机柜空调放置在安装位置上,确保底部与地面平整牢固;2. 使用螺丝刀固定机柜空调,确保其牢固稳定;3. 连接机柜空调的电源线,确保线路连接正确并牢固可靠;4. 将机柜空调的排水管连接到排水口,确保排水通畅;5. 安装完成后,检查各部件和连接是否牢固,排除安装过程中的问题。
四、使用方法1. 接通机柜空调的电源开关,待指示灯亮起后,空调即进入待机状态;2. 使用控制面板上的按钮或遥控器,选择所需的运行模式和参数;3. 根据需要设置温度、风速、定时等功能;4. 空调开始工作后,可以通过观察控制面板上的显示屏或遥控器上的指示灯来了解空调的工作状态;5. 使用过程中,定期清洁机柜空调的滤网,保持空调的通风畅通;6. 如遇突发情况或故障,应立即停止使用空调,并联系售后服务人员进行维修。
五、注意事项1. 在使用机柜空调之前,应阅读并理解本操作说明书,按照要求正确操作;2. 请勿将机柜空调安装在潮湿、尘土较多或温度过高的环境中;3. 请勿将机柜空调暴露在阳光直射或雨淋的环境中;4. 请勿将机柜空调插头插入不匹配的电源插座中;5. 请勿将机柜空调用于其他用途或改装;6. 请勿在机柜空调工作时随意拔插电源线,以免发生电击或其他安全事故;7. 如需进行维修或清洁,应先切断机柜空调的电源,确保安全;8. 请定期检查机柜空调的工作状态和运行效果,如发现异常应及时处理。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
品牌: 泰予
为什么选择泰予空调
1.优质售后服务,让您的采购无风险:
我们承诺:1 、因产品本身质量问题,用户自购机之日起可享受一年的保修;保修期内维修免费及包换全新机器,收到故障机器后一般故障在三个工作日内修复发回给客户,其它维修只收取零配件费用,不收取工时费。
保修期以外所出现的零配件损坏或故障,在更换及修复时,只收取零配件费用,不收取工时费.
2 、产品经维修后,六个月内因质量问题发生同一零配件损坏或故障时可免费更换或修复。
在接到用户报修电话后,收到故障机器后一般故障在三个工作日内修复发回给客户。
3、我们在全国多地设有维修服务点,无论您身处何地,不用担心产品出现问题不知所措。
2.优秀的产品性能
机柜空调C系列是一种专为电气柜内部恒温而设计的蒸汽压缩式工业空调。
该产品通过内外两个独立的空气循环把电气柜内部的空气冷却同时把柜内的热量通过热交换驱散出柜外,从而保护电气柜内的电气元件在可控的温度范围内运行,同时电气柜空调具有除湿功能,保证电气柜内部有理想的温度和湿度环境;在毛绒多、灰尘大、高温场合等特别适用。
机柜空调EA系列外形设计美观、紧凑、体型小、重量轻,维护简单,工作性能稳定,使用寿命长,应用范围广;
机柜空调EA系列整机通过采用微电脑温度控制器控制整机工作,数码显示柜内温度,加上配置的总路开关,打开电气柜柜门前可以很方便的停止空调的运作,同时更加方便了用户的使用及维护机柜空调EA系列采用环保耐高温R134压缩机,环保、节能、高效,在车间环境温度可高达60℃的情况下一样可以工作;
机柜空调EA系列采用高性能、工业级的风机,完全杜绝了柜内空气的短路,并提供最大的散热性;该风机自带特殊高温以及电流过载保护,大大提高使用寿命;
机柜空调EA系列采用独特的冷凝管理系统,能使冷凝水适时挥发;即当电气柜防护等级达到IP54的情况下空调无冷凝水排出,冷凝水在空调内部直接蒸发随外循环排出柜外;在电气柜密封不好或车间湿度特别大、空调蒸发不及的情况下空调冷凝水会从空调备用排水口全部排出柜外;
机柜空调EA系列还全部采用双保险的冷凝水收集装置,百分百地保证了空调冷凝水不会进入电气柜内部;
3.物美价廉:
在同等配置情况下,我们的产品价格更适合您!我们在生产环节有一流的技术沉淀优势,在量产的情况下,同样的高配置产品我们的供应商给予更优惠的价格,同时我们的销售情况要远高于兄弟品牌,因此我们有性价比更高的产品给到您!
4.同样情况下,我们的备货更充裕,一般情况下您付款后,我们就会积极响应,
在2个工作日内发货。
不用为我们的货耽误您项目的宝贵时间。
Product Features
·具有温度调节与去湿功能,保证电器控制柜内理想的温度与湿度;
·采用旋转式压缩机,可靠性高,能耗少;
·柜内空气与环境空气无空气交换,保证柜体内部清洁;
·选用大风量、高静压离心风机,循环风量大;
·合理的出、回风结构,避免空气循环短路;
·带有报警功能,实时监测空调器使用状况;
·体积小、重量轻,安装、使用、保养方便。
Product Advantage
·优质的零部件,电气柜空调器主要零部件均选用国内外知名品牌的产品,如压缩机选用上海日立电器,风机选用德国EBM;换热
器与钣金件委托国内知名空调器配套厂制造加工。
·先进的检测手段,采用德国莱宝卤素检漏仪对制冷系统检测,保证产品质量;澳柯玛成套制冷设备有限公司的高精度试验室,极
大的保证了电气柜空调器的性能。
·完善的服务体系,我司已与国内多家家用空调售后服务部合作,以确保客户能得到最及时,最周全的服务保障。
Application
现已被广泛应用于机床、数据处理、通讯、金融、冶金、石化、建材、汽车、军工等各个领域,目前国内的一些大型数据处理中心
及数控加工中心也已广泛使用。
电器柜空调的卓越功效及优良性能正在逐步被越来越多的国内外高端用户的高度认可。
Selection Formula
ΔT=To-Ti
Qr=5.5×A×ΔT
Qt=1.2×(Qi+Qr)
To 环境温度Ti 控制柜内温度
ΔT 控制柜外温差Qr 控制柜柜体传传热量
Qi 控制柜内产生的热量 A 控制柜表面积
Qt 所需制冷量
: Selection Example
控制柜表面积为8m2(A=8m2),环境温度为35℃(To=35℃),柜内
产生的总热量为150W欲使柜内温度保持为28℃,则电气柜空调
选择计
算方法如下:
ΔT=To-Ti=35-28=7℃
Qr=5.5×A×ΔT=5.5×8×7=308W
Qt=1.2×(Qi+Qr)=1.2×(180+308)=585.6W
则应选择EA-600
EA系列电柜空调产品特点:
1.具有温度调节和去湿功能,保证电器控制柜内理想的温度与湿度;
2.采用旋转式压缩机,可靠性高,能耗少;
3.电气柜与外界空气交换,保证柜体内部清洁;
4. 选用大风量、高静压离心风机,循环风量大,避免电气元件局部高温;
5.合理的出、回风结构,避免空气循环短路;
6.带有报警功能,实时监测空调器使用状况;
电柜空调特别说明:本系列产品均采用高效过滤网,大大提高产品抗油污防粉尘能力,切提供过滤网更换。
极大的延长了产品的使用寿命。
积小,重量轻,安装、使用、保养方便。
本公司竭诚与广大客户合作,一起迎接明天的辉煌!
型号EA-300A
测试工况:电柜内侧干球温度:35℃,湿球温度:26℃,电柜外侧干球温度:35℃
开孔尺寸:。