风机盘管加新风系统示例

风机盘管加新风系统示

SANY GROUP system office room 【SANYUA16H-
风机盘管加新风系统计算示例
一、空气处理过程如图所示:
室内状态点N (26℃,60%相对湿度)、室外状态点W (34.9℃,76%相对湿度)
二、处理过程:
S 点的确定:新风机组做与室内状态点等焓的露点送风,即室内状态点N 的等焓线与相对湿度
90%的焦点S 就是新风机组处理后的状态点。

L 点的确定:风机盘管露点送风,并认为处理后的状态点L 与室内状态点N 的温差为10℃(规范规定温差在10℃范围内,由设计人员自行选择),所以,L 点就是温度为16℃的等温线与相对湿度90%的焦点。

O 点的确定:O 点在L 点和S 点的连线上,由新风和回风的比值确定。

三、计算过程
以面积为38㎡的包厢为例,包厢人数为19人,设计参数见下表。

1、新风机组的计算及选型
新风量:31519285/xf M m h =⨯=
新风负荷: 1.2
285 1.2()(105.1158.45) 4.4336003600
xf xf w s M Q h h kw ⨯⨯=-=-= 由于新风机组一般为一层选择一台,本例题为一单独房间,没有这么小的型号,所以把计算值扩大5倍,以示例如何选择机组。

扩大5倍后,新风量为1425,新风负荷为22.15。

选择天津天大胜远中央空调有限公司的吊顶新风机组,型号为DX1.5*6。

性能参数如下表:
2、风机盘管的计算及选型
由于是等焓处理,所以风机盘管的负荷就等于室内冷负荷。

室内冷负荷:(408417)385358sn Q w =++⨯= 风机盘管风量:336003600 5.358976/1.2() 1.2(58.4541.98)sn sn n L Q M m h h h ⨯=
=-- 选择贝莱特空调有限公司的风机盘管,型号为FP-136,性能指标见下图:(选择时以中速为标准)
3、风量比值
总送风量:39762851261/sn xf M M M m h =+=+=
所以,新风占总风量的比值为285/1261=23%,回风占的比值为77%
由于送风点O 在L 和S 的连线上,由风量比值可以确定混合后的送风点O 的状态参数。

4、热湿比
湿负荷:660.278100.278190.93109100.535/w m n g g s ϕ--=⨯=⨯⨯⨯⨯=
热湿比:35.358100000.53510
w Q m ε-===⨯室
热湿比线与L 和S 连线的焦点,与O 点很近,所以选型正确。

三、洁净室之分类
1.乱流式(TurbulentFlow):
空气由空调箱经风管与洁净室内之空气过滤器(HEPA)进入洁净室,并由洁净室两侧隔间墙板或高架地板回风。

气流非直线型运动而呈不规则之乱流或涡流状态。

此型式适用于洁净室等级1,000-100,000级。

优点:构造简单、系统建造成本,洁净室之扩充比较容易,在某些特殊用途场所,可并用无尘工作台,提高洁净室等级。

缺点:乱流造成的微尘粒子于室内空间飘浮不易排出,易污染制程产品。

另外若系统停止运转再激活,欲达需求之洁净度,往往须耗时相当长一段时间。

2.层流式(Laminar):
层流式空气气流运动成一均匀之直线形,空气由覆盖率100%之过滤器进入室内,并由高架地板或两侧隔墙板回风,此型式适用于洁净室等级需定较高之环境使用,一般其洁净室等级为
Class1~100。

其型式可分为二种:
(1)水平层流式:水平式空气自过滤器单方向吹出,由对边墙壁之回风系统回风,尘埃随风向排出室外,一般在下流侧污染较严重。

优点:构造简单,运转后短时间内即可变成稳定。

缺点:建造费用比乱流式高,室内空间不易扩充。

(2)垂直层流式:房间天花板完全以ULPA过滤器覆盖,空气由上往下吹,可得较高之洁净度,在制程中或工作人员所产生的尘埃可快速排出室外而不会影响其它工作区域。

优点:管理容易,运转开始短时间内即可达稳定状态,不易为作业状态或作业人员所影响。

缺点:构造费用较高,弹性运用空间困难,天花板之吊架相当占空间,维修更换过滤器较麻烦。

3.复合式(MixedType):
复合式为将乱流式及层流式予以复合或并用,可提供局部超洁净之空气。

(1)洁净隧道(CleanTunnel):以HEPA或ULPA过滤器将制程区域或工作区域100%覆盖使洁净度等级提高至10级以上,可节省安装运转费用。

此型式需将作业人员之工作区与产品和机器维修予以隔离,以避免机器维修时影响了工作及品质,ULSI制程大都采用此种型式。

洁净隧道另有二项优点:A.弹性扩充容易;B.维修设备时可在维修区轻易执行。

(2)洁净管道(CleanTube):将产品流程经过的自动生产线包围并净化处理,将洁净度等级提至100级以上。

因产品和作业员及发尘环境相互隔离,少量之送风即可得到良好之洁净度,可节省能源,不需人工的自动化生产线为最适宜使用。

药品、食品业界及半导体业界均适用。

(3)并装局部洁净室(CleanSpot):将洁净室等级10,000~100,000之乱流洁净室内之产品制程区的洁净度等级提高为10~1000级以上,以为生产之用;洁净工作台、洁净工作棚、洁净风柜即属此类。

洁净工作台:等级Class1~100级。

洁净工作棚:为在乱流式之洁净室空间内以防静电之透明塑料布围成一小空间,采用独立之HEPA或ULPA及空调送风机组而成为一较高级之洁净空间,其等级为10~1000级,高度在2.5米左右,覆盖面积约10m2以下,四支支柱并加装活动轮,可为弹性运用。

合集下载

风机盘管加新风系统——处理过程

风机盘管加新风系统——处理过程

空调技术承德石油高等专科学校风机盘管加新风空调过程一、夏季空调过程㈠新风处理到室内焓值(湿工况)新风独立送入独立新风口εh NNO W LN ′新风设计步骤:确定W 和N 点确定新风处理后的终状态点L 12h L =h N确定室内送风状态点O3过N 作ε与φ=90~95% 的交点即为O (最大送风温差)则:G =Q /(h N –h O )Kg/s确定风机盘管处理后的状态点N'4L、O、N'在一条直线上,且有:新回风比:G/G L=ON'/LOW=(h O-h N')/(h L-h O)=(d O-d N')/(d L-d O)推出:h N'= h O-(h L-h O)G W/G Ld N'=d O-(d L-d O)G W/G L其中:G=G-G WL确定新风机组冷量和风机盘管冷量5新风机组:Q=G W(h W-h L)KwO其中:h= h NL盘管:Q=G L(h N-h N')KwO'选择设备:考虑风量、冷量、热量6新风接入风机盘管新风接入机组或送入吊顶εh NNO 风机盘管冷量不变,风量为总风量C ′L W 新风(二)风机盘管加新风系统其他处理方案t NεNOWLN′新风处理到室内干球温度(tL= t N)(二)风机盘管加新风系统其他处理方案d N εOLNWN′新风处理到室内含湿量线上(dL= d N)新风处理到低于室内含湿量(dL <dN)d N εWNO L N′室内盘管1室内冷负荷新风机组2新风冷负荷新风湿负荷室内湿负荷——温湿独立空调系统二、冬季工况空调过程设计㈠新风直接送入室内εW ′N N ′O ′E d Nd o′d E W 1新风机组加热量新风机组加湿量风机盘管加热量㈡新风接入风机盘管处理过程:h—d图:d Ed N d o′εW′NO′EW1C三、风机盘管和新风机组的选择风机盘管机组选择——每个房间分别选取根据计算所得风量、冷量、热量选择合适的产品新风机组——分系统选取机组冷、热、湿、风量应等于所负担各房间的冷、热、湿、风量之和——选取小结风机盘管加新风系统是应用非常广泛的一种空调形式,一般建议采用独立新风系统方式。

风机盘管加新风系统冬季工况的空调过程设计

风机盘管加新风系统冬季工况的空调过程设计

: 为程流理处气空的间房 入 送 后 然 , 点 态 状 风 送 内 室 到 热 加 管盘经, 合混风 回内室与中组机管盘机风在先风新, 况工季冬 计设程过调空的组机管盘机风入接风新 2 .3 。 g k /gk , 量湿含的点态状计设外室 — — — W d 中式 ) 01 ( )W d - E d ( W G = W 。 W 量湿加的组机风新定确 8 .1 .3 )9 ( )W t - 1W t ( p c・ WG = W Q 。 W Q 量热加的组机风新定确 7 .1 .3 。) ℃ ・gk ( / Jk , 容热比压定的气空干 — — — p c 中式 )8 ( ) N t - ′N t ( p c・ LG = L Q 。 L Q 量热加的组机管盘机风定确 6 .1 .3 。 1 W 点态状 的 后 热 加 风 新 出 定 确 可 即 ) 1W d , 1W t ( 由则, W d = 1W d 即 , 程过量湿含等一是热加的气空到意注 。℃ , 度温的 1 W 点态状气空的后热加风新为 1W t ;℃ , 度 温 的 E 点 态 状 的后湿加汽蒸为 E t 中式 E d 48 . 1 + 10 . 1 = E t = 1W t )7 ( E d 005 2 - E h : 即, 度温的 E 点态状于等当应度 温的 1 W 点态状的后热加风新, 此因。 程过温等一
g k /g 8 . 4 = g k / Jk 7 . 82 =
1W t 度温后热加风新 ⑤ WG ′ ) Od - Nd ( - Nd = E d G WG
。 上线长延的 ′OE 在当应亦点 ′N ′ , N 点态状的后 湿 加 汽 蒸 定 确 上 图 d - h 在 可即 ′ ) N d ,′N t ( 由

武建万 院西院学设建南华

ae办公楼中央空调设计(风机盘管加新风系统毕业设计)

ae办公楼中央空调设计(风机盘管加新风系统毕业设计)

ae办公楼中央空调设计(风机盘管加新风系统毕业设计)办公楼中央空调设计摘要本设计为天津市XX公司办公楼中央空调系统,拟为之设计合理的中央空调系统,为室内工作人员提供舒适的工作环境。

建筑共四层,总面积为4446.9m²,首层净高4.2m,其他三层净高均为3.9m。

要求采用空调夏季制冷冬季供暖。

设计的空调系统采用风机盘管—新风系统,选用水冷机组制冷冻水供冷,冬季依靠市政集中供热采暖。

设计的内容包括:选定合适空调系统的类型并确定设计方案,计算部分也十分重要,例如:空调冷负荷的计算;空调系统的划分与系统方案的确定;冷源的选择;风系统的设计与计算;室内送风方式与气流组织形式的选定;水系统的设计、布置与水力计算;风管系统与水管系统保温层的设计等内容。

除此之外,还需要进行空调末端处理设备及机房辅助设备及的选型。

需要结合所选择的空调系统的特点及办公楼的建筑结构选择合适的空调机组及末端设备,合理的布置吊顶内风管与水管的位置。

并根据所选择的空调机组选配合适的辅助设备:冷冻水循环水泵,冷却水循环水泵,开式水箱,冷却水塔,及相应的水管风管阀门等。

关键词:办公楼,中央空调,水冷机组,风机盘管—新风系统THE CENTRAL AIR-CONDITION OFOFFICIAL BUILDINGABSTRACTThe design of central air-conditioning system for the building of a Tianjin company is aimed to get a comfortable working condition indoors. The total area of the building is 4446.97 m². The height of the first floor is 4.2 meters,and the other three floor’heights are all 3.9 meters. The air-condition system is designed to supply cool air in summer, and a fan coil units (FCUs)--fresh air system is selected and central screw water chillers are used to provide the chilling water needed. In winter, the municipal central heating system is used to supply heat and keep official room warm.Some of the main points in this design are given as follows:To design an appropriate air-conditioning system for the building, the overall analysis is important. This includes the calculation, such as cooling load calculation, the estimation of system zoning; the design of air duct system and calculation; the estimation of air distribution method and the selection of relevant equipments; the design of water system and the analysis of its resistance losses; the plan of the insulation of air duct and chilled water pipes; etc.. Meanwhile, equipment selection is also an essential part of the design. According to the requirement, a fan coil units (FCUs)--fresh air system is appropriate. Thus,the main process equipment, i.e. the chiller, the fan coil units, the circulating water pumps, the cooling tower, are also determined in the design considering their characteristics and working conditions.KEY WORDS:official building, central air conditioning, cooling waterchillerfan coil units (FCUs)--fresh air system目录第一章绪论 (1)第二章系统方案的选择确定 (5)第三章工程概况 (10)§ 3.1建筑特点 (10)§ 3.2建筑相关资料 (11)§ 3.3室外设计参数 (13)§ 3.4室内设计参数 (14)第四章空调负荷计算 (16)§ 4.1围护结构瞬变冷负荷计算原理 (16)§ 4.1.1外墙和屋面瞬变传热引起的冷负荷 (16)§ 4.1.2室内传热维护瞬时冷负荷 (18)§ 4.1.3外窗瞬变传热引起的冷负荷 (19)§ 4.1.4设备散热形成的冷负荷 (21)§ 4.1.5新风冷负荷 (24)§ 4.2办公楼围护结构冷负荷计算 (25)§ 4.3各房间送风方式的确定 (29)§ 4.4 办公楼新风量和新风负荷的确定 (31)§ 4.4.1新风负荷计算举例 (31)§ 4.4.2办公楼新风冷负荷计算书 (32)第五章风机盘管加新风系统选型计算 (45)§ 5.1风机盘管系统选型计算 (45)§ 5.2新风机组的选型 (55)第六章空调风系统 (58)§ 6.1空调房间气流组织 (58)§ 6.2风口的布置 (58)§ 6.2.1新风入口注意事项 (59)§ 6.2.2风道的布置和制作要求 (59)§ 6.2.3新、排风口的防雨百叶尺寸的确定 (61)§ 6.2.4风管阀门的选择 (63)§ 6.2.5送风口的布置原则 (64)§ 6.3 风口的选择 (65)§ 6.4 新风管的设计计算 (67)§ 6.6 办公区及卫生间排风 (71)第七章空调水系统 (75)§ 7.1 空调水系统的选型比较 (75)§ 7.2 空调水系统的布置 (79)§ 7.3风机盘管水系统水力计算 (80)§ 7.3.1基本公式 (80)§ 7.3.2标准层的冷冻水供水管路水力计算 (83)§ 7.4 办公楼水管最不利循环水利计算 (91)§ 7.5 空调风机盘管水系统供、回、凝水管 (99)§ 7.6 水管系统中的阀门 (101)第八章机房布置与设备选择 (103)§ 8.1机房布置原则 (103)§ 8.2机房的设备选择 (104)§ 8.2.1冷水机组的选择 (104)§ 8.2.2水泵的选择 (105)§ 8.2.3定压补水水箱选择 (109)§ 8.2.4冷却水塔、水箱的选择计算 (112)第九章管道保温、防腐 (114)结论 (116)参考文献 (119)致谢 (120)附录 (121)第一章绪论本篇文章是对天津某机关办公楼中央空调的设计计算说明。

风机盘管加新风系统和CAD技术

风机盘管加新风系统和CAD技术
经验总结
通过该项目的实施,积累了丰富的 风机盘管加新风系统设计和施工经 验,为后续类似项目提供了有益参 考。
05
未来发展趋势与展望
风机盘管加新风系统的技术发展方向
高效节能技术
研发更高效、低能耗的风机盘管,提高系统的能效比,降低运行 成本。
智能化控制
利用物联网、传感器等技术实现系统智能化控制,提高系统的稳定 性和舒适性。
风机盘管
选择高效、低噪音的风机盘管 ,根据房间大小和负荷需求进
行合理配置。
新风处理设备
根据新风来源和室内空气品质 要求,选择适当的新风处理设 备,如空气过滤器、加湿器、 除湿器等。
水系统
设计合理的水系统,包括水管 、阀门、保温等,确保水系统 的正常运行和节能效果。
控制与监测系统
选择可靠的控制系统和传感器 ,实现对室内环境参数的实时
项目规模
客户需求
客户要求提供舒适、健康的室内环境, 同时要满足节能和环保的要求。
该项目涉及建筑面积约5万平方米, 包括办公楼、商业中心和住宅区等不 同功能区域。
CAD技术在项目中的应用
方案设计
利用CAD软件进行三维建模和方 案设计,模拟不同气流组织形式 和设备布局,优化系统配置。
施工图绘管道布局、 风口布置等,确保施工质量和进 度。
CAD技术在系统设计中的应用
建模与绘图
使用CAD软件建立风机盘管加新风系统的三维模型, 进行管道、风口等部件的精确绘图。
性能分析
利用CAD软件的模拟分析功能,对系统性能进行预测 和优化。
施工图绘制
根据设计模型,生成详细的施工图纸,指导现场施工。
CAD技术对系统性能的提升
优化设计
通过CAD技术,对系统布局、管道走向等进行优化,提高系统效率。

办公楼中央空调设计(风机盘管加新风系统毕业设计)

办公楼中央空调设计(风机盘管加新风系统毕业设计)

办公楼中央空调设计摘要本设计为天津市XX公司办公楼中央空调系统,拟为之设计合理的中央空调系统,为室内工作人员提供舒适的工作环境。

建筑共四层,总面积为4446.9m²,首层净高4.2m,其他三层净高均为3.9m。

要求采用空调夏季制冷冬季供暖。

设计的空调系统采用风机盘管—新风系统,选用水冷机组制冷冻水供冷,冬季依靠市政集中供热采暖。

设计的内容包括:选定合适空调系统的类型并确定设计方案,计算部分也十分重要,例如:空调冷负荷的计算;空调系统的划分与系统方案的确定;冷源的选择;风系统的设计与计算;室内送风方式与气流组织形式的选定;水系统的设计、布置与水力计算;风管系统与水管系统保温层的设计等内容。

除此之外,还需要进行空调末端处理设备及机房辅助设备及的选型。

需要结合所选择的空调系统的特点及办公楼的建筑结构选择合适的空调机组及末端设备,合理的布置吊顶内风管与水管的位置。

并根据所选择的空调机组选配合适的辅助设备:冷冻水循环水泵,冷却水循环水泵,开式水箱,冷却水塔,及相应的水管风管阀门等。

关键词:办公楼,中央空调,水冷机组,风机盘管—新风系统THE CENTRAL AIR-CONDITION OFOFFICIAL BUILDINGABSTRACTThe design of central air-conditioning system for the building of a Tianjin company is aimed to get a comfortable working condition indoors. The total area of the building is 4446.97 m². The height of the first floor is 4.2 meters,and the other three floor’heights are all 3.9 meters. The air-condition system is designed to supply cool air in summer, and a fan coil units (FCUs)--fresh air system is selected and central screw water chillers are used to provide the chilling water needed. In winter, the municipal central heating system is used to supply heat and keep official room warm.Some of the main points in this design are given as follows:To design an appropriate air-conditioning system for the building, the overall analysis is important. This includes the calculation, such as cooling load calculation, the estimation of system zoning; the design of air duct system and calculation; the estimation of air distribution method and the selection of relevant equipments; the design of water system and the analysis of its resistance losses; the plan of the insulation of air duct and chilled water pipes; etc.. Meanwhile, equipment selection is also an essential part of the design. According to the requirement, a fan coil units (FCUs)--fresh air system is appropriate. Thus,the main process equipment, i.e. the chiller, the fan coil units, the circulating water pumps, the cooling tower, are also determined in the design considering their characteristics and working conditions.KEY WORDS:official building, central air conditioning, cooling water chiller fan coil units (FCUs)--fresh air system目录第一章绪论 (1)第二章系统方案的选择确定 (3)第三章工程概况 (5)§ 3.1建筑特点 (5)§ 3.2建筑相关资料 (5)§ 3.3室外设计参数 (6)§ 3.4室内设计参数 (7)第四章空调负荷计算 (8)§ 4.1围护结构瞬变冷负荷计算原理 (8)§ 4.1.1外墙和屋面瞬变传热引起的冷负荷 (8)§ 4.1.2室内传热维护瞬时冷负荷 (8)§ 4.1.3外窗瞬变传热引起的冷负荷 (9)§ 4.1.4设备散热形成的冷负荷 (9)§ 4.1.5新风冷负荷 (11)§ 4.2办公楼围护结构冷负荷计算 (11)§ 4.3各房间送风方式的确定 (14)§ 4.4 办公楼新风量和新风负荷的确定 (15)§ 4.4.1新风负荷计算举例 (15)§ 4.4.2办公楼新风冷负荷计算书 (16)第五章风机盘管加新风系统选型计算 (21)§ 5.1风机盘管系统选型计算 (21)§ 5.2新风机组的选型 (24)第六章空调风系统 (25)§ 6.1空调房间气流组织 (25)§ 6.2风口的布置 (25)§ 6.2.1新风入口注意事项 (25)§ 6.2.2风道的布置和制作要求 (25)§ 6.2.3新、排风口的防雨百叶尺寸的确定 (26)§ 6.2.4风管阀门的选择 (27)§ 6.2.5送风口的布置原则 (27)§ 6.3 风口的选择 (27)§ 6.4 新风管的设计计算 (28)§ 6.6 办公区及卫生间排风 (30)第七章空调水系统 (32)§ 7.1 空调水系统的选型比较 (32)§ 7.2 空调水系统的布置 (33)§ 7.3风机盘管水系统水力计算 (33)§ 7.3.1基本公式 (33)§ 7.3.2标准层的冷冻水供水管路水力计算 (34)§ 7.4 办公楼水管最不利循环水利计算 (37)§ 7.5 空调风机盘管水系统供、回、凝水管 (39)§ 7.6 水管系统中的阀门 (40)第八章机房布置与设备选择 (41)§ 8.1机房布置原则 (41)§ 8.2机房的设备选择 (42)§ 8.2.1冷水机组的选择 (42)§ 8.2.2水泵的选择 (42)§ 8.2.3定压补水水箱选择 (44)§ 8.2.4冷却水塔、水箱的选择计算 (46)第九章管道保温、防腐 (47)结论 (48)参考文献 (49)致谢 (50)附录 (51)第一章绪论本篇文章是对天津某机关办公楼中央空调的设计计算说明。

风机盘管加新风系统示例讲课教案

风机盘管加新风系统示例讲课教案

风机盘管加新风系统示例风机盘管加新风系统计算示例一、空气处理过程如图所示:室内状态点N(26℃,60%相对湿度)、室外状态点W(34.9℃,76%相对湿度)二、处理过程:S点的确定:新风机组做与室内状态点等焓的露点送风,即室内状态点N的等焓线与相对湿度90%的焦点S就是新风机组处理后的状态点。

L点的确定:风机盘管露点送风,并认为处理后的状态点L与室内状态点N的温差为10℃(规范规定温差在10℃范围内,由设计人员自行选择),所以,L点就是温度为16℃的等温线与相对湿度90%的焦点。

O点的确定:O点在L点和S点的连线上,由新风和回风的比值确定。

三、计算过程以面积为38㎡的包厢为例,包厢人数为19人,设计参数见下表。

民用建筑空调冷负荷估算指标房间名称室内人数建筑负荷人体负荷照明负荷新风量人/m2W/m2W/m2W/m2m3/(人·h) 包厢0.5 40 84 17 151、新风机组的计算及选型新风量:31519285/xfM m h=⨯=新风负荷:1.2285 1.2()(105.1158.45) 4.4336003600xfxf w sMQ h h kw⨯⨯=-=-=由于新风机组一般为一层选择一台,本例题为一单独房间,没有这么小的型号,所以把计算值扩大5倍,以示例如何选择机组。

扩大5倍后,新风量为1425,新风负荷为22.15。

选择天津天大胜远中央空调有限公司的吊顶新风机组,型号为DX1.5*6。

性能参数如下表:2、风机盘管的计算及选型由于是等焓处理,所以风机盘管的负荷就等于室内冷负荷。

室内冷负荷:(408417)385358snQ w=++⨯=风机盘管风量:336003600 5.358976/1.2() 1.2(58.4541.98)snsnn LQM m hh h⨯==--选择贝莱特空调有限公司的风机盘管,型号为FP-136,性能指标见下图:(选择时以中速为标准)3、风量比值总送风量:39762851261/sn xfM M M m h=+=+=所以,新风占总风量的比值为285/1261=23%,回风占的比值为77%由于送风点O在L和S的连线上,由风量比值可以确定混合后的送风点O的状态参数。

暖通空调风机盘管+新风系统


N





o
入1


风机盘 管处理
W
走廊
新风机组处理 房间
L1
FCU
FCU
风机盘管个 数与新风口 个数一致
这种方式无需设专门的新风口,当风 机盘管停止运行时,送入室内的新风 量会大于设计值。
风盘散流器
• 较多的时候,风机盘管和散流器结合使用。
回风口混
FCU
FCU
出风口混
回风口混
二、新风处理状态点的分析
• 冬季工况:新风可以加热到室内温度,根据房间 的湿负荷确定新风的加湿量。
小结
• 风机盘管与新风的配合方式: 1、新风口与风机盘管回风口混合; 2、新风口与盘管送风口并联,单独送入; 3、新风管与风盘送风并联,混合送入。
• 新风状态点的确定: 1、新风承担室内湿负荷 a、新风用低温冷冻水处理; b、新风用高温冷冻水除湿,再承担室内湿负荷; 2、新风不承担室内湿负荷,只承担新风负荷; 3、通过计算室内冷负荷、湿负荷及风盘的热湿比来确定 状态点。
• 显热冷负荷和湿负荷(包括新风负荷)由风机盘管 与新风共同承担。如何分配? 目前有4种设计方案:
• 方案一:新风处理到低于室内
含湿量,承担湿负荷。这时 风机盘管只承担室内部分显
N
W
热冷负荷,在干工况下运行。
M
为了使盘管在干工况下进行,
S
φ =100%
必须提高冷冻水温度一般在 15-18℃以上。
L
(2) 干工况
房间冷热负荷和新风负荷。 • 讨论:
1、风机盘管和新风系统之间的关系与匹配? 2、新风状态点如何确定?
一、房间中新风的送风方式

办公楼中央空调设计(风机盘管加新风系统毕业设计)

办公楼中央空调设计摘要本设计为市XX公司办公楼中央空调系统,拟为之设计合理的中央空调系统,为室工作人员提供舒适的工作环境。

建筑共四层,总面积为4446.9m²,首层净高4.2m,其他三层净高均为3.9m。

要求采用空调夏季制冷冬季供暖。

设计的空调系统采用风机盘管—新风系统,选用水冷机组制冷冻水供冷,冬季依靠市政集中供热采暖。

设计的容包括:选定合适空调系统的类型并确定设计方案,计算部分也十分重要,例如:空调冷负荷的计算;空调系统的划分与系统方案的确定;冷源的选择;风系统的设计与计算;室送风方式与气流组织形式的选定;水系统的设计、布置与水力计算;风管系统与水管系统保温层的设计等容。

除此之外,还需要进行空调末端处理设备及机房辅助设备及的选型。

需要结合所选择的空调系统的特点及办公楼的建筑结构选择合适的空调机组及末端设备,合理的布置吊顶风管与水管的位置。

并根据所选择的空调机组选配合适的辅助设备:冷冻水循环水泵,冷却水循环水泵,开式水箱,冷却水塔,及相应的水管风管阀门等。

关键词:办公楼,中央空调,水冷机组,风机盘管—新风系统THE CENTRAL AIR-CONDITION OFOFFICIAL BUILDINGABSTRACTThe design of central air-conditioning system for the building of a Tianjin company is aimed to get a comfortable working condition indoors. The total area of the building is 4446.97 m². The height of the first floor is 4.2 meters,an d the other three floor’heights are all 3.9 meters. The air-condition system is designed to supply cool air in summer, and a fan coil units (FCUs)--fresh air system is selected and central screw water chillers are used to provide the chilling water needed. In winter, the municipal central heating system is used to supply heat and keep official room warm.Some of the main points in this design are given as follows: To design an appropriate air-conditioning system for the building, the overall analysis is important. This includes the calculation, such as cooling load calculation, the estimation of system zoning; the design of air duct system and calculation; the estimation of air distribution method and the selection of relevant equipments; the design of water system and the analysis of its resistance losses; the plan of the insulation of air duct and chilled water pipes; etc.. Meanwhile, equipment selection is also an essential part of the design. According to the requirement, a fan coil units (FCUs)--fresh air system is appropriate. Thus,the main process equipment, i.e. the chiller, the fan coil units, the circulating water pumps, the cooling tower, are also determined in the design considering their characteristics and working conditions.KEY WORDS:official building, central air conditioning, cooling water chillerfan coil units (FCUs)--fresh air system目录第一章绪论 (1)第二章系统方案的选择确定 (3)第三章工程概况 (5)§ 3.1建筑特点 (5)§ 3.2建筑相关资料 (5)§ 3.3室外设计参数 (6)§ 3.4室设计参数 (7)第四章空调负荷计算 (8)§ 4.1围护结构瞬变冷负荷计算原理 (8)§ 4.1.1外墙和屋面瞬变传热引起的冷负荷 (8)§ 4.1.2室传热维护瞬时冷负荷 (8)§ 4.1.3外窗瞬变传热引起的冷负荷 (9)§ 4.1.4设备散热形成的冷负荷 (9)§ 4.1.5新风冷负荷 (11)§ 4.2办公楼围护结构冷负荷计算 (11)§ 4.3各房间送风方式的确定 (14)§ 4.4 办公楼新风量和新风负荷的确定 (15)§ 4.4.1新风负荷计算举例 (15)§ 4.4.2办公楼新风冷负荷计算书 (16)第五章风机盘管加新风系统选型计算 (21)§ 5.1风机盘管系统选型计算 (21)§ 5.2新风机组的选型 (25)第六章空调风系统 (27)§ 6.1空调房间气流组织 (27)§ 6.2风口的布置 (27)§ 6.2.1新风入口注意事项 (27)§ 6.2.2风道的布置和制作要求 (27)§ 6.2.3新、排风口的防雨百叶尺寸的确定 (28)§ 6.2.4风管阀门的选择 (29)§ 6.2.5送风口的布置原则 (29)§ 6.3 风口的选择 (29)§ 6.4 新风管的设计计算 (30)§ 6.6 办公区及卫生间排风 (32)第七章空调水系统 (34)§ 7.1 空调水系统的选型比较 (34)§ 7.2 空调水系统的布置 (35)§ 7.3风机盘管水系统水力计算 (35)§ 7.3.1基本公式 (35)§ 7.3.2标准层的冷冻水供水管路水力计算 (36)§ 7.4 办公楼水管最不利循环水利计算 (39)§ 7.5 空调风机盘管水系统供、回、凝水管 (41)§ 7.6 水管系统中的阀门 (42)第八章机房布置与设备选择 (43)§ 8.1机房布置原则 (43)§ 8.2机房的设备选择 (44)§ 8.2.1冷水机组的选择 (44)§ 8.2.2水泵的选择 (44)§ 8.2.3定压补水水箱选择 (46)§ 8.2.4冷却水塔、水箱的选择计算 (48)第九章管道保温、防腐 (49)结论 (50)参考文献 (51)致 (52)附录 (53)第一章绪论本篇文章是对某机关办公楼中央空调的设计计算说明。

风机盘管加新风系统设计原理及特点

风机盘管加新风系统设计原理及特点风机盘管属于中央空调系统末端,其本身有一定的除湿功能,在家用中央空调领域,风机盘管除湿功能有一定的效果,但要想彻底解决室内空气质量问题,我们必须借助新风新风,采用风机盘管加新风系统的设计形式可以有效的解决空气温度与湿度问题。

风机盘管加新风系统设计原理在通常的风机盘管加新风系统中,室外空气在新风机组里仅被处理到室内状太点等焓的机器露点,新风负荷与部分湿负荷由新风系统承担,室内冷、湿负荷与新风部分湿负荷由风机盘管承担。

由此可知,在此种处理过程中,风机盘管始终处于湿工况下,本来自身处理湿能力就比较差,这种情况下除了处理室内全部负荷外,还要处理新风的部分湿负荷,对于人员密集的大空间超市商场类建筑,如坚持使用这种处理过程,会给风机盘管带来更大的湿处理压力。

这种情况下产生大量凝结水,而时有发生渗顶现象也是合情合理。

为了能够使风机盘管少产生或不产生冷凝水,也就是让新风承担大部分或全部湿负荷的处理过程是人员密集的大空间超市商店类建筑采用的合理过程。

对于夏季当新风承担全部室内负荷,风机盘管仅承担照明、日射、人体等显热负荷的系统可以称作为干工况运行风机盘管加大新风机组除湿机系统。

风机盘管加新风系统特点与传统的风机盘管系统相比有以下主要特点:风机盘管负荷减小,要求冷水温度较高,盘管排数减少;新风机组负荷增大,要求冷水温度较低,大焓差处理,盘管排数增多;风机盘管干工况运行,无滋菌问题,卫生条件好。

不过这种系统国内应用较少。

贝雷片可能是大焓差处理的新风机组不是很普及,但是这是解决风机盘管系统应用到人员密集的大空间超市商场类建筑的一个途径。

中央空调主要功能是系统调节室内温度,除湿只是中央空调附加功能,在天气潮湿的情况下,通过运行中央空调风机盘管可以解决室内过湿问题。

感谢下载!欢迎您的下载,资料仅供参考。

风机盘管加新风夏季处理过程

风机盘管加新风夏季处理过程嘿,朋友们!咱今天来聊聊风机盘管加新风夏季处理过程,这可真是个有意思的事儿呢!你想想看,夏天那热得让人抓狂的天气,要是没有个好的空气处理办法,那可咋整啊!风机盘管加新风就像是我们在炎热夏天里的一把清凉伞。

风机盘管呢,就像是个勤劳的小蜜蜂,不停地工作着,把室内的空气吸进来,处理一下,再送出去,让我们能感受到凉爽舒适的风。

它就那么默默无闻地在那里转啊转,给我们带来舒适。

新风呢,那就像是一股清新的泉水,源源不断地给我们送来新鲜的空气。

咱可不能老闷在那污浊的空气里呀,得有新鲜的气息进来,让我们精神一振。

那这个处理过程是咋样的呢?就好像我们做饭一样,得有一道道工序。

首先呢,新风从外面进来,就像刚买来的新鲜食材。

然后呢,它要经过一系列的过滤啊、处理啊,把那些杂质啊、灰尘啊什么的都去掉,这就好比把食材洗干净、切好。

接下来,风机盘管开始发挥作用啦,它把处理好的新风和室内的空气混合起来,调节好温度和湿度,就像把各种调料加进去,让这道菜变得美味可口。

最后呢,这股舒爽的空气就被送到我们身边啦,让我们感觉就像在大自然里一样。

你说这神奇不神奇?这可比我们自己手动去调节要方便多啦!而且啊,这就像是给我们的房间请了个专业的空气管家,啥都给我们打理得好好的。

咱再想想,如果没有这个风机盘管加新风的处理过程,那夏天得多难熬啊!那空气不流通,闷得慌,人都要憋坏了。

有了它,我们就能舒舒服服地享受夏天啦,不用担心被热得心烦意乱。

总之呢,风机盘管加新风夏季处理过程真的是太重要啦!它让我们的夏天变得不再难熬,让我们能在一个舒适的环境里愉快地生活和工作。

这可不是开玩笑的呀,朋友们!所以啊,我们可得好好珍惜这个神奇的技术,让它为我们的生活增添更多的美好和舒适呢!你们说是不是这个理儿?。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
相关文档
最新文档