施耐德开关电源和变压器选型
施耐德断路器选型手册

!"#$%
!"#
(Ics = 100% Icu)
!
!"
!
Compact
NS
!
!"#
!
!"#$%&'() *+,-./0 Compact
!"#$%&'()*+",
!" #$%&'()*+,
!"#$%&'(
Compact NS
!
4
!"#$%&'()*+,
!"#$
!"#$%&'()*+,-(./01&2345678
1
041625
!"#$
Compact NS100... 630
041638
!"#$%&'( Compact
!
!"#$%&'()W
!
! !
!" TM
Compact NS100 - NS250
!"#$%
!"#$%&'(()*+,-./
Compact NS400 - NS630
!"#$%
!"#$%&
STR53UE
!"#$%&
Ui:
!"#
Uimp:
!"#
Icu:
!"#$%&'()*+,-./
(Ue)
cat:
!
Icw:
!"#
施耐德ABL2平板式开关电源

ABL2平板式开关电源
A A A A
A
A
A
输入电压
5H
88...264 V AC / 110...370 V DC
0H 88...264 V AC / 110...370 V DC
5H
88...264 V AC / 110...370 V DC
5H
88...132 V AC / 180...264 V AC /
11
开关电源和安全隔离变压器
ABL2平板式开关电源
ABL2REM
24
045
H
p ABL2REM 平板式,不带PFC功 能,单相输入
输出电压: p 24V DC
输出电流/功率: p 015 (1.5A/35W) p 020 (2.2A/50W) p 045 (4.5A/100W) p 065 (6.5A/150W) p 085 (8.3A/200W) p 100 (10.5A/250W) p 150 (14.6A/350W)
安装附件 说明
用于电源
最小包装数量 型号
夹合式安装板
ABL2REM24015H/020H;在 5导轨上
5
用于5 35mm
的安装需用一个安装板ABL2REM24045H/
安装导轨
065H/085H/100H/150H:在 5 导轨上
的安装需用2个安装板
四角支架,用于
ABL2REM24085H/100H/150H,每个
说明
ABL 2REM开关电源包括: 1 M3 螺钉的两个固定孔 2 一个115/230 V 输入电压选择开关 (仅针对150 W、200 W、250 W和 350 W 型) 3 一个4 mm2的螺钉夹接线端子,端子排同时标配塑料防护盖,用于连接交流输入电
施耐德低压电器选型手册-2012-01 变压器与母线槽、断路器配合推荐表

第一部分变压器与母线槽、 断路器配合推荐表变压器与母线槽、低压断路器(2 进线 + 1 母联) 选型配合表变电站容量 (kVA) 变压器型号母线槽型号进线、母联断路器+控制单元型号2 x 315 SCB10-315 CFC2508G MT08H1+MIC6.0P2 x 400 SCB10-400 CFC2508G MT08H1+MIC6.0P2 x 500 SCB10-500 CFC2510G MT10H1+MIC6.0P2 x 630 SCB10-630 CFC2510G MT10H1+MIC6.0P2 x 800 SCB10-800 CFC2512G MT12H1+MIC6.0P2 x 1000 SCB10-1000 CFC2516G MT16H1+MIC6.0P2 x 1250 SCB10-1250 CFC2520G MT20H1+MIC6.0P2 x 1600 SCB10-1600 CFC2525G MT25H1+MIC6.0P2 x 2000 SCB10-2000 CFC2532G MT32H1+MIC6.0P2 x 2500 SCB10-2500 CFC2540G MT40H1+MIC6.0P2 x 3150 SCB10-3150 CFC2550G MT50H1+MIC6.0P说明:1. 上表假设变压器高压侧短路容量无穷大计算短路电流,当短路电流的计算结果发生改变时,MT 断路器要从 N1、N2 (50kA), H1 (65kA),H2 (100kA), H3 (150kA), L1 (150kA) 中选取正确的分断能力指标。
2. 母联可以根据要求,相应选择 NA, HA, HF 型的 MT 负荷开关。
根据保护配置和测量功能要求不同,MIC 控制单元型号也将随之改变。
推荐表变压器容量每台变压器变压器流过每台变压总出线断路器总出线断路器分出线处分出线断路器型号并联数量额定电流阻抗电压器的短路电流最小分断能力型号短路电流N x kVA I n (A) U cc (%) (kA) (kA) (kA) ≤100A 160A 250A 400A 630A1 x 50 70 42 2 NSX100F 2 NSX100F2 x 50 70 4 2 2 NSX100F 4 NSX100F NSX160F3 x 50 704 2 4 NSX100F 6 NSX100F NSX160F NSX250F1 x 100 141 4 4 4 NSX160F 4 NSX100F NSX160F2 x 100 141 4 4 4 NSX160F 8 NSX100F NSX160F NSX250F3 x 100 1414 4 8 NSX160F 12 NSX100F NSX160F NSX250F NSX400N1 x 160 225 4 6 6 NSX250F 6 NSX100F NSX160F NSX250F2 x 160 225 4 6 6 NSX250F 12 NSX100F NSX160F NSX250F NSX400N3 x 160 2254 6 12 NSX250F 18 NSX100F NSX160F NSX250F NSX400N NSX630N1 x 250 352 4 9 9 NSX400N 9 NSX100F NSX160F NSX250F NSX400N2 x 250 352 4 9 9 NSX400N 18 NSX100F NSX160F NSX250F NSX400N NSX630N3 x 250 3524 9 18 NSX400N 27 NSX100F NSX160F NSX250F NSX400N NSX630N1 x 400 563 4 14 14 NSX630N 14 NSX100F NSX160F NSX250F NSX400N NSX630N2 x 400 5634 14 14 NSX630N 28 NSX100F NSX160F NSX250F NSX400N NSX630N3 x 400 5634 14 28 NSX630N 42 NSX100N NSX160N NSX250N NSX400N NSX630N推荐表 (续)变压器容量每台变压器变压器流过每台变压总出线断路器总出线断路器分出线处分出线断路器型号并联数量额定电流阻抗电压器的短路电流最小分断能力型号短路电流N x kVA In (A) Ucc (%) (kA) (kA) (kA) ≤100A 160A 250A 400A 630A 1 x 630 887 4 22 22 MT10N1 / MW10 22 NSX100F NSX160F NSX250F NSX400N NSX630N/ NSX1000N2 x 630 887 4 22 22 MT10N1 / MW10 44 NSX100N NSX160N NSX250N NSX400N NSX630N/ NSX1000N3 x 630 8874 22 44 MT10N1 66 NSX100H NSX160H NSX250H NSX400H NSX630H/ NSX1000N1 x 800 1127 6 19 19 MT12N1 / MW12 19 NSX100F NSX160F NSX250F NSX400N NSX630N/ NSX1250N2 x 800 1127 6 19 19 MT12N1 / MW12 38 NSX100N NSX160N NSX250N NSX400N NSX630N/ NSX1250N3 x 800 1127 6 19 38 MT12N1 57 NSX100H NSX160H NSX250H NSX400H NSX630H1 x 1000 1408 6 23 23 MT16N1 / MW16 23 NSX100F NSX160F NSX250F NSX400N NSX630N2 x 1000 1408 6 23 23 MT16N1 / MW16 46 NSX100N NSX160N NSX250N NSX400N NSX630N3 x 1000 1408 6 23 46 MT16N1 69 NSX100H NSX160H NSX250H NSX400H NSX630H1 x 1250 1760 6 29 29 MT20H1 / MW20 29 NSX100F NSX160F NSX250F NSX400N NSX630N2 x 1250 1760 6 29 29 MT20H1 / MW20 58 NSX100H NSX160H NSX250H NSX400H NSX630H3 x 1250 1760 6 29 58 MT20H1 87 NSX100L NSX160L NSX250L NSX400L NSX630L1 x 1600 2253 6 38 38 MT25H1 / MW25 38 NSX100N NSX160N NSX250N NSX400N NSX630N2 x 1600 2253 6 38 38 MT25H1 / MW25 76 NSX100L NSX160L NSX250L NSX400L NSX630L3 x 1600 2253 6 38 76 MT25H1 114 NSX100L NSX160L NSX250L NSX400L NSX630L 1 x 2000 2816 6 47 47 MT32H1 / MW32 47 NSX100N NSX160N NSX250N NSX400N NSX630N/402 x 2000 2816 6 47 47 MT32H1 / MW32 94 NSX100L NSX160L NSX250L NSx400L NSX630L/403 x 2000 2816 6 47 94 MT32H2 141 NSX100L NSX160L NSX250L NSX400L NSX630L1 x 2500 3521 6 59 59 MT40H1 59 NSX100H NSX160H NSX250H NSX400H NSX630H2 x 2500 3521 6 59 59 118 NSX100L NSX160L NSX250L NSX400L NSX630L1 x 3150 4436 6 74 74 MT50H1 74 NSX100L NSX160L NSX250L NSX400L NSX630L2 x 3150 4436 6 74 74 148 NSX100L NSX160L NSX250L NSX400L NSX630L说明:上表计算的依据:1. 上级电网的短路容量是 500MVA2. 变压器为 10kV/400V 变压器3. 表中用 NS630 的地方也可选用 MT06 产品。
施耐德断路器产品参数样本

M12N1/C1251N
38
NS100H
M12N1/C1251N
56
NS100H
M16N1 M16N1 M16N1
23
NS100N
47
NS100H
70
NS630H
M20N1 M20N1 M20N1
29
NS100H
59
NS100H
88
NS100L
M25N1 M25N1 M25N1
38
NS100H
75
NS100L
2
2
NS100N
4
NS100N
2
4
NS100N
5
NS100N
1*100
141
4
2*100
141
4
3*100
141
4
1*160
225
4
2*160
225
4
3*160
225
4
4
4
NS160N
4
NS100N
4
4
NS160N
7
NS100N
4
7
NS160N
11
NS100N
6
6
NS250N
6
NS100N
6
6
NS250N
MD16-2
控制单元(两种) 2:STD28(配电型) 3:STD38(选择型)
标准配置:
电动机构(MCH) 合闸电磁铁(XF) 端子罩(CB)
三极(3P) Lcu=40KA;
分励脱扣器(MX) 灭弧栅盖(CC) 后水平接线端子
抽屉式(D/O)
Lcs=75%Lcu;
lcw=30KA 1s
施耐德电气低压配电产品选型指南说明书

ABB EntrelecSommaireBU0402061SNC 160 003 C0205SummarySelection guide ....................................................................................page 1Screw clamp ........................................................................................page 2Feed through and ground terminal blocks .......................................................page 2 - 5 to 10Single pole, multiclamp terminal blocks..........................................................................page 4Feed through terminal blocks - Double-deck................................................................page 11Feed through terminal blocks - Triple-deck...................................................................page 12Three level sensor, terminal blocks without ground connection...................................page 13Three level sensor, terminal blocks with ground connection ........................................page 14Terminal blocks for distribution boxes, double deck + protection .......................page 15 - 16Interruptible terminal blocks for neutral circuit......................................................page 17 - 18Distribution : phase, ground terminal blocks .......................................................page 19 to 21Single pole or four pole distribution blocks..........................................................page 22 to 24Heavy duty switch terminal blocks with blade......................................................page 25 - 26Heavy duty switch terminal blocks with push-turn knob..............................................page 26Heavy duty switch terminal blocks with contact control pull lever...............................page 29Heavy duty switch terminal blocks with blade - Double-deck .....................................page 27Fuse holder terminal blocks for 5x20 mm (.197x.787 in.) and 5x25 mm (.197x.984 in.)or 6.35x25.4 mm (1/4x1 in.) and 6.35x32 mm (1/4x11/4 in.) fuse s.........................................page 28 - 29Fuse holder terminal blocks for 5x20 mm (.197x.787 in.) and 5x25 mm (.197x.984 in.) fuses -Double-dec k.....................................................................................................................page 27Terminal blocks for test circuits with sliding bridge ......................................................page 30Terminal blocks for metering circuits.............................................................................page 31ESSAILEC terminal blocks.............................................................................................page 32Safety connection terminal blocks ................................................................................page 33Miniblocks for EN 50045 (DIN 46277/2) rail ..........................................................page 34 - 35Spring clamp ......................................................................................page 36Angled terminal blocks - Feed through and ground .....................................................page 36Feed through and ground terminal blocks ...........................................................page 37 to 41Feed through terminal blocks - Double deck ................................................................page 42Terminal blocks for sensors / actuators ........................................................................page 42Terminal blocks for distribution boxes...........................................................................page 43Switch terminal blocks for neutral conductor........................................................page 44 - 45Heavy duty switch terminal blocks with blade..............................................................page 46Fuse holder terminal blocks for 5x20 mm (.197x.787 in.) and 5x25 mm (.197x.984 in.) fuse s....page 47Miniblocks Spring clamp ......................................................................................page 48 to 52ADO - Screw clamp ...........................................................................page 53Feed through and ground terminal blocks ...........................................................page 53 to 56Feed through and ground terminal blocks - Double-deck............................................page 57Heavy duty switch terminal blocks with blade..............................................................page 58Fuse holder terminal blocks for 5x20 mm (.197x.787 in.) and 5x25 mm (.197x.984 in.) fuse s ......page 59 - 60Miniblocks ADO - Screw clamp............................................................................page 61 to 65ADO - ADO .........................................................................................page 66Feed through and ground terminal blocks ...........................................................page 66 to 69Feed through and ground terminal blocks - Double-deck............................................page 70Terminal blocks for sensors / actuators ........................................................................page 71Heavy duty switch terminal blocks with blade..............................................................page 72Fuse holder terminal blocks for 5x20 mm (.197x.787 in.) and 5x25 mm (.197x.984 in.) fuse s ......page 73 - 74Miniblocks ADO - ADO .........................................................................................page 75 to 79Accessories ADO ...........................................................................................................page 80Power terminal blocks .............................................................page 81 to 84Quick-connect terminal blocks .................................................page 85 - 86Terminal blocks for railway applications ................................page 87 to 97Pluggable terminal blocks .....................................................page 98 to 100Accessories......................................................................................page 101Marking..................................................................................page 102 to 104GrossAutomation(877)268-3700··*************************PR30PR3.Z2PR3.G2PR5PR4PR1.Z2Rated wire size :Rated wire size :Rated wire size :Rated wire size :Mounting railsShield terminals forcollector barMarking tableHorizontal Rated wire size :0.5 to 16 mm² (22 to 8 AWG)Rated wire size :Rated wire size :Rated wire size :P a g e t o 29e30 t o 32ag e e3P a ge 8 t o 60a g e6t o 6574P a ge 7 t o 79P a ge 9P a g P a gGrossAutomation(877)268-3700··*************************2ABB Entrelecd010830402051SNC 160 003 C0205MA 2,5/5 - 2.5 mm² blocks - 5 mm .200" spacingAccessoriesGrossAutomation(877)268-3700··*************************3ABB Entrelec D010740402051SNC 160 003 C0205M 4/6 - 4 mm² blocks - 6 mm .238" spacingAccessoriesGrossAutomation(877)268-3700··*************************4ABB EntrelecD011030402051SNC 160 003 C0205M 4/6.3A - 4 mm² blocks - 6 mm .238" spacingM 4/6.4A - 4 mm² blocks - 6 mm .238" spacingGrossAutomation(877)268-3700··*************************5ABB Entrelec D010840402051SNC 160 003 C0205M 6/8 - 6 mm² blocks - 8 mm .315" spacingAccessoriesGrossAutomation(877)268-3700··*************************6ABB EntrelecD010850402051SNC 160 003 C0205M 10/10 - 10 mm² blocks - 10 mm .394" spacingAccessoriesGrossAutomation(877)268-3700··*************************7ABB Entrelec D010860402051SNC 160 003 C0205M 16/12 - 16 mm² blocks - 12 mm .473" spacingAccessoriesGrossAutomation(877)268-3700··*************************8ABB EntrelecD010870402051SNC 160 003 C0205M 35/16 - 35 mm² blocks - 16 mm .630" spacingGrossAutomation(877)268-3700··*************************M 95/26 - 95 mm² blocks - 26 mm 1.02" spacingM 70/22.P - 70 mm² ground block with rail contact - 22 mm .630" spacingSelection35 mm / 1.37"12 mm / 0.47"14-30 Nm / 124-260 Ib.in 1.2-1.4 Nm / 10.6-12.3 Ib.in1000600600415400400577070240 mm 2500 MCM 500 MCM 10 mm 2 6 AWG 6 AWG IEC UL CSANFC DIN0.5 - 160.5 - 100 AWG-600 MCM 2 AWG-500 MCM 50 - 30035 - 24018-6 AWGD 150/31.D10 - 150 mm² blocks - 31 mm 1.22" spacingCharacteristicsD 240/36.D10 - 240 mm² blocks - 36 mm 1.41" spacingSelectionWire size main circuit mm² / AWG VoltageV Current main circuit A Current outputARated wire size main circuit mm² / AWG Rated wire size outputmm² / AWG Wire stripping length main circuit mm / inches Wire stripping length output mm / inches Recommended torque main circuit Nm / Ib.in Recommended torque outputNm / Ib.inSolid Stranded Solid Stranded Wire size output mm² / AWG9.5 mm / .37"0.5-0.8 Nm / 4.4-7.1 Ib.in5003003003220204 mm 212 AWG12 AWG0.2 - 422-12 AWG 22-12 AWG 0.22 - 4IEC ULCSANFC DINCharacteristicsWire size mm² / AWGSolid Stranded D 4/6.T3 - 4 mm² blocks - 6 mm .238" spacingSelectionVoltage V CurrentARated wire sizemm² / AWG Wire stripping length mm / inches Recommended torqueNm / Ib.inM 4/6.T3.P - 4 mm² block - 6 mm .238" spacingD 2,5/6.D - 2.5 mm² blocks - 6 mm .238" spacingD 2,5/6.DL - 2.5 mm² blocks - 6 mm .238" spacingD 2,5/6.DPA1 - 2.5 mm² blocks - 6 mm .238" spacingD 2,5/6.DPAL1 - 2.5 mm² blocks - 6 mm .238" spacingD 4/6... - 4 mm² blocks - 6 mm .238" spacingD 4/6.LNTP - 4 mm² closed blocks - 17.8 mm .700" spacingMA 2,5/5.NT- 2.5 mm² block - 5 mm .200" spacingAccessories**SFB2 : 16 to 35 mm² 6 to 2 AWG H= 3 mm/.12"M 10/10.NT- 10 mm² block - 10 mm .394" spacingAccessories(1) Except for M 35/16 NT (closed block)*SFB1 : 0.5 to 35 mm² 18 to 2 AWG H= 7 mm/.28"**SFB2 : 16 to 35 mm² 6 to 2 AWG H= 3 mm/.12"MB 4/6... - 4 mm² blocks - 6 mm .238" spacingMB 6/8... - 6 mm² blocks - 8 mm .315" spacingMB 10/10... - 10 mm² blocks - 10 mm .394" spacingBRU 125 A - 35 mm² block - 27 mm 1.063" spacingBRU 160 A - 70 mm² block - 35.2 mm 1.388" spacingBRU 250 A - 120 mm² blocks - 44.5 mm 1.752" spacingBRU 400 A - 185 mm² block - 44.5 mm 1.752" spacingAccessoriesAccessoriesBRT 80 A - 16 mm² block - 48 mm 1.89" spacingBRT 125 A - 35 mm² block - 48 mm 1.89" spacingBRT 160 A - 50 mm² block - 50 mm 1.97" spacing9.5 mm / .37"0.5-0.6 Nm / 4.4-5.3 Ib.in4003003002010104 mm 210 AWG 12 AWG 0.5 - 422-10 AWG20-12 AWG0.5 - 2.5IEC ULCSANFC DINMA 2,5/5.SNB - 2.5 mm² blocks - 5 mm .200" spacingCharacteristicsM 4/6.SNB - 4 mm² blocks - 6 mm .238" spacingSelectionWire size mm² / AWGVoltage V CurrentARated wire sizemm² / AWG Wire stripping length mm / inches Recommended torqueNm / Ib.inSolid StrandedM 6/8.SNB - 6 mm² blocks - 8 mm .315" spacing - blade switchingSelectionAccessoriesM 4/8.D2.SF - for fuses 5x20 mm .197x.787 in. and 5x25 mm .197x.984 in. -4 mm² blocks - 8 mm .315" spacingM 4/6.D2.SNBT - 4 mm² blocks - 6 mm .238" spacing - blade switchM 4/8.SF- 4 mm² blocks - 8 mm .315" spacingM 4/8.SFL - 4 mm² blocks - 8 mm .315" spacing12 mm / .472"1.2-1.4 Nm / 10.6-12.3 Ib.in800(1)60060016252510 mm 210 AWG8 AWG0.5 - 1622-10 AWG 22-8 AWG 0.5 - 10IEC ULCSANFC DINCBD2SML 10/13.SF - for fuses 6.35x25.4 mm 1/4x1 in. and 6.35x32 mm 1/4x11/4 in. -10 mm² blocks - 13 mm .512" spacingSelectionAccessoriesCharacteristicsWire size mm² / AWGVoltage V CurrentARated wire sizemm² / AWG Wire stripping length mm / inches Recommended torqueNm / Ib.inSolid Stranded (1) Insulation voltage of terminal block - operating voltage : according to fuse.M 4/6.D2.2S2... - 4 mm² blocks - 6 mm .238" spacing11 mm / .43"0.8-1 Nm / 7.1-8.9 Ib.in50060030306 mm 28 AWG0.5 - 1022-8 AWG0.5 - 6IECULCSANFC DINM 6/8.ST... - 6 mm² blocks - 8 mm .315" spacingCharacteristicsWire size mm² / AWGVoltage V CurrentARated wire sizemm² / AWG Wire stripping length mm / inches Recommended torqueNm / Ib.inSolid Stranded M 6/8.STA - 6 mm² blocks - 8 mm .315" spacing(3)Only for M 6/8.STAM 4/6.ST- 4 mm² blocks - 6 mm .236" spacingBNT...PC...(2) Only for M10/10.ST-SnThe PREM IUM solution for testing the secondary circuits of current or voltage transformers.ESSAILEC, approved by the major electricity utilities, remains the premium choice for the energy market.Implemented in the transformers secondary circuits, ESSAILEC thanks to its intelligent “make before break” design eases and secures any intervention. Cutting the energy supply is avoided with zero risk for the operator.The plug and socket connection cuts cost installation as well as in-situ wiring errors. ESSAILEC is ideal for the wiring of sub-assemblies in the secondary circuits.ESSAILEC terminal blocksProtection relays,Protection relays,Testing :The ESSAILEC socket supplies energy to the protection or counting devices. The insertion of the test plug, which is connected to the measurement equipment, allows the testing of the devices, without perturbing the circuit.ESSAILEC blocks are well adapted to current or voltage measurement :-Current sockets with make before break contacts and pre-wired test plug for current measures-Voltage sockets with open contacts and pre-wired test plug for voltage measures-Up to 4 ammeters or 4 voltmeters connected to the test plugDistributing :The ESSAILEC plug is continuously mounted on the socket to supply current or voltage to secondary circuits sub assemblies.ESSAILEC blocks extreme versatility allow :-Safe current distribution with current socket with mobile contacts since the secondary circuit is not cut when plug is removed-Voltage or polarity distribution with dedicated voltage or polarity socket with closed contactESSAILEC is designed to offer :Great flexibility :-Connection multi contacts « plug and play »-Panel, rail, rack fixed mounting or stand-alone connector -Two wiring technologies, up to 10 mm²Extreme reliability :-Non symmetric blocks -Coding accessories -IP20 design -Locking system -Sealed coverR S T NFor technical characteristics and complete part numbers list, please ask for the ESSAILEC catalog10005006003225254 mm 21.65 mm²12 AWG 13 mm / .51"IECB.SCSANFC DINTS 50-180.5 - 0.8 Nm /4.4 - 7.1 Ib.in0.2 - 422-12 AWG0.22 - 40.5 - 1.50.28 - 1.6580050060041252562.512 AWG 13 mm / .51"0.8 - 1 Nm / 7.1 - 8.9 Ib.inIECB.S CSANFC DINTS 50-180.5 - 1020-12 AWG0.5 - 60.28 - 2.590050060046406510 mm 26 mm² 6 AWG 14 mm / .55"IECB.S UL/CSANFC DINTS 50-181.2 - 1.4 Nm / 10.6 - 12.3 Ib.in0.5 - 1620 - 6 AWG0.5 - 100.28 - 6M 4/6.RS - 4 mm² blocks - 6 mm .238" spacingCharacteristicsWire size mm² / AWGVoltage V CurrentARated wire sizemm² / AWG Wire stripping lengthmm / inches Recommended torque (screw)Nm / Ib.inSolid wire Stranded wire Solid wire Stranded wire Screw clampLugsM 6/8.RS - 6 mm² blocks - 8 mm .315" spacingCharacteristicsWire size mm² / AWGVoltage V CurrentARated wire sizemm² / AWG Wire stripping lengthmm / inches Recommended torque (screw)Nm / Ib.inSolid wire Stranded wire Solid wire Stranded wire Screw clampLugspending M 10/10.RS - 10 mm² blocks - 10 mm .394" spacingCharacteristicsWire size mm² / AWGVoltage V CurrentARated wire sizemm² / AWG Wire stripping lengthmm / inches Recommended torque (screw)Nm / Ib.inSolid wire Stranded wire Solid wire Stranded wire Screw clampLugspending SelectionAccessories(1) Only for block M 4/6.RS (4) For blocks M 4/6.RS and M 6/8.RS(2) Only for block M 6/8.RS(3) Only for block M 10/10.RSDR 1,5/4 - 1.5 mm² blocks - 4 mm .157" spacingDR 1,5/5... - 1.5 mm² blocks - 5 mm .200" spacing。
施耐德选型

9Байду номын сангаас18 26
NS100N NS100N NS100N
NS160N NS160N NS160N
NS250N NS250N NS250N
NS400N NS400N NS400N
NS630N NS630N
4 4 4
14 14 14
14 14 28
NS630N NS630N NS630N
14 28 42
NS100N NS100N NS100N
NS400N NS400N NS400N NS400N NS400N NS400H NS400N NS400H NS400H NS400N NS400H NS400L NS400H NS400L NS400L NS400H NS400L NS400L NS400H NS400L NS400L NS400L
1*630 2*630 3*630 1*800 2*800 3*800 1*1000 2*1000 3*1000 1*1250 2*1250 3*1250 1*1600 2*1600 3*1600 1*2000 2*2000 3*2000 1*2500 2*2500 1*3150 2*3150
887 887 887 1127 1127 1127 1408 1408 1408 1760 1760 1760 2253 2253 2253 2816 2816 2816 3521 3521 4436 4436
12
Masterpact D 空气断路器选型表
MD16-2
控制单元(两种) 2:STD28(配电型) 3:STD38(选择型)
标准配置: 电动机构(MCH) 合闸电磁铁(XF) 端子罩(CB) 三极(3P) Lcu=40KA; 分励脱扣器(MX) 灭弧栅盖(CC) 后水平接线端子 抽屉式(D/O) lcw=30KA 1s
施耐德断路器选择

施耐德断路器选择1进线和分段断路器-空气断路器1.1一般规定变压器容量S≤800kV A,断路器选用MT06~16N 分断能力I cu=I cs=50kA, I cw=36kA (1s)控制单元选用Micrologic 5.0A变压器容量S ≥1000kV A,断路器选用MT20~40H1-H2分断能力I cu=I cs=65-100kA,I cw=65-85kA (1s)控制单元选用Micrologic 5.0A1.2应用举例配电变压器S9-630KV A, 4.5%,二次侧额定电流I n2=909A,最大工作电流I2max=957A,二次侧最大三相短路电流I k=17.91kA,最小16.2kA1.2.1进线断路器选用MT12N2, 1250A,4P空气断路器,额定电流I n=1250A(1)过载长延时保护-反时限,t=k/I2整定电流:I r=1.05×957=1005A,取I r=0.8I n=1000A(整定范围500 ~ 1250A)即0.4~1.0I n长延时整定时间(6I r的动作时间)要与以下条件配合:1)应躲过最大一台电动机起动时间,或自动再起动时间;2)变压器二次侧最大短路时,过载保护动作时间不小于0.4s,即K=179102⨯0.45=(6⨯I r)2⨯t r=60002⨯t r得t=4.01s取t r=4 s或t r=8 s(级差为4s)当变压器过载1.3倍,即I=1.3⨯957=1244A时,若t r=4s保护动作时间:t=(60002⨯4)÷12442=93 s 可见,太保守-完全没有发挥变压器的过载能力取t r=8s(2)短路短延时保护整定电流I sd的整定应取以下两种情况最大者:1)一台变压器带总负荷(不含最大电动机负荷)加上最大一台电动机的起动电流;2)一台变压器带50%总负荷,加上另一段母线上电动机自动再起动电流;有时,为了简化计算,可取2.0~2.5倍变压器额定电流,即认为变压器最大尖峰电流不超过额定电流的2~2.5倍。
施耐德产品选型手册-第十八部分(UPS)

Symmetra LX
模块化 UPS
1:1/3:1
; 输出 IEC 插座或者硬线连接 ; 每个模块 4kVA, 模块化, N+1 冗余设计, 在线双变换, 塔式 / 机架式可转换 ; 后备时间和功率可扩展 可热更换的电池、功率模块和智能模块
产品系列
产品分类
电压制式
10
20KVA~
1600KVA
UPS 选型
型号
上送风
上送风
上送风
下送风
总冷量 (KW)
显冷量
风量
总冷量
(KW)
(m3/h)
(KW)
0151
5.5
5.2
1580
5.5
阿米哥系列
SUA
0251
7.7
6.1
1580
7.7
( 上送风直联风机型 )
0331
9.3
7.4
1950
9.3
SDA
0351
12
10.4
3020
12
( 下送风直联风机型 )
0501
15.4
14.9
4700
15.4
0601
18
15.9
4700
18.1
0611
22.3
21.1
5740
22.3
0721
26.4
26.4
8180
26.4
0722
27
27
8180
27
0921
32.7
30.3
8180
32.7
0922
32.7
30.3
8180
32.7
1021
34.3
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
ő AS-Interface ጆᆩ႙ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
ႎׂ
ᆩࢽ႙
ő Phaseo ਸ࠲ۉᇸ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 ő Phaseo Ҿඇ߰Վუഗ. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ۉᇸ
ਸ࠲ۉᇸࢅҾඇ߰Վუഗ
0
Phaseo ਸ࠲ۉᇸ
ABL8 ࡆڞ๕ਸ࠲ۉᇸ ఇ႙ࢅᆫࣅ႙߾ᄽۉᇸ
ۉუ
ᇑ๘হ߳ۉںᇸڦথ
ெࡔ - 120 V ( ၎၍ࢅዐႠ၍क़ ) - 240 V ( ၎क़ )
౹ዞ - 230 V ( ၎၍ࢅዐႠ၍क़ ) - 400 V ( ၎क़ )
ő ཚᆩ႙ ( ۉუ ) Ő ۉᇸ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Ő ۉᇸ੍Ⴀਦݛӄ
48 V DC
ABL 7RM24025 ( ఇ႙ ) ABL 8REM24030 ( ᆫࣅ႙ )
ABL 7RP4803 ( ᆫࣅ႙ )
ABL 8REM24050 ( ᆫࣅ႙ )
ᄻஓ
17
(1) أକ ABL 8RPM24200.AC 100...120 V ࢅ AC 200...240 Vă
17 ( ఇ႙ ) ࢅ 23 ( ᆫࣅ႙ )
施耐德电气在中国
1987年,施耐德电气在天津成立第一家合资工厂梅兰日兰,将断路器技术带到中国,取代传统保险 丝,使得中国用户用电安全性大为增强,并为断路器标准的建立作出了卓越的贡献。90年代初,施耐 德电气旗下品牌奇胜率先将开关面板带入中国,结束了中国使用灯绳开关的时代。
施耐德电气的高额投资有力地支持了中国的经济建设,并为中国客户提供了先进的产品支持和完善的技 术服务,中低压电器、变频器、接触器等工业产品大量运用在中国国内的经济建设中,促进了中国工业 化的进程。
ெࡔ - 277 V ( ၎၍ࢅዐႠ၍क़ ) - 480 V ( ၎क़ )
ࢇޙޏIEC 61000-3-2
വუԍࢺ (U > 19 V) ࡗሜࢅ܌ୟԍࢺ
ኑीۉഗ
ᇑࠀీఇڦग़ඹႠ
ీଉे ( ֠ئഽ )
ۉუ ୁۉ
0.3 A 0.6 A 1.2 A 2A 2.5 A 3A 4A 5A 6A 10 A 20 A 40 A
目前,施耐德电气在中国共建立53个办事处,28家工厂,7个物流中心,1 个研修学院,3个全球研 发中心,1000多名研发工程师,1 个实验室,1 所能源大学,700多家分销商和遍布全国的销售网 络。施耐德电气中国目前员工数近28,000人。通过与合作伙伴以及大量经销商的合作,施耐德电气
为中国创造了成千上万个就业机会。
रຍ႑တ
ő ጲׂࣅۯණኤ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
୳հۉᇸ
ő ڇ၎ / ෙ၎ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
ೝӱ๕ਸ࠲ۉᇸ
ő ABL1 ဣଚ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 ő ABL2 ဣଚ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
ਸ࠲ۉᇸ
ࡆڞ๕ਸ࠲ۉᇸ ABL8 ဣଚ
ő ถ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
能效管理平台,为企业客户节省高达30%的投资成本和运营成本。
ణ
Phaseo ဣଚ ਸ࠲ۉᇸࢅҾඇ߰Վუഗ
Phaseo ݴૌ ਸ࠲ۉᇸ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 ୳հۉᇸ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Ҿඇ߰Վუഗ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ő ఇ႙ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 ő ᆫࣅ႙ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
–
–
1,25 ڟ1,4 In(1 ݴዓా ) Ljൽਦᇀਏ༹ڦఇ႙ ( ټABL 8MEM)
ޏ
5 V DC
12 V DC
ABL 8MEM12020 ( ఇ႙ )
ABL 8MEM05040 ( ఇ႙ )
ABL 7RP1205 ( ᆫࣅ႙ )
24 V DC
ABL 8MEM24003 ( ఇ႙ ) ABL 8MEM24006 ( ఇ႙ ) ABL 8MEM24012 ( ఇ႙ )
Ҿඇ߰Վუഗ (25-2500 VA)
ő ঢ়ष႙ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 ő ᆫࣅ႙. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 ő ཚᆩ႙ ( ۉუ ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78