串联补偿线路SSR分析研究

合集下载

串联电容补偿线路保护算法的可解性分析

串联电容补偿线路保护算法的可解性分析
LIYi e g .YANG i - a。 n f Jnb i
( .Ifr t nC 1,Gu n d n ca i. h ni g u n d n 2 0 8 hn ;2 hn o ten P we i 1 nomai o. o a g o gO e nUnv ,Z a j n ,O a g o g54 8 ,C ia .C ia Suh r o rGr a d
Co ,L d. . t ,Gu n z o 1 6 3,Ch n ) a g h u5 0 2 ia
Ab ta t n ve o h r b e rsn r m h e isc m p n a i g c p c t n e i t o u e n o ta s s i n l e n h sr c :I i w ft ep o l ms a i g f o t es re o e s tn a a i c n r d c d i t r n mi o i sa d t e i a s n i fu n e o i e p o e t n,t i p p r a a y e h o v b lt f t e mo e t o , a p o e t n ag r t m o e i s n le c n l r t c i n o hs a e n lz s t e s l a i y o h d l me h i d r t c i l o ih f r s re - o c mp n a e r n miso i e .I S i d c t d t a i l n i a s t e me h S t n c sia e h o v n f t i . o e s t d t a s si n l s ti n ia e h tsmp e a d v s la h t o i ,i e e st t s t e s l i g o h r n u d d o d rl e r e u t n g o p ,a d t e r s lso i l t n t s n ac l t n c n i e a l e i t r m h c u lv le . r e i a q a i r u s n h e u t fsmu a i e ta d c lu a i o s r b y d v a e f o t e a t a a u s n o o o d

【双回线】500kV上承双回线路保护与串补保护相互影响分析[1]

【双回线】500kV上承双回线路保护与串补保护相互影响分析[1]

影响, 阐述了串补保护与线路保护的配合情况。 研究结果表明, 纵联电流差动保护受串补影响最小, 优于
其他原理的保护。
关键词: 串联电容补偿; 距离保护; 纵联距离保护; 保护超越
中图分类号: TM773
文献标志码: A
文章编号: 1004-9649(2010)08-0087-04
0 引言
串补技术是在高压长线上加装串联电容以补偿 线路感抗,缩短交流传输的电气距离,提高线路输送 容量,降低线路输送损耗,同时可以限制短路容量, 更加合理地分配输送功率, 从而提高电力系统的稳 定运行水平和经济性、可靠性 。 [1-2] 本文根据上(内蒙 古上都电厂)承(承德 500 kV 变电站)双回线路加装 串补工程的实际情况, 分析串补系统与线路保护的 相互影响。
图 5 距离保护测量阻抗轨迹 Fig.5 Measuring impedance locus diagram of
distance protection
距 离 II 段 和 III 段 的 整 定 要 保 护 整 条 线 路 , 考 虑其与串补本体保护的配合 ,距离 II 段的阻抗定值 按本线路无串补时对末端短路有灵敏度整定, 以保 证串补退出运行时对末端短路有灵敏度。距离 III 段 的阻抗定值按常规整定,由于时间整定较长,不考虑 串补的影响,其特性与常规相同,不做改变。
2.6 串补本体保护与线路保护配合
对于承德站上承线路断路器, 串补保护采用直 跳回路至断路器操作箱;对于上都侧,通过差动保护 及纵联保护通道发远跳命令。 串补本体故障及其保 护的动作行为,主要影响输电线路电流,电压几乎没 有变化,故零序方向与工频变化量距离,几乎不受 影响[6]。 线路发生故障时,线路保护给串补保护开入 信号,具体逻辑如图 7 所示。

TCSC与SVC在SSR中应用及经济性比较

TCSC与SVC在SSR中应用及经济性比较

TCSC与SVC在电力系统SSR中应用及经济性比较XXX(XXXXXXXXXXXXXXXXXXXXXXXX)摘要:针对电力系统远距离、大容量输电中的串联补偿技术容易引起系统次同步谐振(SSR)问题;基于IEEE 次同步谐振第一标准测试系统,在PSCAD/EMTDC中搭建晶闸管控制串联电容器(TCSC)和静止无功补偿器(SVC)模型,利用测试信号法从电气阻尼和经济性两方面讨论TCSC与SVC抑制SSR效果。

研究发现:在实测容量下,SVC较TCSC投资偏多,但在整个次频段内(尤其是在主导模式下)SVC提升电气阻尼较TCSC更多;时域仿真表明加入SVC较TCSC而言,扭矩收敛速度更快,抑制效果更好。

关键词:次同步谐振;可控串补;静止无功补偿器;测试信号法;经济性中图分类号:TM76 文献标识码:A 文章编号:The application in SSR and economic comparison between TCSC and SVCWU Xiao-gang,YUAN Yi-tao,KANG Ji-tao(School of Electrical Engineering,Southwest Jiaotong University,Chengdu 610031,China) Abstract: Aim at the problem of sub-synchronous resonance(SSR) caused by the series compensation technology used in the long-range and high-capacity transmission power system, the models of thyristor controlled series capacitor(TCSC) and static var compensator(SVC) are built in PSCAD/EMTDC based on the first standard IEEE sub-synchronous resonance test system. The suppression effect is discussed from the two aspects of electrical damping and economic with the test signal method. The study shows: the investment of SVC is much bigger than TCSC at the measured capacity; However, the electrical damping enhanced by the SVC is more than TCSC in the all sub-frequency; time domain simulation show that comparied with TCSC, the torque converges is faster and suppression effect is better when adding SVC.Keywords:sub-synchronous resonance; TCSC;SVC; test signal method; economy0引言我国能源分布不均以及随着用电负荷的日益增大,电力系统大容量、远距离输电势在必行;采用串联电容补偿是提高交流输电线路输送能力、控制并行线路之间的功率分配和增强电力系统暂态稳定性的一种十分经济有效的方法[1]。

【精品】高压输电线串联电容补偿问题探讨

【精品】高压输电线串联电容补偿问题探讨

高压输电线串联电容补偿问题探讨1引言对于远距离输电线,其输电能力主要取决于线路的稳定极限[1],功角稳定性使输送功率、输电距离受到限制,必须采取补偿措施。

串联电容器补偿可使系统稳定极限大幅度提高,从而提高线路的输电能力。

但是,普通串补可能引起次同步谐振问题,在工程实际中,一般将普通串补与可控串补结合安装以消除次同步谐振[4]。

而且,串联补偿对短路电流产生严重影响,从而干扰继电保护的正常运行。

实质上,串补电容器的安装位置、补偿容量的确定是一个系统工程,涉及系统稳定性、次同步谐振、继电保护、弗兰蒂效应[2](即轻载过电压)、成本等等方面,本文主要论述前三个方面. 2分布参数模型对于典型的长距离高压架空输电线路,由沿绝缘子串的漏电流以及电晕而产生的并联电导实际上为零,而且,其单位长度电阻远小于单位长度电抗,因此,长距离高压架空输电线路可以视为无损耗传输线,其正弦稳态传输方程[2]为:式中:θ—-电气长度; Z——特征阻抗;VS——线路送端电压相量; IS——线路送端电流相量;Vr——线路受端电压相量;Ir——线路受端电流相量. 电气长度θ=βD,代表线路全长,D为相位常数。

电磁波沿架空输电线路的传播速度接近光速,在50Hz交流系统中,相位常数β≈1.06×10-3rad/km。

经分析,图1所示的π型电路,其二端口网络传输方程与方程(1)完全一致。

而且,实质上,无损耗传输线的分布参数等效电路原理图[3]就是图1.3功角稳定性3.1 无补偿线路的稳定极限根据图1,可以求得无补偿输电线路的功角方程为:式中:Rr—-线路受端输送的有功功率; RS——线路送端输送的有功功率; Qr——线路受端输送的无功功率;QS——线路送端输送的无功功率;δ——线路送端电压与线路受端电压的相角差。

取线路额定电压为U,定义根据公式(2)、(3)、(4),如果VS=Vr=U,则当Pr=P0时,有QS=Qr=0,线路与两端系统之间没有无功功率的交换,对于线路每个单位长度,电容产生的无功功率等于电感吸收的无功功率,而且,沿线电压都为额定电压,这就是电压和无功控制的最佳状态.P0叫作自然负荷。

电气工程论文-次同步谐振对SSR的有效抑制

电气工程论文-次同步谐振对SSR的有效抑制

第1章绪论1.1 课题的背景和意义随着串补技术的广泛应用,电厂大机组台数和类型的增多以及电网互联情况的日趋复杂,SSR的影响因素也急剧增加,潜在的风险也逐步增大[1-6]。

采用传统的抑制方案需要增加机组切机台数才能有效的抑制SSR,已不能完全满足工程要求,因此需要寻求新的解决办法来减少切机台数来抑制SSR发散。

基于此,本文以上都电厂出现的次同步谐振问题为研究对象进行抑制方案的研究[7-15]:目前课题组已对上都电厂串补输电系统一二期工程研究中所采用SEDC+TSR的方式来抑制SSR进行了深入研究,现场试验验证了该方案的有效性。

而对上都电厂远期工程的SSR风险评估发现,采用SEDC+TSR的方式进行SSR抑制,在一些SSR风险比较严重的工况和扰动情况下,由于SEDC受到容量限制等问题,需要TSR进行多台机组的切除才能实现SSR的有效抑制。

之前的抑制措施无法满足上都电厂串补输电系统三期工程的SSR抑制切机需求,经过研究决定采用SEDC+GTSDC+TSR三者协调作用的方案来抑制SSR减少机组的切机台数,然后通过特征值分析和大量的时域仿真证明了方法的有效性,但是只要当SEDC和GTSDC参数恰当的时候才能有效的抑制SSR;相反,若参数不合适还会起到帮助发散的作用,所以如何协调二者的参数是能否起到有效抑制作用的关键问题。

本文也是基于这一点提出了SEDC和GTSDC参数优化设计的方法,可以减少切机台数抑制SSR问题。

对同类次同步谐振的研究也有很强的指导和借鉴意义。

1.2 次同步谐振问题研究现状由串补而引起的次同步谐振问题,国内外学者进行了大量的研究和工程实践,国际电气电子工程师协会专门成立了次同步谐振问题研究小组,对SSR的研究起到了关键的推动作用[16-25]。

国内的专家也进行了大量SSR问题的研究,总结和归纳出了很多研究成果。

- 1 -1.2.1 SSR产生机理与分析方法次同步谐振的产生机理可从以下三个方面加以解释[22-27]:(1)感应发电机效应(2)机电扭振互作用(3)暂态力矩放大作用感应发电机效应和机电扭振互作用属于小扰动稳定,常用线性化模型和小扰动分析方法(如特征分析法、复数力矩系数法)加以研究;而暂态力矩放大作用常出现在大扰动的情况下,会造成发电机轴系较大的扭振,属于大扰动下的强非线性,通常采用电磁暂态程序仿真分析。

输电线路串联电容器补偿研究

输电线路串联电容器补偿研究

输电线路串联电容器补偿研究摘要:串联电容补偿技术是一种提高交流输电线路稳定极限的经济而有效的手段。

然而,串联补偿装置的存在破坏了传输线路的均匀性,容性阻抗的存在使电压和电流的相位发生变化,进而影响保护的动作特性。

文章首先介绍了串联电容器补偿的作用和应用特点,然后分析了串联电容器补偿对线路保护的影响,最后结合福建省电力有限公司电业局实践简要介绍了国内外主流厂家针对串联补偿对线路保护的影响提出的解决办法。

关键词:串联电容器;补偿;线路保护;影响串联电容补偿技术是一种提高交流输电线路稳定极限的经济而有效的手段。

在线路上加装串联补偿能大幅度提高线路的输送能力和输电系统的稳定性,从而确保电网安全、稳定、经济运行,因而在电网建设及改造中日益得到重视,串联补偿技术已经成为建设“智能电网”的有效途径。

目前我国已经在南方电网500 kV天广双回线路、华北电网大房500 kV双回线路、阳城电厂500 kV送出线路等工程中装设了串联电容补偿装置并投入运行。

随着电网规模的不断发展,为提高输送容量,提高稳定极限,对串补技术的应用也将逐渐增加,还有大量输电线路计划加装串联电容补偿装置。

特别是在远距离、大容量坑口电厂的送出线路中,串补及可控串补技术将得到更大范围的应用。

然而,线路上装上串联电容器补偿后会破坏线路阻抗随短路故障点距离增长而增加的简单关系,可能引起线路保护超越动作或失去方向性。

分析研究串联补偿对继电保护的影响,有利于保障工作实践中串联补偿线路工程的实施,文中,笔者将对串联电容器补偿对线路保护的影响重点展开分析。

1 串联电容器补偿的作用串联电容补偿装置是串联在输电线路中以补偿线路感抗,由电容器及保护设备、控制设备等组成的装置。

在输电线路上加入串联电容器对电力系统稳定有较大作用,具体表现如下几个方面:①能够减小线路感抗,缩小两端电势间的相角差,从而获得较大稳定裕度和较高传输容量。

提高电力系统的稳定性,增加系统输送能力。

串联无功补偿技术在配电网中的应用分析

串联无功补偿技术在配电网中的应用分析

赵文忠(1966—),男,副教授,从事电机与电力系统的教学和科研。

串联无功补偿技术在配电网中的应用分析赵文忠1,王东平2(1.河西学院,甘肃张掖734000;2.江苏斯菲尔电气股份有限公司,江苏江阴214429)摘要:通过理论分析和软件仿真,研究了在配电网中采用串联补偿技术的可能性及效果。

研究表明,在配电网中采用串联补偿技术有助于配电网电压稳定,可实现配电网潮流控制和电能质量改善。

其补偿效果优于传统的并联补偿,有一定的工程应用前景。

关键词:配电网;串联补偿;原理;补偿效果中图分类号:TM 714.3文献标识码:A文章编号:1001-5531(2010)05-0037-03Application Analysis of Series Reactive Power Compensation in Distribution NetworkZHAO Wenzhong 1,WANG Dongping 2(1.Hexi University ,Zhangye 734000,China ;2.Jiangsu Sfere Electric Co.,Ltd.,Jiangyin 214429,China )Abstract :On the basis of the theoretical analysis and software simulation ,focused on the possibility and effect of the application of series compensation technology in the power distribution network.It was indicated in the re-search that the application of series compensation technology could help improve the voltage stability in the power istribution network and also made it possible to control the power flow and improve the electrical energy effect of se-ries reactive power compensation surpassed the traditional parallel connection compensation ,there were some pros-pects in applying this technology in engineering.Key words :distribution network ;series compensation ;principle ;compensation effect王东平(1959—),女,工程师,从事电气智能化仪表研究与开发工作。

10kV配网串联补偿方式研究及运行效果

10kV配网串联补偿方式研究及运行效果

10kV配网串联补偿方式研究及运行效果作者:马利来源:《科学与财富》2019年第04期摘要:串联电容器补偿技术在低电压治理领域主要起到改善配网线路全线电压分布、提升线路中特别是末端低电压的作用。

适用于需要改善电压质量、功率因数、电能输送能力的10kV配电网长线路,特别是跨越山区、负荷重或存在大型工业负荷的农村配网线路。

本文基于串补装置在平阳海滨855线的典型应用,结合理论和工程两个方面,论证了串联补偿手段对低电压治理的效果。

关键词:串联电容器补偿;线路;电压1. 引言线路导线与线缆呈感性,线路长度与感性阻抗呈正比,因此越长的线路其末端电压降相对越严重,电能输送能力也越低。

特别是末端负荷分布较多的情况,低电压的现象也更为明显。

在该类线路中采用串联电容器的方式,减小线路等效电抗,提高线路的供电能力,可有效降低线损,提高功率因数,提升线路电压水平,具有良好的经济和社会效益。

概述串补的特点和功能主要有1:1)串补可有效改善全线电压分布,解决低电压问题;2)串联电容器下游线路的负荷发生了大幅度变化时(如大容量电动机启停),电容器补偿的电压能随之实时变化;3)具有“自适应”电压调节和实时响应的特点,电压与无功补偿量随线路电流的变化而实时调节;4)降低了有功损耗,获得不可忽视的经济效益。

(因线路电压水平与功率因数的提高而降低了电流值,从而降低线损)2. 串补应用工程介绍2016年1月22日于国网浙江平阳海滨855线成功投运。

装置通过了轻载期(春节期间)和重载期等不同工况的实际考验,连续稳定运行至今,并取得了显著的节能降耗效果。

国网浙江平阳海滨855线全长31.1公里,供电半径为17.1公里,配变总容量为17.785MVA,主干线为JKLYJ10KV-240导线,同时沿线有多处距离不等的电缆联接。

根据历史数据统计,在最大负荷总量为5.56MW时,全线负荷率接近35%,线路末端电压低于8kV,线路用户的用电受到严重影响。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

发电机的转子对低于系统同步频率的次同步频率
电流表现为视在负电阻特性, 从而向电网提供维
持 er分量的能量, 即感应发电机效应。当发电机 定子流过次同步频率 er的电流, 该电流与转子励 磁电流产生的逆时针方向以 0旋转的磁场作用 产生一个以 0 - er为周期的交变电磁力矩。当 这个交变力矩与轴系的某个自然扭振频率 n接 近时, 就有可能引起轴系扭振, 这时系统的动态特
第 28卷第 3期 2009年 9月
青海电力 Q INGHA I ELECTR IC POWER
Vo .l 28 No. 3 Sep. , 2009
串联补偿线路 SSR分析研究
张志强, 肖湘宁
(华北电力大 学电力系统保护与动态安全监控教育部重点实验室, 北京 102206)
摘 要: 随着我国电力系统 的发展, 串 联电 容补偿 在输 电系统 的应 用越 来越广 泛, 但其 引起 的次 同步 谐振
( SSR ) 问题也随之而来。针对输电网中串联电容补偿引发的次同步谐振, 文章采用基于时域仿真 实现的复转
矩系数法分析了不同发 电机出力以及不同串补度对系统次同步谐振的影响。仿真验证了故障情况下, 较小串
补度系统对次同步谐振 的稳定性。
关键词: 串联补偿; 次同步谐振; 复转 矩系数法; 时域仿真
D ej
+
D
( j
m)
<
0
( 7)
则在此频率下系统会发生不稳定的次同步振
荡或轴系扭振。式中 D ej是第 j个模态频率的电
气阻尼复转矩系数, 单位为
p
u;
D( m) j
是第
j个
图 2 IEEE 第一标准模型 发电机轴系部分采用六质量块模型, 按 IEEE 标准模型所给参数得到系统状态方程形式如下:
X = [A ]X + [B ]U
数, 和 分别是相对于同步旋转坐标系的功
率角增量和角速度增量。上式中各个量分别取标
幺值, 并且 和 之间有如下关系:
=1d
( 2)
0 dt
其中, 0 为同 步角 频率, 时间 的单 位为 秒。
当使发电机转子做频率为 0 的稳态小 值振荡
时 ( < 1) , 将各个量用相量表示, 根据式 ( 2) 有:
图 3 不同出力时的 De- 频率响应曲线 2 3 2 不同串补度的电气阻尼特性
为分析不同串补度对系统 SSR 的影响, 当取 输电线路串补 度依次为 77% 、70% 、60% 、50% 、 30% (以输电线路电抗 为基准 ) 。在计算电气阻 尼特性时, 将发电机看做是单刚体模型, 发电机输 出功率 PG = 0 9 p u , 功率因数 0 9( 滞后 )。计 算所得的系统电气复转矩阻尼系数 - 频率曲线如 图 4所示。
应 ( IGE) 、机电扭振互作用 ( T I) 和暂态力矩放大 作用 ( TA ) 2- 3 。次同步谐振产生的扭转应力会 引起的发电机组轴系永久损坏, 严重威胁着电力 系统安全稳定运行 4 。
本文以国内外学者在 SSR 问题上取 得的研 究成果为基础, 采用基于时域仿真实现的复转矩 系数法 5- 6 和时域仿 真分析方 法, 对 IEEE 次同 步谐振 SSR 第一标准模型系统 7 计算了不同发 电机出力、串补度情况以及安装 SVC 装置前后的 系统电气阻尼 - 频率响应曲线, 分析了不同出力 和串补度对系统电气阻尼的影响, 最后仿真分析 了有扰动时小串补度系统的稳定性。
3 仿真验证
由上小节可知, 对于单机系统当线路的串补 度 < 30% 时, 则可以认为系统的次同步谐振是较 稳定的。以下对此进行仿真验证。以图 2所示的 IEEE 次同步谐振 SSR 第 一标准模型为例, 采用 电磁暂态程序 PSCAD /EMTDC, 取系统的电容串
为研究对象, 系统模型如图 2所示。
图 1 分段集中质量块轴系模型 在小扰动的前提下对轴系模型、发电机模型
以及网络模型进行线性化处理, 消去除 Te, , 以外的变量得到小扰动下发电机电磁转矩增
量的表达式为:
Te= Ke + De
( 1)
式中, Ke 为同步转矩, D e 为阻尼转矩,
Ke 和 De 分别称作同步转矩系数和阻尼转矩系
A, B、发电机、励磁机, 如图 1所示。发电机部分 常采用计及定子暂态的 Park方程描述, 输电网络 部分要采用电磁暂态模型。
模态对应的机 械阻 尼复转 矩系数, 单位 p u, 且
D( m) j
恒大于零。以上就 是基于时域仿真 实现的
复转矩系数法的基本原理。
2 串联补偿线路的次同步谐振分析
2 1 系统模型及轴系自然扭振频率 本文选用 IEEE 推荐的 SSR第一标准模型作
中图分类号: TM 71
文献标识码: A
文章编号: 1006- 8198( 2009) 03- 0011- 04
Analysis of SSR in Series Compensated System
ZHANG Zh i- qiang, XIAO X iang- ning
Abstrac t: W ith the pow er system deve lopm ent in Ch ina, ser ies capacity com pensation has been genera lly used in pow er transm ission system, but it according ly induced subsynch ronous resonance ( SSR ) prob lem. A im ing a t th is prob lem, the paper analyzes the influence o f SSR under d iffe rent generator output and d iffe rent degree of series compensa tion through adopting com plex torque coe fficien t approach based on tim e dom a in s imu la tion. T he simu lation prov es the stab ility of low er degree ser ies capac ity com pensation on SSR. K eywords: se ries com pensa tion; SSR; com plex to rque coeffic ient appro ach; tim e dom a in sim ulation
早在 20世纪 70年代, 人们对 M ohave电厂发 生的机组转子大轴严重损坏事故研究后发现当交 流输电系统采用串联电容补偿, 其电气系统谐振 频率可能会与汽轮发电机轴系的自然扭振频率形 成互补关系, 此时如系统受到扰动, 电气系统与汽 轮发电机轴系之间可能会产生次同步频率的功率 交换, 形成次同步谐振 SSR 1 。 SSR 对发电机组 所造成的影响可归纳为以下 3种: 异步发电机效
( 8)
其中 XБайду номын сангаас是状态变量, U 是输入变量, A是系数
矩阵, B 是关联矩阵。矩阵 A 的特征值以复数形
式成对出现, 实部即衰减系数, 虚部则对应轴系的
自然扭振频率。计算得到系统的自然扭振频率分
别依次为: 15 71 H z, 20 21 H z, 25 55 H z, 32 28
H z和 47 46 H z( 以 上各 值 均 已 经 折算 到 转 子
性将主要表现为机电扭振互作用。如果此时系统
的机械阻尼小于电气负阻尼, 系统就会发生次同
第 3期
张志强等: 串联补偿线路 SSR 分析研究
13
步谐振。 2 3 串补线路电气阻尼特性分析 2 3 1 不同发电机出力下的电气阻尼分析
对于图 2所示的 IEEE次同步谐振 SSR 第一 标准模型 系统, 当线路 电容串联 补偿度为 50% ( 以输电线 路电抗为 基准 ), 采 用电磁 暂态 程序 PSCAD /EMTDC利用基于时域仿真实现的复转矩 系数法, 由式 ( 6) 计算得到不同 发电机出力时的 电气复转矩阻尼系数 - 频率响应曲线, 如图 3所 示。由图 3系统的电气谐振频率约为 28 H z( 折 算到转子 侧 ) , 当 发 电机 的出 力分 别取 P = 0 9 p u , P= 0 5 p u , P= 0 2 p u 时, 对应的最大 电气负阻尼分别为 - 40 56 p u , - 34 24 p u , - 30 29 p u 。可见串联补偿引起的电气负阻尼 与发电机的稳态运行状态有关, 输送功率越大, 产 生的电气负阻尼也越大。随着发电机出力逐渐变 小, 系统的电气负阻尼也逐渐减小, 对应的电气谐 振频率不变。
随着我国电网输送容量的不断增大, 输电距 离的不断增长, 为了减少损耗增加远距离高压输 电系统的传输容量、改善输电系统运行的稳定性, 在输电线路中采用串联电容补偿是一项既经济又 有效的措施。当线路中加入串联补偿之后, 在线 路等效电抗减小, 电气距离缩短的同时, 也给电力 系统安全稳定运行带来了新的问题。
另外, 当线路 串补度取值为 30% 时, 由图 4 中可见, 扫频分析中的系统电气负阻尼最大值约 为 - 2 9 p u , 并且在每一个轴系自然扭振频率 附近电气阻尼复转矩系数值都较小。由于发电机 组轴系存在一定的机械阻尼, 则有 D e + Dm > 0, 说 明系统总的阻尼为正, 系统的次同步振荡是较稳 定的。
1 基于时域仿真实现的复转矩系数法
研究次同步谐振问题时由于发电机轴段之间
作者简介: 张志强 ( 1985- ) , 男, 陕西岐山县人, 硕士研究生, 从事电力系统运行、分析与 控制研究。 收稿日期: 2009- 05- 13
相关文档
最新文档