毕业设计输电线路
输电线路毕业设计

摘要初步设计是工程设计的重要阶段,主要的设计原则都在初步设计中加以明确。
本设计包括导线和地线的比载计算、临界档距判定、应力曲线和安装曲线绘制、导线防振设计、杆塔选型、杆塔基础设计、代表档距的计算,杆塔荷载的计算,接地装置的设计,金具的选取。
在本次设计中,重点是线路设计,杆塔选型和基础设计,对杆塔的组立进行了简要的设计。
关键词:导线;避雷线;比载;应力;弧垂;杆塔定位AbstractThe preliminary design is an important stage of engineering design, the main design principles are addressed in the preliminary design. This design includes wire and ground wire than load calculation, judgement of critical span, stress curve and curve drawing, installation wire vibration control design, selection of tower, tower foundation design, on behalf of the calculation of span, tower load calculation of grounding device design, selection of hardware. In this design, with a focus on the circuit design, selection of the tower and foundation design, the design of tower group made a brief.Key words: conductor; Ground wire; Than the load; Stress; HuChui; Tower positioning目录摘要 (Ⅰ)Abstract (Ⅱ)1 原始资料介绍 (1)1.1设计情况 (1)1.2工程地质及地形情况 (1)1.3设计气象 (2)1.4导线与地线 (2)2 导地线的力学计算及曲线绘制 (5)2.1导线力学计算及曲线绘制 (5)2.2 地线力学计算及曲线绘制 (11)3导线的防振设计 (18)3.1 微风振动的形成 (18)3.2 导线的振动方程 (18)3.3 影响导线振动的因素 (18)3.4 防振措施 (20)3.5 防振锤选取与安装 (20)4 杆塔型式的选择 (23)4.1 杆塔塔型选择的要求 (23)4.2 杆塔在线路中的分类和用途 (23)4.3 钢筋混凝土电杆 (24)4.4 杆塔荷载的计算 (25)5 杆塔基础的设计 (28)5.1 杆塔基础基本要求 (28)5.2 杆塔基础的材料 (29)5.3 杆塔基础型式 (30)5.4 基础的上拔计算 (30)6 绝缘子串和金具 (32)6.1 绝缘子串的选取 (32)6.2 挂线金具 (33)6.3 空气间隙 (33)7 防雷与接地 (34)7.1 防雷设计 (34)7.2 接地设计 (34)7.3 避雷线绝缘设计 (35)8 导线对地和交叉跨越距离 (36)参考文献 (38)附图一路径走向图附图二平断面图附图三导线应力弧垂曲线图附图四导线安装曲线附图五地线应力弧垂曲线附图六地线安装曲线致谢 (39)1原始资料介绍1.1设计情况(1)本工程为新建CBNS-CB110kV线路工程,起自220KVCB(城北)变电站,止于110KVCBNS风电站升压站。
500KV输电线路典型毕业设计

东北电力大学毕业设计论文设计题目:长吉单回路送电线路新建工程学院:建筑工程学院班级:土木043班姓名:指导教师:目录500KV吉长送电线路工程第一耐张段总任务书设计摘要第一章架空线力学计算及排塔定位第一节导线的力学计算 4-16第二节地线的力学计算 16-28 第三节排塔定位 29-42 第二章架空线金具设计第一节确定防震措施,绘制防震锤安装图 43-45 第二节选择线路金具,绘制绝缘子串组装图 45-47 第三章电气设计48-54第四章杆塔结构设计第一节杆塔荷载计算 54-63 第二节断线张力荷载计算 63第三节安装荷载计算 63-66第四节荷载组合 66-67第五节 sap2000内力分析及内力验算 67-70第五章基础设计71-77 SAP2000内力分析结果设计总结读书笔记英文翻译附录附录一导线应力弧垂曲线附录二地线应力弧垂曲线附录三导线安装曲线附录四地线安装曲线附录五杆塔风荷载计算分段图参考文献1、《架空送电线路技术规程》SDJ3-792、《架空电力线路设计》王力中编3、《杆塔结构及基础》刘树堂编4、《高压架空送电线路设计手册(第二版)》东北电力学院编5、《线路电器技术》陈化钢编6、《建筑结构荷载规范》GB50009-20017、《高压架空送电线路技术机械计算》周振山编8、《建筑结构制图标准》GB/T 50105-20019、《架空送电线路施工》孙传坤编10、《送电线路金具设计》程应镗编11、《线路运行与检修1000问》山西省电力公晋城送电分公司编第一章 架空线力学计算及排塔定位第一节 导线的力学计算一、设计资料查询,选择导线型号1、耐张段总长6000m ,高差350m ,经过第七气象区。
2、根据《架空送电线路设计》第8页,500kv 送电线路可不验算电晕的导线最小外径为24.362⨯、82.263⨯、46.21⨯,本设计采用四分裂导线,选择导线型号为LGJ240/30。
由《架空送电线路设计》第245页查得所选的导线(LGJ240/30)相关数据如下:导线面积296.275mm A =,导线直径mm d 6.21=,计算拉断力N P 75620=,单位长度质量km kg G /2.9220=,由第47页查得LGJ240/30导线的最终弹性系数2mm /73000N E =,线膨胀系数C /1106.196-⨯=α。
35KV架空输电线路设计毕业设计.doc

前言通过对单回路35KV架空送电线路设计,培养学生运用所学的基本理论和方法解决实际问题的能力,提高学生实际技能以及分析思维能力和综合运用知识能力,使学生能够掌握文献检索查阅分析的基本方法,提高学生阅读外文书刊和进行科学研究的能力。
为使66KV及以下架空电力线路的身机做到供电安全可靠,技能先进,经济合理,便于施工和检修维护,必须认真贯彻国家的技术经济政策,符合发展规划,积极慎重的采用新技术,新材料,新设备。
综合考虑运行,施工,交通条件等因素,统筹兼顾,全面安排,进行多方案的比较,做到经济合理,安全适用。
架空线路设计必须从实际出发,结合地区特点,杆塔结构设计采用以概率理论为基础的极限状态设计方法,用可靠度指标度量结构构件的可靠度,在规定的各种载组合作用下的极限条件,满足线路安全运行的临界状态。
关键词:导线,避雷线设计,金具设计,杆塔结构设计,防雷设计目录前言 .................................................................................................................................. 错误!未定义书签。
第一章导地线设计 ............................................................................................................ 错误!未定义书签。
1.1导线地线设计 ........................................................................................................ 错误!未定义书签。
1.2导线的比载 ............................................................................................................ 错误!未定义书签。
【】毕业设计(220kv输电线路工程设计)

220kV双分裂双回路输电线路设计学生:阳文闯指导教师:孟遂民(三峡大学科技学院)摘要:本设计讲述了某平丘区段架空输电线路设计的全部内容,主要设计步骤是按《架空输电线路设计》书中的设计步骤,和现实中的设计步骤是不一样的。
本设计包括导线、地线的比载计算、临界档距、最大弧垂的判断,力学特性的计算,金具的选取,定位排杆,代表档距的计算,各种校验,杆塔荷载的计算,接地装置的设计以及基础设计等。
在本次设计中,重点是线路设计,杆塔定位和基础设计。
关键词:导线避雷线比载应力弧垂杆塔定位Abstract:In this text, it includes all the steps in of overhead power transmission line design, which is Accordance with《the design of overhead power transmission line 》, but it is not the same with the reality .this article discussed the conductor and the ground wire's coMParing load critical span .the maximum arc-perpendiculer judgement .mechanics property's fixed position of shaft-tower. various checking .representative span's calculating. load ppplied on iron tower calculating. equipment used in the ground connection design. metal appliance choose .In this paper, it is the focal point of line design. iron tower design and fundament design ,at last ,it is simply introduced the iron tower erecting's design and fundament design followed with fundament construction.Key words:conductor overhead ground wire coMParing loadstress arc-perpendiculer fixed position of shaft-tower前言电力作为一个国家的经济命脉不论是对于国家的各种经济建设还是对于普通老百姓的生活都起着至关重要的作用,而输电线路则是电力不可缺少的一个组成部分。
110kV架空输电线路毕业设计

1 输电线路基本知识
1.1 输电线路分类
输电线路分类方法很多,按输送电流的种类,可分为交流输电线路和直流输 电线路,按线路架设材料不同,可分为架空输电线路和电缆输电线路。一般主要 按电压等级和回路数分类。
关键词:110kV;线路设计;杆塔;接地
Summary
The graduation design based on design specification, guidelines and policies for the national economic construction, technical regulations, the criterion, in combination with the practical situation of project, ensure reliable power supply, flexible scheduling, meet all technical requirements.
表32各种风速下的风速不均匀系数a设计风速20以下2030303535及以上?100850750700无冰综合比载无冰综合比载即无冰有风时架空线自重比载和无冰风压比载的矢量和即22?r00?r02543490?38?602514覆冰综合比载覆冰综合比载即架空线的垂直总比载和覆冰风压比载的矢量和即22?39??r150?r1510886137151035表33各气象条件下导线比载的计算值比载自重比载覆冰无风无冰综合无冰综合无冰综合覆冰综合?100?350?6010?6015?6025?71510数据3277355163314493295538447437325计算临界档距与判断控制气象条件架空线的状态方程式给出了各种气象条件下架空线应力之间的关系
毕业设计输电线路

毕业设计题目:输电线路概述目录前言。
3 概述。
4 配电线路规划。
5电杆。
6架空配电线路杆位的确定。
7电杆埋深。
8架空导线。
9拉线。
11横担与绝缘子。
11线路的施工步骤。
12线路的运行与维护。
13其他配电装置。
14前言:输电线路是电力系统的重要组成部分,是发电厂与电力用户之间输送电能与分配电能的中间环节,包括各电压等级的输电线路和变电所,它担负着输送电能的重要任务。
随着国家科学技术的不断发展和进步,人民生活水平的不断提高。
人们对电力的需求也随之不断增大,电已经成为人们赖以生存和发展不可缺少的一部分。
特别是一些新兴产业的兴起,不仅带动了一方经济的大幅度跨越,也促进了电力行业有了稳定的提升。
在这种环境和背景下,输电线路也逐渐引起人们的重视。
输电线路概述输电线路按输电电压高低,可分为低压配电线路、高压配电线路、高压输电线路、超高压输电线路和特高压输电线路。
低压配电线路是指对地电压在1KV以下的电力线路,1~10KV输电线路称高压配电线路;35KV线路以前归属高压输电线路,但随着我国电力工业的发展,35KV线路一般都是城市与农村,或城市内的联络线路,已不在是电网之间的联络路线,在很多城市中已成为城市配电电网的一部分;110KV(包括66KV)到220KV线路称为高压输电线路;330KV和500KV 线路称为超高压输电线路;750KV及以上线路称为特高压输电线路。
输电线路的输电电压决定于输电容量和输电距离。
电压越高,在一定输送容量下,输送距离可越远;在一定的输送距离下,可输送的容量就越大。
但输电电压越高,线路及两端电气设备绝缘强度较高,从而使线路和设备的投资增大。
因此应通过技术经济比较,确定输电电压与输电容量、距离的合理关系。
由于我所在单位施工能力有限,大多工程为10KV~35KV的线路施工,我就以我对10KV~35KV的线路认识展开论述。
1、配电线路规划配电线路的供电容量应根据负荷统计结果而确定,但对线路设计时需考虑互供互带的可能,从而优化网架结构并提高供电可靠性。
特高压输电线路设计 毕业论文

摘要输电线路的安全距离是特高压输电线路设计过程中需要考虑的关键因素。
本文总结并分析了国内外特高压输电线路的相关研究成果,着重对输电线路的对地安全距离进行了研究。
文中首先分别用几种不同方法探讨了各种不同的天气对于输电线路最大驰度的影响,在此基础上提出了以“最大地面电场强度限值”作为我国交流特高压线路导线最小对地距离的选取原则。
进而基于逐步镜像法建立了特高压架空线下空间电场的数学模型,并以不同的电场控制指标来满足特定区域地面的控制要求,通过计算确定了1000kV级交流特高压单回和同塔双回输电线路导线在特定区域下的最小对地距离。
探讨了线路相间距离、运行电压、导体布置形式、分裂导线结构和双回路相序布置方式等因素对导线最小对地距离取值的影响规律。
关键词:特高压输电线路;最大驰度;工频电场;对地距离AbstractThe safe distance of the transmission line is a key factor to consider in the design process of the UHV transmission lines. This paper summarizes and analyzes the related research outcomes of the UHV transmission lines at home and abroad, and focuses on the safe distance of the transmission line to the ground. First, this article investigates a variety of weather impact for maximum relaxation of the transmission line in several different ways, on this basis; we make China's UHV AC Transmission Line to the maximum surface electric field strength limits "as the principle of a minimum conductor-to-ground distance selection. And then establish the mathematical model of the space electric field, which was based on the step-by-step method of mirror, under the UHV transmission line, and meet region-specific ground control requirements in different electric field control targets, calculate and determine the minimum distance of the 1000KV level UHVAC single back and the same tower back transmission Line in specific areas. This article investigate the influence of the line distance, operating voltage, conductor arrangement, the structure of the split line, and the phase sequence arrangement of the double-loop line.Keywords: UHV transmission lines; maximum relaxation; frequency electric field; distance from the ground目录摘要 (I)Abstract (II)第1章绪论 (1)1.1 特高压输电线路发展的背景与前景 (1)1.1.1 国内外特高压研究和应用的现状 (1)1.1.2 特高压电网的发展目标 (2)1.1.3 特高压输电技术的应用范围及经济性分析。
110kv输电线路毕业设计

110kv输电线路毕业设计110kv输电线路毕业设计引言:输电线路是电力系统中起着重要作用的组成部分,其设计和建设对于电力系统的安全运行和供电质量具有至关重要的影响。
本文将围绕110kv输电线路的毕业设计展开讨论,探讨设计过程中需要考虑的关键因素和技术要点。
一、设计背景和目标在开始毕业设计之前,首先需要明确设计的背景和目标。
110kv输电线路通常用于连接不同地区的电力系统,将电能从发电厂输送到用户。
因此,在设计过程中需要充分考虑输电距离、负荷需求、地形条件等因素,确保线路的稳定性和可靠性。
二、线路选线和布置选线和布置是设计中的重要环节。
在选线时,需要考虑线路的经济性、环境因素、土地利用等方面。
同时,还需要根据地形条件和线路长度确定支柱塔的布置方式,确保线路的安全性和稳定性。
三、线路参数计算线路参数计算是设计过程中的核心任务之一。
在进行线路参数计算时,需要考虑导线的电阻、电抗、电容等参数,以及地线的接地电阻等因素。
通过合理的参数计算,可以确保线路的传输能力和电压稳定性。
四、绝缘设计绝缘设计是保证线路正常运行的重要环节。
在绝缘设计中,需要考虑导线和支柱塔之间的绝缘距离、绝缘子的选型和布置等因素。
合理的绝缘设计可以有效地防止线路发生闪络和击穿等故障,确保线路的安全运行。
五、过电压和短路计算过电压和短路是线路运行中常见的故障情况。
在设计过程中,需要进行过电压和短路计算,以确定合适的保护措施和设备。
同时,还需要考虑可能的故障情况对线路的影响,确保线路的安全性和可靠性。
六、材料选择和施工要求材料选择和施工要求是设计实施的重要环节。
在选择材料时,需要考虑导线的导电性能、绝缘子的耐压能力、支柱塔的稳定性等因素。
同时,还需要制定合理的施工计划和要求,确保线路的质量和安全。
七、经济性分析在设计过程中,需要进行经济性分析,评估设计方案的成本和效益。
经济性分析可以帮助设计人员选择最优的方案,实现资源的合理利用和经济效益的最大化。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
毕业设计题目:输电线路概述目录前言。
3 概述。
4 配电线路规划。
5电杆。
6架空配电线路杆位的确定。
7电杆埋深。
8架空导线。
9拉线。
11横担与绝缘子。
11线路的施工步骤。
12线路的运行与维护。
13其他配电装置。
14前言:输电线路是电力系统的重要组成部分,是发电厂与电力用户之间输送电能与分配电能的中间环节,包括各电压等级的输电线路和变电所,它担负着输送电能的重要任务。
随着国家科学技术的不断发展和进步,人民生活水平的不断提高。
人们对电力的需求也随之不断增大,电已经成为人们赖以生存和发展不可缺少的一部分。
特别是一些新兴产业的兴起,不仅带动了一方经济的大幅度跨越,也促进了电力行业有了稳定的提升。
在这种环境和背景下,输电线路也逐渐引起人们的重视。
输电线路概述输电线路按输电电压高低,可分为低压配电线路、高压配电线路、高压输电线路、超高压输电线路和特高压输电线路。
低压配电线路是指对地电压在1KV以下的电力线路,1~10KV输电线路称高压配电线路;35KV线路以前归属高压输电线路,但随着我国电力工业的发展,35KV线路一般都是城市与农村,或城市内的联络线路,已不在是电网之间的联络路线,在很多城市中已成为城市配电电网的一部分;110KV(包括66KV)到220KV线路称为高压输电线路;330KV和500KV 线路称为超高压输电线路;750KV及以上线路称为特高压输电线路。
输电线路的输电电压决定于输电容量和输电距离。
电压越高,在一定输送容量下,输送距离可越远;在一定的输送距离下,可输送的容量就越大。
但输电电压越高,线路及两端电气设备绝缘强度较高,从而使线路和设备的投资增大。
因此应通过技术经济比较,确定输电电压与输电容量、距离的合理关系。
由于我所在单位施工能力有限,大多工程为10KV~35KV的线路施工,我就以我对10KV~35KV的线路认识展开论述。
1、配电线路规划配电线路的供电容量应根据负荷统计结果而确定,但对线路设计时需考虑互供互带的可能,从而优化网架结构并提高供电可靠性。
配电线路供电半径需根据当地情况合理确定。
但若供电半径过大,将导致电压损失增大和线损增加,所以一般规定10kV配电线路供电半径不得大于15km,低压主干线供电半径不得大于500m。
配电线路路径选择得是否合适,不仅直接影响到线路的建设费用,而且会影响到线路的运行和维护。
由于农村配电线路是直接向农村用电负荷供电,所以配电线路的路径必然与各用电负荷及其分布情况紧密相关,而负荷情况又取决于农村发展计划,所以时必须结合农村电力发展计划来综合考虑。
在确定线路路径时,可首先将配变位置及各负荷点标在地理图上,根据图上道路、建筑、河流及设施分布等情况,结合负荷分布位置在图上画出线路的路径,包括分支线路径和接户线位置。
在配电线路路径选择时要注意以下几点:①应能满足计划年限内各负荷点的供电要求;②配电线路路径应尽量接近直线,走近路、走直路,避免曲折迂回,并力求转角少;③应尽量减少交叉跨越,避免与铁路、公路、通讯线路等交叉,应避开易燃易爆地带;若必须交叉跨越时要与有关部门联系,取得协议,并注意安全距离;④尽量靠近道路,施工和运行维护方便,但不要影响生产、交通;⑤地势越平坦越好,要避开洼地、冲刷地带,避开果树林、防护林等地方;⑥尽量少占农田、良田;⑦若有重要负荷可采用专供线供电方式,以提高供电可靠性。
2、电杆电杆是架空配电线路中的基本设备之一,按所用材质可分为木杆、水泥杆和金属杆三种。
水泥杆具有使用寿命长、维护工作量小等优点,使用较为广泛。
水泥杆中使用最多的是拔梢杆,锥度一般均为1/75,分为普通钢筋混凝土杆和预应力型钢筋混凝土杆。
电杆按其在线路中的用途可分为直线杆、耐张杆、转角杆、分支杆、终端杆和跨越杆等。
①直线杆:又称中间杆或过线杆。
用在线路的直线部分,主要承受导线重量和侧面风力,故杆顶结构较简单,一般不装拉线。
②耐张杆:为限制倒杆或断线的事故范围,需把线路的直线部分划分为若干耐张段,在耐张段的两侧安装耐张杆。
耐张杆除承受导线重量和侧面风力外,还要承受邻档导线拉力差所引起的沿线路方面的拉力。
为平衡此拉力,通常在其前后方各装一根拉线。
③转角杆:用在线路改变方向的地方。
转角杆的结构随线路转角不同而不同:转角在15度以内时,可仍用原横担承担转角合力;转角在15度~30度时,可用两根横担,在转角合力的反方向装一根拉线;转角在30度~45度时,除用双横担外,两侧导线应用跳线连接,在导线拉力反方向各装一根拉线;转角在45度~90度时,用两对横担构成双层,两侧导线用跳线连接,同时在导线拉力反方向各装一根拉线。
④分支杆:设在分支线路连接处,在分支杆上应装拉线,用来平衡分支线拉力。
分支杆结构可分为丁字分支和十字分支两种:丁字分支是在横担下方增设一层双横担,以耐张方式引出分支线;十字分支是在原横担下方设两根互成90度的横担,然后引出分支线。
⑤终端杆:设在线路的起点和终点处,承受导线的单方向拉力,为平衡此拉力,需在导线的反方向装拉线。
3、架空配电线路杆位的确定当配电线路路径确定后,就可以测量确定杆位了。
首先确定首端杆和终端杆的位置,并且打好标桩作为挖坑和立杆的依据;若线路因地形限制或用电需要而有转角时,将转角杆的位置确定下来;这样首端杆、转角杆和终端杆就把线路划分为若干直线段;在直线段内均匀分配档距,就可一一确定直线杆的位置了;若线路较长,在必要时可再划分几个耐线段,耐张段长度一般不大于2km。
架空线路的档位需根据配电线路电压等级、导线的对地距离及地形等情况确定。
档距越大,电杆数越少,但为保证导线对地的安全距离,电杆就得加高。
因此高压配电线路档距一般为:在集镇和村庄为40~50m,在田间为60~100m;低压配电线路使用铝铰线时,在集镇和村庄档距一般为40~50m,在田间为50~70m;低压配电线路使用绝缘导线时的档距一般为30~40m,最大不超过50m。
对于高低压同杆架设的配电线路,其档距应满足低压线路的技术要求。
杆位确定还需注意以下几个问题:①档距尽量一致,只有在地形条件限制时才可适当前后挪移杆位;②在任何情况下导线的任一点对地应保证有足够的安全距离;③遇到跨越时,若线路从被跨越物上方通过,电杆应尽量靠近被跨越物(但应在倒杆范围以外),若线路从被跨越物下方通过,交叉点应尽量放在档距之间;跨越铁路、公路、通航河流等时,跨越杆应是耐张杆或打拉线的加强直线杆。
4、电杆埋深电杆的埋设深度,应根据电杆的材料、高度、土壤情况而定,但不应小于杆长的1/6,使电杆在正常情况应能承受风、冰等荷载而稳定不致倒杆。
为使电杆在运行中有足够的抗倾覆裕度,对电杆的稳定安全系数有如下规定:直线杆不应小于1.5 ;耐张杆不应小于1.8,转角、终端杆不应小于2.0。
电杆埋深一般值见表。
5、架空导线架空线路导线是传送电能的导体元件,运行中还将承受各种热效应和机械应力,所以对导线有如下要求:导电能力强、机械强度大、抗腐蚀、重量轻、价格便宜。
农村配电线路一般采用裸铝绞线,居民密集的城镇低压配电线路宜采用绝缘导线。
架空导线应采用符合国家技术标准的产品,禁止使用单股铝线、拆股线和铁线。
5-1架空导线截面的选择架空线路所用导线的正确选择直接关系到线路的安全经济运行和供电质量,同时直接影响到线路投资。
对导线截面的选择一般有以下几种方法:Ⅰ、按允许载流量选:当导线通过工作电流时,因电流的热效应会使导线温度升高,尤其是在导线接头处会因此而加快氧化,氧化又使接触电阻增大,使接头处温度进一步升高,形成恶性循环,将有可能造成接头处松脱或熔融。
温度升高还将导致导线的机械强度下降、导电能力下降、绝缘导线的绝缘受到损坏,甚至造成导线烧断,所以对导线有一个最高允许温度。
按允许载流量选择导线时,就是使负荷电流长期流过导线所引起的温升不致于超过最高允许温度。
Ⅱ、按经济电流密度选对线路导线而言,有一个年运行费用最小的截面,称经济截面S。
因此对应于不同材料和最大负荷利用小时数的线路导线就有经济电流密度J,经济电流密度J可从相关规程手册中查得Ⅲ、按允许电压损失选择由于农村电力负荷的特点,使得农村配电线路往往延伸较长,导线上的电压降相对较大。
为确保用户的电压质量,必须将线路电压损失限制在一定范围内,即按允许电压损失选择导线截面。
Ⅳ、按机械强度校验导线截面架空导线本身具有一定的重量,同时还要承受风雪、覆冰等外力,温度变化时还会因热胀冷缩引起受力变化,所以为了防止断线事故,导线应具有一定的机械强度,为此规定了导线的最小允许截面。
5-2 导线在电杆上的排列方式高压架空配电线路一般采用三角形排列或水平排列,大多采用三角形排列;低压架空线路一般采用水平排列;多回路导线可采用三角形排列、水平排列或垂直排列。
5-2-1 三相导线排列的次序三相导线排列的次序为:面向负荷侧从左至右,高压配电线路为A、B、C相,低压配电线路为A、O、B、C相。
在一个地区内,零线的位置应统一并有明显的标志,零线应靠近电杆或房屋内侧,在垂直布置时零线应处于最下方。
6、拉线拉线是用来平衡导线拉力和风力而设置的,以加强电杆稳定性防止倒杆。
Ⅰ、拉线的种类①普通拉线:应用于终端杆、转角杆、分支杆等处,主要用来平衡固定性的不平衡荷载力。
拉线一般固定在横担下不大于300mm处,与电杆成45度角,若受地形限制,角度可适当增大或减小,但不应大于60度或小于30度。
②人字拉线:多用于中间直线杆,用来增强电杆防风倾倒能力。
③水平拉线:电杆附近有道路等设施不宜装设普通拉线时,可安装水平拉线,。
④弓形拉线:又称自身拉线,用在受地形或环境限制不能装设普通拉线处。
普通拉线通常由上、中、下三把组成。
上把固定在抱箍上,中把是通过拉线绝缘子连接,下把通过花篮螺丝或UT型线夹与拉线棒连接。
拉线的地下部分称底把,一般采用直径不小于Φ16的拉线棒,也可采用镀锌铁线。
拉线在地下应固定在拉线盘上,拉线盘多采用钢筋混凝土块或石条。
电杆拉线要装设拉线绝缘子,安装位置距地面应不小于3米。
拉线一般宜用镀锌纲绞线,其截面应不小于1.2~1.5M,其拉拔稳定安全系数不应小于:直线杆为1.5,耐张杆为1.8,转角杆和终端杆为2.0。
7、横担与绝缘子①横担横担的作用是支持绝缘子、导线等设备,并使线路导线间保持有一定距离,所以横担必须要有一定的长度和机械强度。
配电线路常用的横担有角铁横担、瓷横担和木横担三种。
瓷横担是一种实心陶瓷构件,起绝缘子和横担的双重作用。
10kV配电线路一般用瓷横担,而低压配电线路宜采用镀锌铁横担。
横担的截面应根据导线截面和根数选择,但10kV配电线路的角铁横担的截面不应小于63mm×63mm×6mm,低压配电线路的角铁横担的截面不应小于50mm×50mm×5mm。