低压电气设备的高电压试验技术第一部分:定义和试验要求
高电压试验技术

1、高电压试验技术GB/T16927 高电压试验技术[1] GB/T 16927.1-1997, 高电压试验技术 第一部分: 一般试验要求High voltage test techniques--Part 1: General test requirements[2] GB/T 16927.2-1997, 高电压试验技术 第二部分:测量系统High voltage test techniques--Part 2: Measuring systemsGB/T 17627 低压电气设备的高电压试验技术[1] GB/T 17627.1-1998, 低压电气设备的高电压试验技术 第一部分:定义和试验要求High-voltage test techniques for low-voltage equipment Part 1: Definitions,test and procedure requirements[2] GB/T 17627.2-1998, 低压电气设备的高电压试验技术 第二部分:测量系统和试验设备High-voltage test techniques for low-voltage equipment Part2:Measuring system and test equipmentDL/T 848 高压试验装置通用技术条件[1] DL/T 848.1-2004, 高压试验装置通用技术条件 第1部分:直流高压发生器General technical specification of high voltage test devices Part 1: High voltage DC generator [2] DL/T 848.2-2004, 高压试验装置通用技术条件第2部分:工频高压试验装置General technical specification of high voltage test devices Part 2: Power frequency high voltage test device[3] DL/T 848.3-2004, 高压试验装置通用技术条件第3部分:无局放试验变压器General technical specification of high voltage test devices Part 3: Non partial discharge testing transformer[4] DL/T 848.4-2004, 高压试验装置通用技术条件第4部分:三倍频试验变压器装置General technical specification of high voltage test devices Part4:Triple-frequency test transformer[5] DL/T 848.5-2004, 高压试验装置通用技术条件 第5部分:冲击电压发生器General technical specification of high voltage test devices Part 5 : impulse voltage generatorDL/T846 高电压测试仪器通用技术条件[1] DL/T 846.1-2004, 高电压测试设备通用技术条件 第1部分:高电压分压器测量系统General technical specifications for high voltage test equipments Part 1 : high voltage divider measuring system[2] DL/T 846.2-2004, 高电压测试设备通用技术条件 第2部分:冲击电压测量系统General technical specifications for high voltage test equipments Part2:Impulse voltage measuring system[3] DL/T 846.3-2004, 高电压测试设备通用技术条件 第3部分:高压开关综合测试仪General technical specifications for high voltage test equipments Part 3: High voltage switch integrate detector[4] DL/T 846.4-2004, 高电压测试设备通用技术条件 第4部分:局部放电测量仪General technical specifications for high voltage test equipments Part 4: Partial discharge detector [5] DL/T 846.5-2004, 高电压测试设备通用技术条件 第5部分:六氟化硫微量水分仪General technical specifications for high voltage test equipments Part5: Analyzer for trace moisture in SF6 gas[6] DL/T 846.6-2004, 高电压测试设备通用技术条件 第6部分:六氟化硫气体检漏仪General technical specifications for high voltage test equipments Part 6: SF6 gas leak detector [7] DL/T 846.7-2004, 高电压测试设备通用技术条件 第7部分:绝缘油介电强度测试仪General technical specifications for high voltage test equipments Part7:Dielectric strength detector of insulating oils[8] DL/T 846.8-2004, 高电压测试设备通用技术条件 第8部分:有载分接开关测试仪General technical specifications for high voltage test equipments Part 8: Detector of on-load tap-changers[9] DL/T 846.9-2004, 高电压测试设备通用技术条件 第9部分:真空开关真空度测试仪General technical specifications for high voltage test equipments Part 9: Vacuum interrupter detectorIEC标准[1] IEC 60060-1-2010 高压试验技术.第1部分:一般定义和试验要求High-voltage test techniques - Part 1: General definitions and test requirements[2] IEC 60060-2-2010 高压试验技术.第2部分:测量系统High-voltage test techniques. Part 2: Measuring systems[3] IEC 60060-3-2006 高压试验技术.第3部分:现场试验的定义和要求High voltage test techniques - Part 3: Definitions and requirements for on-site testing[4] IEC 60060-4-1988 高压试验技术.第4部分:测量装置应用导则High-voltage test techniques. Part 4 : Application guide for measuring devices[5] IEC 60270-2000 高电压试验技术:局部放电测量High-V oltage Test Techniques – Partial Discharge Measurements-Third EditionIEEE标准[1] 4-1995 IEEE Standard Techniques for High-V oltage Testing (Revision of IEEE Std 4-1 978)[2] 4a-2001 Amendment to IEEE Standard Techniques for High-V oltage Testing[3] 48-2009 IEEE Standard for Test Procedures and Requirements for Alternating-Current Cable Terminations Used on Shielded Cables Having Laminated Insulation Rated 2.5 kV through 765 kV or Extruded Insulation Rated 2.5 kV through 500 kV[4] 95-2002 IEEE Recommended Practice for Insulation Testing of AC Electric Machinery (2300 V and Above) With High Direct V oltage[5] 400.1-2007 IEEE Guide for Field Testing of Laminated Dielectric, Shielded Power Cable Systems Rated 5 kV and Above With High Direct Current V oltage[6] 400-2001 IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems[7] 433-2009 IEEE Recommended Practice for Insulation Testing of AC Electric Machinery with High V oltage at Very Low Frequency[8] C37.09-2005 IEEE Standard Test Procedure for AC High-V oltage Circuit Breakers Rated on aSymmetrical Current Basis[9] C37.081-1981 IEEE Guide for Synthetic Fault Testing of AC High-V oltage Circuit Breakers Rated on a Symmetrical Current Basis[10] C37.083-1999 IEEE Guide for Synthetic Capacitive Current Switching Tests of AC High-V oltage Circuit Breakers[11] C37.34-1994 IEEE Standard Test Code for High-V oltage Air Switches[12] C37.41-2008 IEEE Standard Design Tests for High-V oltage (>1000 V) Fuses, Fuse and Disconnecting Cutouts,Distribution Enclosed Single-Pole Air Switches,Fuse Disconnecting Switches, and Fuse Links and Accessories Used with These Devices[13] C37.53.1-1989 American National Standard High-V oltage Current-Limiting Motor-Starter Fuses - Conference Test Procedures[14] C37.301-2009 IEEE Standard for High-V oltage Switchgear (Above 1000 V) Test Techniques - Partial Discharge Measurements[15] C37.016 :2006 IEEE Standard for AC High-V oltage Circuit Switchers rated 15.5 kV through 245 kV二、冲击电压发生器和冲击电压试验[1] DL/T 846.2-2004, 高电压测试设备通用技术条件 第2部分:冲击电压测量系统General technical specifications for high voltage test equipments Part2:Impulse voltage measuring system[2] DL/T 992-2006,冲击电压测量实施细则Detailed implementation guide for impulse voltage measurement[3] JB/T 7083-1993, 低压电器冲击电压试验仪未注英文名称[4] JB/T 7080-1993, 绕组匝间冲击电压试验仪未注英文名称[5] DL/T848.5-2004, 高压试验装置通用技术条件 第5部分:冲击电压发生器General technical specification of high voltage test devices Part 5 : impulse voltage generator [6] GB/T 16896.1-2005, 高电压冲击测量仪器和软件 第1部分:对仪器的要求Instruments and software used for measurements in high-voltage impulse tests-Part1: Requirements for instruments[7] GB/T 21222-2007, 绝缘液体 雷电冲击击穿电压测定方法Methods for the determination of the lightning impulse breakdown voltage of insulating liquids [8] GB/T 18134.1-2000, 极快速冲击高电压试验技术 第1部分:气体绝缘变电站中陡波前过电压用测量系统High-voltage testing techniques with very fast impulses --Part 1:Measuring systems for very fast from overvoltages generated in gas-insulated substations[9] DL/T557- 2005, 高压线路绝缘子空气中冲击击穿试验―定义、试验方法和判据Insulators of ceramic or glass material overhead lines with a nominal voltage greater than 1000V -- impulse puncture tests in air[10] GB/T 1094.4-2005, 电力变压器 第4部分:电力变压器和电抗器的雷电冲击和操作冲击试验导则Power transformers—Part 4:Guide to the lightning impulse and switching impulse testing—Power transformers and reactors[11] GB/T 17626.5-2008, 电磁兼容 试验和测量技术 浪涌(冲击)抗扰度试验Electromagnetic compatibility - Testing and measurement techniques - Surge immunity test [12] GB/T 14598.18-2007, 电气继电器 第22-5部分:量度继电器和保护装置的电气骚扰试验-浪涌抗扰度试验Electrical relays—Part22-5:Electrical disturbance test for measuring relays and protection equipment—Surge immunity test[13] JB/T 7616-1994, 高压线路绝缘子陡波冲击耐受试验未注英文名称[14] DL/T 557-2005, 高压线路绝缘子空气中冲击击穿试验―定义、试验方法和判据Insulators of ceramic or glass material overhead lines with a nominal voltage greater than 1000V -- impulse puncture tests in airIEC标准[1] IEC 60897-1987 绝缘液体的雷电冲击击穿电压的测定方法Methods for the determination of the lightning impulse breakdown voltage of insulating liquids [2] IEC 61083-1-2001 高压冲击试验中测量用仪器及软件 第1部分:仪器的要求 Instruments and software used for measurement in high-voltage impulse tests-Part1: Requirements for instruments[3] IEC 61083-2-1996 高压冲击试验中测量用数字记录仪 第2部分:测定冲击波形参数用软件的评估Digital recorders for measurements in high-voltage tests - Part 2: Evaluation of software used for the determination of the parameters of impulse waveformsIEEE标准[1] 82-2002 IEEE Standard Test Procedure for Impulse V oltage Tests on Insulated Conductors[2] C37.013a-2007 IEEE Standard for AC High V oltage Generator Circuit Breakers Rated on a Symmetrical Current Basis - Amendment 1: Supplement for Use With Generators Rated 10-100 MV A[3] C37.101 :2006 IEEE Guide for Generator Ground Protection[4] C37.102 :2006 IEEE Guide for AC Generator Protection[5] C57.98-1993 IEEE Guide for Transformer Impulse Tests[6] 1122-1998 IEEE Standard for Digital Recorders for Measurements in High- V oltage Impulse Tests[7]C57.138-1998IEEE Recommended Practice for Routine Impulse Test for Distribution Transformers3、工频试验变压器和工频电压试验[1] JB/T 9641—1999,试验变压器Testing transformers[2] JB/T 501-2006 电力变压器试验导则Test guide for power transformers[3] DL/T 848.2-2004, 高压试验装置通用技术条件第2部分:工频高压试验装置General technical specification of high voltage test devices Part 2: Power frequency high voltage test device[4] DL/T 848.3-2004, 高压试验装置通用技术条件第3部分:无局放试验变压器General technical specification of high voltage test devices Part 3: Non partial discharge testing transformer[5] GB/T 1408.1-2006, 绝缘材料电气强度试验方法 第1部分:工频下试验Electrical strength of insulating materials - Test methods - Part 1: Tests at power frequencies [6] GB2536—1990 ,变压器油Transformer oils[7] GB/T 17626.28-2006, 电磁兼容 试验和测量技术 工频频率变化抗扰度试验Electromagnetic compatibility(EMC) - Testing and measurement techniques - Variation of power frequency immunity test[8] GB/T 3333-1999, 电缆纸工频击穿电压试验方法Cable paper--Determination of electrical strength at power frequence[9] GB/T 14517-1993, 绝缘胶粘带工频耐电压试验方法Test method for dielectric strength of insulating adhesive tape at power frequency[10] DL/T 812-2002, 标称电压高于1000V架空线路绝缘子串工频电弧试验方法Insulators string for overhead lines with a normal voltage above 1000V-AC power arc test method [11] GB/T 7252-2001, 变压器油中溶解气体分析和判断导则Guide to the analysis and the diagnosis of gases dissolved in transformer oil[12] DL/T 536-1993, 耦合电容器及电容分压器订货技术条件未注英文名称[13] JB/T 8169-1999, 耦合电容器及电容分压器Coupling capacitors and capacitor dividersGB1094 电力变压器[1] GB 1094.1—1996 ,电力变压器 第1部分:总则Power transformers--Part 1: General[2] GB 1094.2—1996 ,电力变压器 第2部分:温升Power transformers--Part 2: Temperature rise[3] GB 1094.3—2003,电力变压器 第3部分: 绝缘水平、绝缘试验和外绝缘空气间隙(eqv IEC 60076-3:2000)Power transformers--Part 3 : Insulation levels,dielectric tests and external clearances in air[4] GB/T 1094.4-2005, 电力变压器 第4部分:电力变压器和电抗器的雷电冲击和操作冲击试验导则Power transformers—Part 4:Guide to the lightning impulse and switching impulse testing—Power transformers and reactors[5] GB 1094.5—2008 ,电力变压器 第5部分:承受短路的能力Power transformers--Part 5: Ability to withstand short circuit[6] GB/T 1094.7-2008, 电力变压器 第7部分:油浸式电力变压器负载导则Power transformers—Part7:Loading guide for oil-immersed power transformers[7] GB/T 1094.10-2003, 电力变压器 第10部分:声级测定Power transformers—Part10:Determination of sound levels[8] GB 1094.11—2007,电力变压器 第11部分:干式变压器Power transformers--Part 11 : Dry-type transformersIEC标准[1] IEC 60076-10-1-2005 电力变压器.第10-1部分:声级的测定.应用指南Power transformers Part 10-1: Determination of sound levels Application guide-Edition 1[2] IEC 60076-10-2005 电力变压器.第10部分:声级的测定Power Transformers Part 10: Determination of Sound Levels[3] IEC 60076-11-2004 电力变压器.第11部分:干式变压器Power transformers Part 11: Dry-type transformers-First Edition[4] IEC 60076-12-2008 电力变压器.第12部分:干型电力变压器用负荷指南Power transformers - Part 12: Loading guide for dry-type power transformers[5] IEC 60076-13-2006 电力变压器.第13部分:自我保护式充液变压器[6] IEC 60076-15 Ed.1.0 (2008) Power transformers - Part 15: Gas-filled power transformers[7] IEC 60076-15-2008 电力变压器.第15部分:充气电力变压器Power transformers – Part 15: Gas-filled power transformers[8] IEC 60076-2-1993 电力变压器 第2部分:温升Power Transformers; Part 2: Temperature Rise-Second Edition[9] IEC 60076-3-2000 电力变压器 第3部分:绝缘水平、电介质试验和空气中的外间隙Power Transformers Part 3: Insulation Levels. Dielectric Tests and External Clearances in Air-Edition 2[10] IEC 60076-4-2002 电力变压器.第4部分:闪电脉冲和开关脉冲试验指南.电力变压器和电抗器Power transformers - Part 4: Guide to lightning impulse and switching impulse testing; Power transformers and reactors[11] IEC 60076-5-2006 电力变压器 第5部分:承受短路的能力Power Transformers Part 5: Ability to Withstand Short Circuit-Edition 3.0[12] IEC 60076-6-2007 电力变压器.第6部分:电抗器Power transformers – Part 6: Reactors-Edition 1.0[13] IEC 60076-7-2005 电力变压器.第7部分:油浸电力变压器负载指南Power transformers Part 7: Loading guide for oil-immersed power transformers-First Edition [14] IEC 60076-8-1997 电力变压器 第8部分:应用指南Power Transformers - Application Guide-First Edition[15] IEC/TS 60076-14-2004 电力变压器.第14部分:使用高温绝缘材料的液浸式电力变压器的设计和应用Power transformers – Part 14: Design and application of liquid-immersed power transformersusing high-temperature insulation materials-Edition 2.0[16] IEC 62032-2005, 移相变压器的应用、规范和试验指南Guide for the application. specification. and testing of phase-shifting transformersIEEE标准[1] 62.2-2004 IEEE Guide for Diagnostic Field Testing of Electric Power Apparatus - Electrical Machinery[2] 62-1995 IEEE Guide for Diagnostic Field Testing of Electric Power Apparatus - Part 1: Oil Filled Power Transformers, Regulators, and Reactors[3] C57.135-2005 IEEE Guide for the Application, Specification, and Testing of Phase-Shifting Transformers[4] 644-1994 IEEE Standard Procedures for Measurement of Power Frequency Electric and Magnetic Fields From AC Power Lines4、工频谐振试验设备和试验技术[1] DL/T 849.6-2004, 电力设备专用测试仪器通用技术条件 第6部分:高压谐振试验装置General technical specification of test instruments used for power equipments Part 6: High voltage resonant test system5、冲击电流发生器和冲击电流试验技术[1] GB 4208-2008, 外壳防护等级Degrees of protection provided by enclosure[2] GB 18802.1-2002, 低压配电系统的电涌保护器(SPD)第1部分:性能要求和试验方法Surge protective devices connected to low-voltage power distribution systems--Part 1:Performance requirements and testing methods[3] GB 11032-2000 交流无间隙金属氧化物避雷器Metal oxide surge arresters without gaps for a. c. systems[4] GB/T 18802.311-2007 低压电涌保护器件 第311部分:气体放电管(GDT)规范(等同IEC 61643-311-2001)Components for low-voltage surge protective—Part311:Specification for gas discharge tubes(GDT)[5] GB/T 17626.5-2008, 电磁兼容 试验和测量技术 浪涌(冲击)抗扰度试验Electromagnetic compatibility - Testing and measurement techniques - Surge immunity testIEC标准[1] IEC TR 61000-1-5 :2004 Electromagnetic compatibility (EMC) Part 1-5: General High power electromagnetic (HPEM) effects on civil systems-First Edition[2] IEC 60099-4 AMD 2 :2009 AMENDMENT 2 Surge arresters – Part 4: Metal-oxide surge arresters without gaps for a.c. systems-Edition 2.0[3] IEC 61643-311 :2001 Components for Low-V oltage Surge Protective Devices - Part 311: Specification for Gas Discharge Tubes (GDT)-First Edition[4] IEC 61643-1 :2005 Low-voltage surge protective devices – Part 1: Surge protective devices connected to low-voltage power distribution systems – Requirements and tests-Edition 2.0[5] IEC 61643-12 :2008 Low-voltage surge protective devices – Part 12: Surge protective devices connected to low-voltage power distribution systems–Selection and application principles-Edition 2.0IEEE标准[1] C62.11a-2008 IEEE Standard for Metal-Oxide Surge Arresters for Ac Power Circuits (>1 kV). Amendment 1: Short-Circuit Tests for Station, Intermediate, and Distribution Arresters[2] C62.11-2005 IEEE Standard for Metal-Oxide Surge Arresters for AC Power Circuits (>1 kV)[3] C62.22-2009 IEEE Guide for the Application of Metal-Oxide Surge Arresters for Alternating-Current Systems[4] 1299/C62.22.1-1996 IEEE Guide for the Connection of Surge Arresters to Protect Insulated, Shielded Electric Power Cable Systems[5]C62.34-1996IEEE Standard for Performance of Low-V oltage Surge-Protective Devices (Secondary Arresters)[6] C62.41.1-2002 IEEE Guide on the Surge Environment in Low-V oltage (1000 V and less) AC Power Circuits[7] C62.41.2-2002 IEEE Recommended Practice on Characterization of Surges in Low-V oltage (1000 V and Less) AC Power Circuits[8] C62.41-1991 IEEE Recommended Practice on Surge V oltages in Low-V oltage AC Power Circuits[9] C62.42-2005 IEEE Guide for the Application of Component Surge-Protective Devices for Use in Low-V oltage [Equal to Or Less Than 1000 V (AC) Or 1200 V (DC)] Circuits[10] C62.62-2010 IEEE Standard Test Specifications for Surge-Protective Devices (SPDs) for Use on the Load Side of the Service Equipment in Low V oltage (1000 V and less) AC Power Circuits[11] C62.62-2000 IEEE Standard Test Specifications for Surge-Protective Devices for Low-V oltage AC Power Circuits6、其他GB 311.1-1997,高压输变电设备的绝缘配合Insulation co-ordination for high voltage transmission and distribution equipmentGB/T11920-2008, 电站电气部分集中控制设备及系统通用技术条件General specification of central control equipment and system for electrical parts in power stations and substationsGB/T 7354-2003, 局部放电测量Partial discharge measurementsJB/T 8749.1-2007, 调压器 第一部分:通用要求和试验V oltage regulators--Part 1: General requirements and testsJB/T 7070.1-2002 ,调压器试验导则 第1部分:接触调压器和接触自动调压器试验导则Test guide for regulator Part 1: Test guide for variable regulators and automatic variable regulators GB/T 191-2008, 包装储运图示标志Packaging - Pictorial marking for handling of goods。
电力行业常用技术规范

52
JJG 856-1994
500℃以下工作用辐射温度计检定规程
53
DL/Z 713-2000
500KV变电所保护和控制设备抗扰度要求
54
HJ/T 24-1998
500kV超高压送变电工程电磁辐射环境影响评价技术规范
55
DL/T 5122-2000
500kV架空送电线路勘测技术规程
27
JJG 2062-1990
13.81 ~ 273.15K温度计量器具检定系统
28
GB/T 17215.321-2008
1级和2级静止式交流有功电度表
GB/T 17215-2002
29
GB/T 17442-1998
1级和2级直接接入静止式交流有功电度表验收检验
30
DL/T 610-1996(2005)
84
JJG 158-1994
标准补偿式微压计检定规程
85
JJG 153-1996
标准电池检定规程
86
JJG 183-92
标准电容器检定规程
87
GB/T 20000.3-2003
标准化工作指南 第3部分:引用文件
GB/T1.22-1993
88
JJG 161-2010
标准水银温度计检定规程
JJG 161-1994
DL/T 378-2010
变压器出线端子用绝缘防护罩通用技术条件
75
DL/T 574-2010
变压器分接开关运行维修导则
DL/T574-1995
76
GB/T 7065-2004
变压器用压力释放阀
77
GB/T 7069-2004
IEC 61643-1_2005译文

IEC 61643-1:2005(第2版) 2005-03《低压电涌保护器–第1部分:低压配电系统的电涌保护器–性能要求和试验方法》目次前言引言1 总则1.1 适用范围规范性引用文件1.2 规范性引用文件2 使用条件2.1 正常使用条件2.2 异常使用条件3 定义4分类4.1端口数4.2SPD的设计类型4.3SPD的I、II和III级试验4.4使用地点4.5易触及性4.6安装方式4.7SPD的脱离器4.8过电流保护4.9按IEC 60529的IP代码的外壳防护等级4.10温度范围5 标准的额定值5.1I级试验的冲击电流I imp优选值5.2II级试验的标称放电电流I n优选值5.3III级试验的开路电压U oc优选值5.4电压保护水平U p优选值5.5交流有效值或直流的最大持续工作电压U c的优选值6 技术要求6.1一般要求6.2电气性能要求6.3机械性能要求6.4环境要求6.5安全要求I6.6对二端口和输入/输出分开的一端口的SPD的附加试验要求7 型式试验7.1 一般试验程序7.2 标识和标志7.3 接线端子和连接7.4 直接接触防护试验7.5 确定测量限制电压7.6 动作负载试验7.7 SPD的脱离器和SPD过载时的安全性能7.8 二端口和输入/输出端子分开的一端口的SPD试验7.9 附加试验8 常规和验收试验8.1常规试验8.2验收试验附录A(资料性附录)应用I级试验时对SPD的考虑附录B(规范性附录)TOV值参考文献图1- 用于单相电源去耦网络的示例图2 –用于三相电源去耦网络的示例图3 –确定电压保护水平U p的流程图图4 –测量限制电压的替代试验图5 –动作负载试验的流程图图6 –预处理和动作负载循环试验程序图6 a–I fi低于声明的短路耐受能力的SPD的试验电路图7–在低压系统故障引起的TOV下试验的试验电路示例和相应的时间程序图图8–电缆保持力的试验装置图9–弯曲试验装置图10a–试验装置图10–撞击试验装置图11–滚筒图12a–球压试验装置图12b–球压试验的载荷杆图A.1 –一般雷电流的分布表1 – I、II和III级试验表2 –适用于SPD的型式试验要求表3 – I级试验参数II表4 – III级试验波形参数的允许误差表5 –螺钉的螺纹直径和施加的扭矩表6 –螺钉型端子或无螺纹端子能连接的铜导体截面积表7 –拉力(螺钉型端子)表8 –导体尺寸表9 –拉力(无螺纹端子)表10 –确定测量限制电压需进行的试验表11 –预期短路电流和功率因数表12 –夹紧螺钉的紧固要求表13 –用于撞击要求的落下距离表14 –户外型SPD的电气间隙和爬电距离表15 –户内型SPD的电气间隙和爬电距离表16 –介电强度表17 –过载状况的电流系数k表18 –均衡浪涌电流的误差表B.1 – TOV 试验值III国际电工委员会______________低压电涌保护器–第1部分:低压配电系统的电涌保护器–性能要求和试验方法前言1) IEC(国际电工委员会)是一个由各国家电工委员会(IEC国家委员会)组成的国际性标准化组织。
GB4706-2005检测标准

第1章范围本部分涉及的单相器具额定电压不超过250V,其他器具额定电压不超过480V的家用和类似用途电器的安全。
不作为一般家用,但对公众仍可能引起危险的器具,例如打算在商店、轻工业和农场中由非专业的人员使用的器具也属于本部分的范围。
注1:这种器具的示例为:工业和商业用炊事设备、清洁器具以及在理发店使用的器具。
就实际情况而言,本部分所涉及的各种器具存在的普通危险,是在住宅和住宅周围环境中所有的人可能会遇到的。
然而,一般说来本部分并未涉及:——无人照看的幼儿和残疾人使用器具时的危险;——幼儿玩耍器具的情况。
注2:注意下述情况:——对于打算用在车辆、船舶或航空器上的器具,可能需要附加要求。
——在许多国家中,全国性的卫生保健部门,全国性劳动保护部门,全国性供水管理部门以及类似的部门都对器具规定了附加要求。
注3:本部分不适用于:——专为工业用途而设计的器具;——打算使用在经常产生腐蚀性或爆炸性气体(如灰尘、蒸汽或瓦斯气体)特殊环境场所的器具;——音频、视频和类似电子设备(GB8898);——医用电气设备(GB9706.1);——手持式电动工具(GB3883.1);——信息技术设备(GB4943);——可移动式电动工具(GB 13960)。
*******************************************.以下哪些危险是安规工程师需要考虑的:电击危险机械危险辐射危险化学危险.GB4706.1-2005标准所认可的是家用和类似用途电器在注意到制造商使用说明的条件下按正常使用时,对器具的电气、机械、火灾以及辐射等危险防护的一个国际可接受水平。
.就实际情况而言,GB4706.1所涉及的各种器具存在的普通危险,指的是什么危险?火灾危险机械危险烫伤危险触电危险辐射危险第2章规范性引用文件下列文件中的条款通过本部分的引用而成为本部分的条款。
凡是标注日期的引用文件,其随后所有的修改单(不包括勘误内容)或修订版均不适用于本部分,然而,鼓励根据本部分达成协议的各方研究是否可使用这些文件的最新版本。
GB4706-2005检测标准

第1章范围本部分涉及的单相器具额定电压不超过250V,其他器具额定电压不超过480V的家用和类似用途电器的安全。
不作为一般家用,但对公众仍可能引起危险的器具,例如打算在商店、轻工业和农场中由非专业的人员使用的器具也属于本部分的范围。
注1:这种器具的示例为:工业和商业用炊事设备、清洁器具以及在理发店使用的器具。
就实际情况而言,本部分所涉及的各种器具存在的普通危险,是在住宅和住宅周围环境中所有的人可能会遇到的。
然而,一般说来本部分并未涉及:——无人照看的幼儿和残疾人使用器具时的危险;——幼儿玩耍器具的情况。
注2:注意下述情况:——对于打算用在车辆、船舶或航空器上的器具,可能需要附加要求。
——在许多国家中,全国性的卫生保健部门,全国性劳动保护部门,全国性供水管理部门以及类似的部门都对器具规定了附加要求。
注3:本部分不适用于:——专为工业用途而设计的器具;——打算使用在经常产生腐蚀性或爆炸性气体(如灰尘、蒸汽或瓦斯气体)特殊环境场所的器具;——音频、视频和类似电子设备(GB8898);——医用电气设备(GB9706.1);——手持式电动工具(GB3883.1);——信息技术设备(GB4943);——可移动式电动工具(GB 13960)。
*******************************************.以下哪些危险是安规工程师需要考虑的:电击危险机械危险辐射危险化学危险.GB4706.1-2005标准所认可的是家用和类似用途电器在注意到制造商使用说明的条件下按正常使用时,对器具的电气、机械、火灾以及辐射等危险防护的一个国际可接受水平。
.就实际情况而言,GB4706.1所涉及的各种器具存在的普通危险,指的是什么危险?火灾危险机械危险烫伤危险触电危险辐射危险第2章规范性引用文件下列文件中的条款通过本部分的引用而成为本部分的条款。
凡是标注日期的引用文件,其随后所有的修改单(不包括勘误内容)或修订版均不适用于本部分,然而,鼓励根据本部分达成协议的各方研究是否可使用这些文件的最新版本。
高电压试验技术

二、高压交流分压器 R1 R2 k 1.分压比: R
2
C1 C 2 k C1
分压器基本要求:无感。
• 电阻分压器一般不用来测量较高的电压
CVT
C1 TT C2 δ A S L E F C3 X af R0 xf a
特高压柱式CVT
标准电压互感器
1000kV试验线段出线构架
2. 杂散电容的影响
磁电式、电动式、电磁式、整流式、静电式、感应式
磁电式:平均值; 电动式:有效值; 电磁式:有效值;
整流式:平均值; 静电式:有效值;
试品放电问题
• 试验完毕,切断电源,需待试品上的电压降至1/2试验电压以 下,将被试品经电阻接地放电,最后直接接地放电。 • 对大容量试品如长电缆、电容器等,需长时间放电。 • 对附近设备,有感应电压的可能时,也应放电或事先短路。 • 经过充分放电后,才能接触试品。 • 对于在现场组装的倍压整流装置,要对各级电容器逐级放电 后,才能进行更改接线或结束试验,拆除接线。 • 对电缆、发电机等,必须先经适当的电阻对试品进行放电。 如直接放电,可能产生频率极高的振荡过电压。 • 放电电阻视试验电压高低和试品的电容而定,须有足够的阻 值和热容量。常采用水电阻,阻值每千伏200~500欧。 • 放电棒的绝缘部分总长不小于1m,其中自握手护环到放电电 阻器下端接地线连接端的长度为0.7m,握手部分为0.3m
二、 串级直流高压装置 1.两级串级回路
2.各点电位分析
u1 U m sin t u 2 2U m u 4 4U m u3 U m U m sin t u5 3U m U m sin t
3.各元件最大工作电压
u C1 U m uC 2 uC 3 uC 4 2U m u D1 u D 2 u D3 u D 4 2U m
220kV及以上输变电设备气象管理平台技术规范书

220kV及以上输变电设备气象管理平台1总则1.1一般规定1.1.1 本技术规范规定了产品的功能要求、性能指标、资料交付、服务、验收等方面的技术要求。
1.1.2 本技术规范书提出的是最低限度的技术要求,并未对一切技术细节做出规定,也未充分引述有关标准和规范的条文,卖方应提供符合工业标准和本规范书的优质产品。
1.1.3 如果卖方没有以书面形式对本规范书的条文提出异议,则意味着卖方提供的产品完全符合本规范书的要求。
如有异议,不管是多么微小,都应在报价书中以“对规范书的意见和同规范书的差异”为标题的专门章节中加以详细描述。
1.1.4标书内技术资料应根据技术条件参数提供投标产品,提供制造方主要的材料明细。
1.1.5 对本技术条件书各条目的应答为“满足”、“不满足”、“部分满足”,不得使用“明白”、“理解”等词语。
在答复中,要求明确满足的程度,并逐条做出具体、详细的说明,凡采用“详见”、“参见”方式说明的,应指明参见文档中的具体的章节或页码,否则将导致废标。
1.1.6 本技术规范书经招标、投标双方确认后作为订货合同的技术附件,与合同正文具有同等法律效力。
1.1.7 本技术规范未尽事宜, 由买、卖双方协商确定。
1.2标准和规范本规范主要的技术依据为表1-2所列规范,这些规范的内容与本技术规范具有同等法律效力(若有不一致之处,以招标文件技术规范为准),投标产品应满足表2-1所列规范的要求。
表1-2引用的标准2技术要求2.1环境条件设备产品使用环境条件应满足表2-1指标要求。
表2-1使用环境2.2工作条件(1)微气象在线监测装置技术要求如下:多元化应用等功能,有效保障河南境内用电需求和省外特高压沿线的电力供应。
2.4系统设计要求平台的系统设计要求包括:实时监测气象数据、数据处理和分析功能、可视化界面展示、多维度告警设置、设备管理、与PMS3.0设备台账数据集成、气象预测和模拟、智能巡检、系统管理和权限管理。
这些要求旨在确保系统能够全面监测气象条件和设备状态,提高输变电设备的安全运行和可靠性。
GB4706_2005word检测标准

第1章范围本部分涉及的单相器具额定电压不超过250V,其他器具额定电压不超过480V的家用和类似用途电器的安全。
不作为一般家用,但对公众仍可能引起危险的器具,例如打算在商店、轻工业和农场中由非专业的人员使用的器具也属于本部分的范围。
注1:这种器具的示例为:工业和商业用炊事设备、清洁器具以及在理发店使用的器具。
就实际情况而言,本部分所涉及的各种器具存在的普通危险,是在住宅和住宅周围环境中所有的人可能会遇到的。
然而,一般说来本部分并未涉及:——无人照看的幼儿和残疾人使用器具时的危险;——幼儿玩耍器具的情况。
注2:注意下述情况:——对于打算用在车辆、船舶或航空器上的器具,可能需要附加要求。
——在许多国家中,全国性的卫生保健部门,全国性劳动保护部门,全国性供水管理部门以及类似的部门都对器具规定了附加要求。
注3:本部分不适用于:——专为工业用途而设计的器具;——打算使用在经常产生腐蚀性或爆炸性气体(如灰尘、蒸汽或瓦斯气体)特殊环境场所的器具;——音频、视频和类似电子设备(GB8898);——医用电气设备(GB9706.1);——手持式电动工具(GB3883.1);——信息技术设备(GB4943);——可移动式电动工具(GB 13960)。
*******************************************.以下哪些危险是安规工程师需要考虑的:电击危险机械危险辐射危险化学危险.GB4706.1-2005标准所认可的是家用和类似用途电器在注意到制造商使用说明的条件下按正常使用时,对器具的电气、机械、火灾以及辐射等危险防护的一个国际可接受水平。
.就实际情况而言,GB4706.1所涉及的各种器具存在的普通危险,指的是什么危险?火灾危险机械危险烫伤危险触电危险辐射危险第2章规范性引用文件下列文件中的条款通过本部分的引用而成为本部分的条款。
凡是标注日期的引用文件,其随后所有的修改单(不包括勘误内容)或修订版均不适用于本部分,然而,鼓励根据本部分达成协议的各方研究是否可使用这些文件的最新版本。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
lCS27.100F 24中华人民共和国国家标准GB/T17627.1----1998eqv IEC 1180-1:1992低压电气设备的高电压试验技术第一部分:定义和试验要求High- voltage test techniques forlow-voltage equipmentPart1:Definitions,test and procedure requirements1998-12-14发布1999-12-01实施国家质量技术监督局发布目次前言IEC前言1 范围2 引用标准3 定义4 对试验程序和试品的一般要求5 大气条件6 直流电压试验7 交流电压试验8 冲击电压试验9 冲击电流试验10 合成试验附录A(提示的附录) 合成试验的布置附录B(提示的附录) 试验报告中应给出的资料前言本标准是根据电力工业部1992年电力行业标准计划项目的安排,由全国高电压试验技术分标委会负责制定。
本标准是根据国际电工委员会第42技术委员会制定的标准IEC 1l80-l:1992《低压电气设备的高电压试验技术第一部分:定义和试验要求》制定的。
在技术内容上与国际标准IEC l180-l等效,编写规则上与之相同。
根据GB/Tl.l的规定,保留了该国际标准的前言(IEC前言),同时增加了《前言》。
为了使国际标准转化为本国家标准时,符合GB/Tl.1标准格式的规定,章节及条号上与国际标准稍有改变。
本标准的附录A和附录B是提示的附录。
本标准由电力工业部提出。
本标准由全国高电压试验技术及绝缘配合标准化技术委员会归口。
本标准起草单位:电力部武汉高压研究所。
本标准主要起草人:朱同春、蔡爱姣、钟连宏。
IEC前言l)IEC在技术问题上的正式决定或协议,是由代表了对此特别关切的所有国家委员会的技术委员会准备的。
它们尽量表达国际间在所涉及问题上的一致意见。
2)这些决定或协议,采用推荐标准的形式以便国际上使用,并在此意义上为各国委员会所接受。
3)为了促进国际上的统一,IEC希望所有的国家委员会在本国条件允许的范围内,尽可能采用IEC推荐标准的文本作为国家标淮。
IEC推荐标准和相应的国家标准之间的任何区别、应尽可能清楚地在国家标准中说明。
本标准由IEC第42(高电压试验技术)技术委员会准备。
本标准的文本根据下列文件:投票批准本标准的全部资料可以在上表指出的表决报告中查到。
中华人民共和国国家标准低压电气设备的高电压试验技术第一部分:定义和试验要求GB/T17627.1—1998eqvIEC1180-1:1992High-voltage test techniques for low-voltage equipment Part 1:Derinitions,test and procedure requirements国家质量技术监督局1998-12-14批准1999-12-01实施1 范围1.1 主题内容本标准规定了对试验程序和试品的一般要求,试验电压和电流的产生及测量方法、试验程序、试验结果的评估方法和试验是否合格的判据。
还规定了与试验有关的术语。
1.2 适用范围本标准适用于额定电压交流lkV及以下和直流1.5kV及以下设备的下列试验:a)直流电压绝缘试验;b)交流电压绝缘试验;c)冲击电压绝缘试验;d)冲击电流试验;e)上述各项试验的合成试验。
2 引用标准下列标准所包含的条文,通过在本标准中引用而构成为本标准的条文。
本标淮出版时,所示版本均为有效。
所有标准都会被修订,使用本标准的各方应探讨使用下列标准最新版本的可能性。
GB/T8l3—l989 冲击试验用示波器和峰值电压表(neq IEC 790:l984)GB/T2900.l9—1994 电工术语高电压试验技术和绝缘配合GB/T7354—l987 局部放电测量(neq IEC 270:1981)GB/Tl6927.1—l997 高电压试验技术第一部分一般试验要求(eqv IEC60-l:1989)GB/T16927.2—l997 高电压试验技术第二部分测量系统(eqv IEC60-2:1994)GB/Tl7627.2—1998 低压电气设备的高电压试验技术第二部分:测量系统和试验设备(eqvIEC1l80-2:1994)3 定义3.1 冲击技术和绝缘3.1.1 冲击impulse试验时施加的非周期性瞬态电压或电流。
它通常迅速上升至峰值然后较缓慢地降到零。
3.1.2 部分击穿partial breakdown当冲击施加到固体绝缘时可能产生这种现象。
它表示为在冲击电压作用下前期发生的冲击电压波形的阶跃性降低,或有关设备标准所述的其他现象。
这表明绝缘有渐进性损坏。
3.1.3 电气间距clearance两导电部分间的最短空气距离。
3.1.4 爬距creepage distance在两导电部分之间沿绝缘材料表面的最短距离。
3.1.5 固体绝缘solid insulation在两导电部分之间的固体绝缘材料。
3.2 与破坏性放电和试验电压有关的特性3.2.1 破坏性放电disruptive discharge固体、液体、气体介质及组合介质在电压作用下产生放电,放电完全桥接被试绝缘,电极间的电压迅速下降到零或接近于零的现象。
注l 试品暂时由火花或电弧短接的非持续破坏性放电可能发生,在这些情况下,试品两端的电压瞬时降到零或接近于零,根据试验回路和试品的特性,绝缘强度可能恢复并可能允许试验电压达到更高的值,这些情况也应称为破坏性放电,除非有关设备标准另有规定。
2 有些非破坏性放电称为“局部放电”,参见GB/T7354。
3 在气体或液体介质中发生的破坏性放电使用术语“火花放电”。
沿绝缘介质表面发生的破坏性放电使用术语“闪络”。
在固体介质中发生的破坏性放电使用术语“击穿”。
3.2.2 试验电压的特性characteristics of the test voltage为了定义不同类型的试验电压,本标淮规定的那些特性。
3.2.2.1 试验电压的预期特性prospective characteristics of the test voltage如果没有破坏性放电发生或限压装置不发生动作时所得到的电压特性。
3.2.2.2 试验电压的实际特性actual characteristics of the test voltage在试验期间,试品两端所呈现的特性。
3.2.2.3 试验电压值value of the test voltage各种波形的试验电压值分别在6.l.l,7.1.3,8.l.1.l中规定。
3.2.3 破坏性放电电压disruptive discharge voltage引起破坏性放电的试验电压值。
对于不同试验的规定参见6.3.2,7.3.2,8.5.3。
3.2.4 耐受电压withstand voltage耐压试验中,表征试品绝缘特性所规定的电压值。
除另有规定外,耐受电压是对标准参考大气条件而言(见5.l)。
3.2.5 确保破坏性放电电压assured disruptive discharge voltage表征与破坏性放电试验有关的特性所规定的预期电压值。
除另有规定外,确保破坏性放电电压是对标准参考大气条件而言(见5.l)。
4 对试验程序和试品的一般要求4.1 对试验程序的一般要求对于特定类型试品的试验程序,例如所用的极性,用两种极性试验时电压极性的顺序,加压次数及加压间隔时间,调整及预调整等应由有关设备标淮规定,并考虑下列因素:a)试验结果所要求的准确度;b)被观察现象的随机性和被测特性与极性的关系;c)重复加压时绝缘逐渐劣化的可能性。
4.2 试品的一般布置试验时,试品应是完整地安装上对绝缘有影响的所有部件并按照类似设备的规定工艺处理。
除有关设备标准另有规定外,试品应是干燥、清洁的,并处于稳定的环境条件中,如果有关设备标准没有其他规定,试验应在环境温度下进行,加压的程序在本标准的有关条件中规定。
5 大气条件5.1 标准参考大气条件标准参考大气条件为:温度:t0=20℃;气压:P0=l0l.3kPa。
5.2 大气条件修正系数外绝缘破坏性放电电压与试验时的大气条件有关。
通常在空气中给定路径的破坏性放电电压随着空气密度的增加而升高。
当相对湿度约大于75%时,破坏性放电电压变得不规则,特别是闪络发生在绝缘表面时。
利用修正系数可将给定条件(温度t,压力P)下所测得的破坏性放电电压换算到标准大气条件(t0,P0)下的电压值。
反之,也可将标准参考大气条件下规定的试验电压值换算到试验时环境条件下的试验电压值。
破坏性放电电压值正比于空气密度修正系数k。
除有关设备标准另有规定外,在外绝缘试验期间所施加的电压值可以由规定的耐受电压值U0乘以k得到:反之,测量到的破坏性放电电压U除以k可以校正到标准参考大气条件下的电压值U0;试验报告应包括试验时的实际大气条件(温度、气压、相对湿度)的记录和所使用的修正系数。
空气密度修正系数k取决于相对空气密度;式中:t——试验时大气温度,℃;P——试验时大气气压,kPa。
注l 当气压比值超出这个范围时参照有关设备标准。
2 当修正系数k与l有很大差别,并且涉及到空气间隙和固体绝缘时,由有关设备标准规定必要的试验程序来确保绝缘上施加到规定的电压值。
6 直流电压试验6.1 直流电压试验的定义6.1.1 试验电压值算术平均值。
6.1.2 纹波为与直流电压的算术平均值的周期性偏差。
纹波幅值是指最大值和最小值之差的一半,纹波系数则是纹波幅值与算术平均值之比值。
6.2 试验电压6.2.1 对试验电压的要求6.2.1.1 电压波形除在有关设备标淮中另有规定外,施加到试品上的试验电压应为纹波系数不大于3%的直流电压。
要注意到接入试品和试验条件可能影响纹波系数。
6.2.1.2 容许偏差如果有关设备标准没有其他规定,规定和测量到的试验电压值之间容许有±3%的偏差。
注:容许偏差为规定值和实际测量值之间的偏差。
它与测量误差不同,测量误差是指测量值和真值之间的偏差。
6.2.2 试验电压的产生和测量试验电压一般由整流装置产生。
对试验电源的要求很大程度上取决于试品的类型和试验条件,这些要求主要由电源可提供的试验电流值和性质所决定。
电源的特性应该满足在相当短的时间内对试品电容充电的要求,当试品电容很大时,也允许长达几分钟的充电时间。
电源(包括储能电容)还应能供给泄漏和吸收电流以及任何内部和外部的局部放电电流,试验中电压降不应超过5%。
试验电源的特性和测量系统的校验应按照GB/T 17627.2中的要求来进行验证。
6.3 试验程序6.3.1 耐受电压试验对试品施加电压时应从足够低的电压值开始,以防止操作瞬变过程引起的过电压的任何影响,然后应缓慢地升高电压以便能在仪表上准确读数,但也不能太慢,以免造成接近试验电压时试品上承受电压时间过长。