供暖系统毕业设计说明书

合集下载

供热管网毕业设计说明书

供热管网毕业设计说明书

沈阳建筑大学毕业设计说明书毕业设计题目哈尔滨市滨江小区供热管网及换热站设计学院专业班级市政与环境工程学院建筑环境与设备工程2003-2班学生姓名张芸栗性别女指导教师王宏伟职称副教授2007年6月11日摘要本工程为哈尔滨市滨江小区供热管网及换热站设计。

小区内所有建筑物均为民用住宅,四周为商业网点。

小区占地面积约为12万㎡,建筑面积约为15万㎡。

供暖热负荷0.68×107W,总循环水量265.03t/h。

小区一次水供回水温130℃/80℃,二次水供回水温95℃/70℃。

管网布置为闭式双管异程式系统,枝状形式。

采用补水泵定压方式,系统运行时,采用质调节调节方式,以适应热负荷的变化。

整个管道均为无补偿直埋敷设,所有管段采用预制保温管,保温材料为聚氨酯,保护层为聚乙烯,由国家标准设计图集《管道及设备保温》98R418确定其保温层厚度,通过水力计算确定管径。

小区设一个地下换热站,内设2台型号BR0.5板式换热器,2台型号为IS200-150-400C的热水循环泵(一备一用),2台型号为IS50-32-200C的补水泵(一备一用),卧式直通除污器。

整个网路由绘制的水压图可知网路压力工况均满足技术要求。

关键词:热负荷;水压图;热力交换站AbstractThis project designed the heat supply pipe network and heat—exchanging station of BinJiang district in Haerbing .All the buildings in this district are for residential use. Area covers approximately 120,000 ㎡and a building area of about 150,000 ㎡. Heating load 0.68 ×107W, with a total circulation stood 265.03t / h.Once water provides to return to water temperature 130 ℃/80 ℃, two waters provide to return to water temperature 95 ℃/70 ℃ Adopt the way of patch water pump fix press.The pipe network is designed as seamless two-pipe system with tree-shaped. When the system is functioning, it adopt the quality flux regulates, in order to adapt to the changes ofheat-load.The whole pipe is directly buried and self-compensated, the entire pipe sections are insulating constructive, (heat preservation material is polymer of ammonia and ester, protect layer is polyethylene). Design standards by the State Atlas "piping and equipment insulation" 98R418 its insulating layer thickness, through hydraulic calculation to determine diameter. We establish one underground heat-exchanging station. In this station, there are two platform board type exchange heat organ, their model is BR0.5, there are two platform cycle pump,IS200-150-400C, (with a prepared one) and there are two platform patch water pump,their model is IS50-32-200C(with a prepared one). Drawing from the entire network of hydraulic pressure on the network map known conditions are met technical requirementsKey words:heat-load;hydraulic plot;Heat-exchange station.目录第一章供热方案的确定 (3)1.1前言 (3)1.2集中供暖热负荷 (4)1.2.1集中供热系统热负荷的概算和特征 (4)1.2.2热负荷的计算 (4)1.3供热方案的确定及管道布置 (10)1.3.1供热方案的确定 (10)1.3.2热水供热管网平面布置型式 (10)1.3.3补偿器的选择及校核 (11)第二章水力计算 (14)2.1确定各用户的设计流量 (14)2.2主干线水力计算 (14)2.3支线水力计算 (14)2.4水压图绘制 (16)2.4.1热水网路压力状况的基本技术要求 (16)2.4.2绘制热水网路水压图的步骤: (16)2.5连接方式的确定 (18)第三章热水供热系统的供热调节 (19)3.1供热调节 (19)3.2直接连接质调节计算 (19)第四章换热站的形式选择及计算 (21)4.1换热站的形式选择 (21)4.2换热站的内部设备计算 (21)4.2.1循环泵的计算和选择 (22)4.2.2补给水泵的计算和选择 (23)4.2.3补水箱的选择 (23)4.2.4换热器的计算和选择 (23)4.2.5除污器的选择 (26)4.2.6换热站换热设备的布置 (26)第五章供热管道的选择及其附件 (27)5.1管材的选择及管道的链接 (27)5.2阀门的选择 (27)5.3管道的放气排水装置的布置 (28)5.4检查井的布置 (28)5.5供热管道的保温 (29)第七章技术经济分析 (31)第八章结论 (32)参考文献 (33)附表1:水温调节曲线 (1)附表2:水利计算表 (2)附表3:外文翻译 (28)哈尔滨市滨江小区供热管网及换热站设计第一章供热方案的确定1.1前言所谓集中供热是指由集中热源所产生的蒸汽,热水,通过管网供给一个城市或部分区域生产,采暖和生活所需的热量方式。

(完整版)建环暖通毕业设计说明书

(完整版)建环暖通毕业设计说明书

毕业设计(论文)哈尔滨通达6号楼采暖及换热站设计Harbin Tongda Building 6, design长春工程学院摘要现如今,随着经济的发展,人们生活水平的提高,大家对室内环境的要求也随之提高,集中供热被广泛地应用,采用集中供暖可以减少能量的浪费,提高供热效率,减少环境污染,利于管理。

我国的供暖设计、施工和运行管理工作,主要是以学习前苏联供暖技术为依据。

经过了数十年供暖通风技术人员的努力,在1975年建设部颁布的设计规范基础上,1987年颁布了适合我国国情的总结了供暖通风技术经验的国家标准《采暖通风与空气调节设计规范》(GBJ19-87)。

规范中对室外计算温度和供暖热负荷的确定以及计算原则和方法,进行了大量的研究和编制工作,其成果与世界先进国家的相比毫不逊色。

3003年颁布了现行的《采暖通风与空气调节设计规范》在进行采暖设计的时候,系统大容易出现系统的垂直失调或者水平失调,无论出现何种的失调现象,都乎对采暖系统的预期效果产生很大的影响,所以我们在进行设计的同时一定要注意这一点。

为了防止失调的产生,本设计对建筑划分成六个采暖分区进行设计,这样就能有效的防止在本设计中出现水力失调的产生。

关键词:集中供热规范水力平衡节能AbstractNow, along with economic development, people's living standards improve, people on the indoor environment requirements also will increase, central reduce energy waste, improve , which will , construction and operation management of the former Soviet Union, mainly to learn efforts of technical staff, the Ministry of Construction issued in 1975 on the basis of the design specifications, in 1987 issued a summary suitable for China's national experience in the technology standard " and air conditioning design specifications" (GBJ19-87). Specification of the outdoor temperature and to determine and calculate the principles and methods, a great deal of research and preparation, the results with the world advanced countries compared favorably. 3003 was enacted in the current " and air conditioning design specification" During , the system is prone to large systems or attention to this point. In order to prevent the generation of offset, the design of the building is divided into six design, this can effectively prevent the water appears in the design of the generation of imbalance.Keywords:Central ,供暖系统在单位时间内向建筑供给的热量。

供热工程毕业设计指导书

供热工程毕业设计指导书

供热工程毕业设计指导书适用专业:建筑环境与设备工程专业执笔:刘成丹2008.3说明:每位同学的设计内容可根据具体题目在本指导书规定的内容基础上进行适当取舍,本指导书仅供参考。

一、供热工程毕业设计任务内容㈠、设计目的在课程设计的基础上,运用学过的基础理论和专业知识,结合工程实际,参考国家有关规范、标准、工程设计图集及其它参考资料,独立完成所要求的设计任务。

同时要求系统地掌握设计计算步骤、方法,培养学生分析、解决问题的能力,为以后的工作奠定基础。

㈡、设计内容1、设计题目××建筑供暖系统设计(参数由建筑物用途及所给图纸确定)××小区供热管网设计2、基本要求设计方案的确定应依据国家有关规范,考虑设计地区的实际,综合协调热源、管网和热用户三者间的关系,经过技术、经济比较之后,方可最后决定出技术上先进可靠、经济上合理节约、使用上安全可行的最佳方案。

3、设计成果⑴、图纸这个设计要求绘制出的图纸包括管网平面布置图、管沟平面布置图、管沟纵断面图、管沟横断面图、水压图、节点(检查井)详图,供热系统原理图等,图纸一般采用1#幅面,并要求用计算机绘图。

图纸张数不少于8张。

⑵、曲线除了正式图纸之外,尚应包括如下一些曲线:热负荷随室外温度变化曲线;热负荷延续图;调节曲线(含水温变化曲线和水量变化曲线);水泵选择曲线;⑶、说明书由全部设计步骤和集散结果整理而成,其内容包括原始资料,设计方案论证,设计计算,设备及附件选择、材料清单、设计施工说明、工程概算、经济分析以及专题论述等,全部内容以70~100页为宜。

二、主要原始资料1、设计地区气象资料设计地区:供暖室外计算温度;室内采暖设计温度;冬季室外平均风速及主导风向;供暖天数(5t ℃的天数);供暖期日平均温度;不同室外温度的延续天数(小时数);最大冻土深度。

2、土建资料建筑物平面图及立面图,建筑物用途;3、热源情况现有发电厂或区域锅炉房与设计建筑的关系三、设计步骤及设计指导㈠、热负荷计算1、 采暖热负荷;2、 热水供应热负荷‘对区域系统中的宾馆、高级住宅、学生宿舍等建筑考虑热水供应,其计算方法可参阅《室内给水排水和热水供应设计规范》。

供暖课程设计说明书.

供暖课程设计说明书.

……………………………………………………………………目录第1章建筑概况 (1)1.1 工程概况 (1)1.2 设计概况 (1)1.3 设计内容 (1)第2章设计参数 (1)2.1 室外气象参数 (1)2.2 室内设计参数 (2)2.3 围护结构热工参数 (2)第3章供暖负荷计算 (3)3.1 热负荷组成 (3)3.2 校核最小传热组 (3)3.2.1 校核外墙最小热阻 (3)3.2.2 校核屋面最小热阻 (3)3.3 热负荷计算 (4)3.3.1 主要计算公式 (4)3.3.2 热负荷计算实例 (5)第4章供暖系统方案的确定 (7)第5章散热器的选择计算 (8)5.1 散热器的选用 (8)5.2 散热器的布置 (8)5.3 散热器的计算 (8)5.3.1 基本公式 (8)5.3.2 散热器计算实例 (9)5.3.3各房间散热器片数 (9)第6章水力计算 (10)6.1确定系统原理图 (10)6.2 系统水力计算 (10)设计小结 (17)参考文献 (17)第1章建筑概况1.1 工程概况本工程设计对象位于天津市,建筑功能为住宅小区,占地面积222.6㎡。

建筑面积1113㎡。

一至五层为单元房,根据建筑使用功能分析,房间主要分以下类型:卧室、餐厅、客厅、走道、卫生间、厨房1.2 设计概况本设计为整栋住宅楼冬季室内采暖工程,按要求应实行采用分户计量系统。

1.3 设计内容(1)设计准备(收集和熟悉有关规范、标准并确定室内外设计参数)(2)采暖设计热负荷及热指标的计算(3)散热设备选择计算(4)布置管道和附属设备选择,绘制设计草图(5)管道水力计算(6)平面布置图、系统原理图等绘制(7)设备材料表、设计及施工说明的编制第2章设计参数2.1 室外气象参数(1)地理纬度:北纬39°,东经117°16′;(2)大气压力及海拔:冬季大气压力102660Pa,夏季大气压力100480Pa;(3)室外计算干球温度:冬季供暖-9℃;(4)冬季最多风向的平均风速:6m/s;(5)冬季室外平均风速:3.1m/s;2.2 室内设计参数本住宅楼供住户使用,精度要求不高,主卧室和次卧室供住宿或书房使用,餐厅、厨房、客厅和走道相通故设计温度相同,为方便起见都取18℃,主卫生间和客卫生间可供洗澡用故设为23℃,户间传热邻室温差取6℃,户内邻室传热温差为5℃。

暖通专业毕业设计设计说明书

暖通专业毕业设计设计说明书

暖通专业毕业设计设计说明书1 绪论1.1设计⽬的毕业设计是⼯科⼤学培养学⽣的最后⼀个教学环节,是对四年所学知识的⼀次全⾯总结,是把理论知识应⽤于实践⼯程的⼀次很好的锻炼。

在毕业设计中,除了要熟练掌握⼤学四年所学的理论知识外,还要熟习和掌握国家有关的建设⽅针政策,综合运⽤所学的基础理论和专业知识,联系实际来解决⼯程设计问题。

通过毕业设计,明确设计程序,设计内容及各设计阶段的⽬的要求和各⼯种间的必要配合。

1.2 设计要求:1.2.1初步设计:学⽣接受设计任务后,熟习⼟建图纸与原始资料,查阅和收集资料,对设计对象选择多种空调⽅式,经过综合⽐较后,最后选定⼀种较好的⽅案。

根据有关设计规范及概算指标,对冷热负荷进⾏初步估算,初步确定冷热源⽅式、容量、台数、机房位置和⾯积并确定送、排风⽅式。

1.2.2施⼯图设计1.设计计算⑴计算室内冷、热、湿负荷;⑵确定设计⽅案。

包括系统划分、空⽓处理过程设计、计算总冷量、总热量、总风量;⑶根据冷量和风量确定选⽤空⽓处理设备和制冷设备、绘出空⽓处理系统草图;⑷全年运⾏⼯况调节分析;⑸确定室内⽓流组织形式,进⾏⽓流组织计算;⑹进⾏系统风道布置及管道⽔⼒计算;⑺系统消声减振设计;⑻系统防排烟及保温设计;⑼对⼟建、⽔、电、动⼒专业的要求;⑽设计总结。

2.绘图图纸应包括⾸页图、空调系统布置平⾯图、系统图、⼤样图、机房布置平⾯图、系统图、⼤样图。

2 设计任务及依据2.1 ⼯程概况本设计对象为长沙市某科研⼤厦,⼤厦主要有:办公室,会议室,多功能厅等。

其中地下⼀层地上⼋层,预计将机房布置于地下层。

⼯程位于长沙市,东经113?04?,北纬28?12?,海拔44.9 m 。

总空调⾯积为5625m 2。

本⼯程空调设计的任务包括本⼤厦的中央空调系统的设计及通风设计。

本中央空调系统设计要求能够实现夏季供冷和冬季供热,并能满⾜⼈体的舒适性要求。

2.2 设计依据2.2.1 长沙市室外空调设计参数台站位置:北纬28?12?,东经113?04?,海拔44.9 m ⽓象参数为:夏季:⼤⽓压:99.94 kpa 室外⽇平均温度:32.0℃室外计算⽇温差:7.3℃室外⼲球温度:35.8℃室外湿球温度:27.7℃室外平均风速:2.6m/s 冬季:⼤⽓压:101.99 kpa 采暖计算温度:0℃空调计算温度:-3℃相对湿度:81% 室外平均风速:3.7m/s 2.2.1 室内空调主要设计参数表2.1 室内设计参数办公室263 负荷计算表3.1维护结构参数3.1冷负荷计算3.1.1外墙和屋⾯瞬变传热引起的冷负荷Q c(τ)=A K[(t c(τ)+t d)kαkρ-t R]式中Q c(τ)—外墙和屋⾯瞬变传热引起的逐时冷负荷,W;A —外墙和屋⾯的⾯积,m2;K —外墙和屋⾯的传热系数,W/(m2?℃),由《暖通空调》附录2-2和附录2-3查取;t R —室内计算温度,℃;t c(τ)—外墙和屋⾯冷负荷计算温度的逐时值,℃,由《暖通空调》附录2-4和附录2-5查取;t d—地点修正值,由《暖通空调》附录2-6查取;kα—吸收系数修正值,取kα=1.0;kρ—外表⾯换热系数修正值,取kρ=0.9;3.1.2内围护结构冷负荷Q c(τ)=A i K i(t o.m+Δtα-t R)式中k i —内围护结构传热系数,W/(m2?℃);A i —内围护结构的⾯积,m2;t o.m —夏季空调室外计算⽇平均温度,℃;Δtα—附加温升,可按《暖通空调》表2-10查取。

供暖毕业设计

供暖毕业设计
改善卫生条件。 6. 房 间 的 分 隔 可 以 任 意 变 化 。 7. 在 建 立 同 样 舒 适 条 件 的 前 提 下 ,辐 射 供 暖 时 房 间 的 设 计 温 度 可 以 比 对
流 供 暖 时 降 低 2 — 3 ℃ ( 高 温 辐 射 时 可 以 降 低 5 — 10 ℃ ), 从 而 , 可 以 节省供暖能耗。 8. 有 可 能 兼 作 夏 季 降 温 的 供 冷 表 面 。 9. 有 可 能 以 塑 料 管 代 替 金 属 管 作 为 埋 管 。 同时考虑到该建筑物的外围护结构采用了一定面积的玻璃幕墙,如 果使用散热器采暖会影响建筑物的美观,因此决定采用低温地板辐射采 暖系统,而不使用散热器采暖。 在使用地板采暖时应注意以下几个问题: 1、低 温 热 水 地 板 辐 射 采 暖 系 统 的 供 水 温 度 不 宜 超 过 60 ℃ ,供 热 系 统 的 工 作 压 力 不 得 超 过 0.8MPa。 2、 地 暖 系 统 每 年 在 使用 前应 清洗 一次 过 滤 器。 具 体方 法 如 下 :首先 关闭
( 7) 热 水 暖 风 机 的热 水应 经 过 软化 处 理 , 以 减少 水垢产 生 。 ( 8) 暖 风 机 长 期 不用 时, 管 路 系统 内 充 满 水 ,以 减少氧 腐 蚀 4、 采 用 暖 风 机 采 暖 应注 意以 下几 点: ( 1)暖 风 机 安 装 后 应 进 行 水 压 试 验 ,设 计 无 规 定 时 ,单 项 试 压 以 不 小 于 0.7mpa 表 压 试 验 , 不 漏 不 渗 十 分 钟 压 降 不 超 过 10%为 合 格 综 合 试 压 以 不 小 于 0.5mpa 表 压 试 验 , 不 漏 不 渗 时 一 小 时 压 降 不 超 过 10%为 合 格 。 ( 2)应 按 厂 房 内 部的 几何 形 状 ,工 艺 设 备 布 置情 况及 气 流 作 用范 围 等因素,设计暖风机台数及位置; ( 3) 室 内 空 气 的 换 气 次 数 , 宜 大 于 或 等 于 1.5 次 /h; ( 4) 热 媒 为 蒸 汽 时, 每台 暖 风 机应 单 独 设 置 阀门 和疏水 装 置 。

小区供热系统的毕业设计说明书最终

小区供热系统的毕业设计说明书最终

摘要本次毕业设计的课题为宝鸡阳光城小区的供暖系统,包括供热外网和换热站的设计。

该小区包括住宅楼与商业用楼,总建筑面积为105410m2,热用户计算热负荷为4849kW。

小区换热站以城市供热管网130/70℃的水为热媒,用地板辐射采暖,采暖供回水温度为55/45℃。

首先,根据设计题目搜集资料,确定供热系统的相关方案。

包括集中供热系统的选择、枝状管网的确定、热负荷的计算、热媒的选择及其参数的确定。

然后,进行小区供热外网的设计。

包括管道的敷设、管网中固定支架、阀门井、补偿器等附件的位置与数量的确定,管道的保温,管网的水力计算。

通过水力计算确定管网的管径以及压力损失,并进行不平衡率的计算,尽量使每段管线都能达到水力平衡。

接着,确定换热站系统流程;对换热器、循环水泵、定压水泵等主要设备进行选型计算;合理布置所有的设备以及它们之间的管道。

同样,还要对换热站内部进行水力计算以求得各种管路的管径。

最后,根据设计的供暖系统的特点提出合理有效的运行调节方法,利用自控装置,将整个供热系统设计成为根据用户需要变质量流量运行的智能系统。

关键词:供热外网;换热站;水力计算;运行调节AbstractThis is a heating system design about one district in Bao Ji, which includes outdoor heating pipe network and heat transfer station. The district contents residence building and business building, the total constructiong area is about 105410 m2 and heat load is about 4849kW. In the heating system, the heat transfer station which takes 130/70℃high temperature heat medium as high temperature heat medium and 55/45 ℃water circulating water as heat-supplying-medium. Firstly, needing to collect some information basis the design subject, and confirming the correlation scheme about the heating system. It contents the option of the concentrate heating system, the confirming of branch pipeline network, the calculate of the heating system, the choosing of heat medium and its parameter. Secondly, putting up the design about the outdoor heating pipe network. It contents the laying of pipe, defining the position and number of the accessories such as fixed supports, valve wells and compensators, the defining of the pipeline, the hydraulic computation of the pipeline . Through the hydraulic computation, we can confirm the diameter of the pipling and the pressure lossing, computing the hydraulic unbalance rate in order to make the hydraulic balance on every pipling. Then, the process of heating medium flow is determined. After the type of heat exchanger, water circulating pumps and make-up water pumps are chosen; they and the pipelines among them are arranged rationally. Also, the hydraulic computation of internal heat transfer station shouid be workouted to meet the need of every pipling. Finally, according to the characteristic of the heating system, a reasonable and effective operation and regulation method should be proposed.Keywords: outdoor heating pipe network; heat transfer station; hydraulic calculation;operation and regulation目录前言 (4)第一章原始资料 (5)1.1工程概况 (5)1.2原始资料 (5)1.2.1气象资料 (5)1.2.2建筑资料资料 (5)1.2.3燃料资料 (5)1.2.4水质资料 (6)第二章集中供热系统的热负荷 (7)2.1集中供热热负荷的特征 (7)2.2集中供热热负荷的计算 (7)2.3集中供热系统热媒的选择 (10)2.4集中供热系统热媒参数的确定 (10)2.5热网系统型式的确定 (11)第三章室外管网的设计 (12)3.1外网管道布置原则 (12)3.2外网管道敷设方式 (13)3.3供热管道及其附件 (15)3.3.1供热管道 (15)3.3.2阀门 (17)3.3.3管道的放气与排水 (19)3.4补偿器 (20)3.4.1补偿器的特性及计算 (20)3.4.2补偿器的分类和型号选择 (21)3.5支架 (22)第四章外网水力计算 (25)4.1水力计算的主要任务 (25)4.2水力计算的基本原则 (25)4.3水力计算方法及步骤 (25)4.4管路水力计算举例 (26)第五章换热站的设计 (34)5.1设计题目 (34)5.2原始资料 (34)5.3换热站概述 (35)5.4换热站设计原则 (35)5.5换热站的布置原则 (36)5.6设计方案 (36)5.6.1换热站设计方案 (37)5.6.2采暖热水供回水系统 (37)5.6.3补水定压系统 (37)5.7设备的选择与计算 (38)5.7.1换热器 (38)5.7.2循环水泵 (39)5.7.3补水泵 (41)5.7.4补水箱的选型 (44)5.7.5水处理设备的选型 (45)5.7.6分集水器的选型 (47)5.7.7除污器的选型 (48)5.8换热站内部水力计算 (50)第六章供热系统运行调节 (53)6.1供热系统的初调节 (53)6.2供热系统的运行调节 (54)第七章供热管道的保温与防腐 (58)7.1供热管道的保温 (58)7.2供热管道的防腐 (59)参考文献 (61)致 (62)前言本次设计是关于供热外网及热源的工程设计,由换热站通过热网输送给用户所需的热量。

供热外网毕业设计说明书概要

供热外网毕业设计说明书概要

毕业设计(论文摘要随着人们生活水平的提高,集中供热被越来越多地采用,采用集中供暖可以减少能量的浪费,提高供热效率,减少环境污染,利于管理.同时采用集中供热可提高供热质量,提高人们的生活质量.但是在以往的设计中,由于外网与内网的配合往往出现缝隙,使得各个建筑物的资用压头与实际需要的出现偏差,使系统水力失调, 浪费了大量的热量,而供热效果却不甚理想.本次设计要求解决这一问题,使得系统的平衡性有一个较大的提高,减少系统的失调损失,节省燃料和电、水的消耗,并提高供热质量。

间接连接供热因其热源补水率低,热网的压力工况和流量工况不受用户的影响,便于热网运行管理。

在近年来已经成为流行的供热方式。

本次设计为贴近实际也采用了间接连接供热,在各个小区设置了热力站。

地沟敷设已被使用很久,使传统的供热管道敷设方式,本次设计的一级网使用了这种成熟的辐设方式。

近年来兴起的直埋敷设因其造价低,施工快,维护简单等特点以及越来越可靠的性能,在实际工程中也有了很多应用,本次设计的的二级网采用了这种新型的敷设方式。

关键词:间接连接供热;直埋敷设;水力平衡说明书勘误:水泵的选取有误要求必须按照正确的方法选取,而且需要知道步骤尤其是水泵的特性曲线,水泵图谱一定要明白。

不要使用软件选水泵热源循环水泵应尽量选取一用一备,不应有富裕值,两台并联使用时型号应不相同,用以调节使用。

补给水泵应选取一用一备。

Q应为1.1倍的计算值。

H应为1.2倍的理论计算值。

热力站循环水泵应选取一用一备,多台并联时,型号不应相同补给水泵一用一备。

Q应为1.1倍的计算值。

H应为1.2倍的理论计算值。

摘要的英文翻译应当重新翻译,作者水平有限,错误甚多。

- I -毕业设计(论文- II -AbstractWith the the exaltation of people’s life. The district heating system has been adopted more and more, the adoption of can reduce the waste of energy, raise the efficiency of heating, decrease the pollution of environment, benefit in management.Adopt district heating system can raise the heating quality,raise people's living quality at the same time.But in the former design, because of the match of the outside net with the inside usually appears blind side, making the press of the system providing deviation of each building need,which makes the maladjustment of the press.effective demand, make the system maladjustment, waste a great deal of energy, but provide bad heating quality.This design request resolves this problem, making the balance of the system have a biggerexaltation, reducing the of the system maladjustment, reduce the consume of electric,water.The indirect conjunction heating because of its low needing of water, the pressure condition and discharge work condition of the system is independence to the user.It is easy for the management of the heating system. The indirect conjunction heating system have already become popular in recent years.This design use this system,too.Set thermodynamic station in each block.The ditch spread have already been used for a long time, this traditionally mode is used in the first class net. Direct buried spread rise in recent years because of it’s low price,quick construction,more and more dependable function.Direct buried pipeline has been used in a lots of projects.The second class net of this design adopt this kind of new spread method.Keyword:the indirect conjunction heating system; Direct buried pipeline;press balance毕业设计(论文目录摘要 (I)ABSTRACT ........................................................... II 第一章绪论 (11.1设计题目 (11.2原始资料 (11.2.1 设计地区气象资料 (11.2.2 设计参数资料 (11.2.3 基本设计要求 (1第二章热负荷的计算及热负荷延续图的绘制 (2 2.1集中供热系统热负荷的概算 (22.1.1 集中供热系统以及热负荷的类型 (22.2热负荷的计算 (22.2.1 采暖设计热负荷的计算 (22.2.2 生活用热的设计热负荷 (52.2.3 年负荷的计算 (62.3热负荷延续时间图的绘制 (72.3.1 绘制热负荷延续时间图的意义 (72.3.2 热负荷延续时间图的绘制 (7第三章供热方案的确定 (113.1室外供热管道的平面布置 (113.1.1 供热管道的平面布置类型 (113.1.2 供热管道的定线原则 (113.1.3 热水供应方案的确定 (12第四章管网水力计算与水压图 (144.1一级网的水力计算 (144.1.1 计算方法 (14- III -毕业设计(论文4.1.2 水力计算的步骤 (144.1.3 部分管路计算实例 (154.2二级网水力计算 (194.2.1 计算步骤 (194.3绘制网路水压图 (214.3.1 绘制网路水压图的必要性 (214.3.2 网路水压图的原理及其作用 (224.3.3 绘制水压图的原则和要求 (224.3.4 绘制热水网路水压图水压图的步骤和方法 (22 第五章热水供暖系统的运行调节调节曲线 (245.1运行调节概述 (245.1.1 运行调节的意义 (245.1.2调节方式的确定 (245.1.3 二级网的调节曲线的确定 (245.1.4 确定一级网路质量—流量调节曲线 (27第六章设备选择 (296.1一级网设备选择 (296.1.1循环水泵的选择 (296.1.2补水泵的选择 (316.1.3 波纹管补偿器 (346.2 二级网设备选择 (346.2.1 循环水泵的选择 (356.2.2 补给水泵的选择 (376.2.3换热器的选取 (406.2.4 分水器、集水器 (436.2.5 补水箱的选择 (446.2.6 除污器的选择 (44第七章管道的敷设与保温 (46 7.1管道的保温 (467.1.1 保温的目的 (467.1.2 保温材料的选择 (46IV毕业设计(论文7.1.3 保温层厚度 (467.1.4 直埋管道的保温层计算 (487.2管道敷设方式 (497.2.1 敷设方式确定 (49第八章供热管道附件及应力计算 (518.1供热管道及附件 (518.1.1管道和阀门 (518.1.2 补偿器 (518.1.3 管道支座 (548.2管壁厚度及活动支座间距的确定 (548.2.1 管壁厚度的选定与校核 (548.2.2 管道活动支座间距的确定 (578.3固定支座最大间距确定 (588.4直埋管道的应力计算 (598.4.1 直埋敷设预制保温管道的应力验算方法 (59 8.4.2 直埋预制保温管的应力验算的规定 (598.5直埋管道管壁厚度的计算 (608.5.1 管道的理论计算壁厚计算 (608.5.2 基本许用应力修正系数(φ的取用 (608.6直埋管段的补偿与失稳计算 (618.6.1 管道屈服温差的计算 (618.6.2 失稳计算 (61附录 1 设备一览表 (64附录2 热力站设备样本 (65V毕业设计(论文1第一章绪论1.1 设计题目XX 市XX 区供热外网设计1.2 原始资料1.2.1 设计地区气象资料采暖室外计算温度: 24w t C =-︒; 采暖季天数:186N =天;采暖室外平均温度:9.1w pj t C =-︒ ; 最大冻土层深度:189CM 。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
本次设计对象为青海省西宁市开发区世家馨城综合楼,设计任务为下部三层商城和四至十二层居民住宅楼供暖的热负荷计算,供暖系统形式设置,采暖管道系统布置和水力计算,以及采暖附件的选择计算等。
My design title is the heating network designing ofxining.In this design ,manual of heating system mainly includes indoor and outdor parameters,calculation of heat load,choice of heating system,decision of the type of radiator anddefinitediameters of water pipe through calculation of water power.
选择供热系统需要的各种必要的设备和水泵等。整个设计严格按照规范,充分考虑技术,经济同时关注节能,使整个热网有一个较高的效率。
关键词:区域供热,热负荷,散热器,热网,系统
ABSTRACT
th the city construct's developing and energy save and environment require,theheating systems have changed from single heating to district heating.So many district heating system come out in many north cities in China.
4.本人所呈交的毕业论文,是在指导老师的指导下独立进行研究所取得的成果。论文中凡引用他人已经发布或未发表的成果、数据、观点等,均已明确注明出处。论文中已经注明引用的内容外,不包含任何其他个人或集体已经发表或撰写过的研究成果。对本文的研究成果做出重要贡献的个人和集体,均已在论文中已明确的方式标明。
学位论文作者(签名):
年 月
关于毕业论文使用授权的声明
本人在指导老师的指导下所完成的论文及相关的资料(包括图纸、实验记录、原始数据、实物照片、图片、录音带、设计手稿等),知识产权归属华北电力大学。本人完全了解大学有关保存,使用毕业论文的规定。同意学校保存或向国家有关部门或机构送交论文的纸质版或电子版,允许论文被查阅或借阅。本人授权大学可以将本毕业论文的全部或部分内容编入有关数据库进行检索,可以采用任何复制手段保存或编汇本毕业论文。如果发表相关成果,一定征得指导教师同意,且第一署名单位为大学。本人毕业后使用毕业论文或与该论文直接相关的学术论文或成果时,第一署名单位仍然为大学。本人完全了解大学关于收集、保存、使用学位论文的规定,同意如下各项内容:
I choose the basic equipment such as bump,heat exchanger with these calculatings.In my design,I supply some districts with hot water .All the designs have a stict to the bans,considering the and enconme and energy save,in order to make the network be a high efficient.
KEY WORDS :district heating,network design,heat Load,system
前 言
在人们的日常生活和社会生产过程中,都可能要用到大量的热能。所谓供暖,就是用人工方法向室内供给热量,使室内保持一定的温度,以创造适宜的生活、生产和工作条件的技术。
所有供暖系统都由热媒制备(热源)、热媒输送和热媒利用(散热设备)三个主要部分组成。热源和散热设备分别设置,用热媒管道连接起来,由热源向各个房间或者各个建筑物供给热量的供暖系统,称为集中式供暖系统,由热源、供热管网和热用户组成。按人体生理机制对气温和环境的要求,人们活动的环境温度在12℃以上较为适宜,集中供热的标准温度18℃±2℃是根据人们的生理机制而确定的。 在严寒的冬季,由于房屋围护结构的保温作用,室内的温度一般要比室外高出5℃左右,但是当室外温度在8℃以下时,室内就不能保证温度在12℃以上,这时人体就会产生寒冷感,此时就需要人为的提供一定的热量来满足舒适性要求,所以我国把采暖的室外界线温度定为8℃。
毕业论文声明
本人郑重声明:
1
2.本人完全了解学校、学院有关保留、使用学位论文的规定,同意学校与学院保留并向国家有关部门或机构送交此论文的复印件和电子版,允许此文被查阅和借阅。本人授权大学学院可以将此文的全部或部分内容编入有关数据库进行检索,可以采用影印、缩印或扫描等复制手段保存和汇编本文。
3.若在大学学院毕业论文审查小组复审中,发现本文有抄袭,一切后果均由本人承担,与毕业论文指导老师无关。
按照学校要求提交学位论文的印刷本和电子版本;学校有权保存学位论文的印刷本和电子版,并采用影印、缩印、扫描、数字化或其它手段保存或汇编本学位论文;学校有权提供目录检索以及提供本学位论文全文或者部分的阅览服务;学校有权按有关规定向国家有关部门或者机构送交论文的复印件和电子版,允许论文被查阅和借阅。本人授权大学可以将本学位论文的全部或部分内容编入学校有关数据库和收录到《中国学位论文全文数据库》进行信息服务。在不以赢利为目的的前提下,学校可以适当复制论文的部分或全部内容用于学术活动。
论文作者签名: 日期:
指导教师签名: 日期:
供暖系统毕业设计说明书
摘 要
随着我国城市建设事业的发展,以及国家对于能源与环境保护的要求,供暖系统的规模从单幢采暖系统发展成为中大型区域集中供暖系统,出现了大量住宅,公共建筑的集中供暖系统。集中供暖在节能和坏境保护方面都有很大的优势,发展速度很快。
本设计题目为青海省西宁市世家馨城综合楼的集中供暖设计,在设计中包括室内外设计参数的确定、供暖热负荷的计算、供暖系统方案的选定、散热器类型的选定及供暖系统水力计算。
相关文档
最新文档