htjf-h说明书
GEFRAN智能HART熔化压力变送器HW、HM、HK系列说明书

SMART HART MELT PRESSURE TRANSMITTERSHW, HM, HK SERIESINSTRUCTION MANUALcod. 80169I Edit. 12/2021 - ENGATTENTION!This manual is an integral part of the product,and must always be available to operators.This manual must always accompany theproduct, including if it is transferred to another user.Installation and/or maintenance workers MUSTread this manual and scrupulously follow all of the instructions in it and in its attachments.GEFRAN will not be liable for damage topersons and/or property, or to the product itself, if the following terms and conditions are disregarded.The customer must respect trade secrets.Therefore, this manual and its attachments maynot be tampered with, changed, reproduced, or trans-ferred to third parties without GEFRAN’s authorization.T h i s d o c u m e n t i s t h e p r o p e r t y o f G E F R A N a n d m a y n o t b e r e p r o d u c e d o r t r a n s f e r r e d t o t h i r d p a r t i e s w i t h o u t a u t h o r i z a t i o n .Gefran Smart HART series ➡ READY-TO-USE GUIDE ��������������������������������������������������������������������������������������������������������4. READY-TO-USE Using magnetic pen / pin CAL feature (4). READY-TO-USE Using HART Communicator (4). Menu Tree ➡ H Pres Transmitter (5)1� GENERAL INFORMATION ���������������������������������������������������������������������������������������������������������������������������������������������������6 1.1. General information (6)1.2. Copyright (6)1.3. Correct use (6)2� ACRONYMS ��������������������������������������������������������������������������������������������������������������������������������������������������������������������������6 3� NAME CODING ���������������������������������������������������������������������������������������������������������������������������������������������������������������������7 4� SENSOR TECHNICAL SPECIFICATIONS ��������������������������������������������������������������������������������������������������������������������������8 5� MECHANICAL DIMENSIONS ���������������������������������������������������������������������������������������������������������������������������������������������13 6� INSTALLATION AND POSITIONING ON THE MACHINE ������������������������������������������������������������������������������������������������13 6.1. Installation seat (13)6.2. Drilling Tool Kit (14)6.3. Wiring and calibration (16)7� ELECTRICAL CONNECTIONS �����������������������������������������������������������������������������������������������������������������������������������������17 8� COMMAND MODES ����������������������������������������������������������������������������������������������������������������������������������������������������������19 8.1. Using Magnetic pen and Pin CAL (19)8.2. Using HART Communication (21)9� MAINTENANCE ������������������������������������������������������������������������������������������������������������������������������������������������������������������27 9.1. Transport, storage and disposal (27)10� FUNCTIONAL SAFETY NOTES (for SIL 2 / PL d certified versions only) �������������������������������������������������������������������28 10.1. NE21 and NE43 compatibility specifications (33)11� RELAY APPLICATION NOTES ������������������������������������������������������������������������������������������������������������������������������������������34 12� SAFETY NOTES FOR APPLICATIONS IN POTENTIALLY EXPLOSIVE ATMOSPHERES: HWX AND HMX VERSIONS ����38 12.1. NEPSI Ex requirements (39)13� ANNEXES ��������������������������������������������������������������������������������������������������������������������������������������������������������������������������40This Ready-to-Use guide can be used by expert instrumentation operators to configure the transmitter using HART Communication or Autozero/Calibration features through magnetic pen or contacts on output connector.For more full information please refer to the complete manual before operating.The Ready-to-Use procedure with HART is intended for users already familiar with HART Communicator and loop powered equipment.READY-TO-USE Using magnetic pen / pin CAL featureBring the system to the working temperature with the transmitter installed and connected to the measurement instrument without any pressure applied. For a 6 or 8 pin connector version, Pin A is Sig+/Exc+ and pin B is Sig-/Exc-.For conduit output configurations, please look at Electrical Connections chapter.Assure proper loop feeding voltage is applied to transmitter.The measurement chain connected to the transmitter is calibrated as follows:1) Reset the offset on the instrument by eliminating the thermal drift with the Autozero function.With the sensor installed and the extruder at working temperature, wait until the temperature itself is stable, with a pos- sible variation of ± 1°C. Consequently Autozero can be activated.This allows to compensate all the signal drifts caused by tightening and temperature. Additional Autozero activations could be run once the temperature stability is reached, with ± 1°C of possible variation.2) Calibrate the instrument activating the CAL function.The transducer brings its output to the calibration value shown on the transducer data plate (80% of full scale default, if changed with HART command it could be different). With the external Autozero function the calibration procedure is not feasible.3) If the instrument does not exactly indicate zero, repeat points 1) and 2).READY-TO-USE Using HART CommunicatorBring the system to the working temperature with the transmitter installed and connected to the measurement instrument without any pressure applied.1) Connect Communicator to the loop. In case it’s not sure on how to do this, please refer to “Connecting the HART Handheld Communicator” (Figure 8.1).2) Switch on HART Communicator. For reference please refer to HART Command tree on the following page.3) From the main menu:a. Enter Tag (Fast Key 1, 3, 1)b. Set Pressure Units (Fast Key 1, 3, 3), if neededc. Set URV (Fast Key 1, 3, 4) if output turndown (rescaling), is neededd. Perform Autozero (Fast Key 1, 2, 6, 3, 1)4) Check loop output is zero (4mA).5) Remove HART Communicator from loop.Menu Tree H Pres Transmitter(*) Equal to 0 for HM, HW, HK (≠ 0 for HI).This manual applies to the following products:HME, HWE, HKE series as well as HMX and HWX, series produced by Gefran spa, via sebina 74 – 25050 Provaglio di Iseo - BS - Italy.1.1 General informationThis manual must be kept near the equipment for easy reading and consultation.It must be read, understood, and strictly follow in order to avoid and prevent accidents and/or malfunctions.Gefran will not be liable for any injury to people and/or damage to property deriving from disregard of this manual.1.2 CopyrightAny reproduction of this document, even partial or for internal use, requires Gefran’s approval.1.3 Correct useGefran Melt pressure sensors with amplified current output with HART protocol are designed and builtto measure the pressure and temperature variable of melted plastic at different temperatures accor-ding to the filling fluid used. The correct temperature range is:• Up to 315°C for HW series (i.e. oil filling fluid)• Up to 400°C for HM series (i.e. mercury filling fluid)• Up to 538°C for HK series (i.e. Na-K filling fluid)If the sensors are used as a safety component in compliance with the Machinery Directive, it’s necessary to read carefully the “Safety Manual” (chapter 10).In case the sensors are used for applications in potentially explosive atmospheres, please read carefully (chapter 12).Installation and maintenance must only be carried out by suitably skilled and qualified personnel.The following acronyms are frequently used:BFSL Best Fit Straight LineDD Device DescriptorEEPROM Electrically Erasable Programmable Read Only MemoryFS Full Scale OutputHART Highway Addressable Remote TransducerLRV Lower Range ValuePT Pressure TransmitterPV Primary Variable (Pressure)RTD Resistance Temperature Detector (A very accurate temperature sensor)SV Secondary Variable (Electronics Temperature)TV Tertiary Variable (Snout Temperature)URV Upper Range ValueWatchdog An internal timing control for the electronicsHWE Hart Oil Filled Melt Pressure TransducerHWX Hart Oil Filled Melt Pressure Transducer Ex CertifiedHWE P Hart Oil Filled Melt Pressure Transducer PL d CertifiedHWX P Hart Oil Filled Melt Pressure Transducer Ex and PL d CertifiedHWE S Hart Oil Filled Melt Pressure Transducer SIL 2 CertifedHWX S Hart Oil Filled Melt Pressure Transducer Ex and SIL 2 CertifedHME Hart Mercury Filled Melt Pressure TransducerHMX Hart Mercury Filled Melt Pressure Transducer Ex CertifiedHME P Hart Mercury Filled Melt Pressure Transducer PL d CertifiedHMX P Hart Mercury Filled Melt Pressure Transducer Ex and PL d CertifiedHME S Hart Mercury Filled Melt Pressure Transducer SIL 2 CertifedHMX S Hart Mercury Filled Melt Pressure Transducer Ex and SIL 2 CertifedHKE Hart NaK Filled Melt Pressure TransducerHKE P Hart NaK Filled Melt Pressure Transducer PL d CertifiedHKE S Hart NaK Filled Melt Pressure Transducer SIL 2 CertifedGefran Melt sensors are pressure/temperature transmitters designed for use in high temperature envi-ronments. They read media pressure up to a temperature of 538°C, and resist such high temperatures thanks to their special mechanical construction, in which the measurement element is isolated from the Melt.The constructive principle is based on hydraulic transmission of pressure; mechanical strain is transferred by means of a non-compressible transmission liquid.The liquid used in these sensors may be mercury (i.e. HM series), FDA-approved oil (i.e. HW series) or NaK (i.e. HK series). Strain gauge technology translates the physical quantity (pressure) into an electrical signal. Four different designs are available: rigid rod, flexible sheathing, flexible plus thermocouple, and exposed tip. Gefran Melt sensors satisfy all installation and field requirements.The sensors can read an extremely wide range of pressures: from a version with minimum range of 0-17 bar up to a version with a scale of 0-2000 bar.All models in the catalog can be supplied in two different classes of accuracy*: class M, with accuracy of 0.5% FS, and class H, with accuracy of 0.25% FS. Ex and Performance Level ‘d’ or SIL2 certified versions are available.* For HMX/HWX products sold to EAC Customs Union (EAC mark), due to a different method of calculation, the limits of accuracy are the following:_M = 1%_H = 0,5%For all the other details and technical features please keep as reference the product datasheets or Gefran website .4.1 HWE – Technical dataAccuracy (1) H <±0.25%FS (100...1000 bar)M <±0.5%FS (17...1000 bar) Resolution16 bitMeasurement range0..17 to ... 0..1000bar0..250 to 0..15000psi Rangeability3:1Maximum overpressure (without degrading performances) 2 x FS1.5 x FS above 500bar/7500psi Measurement principle ExtensimetricPower supply13...30VdcMaximum current absorption23mA (40mA with relay optional) Output signal Full Scale (FS)20mAZero balance (tollerance ± 0.25% FS)4mACalibration signal80% FSPower supply polarity reverse protection YesCompensed temperature range housing0...+85°COperating temperature range housing-30...+85°CStorage temperature range housing-40...+125°CThermal drift in compesated range: Zero / Calibration / Sensibility< 0.02% FS/°C Diaphragm maximum temperature315°C / 600°FZero drift due to change in process temperature (zero)< 0.04 bar/°CStandard material in contact with process medium Diaphragm:• 17-7 PH corrugated diaphragm with GTP+ coating Stem:• 17-4 PHThermocouple (model HWE2)STD: type “J” (isolated junction) Protection degree (with 6-pole female connector)IP65Electomagnetic compatibility – Emissions EN 61326-1 EN 61326-2-3 EN 61326-3-1Electomagnetic compatibility – Immunity EN 61326-1 EN 61326-2-3 EN 61326-3-1FS = Full scale output(1) BFSL method (Best Fit Straight Line): includes combined effects of Non-Linearity, Hysteresis and Repeatability.For products sold to EAC Customs Union (EAC mark), due to a different method of calculation, the limits of accuracy are the following: _M = +-1%_H = +-0,5%4.2 - HME – Technical dataAccuracy (1) H <±0.25%FS (100...2000 bar)M <±0.5%FS (17...2000 bar) Resolution16 bitMeasurement range0..17 to 0..2000bar0..250 to 0..30000psi Rangeability3:1Maximum overpressure (without degrading performances) 2 x FS1.5 x FS above 1000bar/15000psi Measurement principle ExtensimetricPower supply13...30VdcMaximum current absorption23mA (40mA with relay optional) Output signal Full Scale (FS)20mAZero balance (tollerance ± 0.25% FS)4mACalibration signal80% FSPower supply polarity reverse protection YesCompensed temperature range housing0...+85°COperating temperature range housing-30...+85°CStorage temperature range housing-40...+125°CThermal drift in compesated range: Zero / Calibration / Sensibility< 0.02% FS/°C Diaphragm maximum temperature400°C / 750°FZero drift due to change in process temperature (zero)< 0.02 bar/°CStandard material in contact with process medium Diaphragm:• 15-5 PH with GTP+ coating• 17-7 PH corrugated diaphragm with GTP+ coating for ranges <100 bar (1500psi)Stem:• 17-4 PHThermocouple (model HME2)STD: type “J” (isolated junction) Protection degree (with 6-pole female connector)IP65Electomagnetic compatibility – Emissions EN 61326-1 EN 61326-2-3 EN 61326-3-1Electomagnetic compatibility – Immunity EN 61326-1 EN 61326-2-3 EN 61326-3-1FS = Full scale output(1) BFSL method (Best Fit Straight Line): includes combined effects of Non-Linearity, Hysteresis and Repeatability.Sense resistor Load Line250 ohm minimum for HART communicationSensors are manufactured in compliance with: - EMC compatibility directive - RoHS directive - Machinery directiveElectrical installation requirements and Conformity certificate are available on our web site: 100200300400500600700800900R ( Ω)Vcc (V)WORKING AREA4.4 - HWX – Technical dataAccuracy (1) H <±0.25%FS (100...1000 bar) M <±0.5%FS (17...1000 bar)Resolution16 bitMeasurement range 0..17 to 0..1000bar 0..250 to 0..15000psi Rangeability3:1Maximum overpressure (without degrading performances) 2 x FS1.5 x FS above 500bar/7500psi Measurement principle Extensimetric Power supply13...30Vdc Maximum current absorption23mAOutput signal Full Scale (FS)20mA Zero balance (tollerance ± 0.25% FS)4mA Calibration signal80% FS Power supply polarity reverse protection YesCompensed temperature range housing 0...+85°C Operating temperature range housing -30...+85°C Storage temperature range housing-40...+125°C Thermal drift in compesated range: Zero / Calibration / Sensibility < 0.02% FS/°C Diaphragm maximum temperature315°C / 600°F Zero drift due to change in process temperature (zero)< 0.04 bar/°C Standard material in contact with process medium Diaphragm:• 17-7 PH corrugated diaphragm with GTP+ coating Stem:• 17-4 PHThermocouple (model HWX2)STD: type “J” (isolated junction)Protection degree (with 6-pole female connector)IP65Electomagnetic compatibility – EmissionsEN 61326-1EN 61326-2-3EN 61326-3-1Electomagnetic compatibility – ImmunityEN 61326-1EN 61326-2-3EN 61326-3-1FS = Full scale output(1) BFSL method (Best Fit Straight Line): includes combined effects of Non-Linearity, Hysteresis and Repeatability.Sense resistor Load Line250 ohm minimum for HART communicationSensors are manufactured in compliance with: - EMC compatibility directive - Machinery directive- Ex regulations (ref. par.12)Electrical installation requirements and Conformity certificate are available on our web site: 100200300400500600700800900R ( Ω)Vcc (V)WORKING AREA4.5 - HMX – Technical dataAccuracy (1) H <±0.25%FS (100...2000 bar) M <±0.5%FS (17...2000 bar)Resolution16 bitMeasurement range 0..17 to 0..2000bar 0..250 to 0..30000psi Rangeability3:1Maximum overpressure (without degrading performances) 2 x FS1.5 x FS above 1000bar/15000psi Measurement principle Extensimetric Power supply13...30Vdc Maximum current absorption23mAOutput signal Full Scale (FS)20mA Zero balance (tollerance ± 0.25% FS)4mA Calibration signal80% FS Power supply polarity reverse protection YesCompensed temperature range housing 0...+85°C Operating temperature range housing -30...+85°C Storage temperature range housing-40...+125°C Thermal drift in compesated range: Zero / Calibration / Sensibility < 0.02% FS/°C Diaphragm maximum temperature400°C / 750°F Zero drift due to change in process temperature (zero)< 0.02 bar/°C Standard material in contact with process mediumDiaphragm:• 15-5 PH with GTP+ coating• 17-7 PH corrugated diaphragm with GTP+ coating for ranges <100 bar (1500psi)Stem:• 17-4 PHThermocouple (model HMX2)STD: type “J” (isolated junction)Protection degree (with 6-pole female connector)IP65Electomagnetic compatibility – EmissionsEN 61326-1EN 61326-2-3EN 61326-3-1Electomagnetic compatibility – ImmunityEN 61326-1EN 61326-2-3EN 61326-3-1FS = Full scale output(1) BFSL method (Best Fit Straight Line): includes combined effects of Non-Linearity, Hysteresis and Repeatability.Sense resistor Load Line250 ohm minimum for HART communicationSensors are manufactured in compliance with: - EMC compatibility directive - Machinery directive- Ex regulations (ref. par.12)Electrical installation requirements and Conformity certificate are available on our web site: 100200300400500600700800900R ( Ω)Vcc (V)WORKING AREAFor the mechanical dimensions please keep as reference the product datasheets or Gefran website TECHNICAL DATAExtrusion processes require very high temperatures. Extrusion pressure can be checked by means of espe-cially designed transducers. Thanks to their special mechanical construction, in which the measurement ele-ment is isolated from the Melt, they resist to such high temperatures. The constructive principle is based on hydraulic of pressure; mechanical strain is transferred by means of a non-compressible transmission liquid. Strain gauge technology translates the physical quantity (pressure) into an electrical signal.Following advice for extending the sensors lifetime.a) Avoid shocks and abrasions to the in contact diaphragm. Protect the transducer with its cover each time you remove it from its seat.b) The seat must be prepared perfectly and with appropriate tools in order to respect the depth and axiality of the holes and tapping.Pay particular attention to the coaxiality of the holes to the thread, because diaxialities greater than 0.2 mm will break the transducer during assembly. It is essential that hole depth guarantees the absence of chambers or air pockets in which extrusion material may be trapped.To prevent contact with the extrusion screw or with tools used to clean the extrusion chamber, the front diaphragm must not extend from the inner wall of the extruder.c) Before assembling the transducer in machines already in operation, make sure that the housing is clean. Remove any residual with the suitable cleaning device.d) The transducer should be removed only with the machine empty (without pressure) but still hot.e) The transducer should be cleaned with solvents for the material being processed.Any mechanical action on the contact diaphragm modifies its operation and could break it.6.1 - Installation seatThe installation seat has to be realized:Drilling kitA drilling kit with formed tools for drilling, reaming and tapping is available to facilitate correct preparation of the assembly seat. The assembly seat must be perfect to assure proper transducer function and long lifetime. Drilling kits are available in the following versions: KF12, KF18.Drilling procedure1) To drill hole (D4) up to a distance from the hole equal to the sum of (A+B+C) (tool 3).2) Make the pass through hole (D2) by the tool 1.3) To create the seal seat at a distance from the hole equal to dimension (A) (tool 4).4) With a roughing tap, create threading 1/2-20UNF-2B (recognizable from the greater number of threads beveled at the mouth) (tool 5).5) With a finishing tap, go over threading 1/2-20UNF-2B up to a distance from the bottom equal to the sum of (A+B) (tool 6).6) To ream the hole (D2) with reamer (tool 2).Installation seat checkThe dimensions of the assembly seat have to be checked after preparation and before the transducer installation.Use dummy plug SC 12/18 as follows:1) Coat the end of the rod with the appropriate ink.2) Lubricate the threaded part to prevent friction.3) Insert the dummy plug and screw it fully down.4) Remove the rod and examine it.With the exception of 45° surfaces, the ink should be intact on the entire surface .6�2 DRILLING TOOL KITCORRECT INSTALLATIONWRONGWRONGWRONGCORRECTVERSION CODE KF12KF18THREADING TYPE 1/2-20UNF-2BM18x1.51Ø 7.6Ø 9.752Ø 7.95Ø 10.13Ø 13Ø 204Ø 11.5 with pilot guideØ 16 with pilot guide51/2-20UNF-2Broughing M18x1.5roughing61/2-20UNF-2Bfinishing M18x1.5finishingIncorrect working or shape of the side can result in properties out of specification, bad behaviour or damage to the sensor.The side should be clean and without any polymer residual.contact surfaceTRANSDUCER INSTALLATIONInstallation procedure1) Make sure the drilling procedure has been realized correctly. If the sensor is installed in a previously used hole, make sure the hole is completely clean and free of any plastic residual.2) Remove the protective cap from the sensor tip.3) Lubrificate the thread with non-grip grease such as Neverseez (Bostik), or C5A (Felpro), or equivalent.4) Insert firmly the sensor into the hole, first by hand and then with a wrench, 1/4 turn at a time.Recommended torque: 50 Nm, the maximum is 56.5 Nm.Removal (Figure 1)To remove the transducer from its seat and carry on the working process, dummy plugs with identical mecha-nical dimensions are available.The dummy plugs differ by type of threading; max pressure range is 2000 bar for all rods.The dummy plugs are available in the following versions: SC12 1/2-20UNF seat - SC18 M18x1,5 seat.Brackets (Figure 2)Models with flexible sheaths require the housing precise fixing. Suitable fastening brackets (SF18) are recom-mended.Remember that the fastening point must be vibration-free (vibrations affect the measurement) and that tem-peratures must not exceed the maximum temperature range for the strain gauge housing (as stated on the sensor technical sheet).Extruder startingBring the system to working temperature with the transducer installed and without any pressure applied. Wait until all the material is at the same temperature to prevent the transducer damage by semi-solid material.Seat cleaning & Cleaning toolAs mentioned in the notes, the seat must be cleaned before the transducer installation.The cleaning tool is a hard metal cutting tool specially designed to remove working materials residuals.Recommended procedure (Figure 3)The following procedure must be implemented with the material in a fluid condition.1) Insert the tool in the seat and screw down the cutting rod (normally a 1/4 turn at a time).2) Turn the pilot cutter clockwise until there is no resistance to cutting.3) Repeat the procedure until the seat is completely clean.For constructive reasons, the maximum torque applicable to the cutter is 15 Nm (1.5 Kgm).If the hole occlusion requires higher torque for removal, use the drilling kit and follow the recommended procedure.The cleaning tool is available in the following versions: CT12 1/2-20UNF seat - CT18 M18x1,5 seat.Figure 1Figure 3Figure 26�3 - Wiring and calibrationConnectionsThe sensors have to be connected as shown in the diagram at chapter 7.To obtain a higher immunity from field noise, connect the cable shield to the female connector case on sen-sor side.Calibration procedure using the magnetic pen/Pin CALBring the system to the working temperature with the transmitter installed and connected to the measure-ment instrument without any pressure applied.The measurement chain connected to the transmitter is calibrated as follows:1) To reset the offset on the instrument by eliminating the thermal drift with the autozero function.With the sensor installed and the extruder at working temperature, wait until the temperature itself is stable, with a possible variation of ± 1°C. Consequently Autozero can be activated. This allows to compensate all the signal drifts caused by tightening and temperature.Additional Autozero activations could be run once the temperature stability is reached, with ± 1°C of possible variation.2) Calibrate the instrument activating the CAL function. The transducer brings its output to the calibration value shown on the transducer data plate (80% of full scale default, if changed with HART command it could be different).With the external Autozero function the calibration procedure is not feasible.3) If the instrument does not exactly indicate zero, repeat points 1) and 2).In this way, the instrument is calibrated to give the exact indication in the chosen engineering unit.Calibration procedure using HART communicationBring the system to the working temperature with the transmitter installed and connected to the measure-ment instrument without any pressure applied.1) Connect Communicator to the loop. In case it’s not sure on how to do this, please refer to “Connecting the HART Handheld Communicator” (Fig. 8.1).2) Switch on HART Communicator. Please refer to HART Command tree on Ready-to-Use guide.3) From the Main Menu:a. Enter Tag (Fast Key 1, 3, 1)b. Set Pressure Units (Fast Key 1, 3, 3), if neededc. Set URV (Fast Key 1, 3, 4) if output turndown (rescaling), is neededd. Perform Autozero (Fast Key 1, 2, 6, 3, 1)4) Check loop output is zero (4mA).5) Remove HART Communicator from loop.ORDER CODES FOR TOOLS and ACCESSORIESThe interface to controller can be:- the multi-polar connector type VEAM VP07RA10-6PT2 (code GEFRAN CON301),- the multi-polar connector type BENDIX PC02E-12-8P 8 poles (code GEFRAN CON356)- the multi-polar cable outlet with conduit output type ½ 14-NPT as illustrated in fig 7.1.where are also pointed out the connections (2 wires connection current amplified). In the case of relay output with retransmitted output in current (2 wires) the connections are shown in fig. 7.2.CURRENT OUTPUT (NO RELAY)The cable shield is tied to both sides, i.e. to the sensor connector and to the controllerFig 7.1RELAY OUTPUTThe cable shield is tied to both sides, i.e. to the sensor connector and to the controllerFig 7.2。
HTYWS-H微量水分测定仪菜单及按键操作说明

HTYWS-H微量水分测定仪HTYWS-H微量水分测定仪菜单及按键操作说明仪器按键为无标识按键,在不同的显示界面下,按键具有不同的功能,由对应显示的菜单来决定,这样的设计减少了按键数量,按键功能定义明确,使得人机界面更加友好。
由于采用了大屏幕液晶,每屏画面所能显示的信息量更丰富,减少了切换显示画面的数量,用户学习使用仪器变得更简单。
仪器共分为5个显示画面:1、开机欢迎画面;2、时间调整画面;3、历史记录画面;4、样品测定画面;5、测定结果画面。
以下按键操作说明中,加黑反显的数字或图形为当前调整修改的内容注:在不含蓄电池的仪器画面中不会出现电池电量符号1. 开机显示画面:液晶屏幕显示如图6-1图6-1 开机显示连接好仪器电源线,打开电源开关,进入开机画面。
在当前显示界面下有以下按键操作:测定:进入样品测定画面。
HTYWS-H微量水分测定仪记录:进入历史记录查看画面。
调时:进入时间调整画面。
2. 时间调整显示画面:液晶屏幕显示如图6-2图 6-2 时间调整调整内容分为:“年,月,日,时,分,秒”在当前显示界面下有以下按键操作:跳格:光标在各数字项移动。
增加:光标处的数字加1,长时间按下该键,数字快速增加。
减少:光标处的数字减1,长时间按下该键,数字快速减少。
对时:更新当前的日期与时间。
将调整后的日期、时间写入仪器。
退出:退出时间调整画面,回到开机欢迎画面3. 历史记录显示画面:液晶屏幕显示如图6-3图6-3 历史记录 HTYWS-H微量水分测定仪在当前显示界面下有以下按键操作:前页:显示前一条历史记录,记录号减1,长时间按下该键,快速向前翻页,最大记录号为255。
后页:显示后一条历史记录,记录号加1,长时间按下该键,快速向后翻页,最小记录号为0。
删除:删除当前的记录,显示下一条记录。
打印:打印当前的历史记录,打印内容包括:样品编号、含水量、含水率、检测日期、检测时间。
退出:退出历史记录画面,回到开机欢迎画面。
Exheat FP-RCH 型防爆水热器说明书

OPERATING & MAINTENANCEINSTRUCTIONS FOR EXHEATFP-RCH TYPE FLAMEPROOF WATERHEATER1.0 GENERAL1.1 All work should be carried out by suitably qualified personnel.1.2 Heaters must be handled with care & stored in dry conditions.1.3 Adequate withdrawal space must be provided to allow the removal of the heater assembly.1.4 Carefully remove all protective packaging & visually inspect unit for any transit damage.1.5 All prevailing rules, regulations & bylaws in force at the time & place of installation must be observed.1.6 Heaters must only be immersed in the fluid they are designed to heat.1.7 The introduction of alternative fluids even in small concentrations for purposes such as sterilising may cause seriousdamage to the heater & will invalidate the warranty.1.8 Any modification not carried out by Exheat Limited or its approved agent will invalidate certification & warranty. 1.9 For Hazardous area heaters reference must be made to EN 60079-17.1.10 All electrical testing must be carried out in a non-hazardous area.1.11 Precautions must be taken to prevent damage to machined surfaces & threads of flameproof enclosures.1.12 Ensure that any special conditions for safe use detailed on the hazardous area certification are compiled with.2.0 INSTALLATION Refer to Fig.12.1 The heater should be securely fixed in position & all terminal connections checked for tightness before energising. 2.2 The unit must be wall mounted allowing one metre above the highest draw off point to ensure good flow.2.3 Sufficient clearance must be allowed to ensure access to the ball valve assembly.2.4 The wall fixing points are designed to accept 8mm bolts which should not be less than 50mm in length.2.5 Always ensure that the wall is sufficiently strong to carry the weight of the unit when it is full of water.3.0 PIPEWORK CONNECTIONS Refer to Fig.23.1 The installation must conform to any local authority byelaws.3.2 The cold water supply & warning pipe assembly (overflow) can be connected to either side of the unit, the respectiveapertures are pre-formed in the outer case & these should be used as guides for cutting through the cold water tank. 3.3 A 22mm hole saw is required for the inlet & a 27mm hole saw for the warning pipe.3.4 An isolating valve must be fitted to the cold water mains supply to allow for servicing.4.0 FITTING TO COLD WATER TANK Refer to Fig.34.1 The FP-RCH series of water heaters are supplied with all the components that are required to comply with the UKWRC byelaw 30.4.2 The filter & breather assembly is a push snap-fit connection & should be fitted to the lid in the aperture provided.4.3 The warning pipe assembly (overflow) comprises of three components.4.4 The threaded elbow (tank connector) is inserted through the hole that has been cut, & tightened with the nut & sealingwasher on the inside of the tank.4.5 The 90° bend internal “dip tube” is pushed firmly into the connector facing downwards. The warning pipe (overflow)screen is located securely in to downwards external connection of the connector.4.6 The ball valve assembly is fitted as required, adjusting the float to ensure that the water level in the tank does notexceed the water level line.4.7 Before making electrical connections it is recommended that the unit is filled & checked for leaks.4.8 After installation, replace lid & secure with retaining screw supplied.5.0 ELECTRICALSUPPLY CONNECTIONS Refer to Fig.45.1 Refer to wiring diagram (Fig.4)5.2 The cable entry is positioned on the side of the terminal box.5.3 Before connection ensure that the supply corresponds with that specified on the rating label.5.4 Ensure that the sizes & types of cable to be used are suitably rated for the load & temperature of the unit.5.6 Each heater must be protected by a suitably rated over current device.5.7 The cables must enter the heater terminal box via a certified Ex d cable gland (not supplied) & be fitted by a qualifiedperson.5.8 The covers & bodies of RF series terminal boxes are unscrewed after slackening the locking grub screw. When re-fitting ensure that the “O” ring seal is in good condition & correctly located. The main cover threads MUST be kept clean & free from any debris at all times.5.9 The installer or end user must connect to the Exheat supplied terminals within the terminal box – DO NOT – connectto or disturb factory fitted heating element wiring.CONNECTION6.0 EARTH6.1 WARNING – these heaters MUST BE EARTHED.6.2 The external earth connection is located adjacent to one of the terminal box cable entries.6.3 An internal earth connection is provided inside the terminal box.7.0 OPERATION7.1 Important – the unit MUST be full of water before switching on the electricity supply & at all times whilst energised.7.2 The cold water supply to the integral cistern is controlled by the ball valve; water drawn from the unit is replaced fromthe contents of the cold water cistern that is refilled automatically.7.3 Heat is transferred by means electric heating elements.7.4 Control of the heater is facilitated by thermostats, & reference should be made to the wiring diagram to ensure thatthese are correctly connected & set prior to energising the heater.7.5 Where a manual reset cut-out is installed, the terminal box cover will have to be removed to enable a reset to becarried out.MUST NOT be used if suspected of being frozen. If water ceases to flow switch off the electricity supply 7.6 Theunitimmediately at the isolating switch. If the unit is to be serviced or drained disconnect the electricity supply beforecommencing the operation.8.0 MAINTENANCE8.1 All prevailing site safety regulations shall be adhered to at all times.8.2 Before & whilst any maintenance activity is carried out, it must be ensured that there are no hazardous gases present.8.3 Equipment is to be fully isolated from the electricity supply before & whilst any work is being carried out.8.4 Any damage or faults should be notified to Exheat Limited immediately.8.5 For equipment certified for use in hazardous areas reference should be made to EN 60079-17 (especially table 1) inaddition to the following recommendations.8.6 Any replacement parts required must be obtained directly from Exheat. The use of any other parts will void anycertification and warrantyMonthly8.7 3a. Generally inspect the equipment for external damage or leaks.Monthly8.8 6a. Isolate the electrical supply & remove the cover.b. Internals should be clean & dry.c. Insure terminals are intact & secure.d. Heating element insulation resistance to be at least 2 megaohm.e. Refit cover with new gasket or “O” ring if required.f. Earth continuity must be maintained between all earth points & main structure.8.9 Annuallya. Check all above.b. Check for element failure or low insulation resistance.c. Check operation of level switch by draining & re-filling unit with electrical fully isolated.8.10 Only Exheat Limited or its approved agent to carry out element or level switch replacement in hazardous area heatersotherwise the certification will be invalidated.8.11 If heater is being left unused for a period greater than 3 months carry out 6 monthly maintenance before energizing.9.0 Marking9.1 II 2 G/DEx d IIC T4 to T610.0 Certification10.1 LCIE 01 ATEX 6026 XModel Capacity (Litres) Dimensions (mm) Weight (kg)Hot Cold A B C D E F EmptyFullFP-RCH25 25 8 815 470 785 210 670 320 24 57 FP-RCH50 50 24 860 600 830 320 715 450 36 110 FP-RCH75 75 24 10306001005320890450 41 140 FP-RCH100 100 24 1190600 1160320 1045450 44 168 Fig.2Fig.3Fig.4。
哈迪洛克高效热交换器产品说明书

Industrial GradeHeat-Exchanger Unit HeatersWARNING!Please adhere to all instructions published in this manual. Failure to do so may be dangerous and may void your warranty.The HHP heat-exchanger core is covered by the Safety Codes Act and therefore is not field repairable.Contact factory for a replacement core if fluid leakage occurs.Part No. HHP2-OM-BPrinted in CanadaHydronic High Performance HeaterCRN: 0H14856.2COwner’s Manual, Part No. HHP2-OM-BThis manual covers installation, maintenance,repair, and replacement parts.∙ * Other voltages available upon request. Longer lead times may apply. Contact factory. ∙ Motors are designed to be operated at rated voltage with tolerances of ± 10%.∙ If ordering explosion-proof motor, ensure equipment meets the requirements of your hazardous area rating. ∙†Standard ex-proof motor suitable for Class I & II, Div. 1 & 2, Groups C, D, F & G; T3BHHP2 Model CodingModel Code Sequence Required for OrderingFactory AssignedHHP2-30 Front & Rear ViewsApprovalsCRN: 0H14856.2C - steam or fluids (not for use with lethal fluids asdefined by ASME, Section VIII, Div. 1, UW-2). Maximum Pressure Rating 450 psig (3103 kPa). Maximum Design Temperature550°F (288°C).Cabinet Material 14-gauge (0.075 in.) (1.9 mm) steel. HHP2-30 is 12-gauge (0.105)(2.7 mm) steel on top and bottom panels and motor mount. Yellow epoxy/polyester powder coated with five-stage pretreatment, including iron phosphate.Louver Blades Anodized extruded aluminum.Fan Spark-proof 3-blade aluminum (HHP2-30 is 6 blade).Fan GuardSplit design with close wire spacing. A 3/8 in. (9.5 mm) diameter probe will not enter.Motor Drive Thermally protected CSA or UL Listed 1725 RPM permanently lubricat-ed ball bearing type with 56 frame and “easy-off” fan blade replace-ment feature . HHP2-30 is a 56C frame motor and a maintenance-free speed reducer. Refer to page 2 for motor details.Mounting Holes 9/16” diameter holes – Two at top and two at bottom of heater. Fluid Connections 1-1/2 in. NPT male Schedule 40 inlet and outlet. Optional 1–1/2" (4 bolt) & 2" (8 bolt) CL300# RF flanges available. [see ^ symbol on Page 2 for 8 bolt description]Header Material 3/16 in. (4.8 mm) carbon steel plate conforming to ASME requirements.Finned Tubes5/8 in. (15.9 mm) outside diameter [16-gauge, 0.065 in. (1.6 mm) wall thickness] carbon steel tubes with 1-1/2 in. (38.1 mm) outside diame-ter copper-free, L-foot, tension-wound aluminum fins @ 10 fins per in. Exchanger CoatingsStandard coating is a black, high-heat enamel paint. Optional corrosion resistant paint or Heresite phenolic coating available.Minimum Design Metal Temperature -20°F (-29°C).HHP2 General SpecificationsModelHHP2-12 HHP2-16 HHP2-20 HHP2-24 Fan Diameter in. (mm) 12 (304.8) 16 (406.4) 20 (508.0)24 (609.6)Air Delivery* CFM (m 3/hr) 1024 (1740) 1665 (2829) 3225 (5479) 4590 (7798) Approx. Air Velocity* FPM (m/s) 1226 (6.2) 1121 (5.7) 1407 (7.1) 1374 (7.0) Air Throw* @ 15 psi steam ft (m) 40 (12.2)47 (14.3)66 (20.1) 72 (21.9) Motor Power HP (Watts) 1/2 (373) 1/2 (373) Rec. Min. Mounting Height ft (m)7.5 (2.3)7.5 (2.3) 7.5 (2.3) 7.5 (2.3) Net Weight (without flanges)102 (46.3) 131 (59.4) 168 (76.2) 219 (99.3)Approx. Shipping Weight (without flanges)152 (68.9) 183 (83.0)227(103.0) 280 (127.0) 1/4 (186) or 1/3 (248) Lbs (kg) (with flanges)168 (76.2)199 (90.3) 243 (110.2) 296 (134.3) Lbs (kg) (with flanges) 118 (53.5) 147 (66.7) 184 (83.5)235 (106.6) HHP2-3030 (762.0)7300 (12403) 1715 (8.7) 75 (22.9) 1 (746) 7.5 (2.3) 354 (160.6)370 (167.8)457 (207.3)473 (214.5)HHP2 Specifications By Model* At 70°F (21°C), 60 Hz and sea level.1. Heater is to be connected and serviced only by qualified personnel experienced in electrical, and pipingwork.2. Installation and wiring of the heater must adhere to all applicable codes.3. For use with non-lethal fluids only, see ASME Section VIII, Div 1, UW-2.4. Heater is suitable for maximum operating pressure of 450 psi (3103 kPa) and maximum operatingtemperature of 550°F (288°C). Refer to heater and heat-exchanger data plate.5. Heater is suitable for use in hazardous locations only if fitted with an approved electric motor and the heatexchanger fluid temperature is below the ignition temperature of the atmosphere. Ensure installation and service work is performed by a qualified electrician experienced with hazardous location equipment.6. Do not operate heater in atmospheres which are corrosive to aluminum or steel, unless it has been coatedwith a factory approved protective coating.7. Heater must be kept clean. When operating in a dirty environment, regularly clean the fin tubes, fan, and fanguard. Refer to recommended maintenance procedures.8. Use factory approved replacement parts only.— INSTALLATION —These instructions are to be used as a general guideline only.LocationPlease follow guidelines below for optimum heating results:1. Do not install heaters such that airflow is blocked or impeded by equipment or walls.2. For occupant comfort, position heaters so that air discharge is directed across areas of highest heat loss,such as doors, windows, and outside walls.3. For large areas, arrange heaters such that the air discharge of one heater is directed towards the inlet of thenext heater. This sets up a rotational airflow with air circulation in the central area of the building.4. For equipment freeze protection, direct air discharge at required equipment.5. For large workshops or warehouses it may be acceptable to use fewer, but larger heaters.6. Do not direct air discharge towards a room thermostat.Mounting1. A variety of mounting brackets are available from the factory to aid in installation.2. The heater is designed to be installed in an upright and level position. While it may be installed in otherpositions, for steam service, the inlet must be above the outlet and the bottom of the heat exchanger must drain towards the outlet.3. Heaters are designed to be mounted from the top or bottom of cabinet using two 1/2 in. (12 mm) bolts orthreaded rod/pipe (rod or pipe can be extended through both top and bottom panels for extra support).4. It is essential that adequate structural support be provided for installation. The mounting structure must bestrong enough to support the heaters weight, provide sufficient stiffness to prevent excessive vibration, and withstand all probable abusive situations such as transportable installations where truck off-loading impacts, etc. may occur.Mounting Heights and Clearances1. To ensure that warm air reaches the floor, heaters are usually mounted 7-1/2 ft. (2.3m) to 12 ft. (3.6 m)above the floor. Heaters may be mounted at higher elevations and still provide warm air at floor level however, the maximum mounting elevation at which this occurs depends on location and operational conditions.2. Louvers may be adjusted to provide greater downward deflection of the discharge air. However, it isrecommended that louvers not be set less than 15 degrees from the closed position.3. Leave at least 22 in. (559 mm) clearance between the rear of the motor and the nearest obstruction.— Piping Practices —1. Steam unit heaters condense steam rapidly, especially during warm-up periods. The return piping must beplanned to keep the heat-exchanger’s core free of condensate during periods of maximum heat output, and steam piping must be able to carry a full supply of steam to the unit heater to take the place of condensed steam. Adequate pipe size is especially important when a unit heater fan is operated under on-off control because the condensate rate fluctuates rapidly.2. Heater is to be connected and serviced only by qualified personnel experienced in piping work. For addi-tional piping information refer to industrial piping handbooks and related literature.3. Eliminate pipe stress by adequately supporting all piping. Do not rely on heater to support piping.4. Take off all branch lines from the top of steam mains, preferably at a 45° angle, although vertical 90°connections are acceptable.5. Pipe the branch supply line into the steam unit heater’s inlet at the top and the return branch line from theoutlet at the bottom.6. In steam systems, the branch from the supply main to the heater must pitch down towards the main and beconnected to its top in order to prevent condensate in the main from draining through the heater, where it might reduce capacity and cause noise. In long branch lines, a drip trap may be needed.7. Allow for pipe expansion to prevent excessive strain on the unit heater’s heat-exchanger core.8. The return piping from steam unit heaters should provide a minimum drop of 10 in (254 mm) below theheater so that the pressure of water required to overcome resistances of check valves, traps, and strainers will not cause condensate to remain in the heater.9. In steam systems, where horizontal piping must be reduced in size, use eccentric reducers that permit thecontinuance of uniform pitch along the bottom of piping (in downward pitched systems). Avoid using concentric reducers on horizontal piping, because they can cause water hammer.10. Installing dirt pockets at the outlet of unit heaters and strainers with 0.063 in. (2 mm) perforations to preventrapid plugging are essential to trap dirt and scale that might affect the operation of check valves and traps.Strainers should always be installed in the steam supply line if the heater is valve controlled.11. In steam or hot water systems, rapid air removal is required because entrained air is a cause of corrosion.Hot water systems should be equipped with suitable air vent valves for rapid and complete air removal at high points, at the top of each unit heater, and ends of both supply and return mains. Proper air venting for steam systems can be achieved by use of a steam trap with an internal air vent.12. Steam traps must be located below the outlet of the unit heater. Consult the trap manufacturer for specificrecommendations. Each steam unit heater should be provided with a trap of sufficient size and capacity to pass a minimum of twice the normal amount of condensation released by the unit at the minimum differen-tial pressure in the system. Trap capacity is based on the pressure differential between supply and return mains. Steam systems should be equipped with a float and thermostatic trap or inverted bucket trap with an air bypass.13. If the condensate return line is above the heater outlet or is pressurized, install a check valve after thesteam trap and a drain valve at the strainer to drain the system during the off season.14. Install pipe unions and shut-off valves at connection points of each unit heater to allow maintenance orreplacement of unit without shutting down and draining the entire system. For hot water systems include a balancing valve in return line for flow regulation. A drain valve should be provided below each unit heater to allow removal of water from the heat-exchanger core if located in an area subject to freezing.15. Adequate air venting is required for low-pressure closed gravity systems. The vertical pipe connection tothe air vent should be at least 3/4 in. NPT to allow water to separate from the air passing to the vent. If ther-mostatic instead of float-and-thermostatic traps are used in vacuum systems, a cooling leg must be installed ahead of the trap.16. In high-pressure systems, it is customary to continuously vent the air through a petcock unless the steamtrap has a provision for venting air. Most high-pressure return mains terminate in flash tanks that are vent-ed to the atmosphere. When possible, pressure reducing valves should be installed to permit operation of the heaters at low pressure. Steam traps must be suitable for the operating pressure encountered.17. On steam systems where the steam supply to the unit heater is modulated or controlled by a motorizedvalve, a vacuum breaker should be installed between the unit outlet and a float and thermostatic trap.Heat-Exchanger Core Assembly Replacement1. Remove heater from its mounting location and lower to floor or stable working surface. Assistance is usually required to remove heater safely.2. Remove louver blades from front of cabinet using a 5/16 in. wrench or socket.3. Remove four 1/4 in. bolts holding left-side cabinet panel (when facing heater front) to top & bottom panels.4. While supporting the weight of the heat-exchanger core, by the left piping connection, remove the two 1/4 in. core bolts from left and right-side cabinet panels. Allow heat-exchanger core to rest on bottom of cabinet.5. Remove the left-side fan guard and left-side cabinet panel as follows (if heater has optional flanged connections, also remove top cabinet panel): (a) While supporting the motor mount, remove the two 5/16 in. bolts holding the motor mount to the left side of the cabinet and fan panel assembly. (b) Remove left-side cabinet panel and then reinsert the 5/16 in. bolts into the fan panel assembly. Place a support under the motor mount to prevent cabinet from tipping backwards towards motor during removal of heat-exchanger core.6. With the left-side cabinet panel removed and motor mount supported, slide heat-exchanger core out of cabinet.7. To install heat-exchanger core into cabinet, reverse order of above procedure and tighten fasteners to proper torque setting.Fan, Fan Guard or Motor Replacement1. For replacement of fan or fan guard remove four bolts holding motor to the motor mount. For HHP2-30 alsoremove speed reducer bolts. If replacing motor only on HHP2-30, only remove motor mounting bolts and C-face flange bolts. 2. Detach two-piece fan guard assembly by removing top and bottom screws that attach the fan guard to thecabinet. 3. Remove fan guard pieces through top or bottom. Due to stiffness of fan guards, you may need to removetwo outer top or bottom bolts that attach the fan panel to the top or bottom cabinet panels to provide suffi-cient clearance. 4. Lift the motor, speed reducer (for HHP2-30 only) and fan assembly off the motor mount. 5. Loosen fan hub screws and remove fan blade from motor shaft.6. To reassemble, position fan on motor shaft with end of shaft even with face of hub. Ensure the set screw isfaced towards motor and lined up perpendicular to factory-ground flat on motor shaft. This flat is our “Easy-Off” fan blade replacement feature and only comes on motors purchased from Hazloc Heaters. Tighten set screw to 150 in-lbs torque. 7. Place motor, speed reducer (for HHP2-30 only) and fan assembly onto motor mount and fasten the two-piece fan guards to the cabinet. 8. Center fan in fan-shroud opening and leave approximately 1/16” to 3/16” (1.6 to 4.8 mm) gap betweenmotor face and fan guard. 9. Bolt motor to motor mount, tighten nuts to 250 in-lbs torque. Manually spin the fan blade to ensure it rotatesfreely before reconnecting heater to power supply. Fan must rotate counterclockwise when viewed from rear of heater.— Repair and Replacement —Torque SettingsItem Torque (in-lbs)Fan blade set screw 150 5/16 - 18 UNC motor nuts 250 5/16 - 18 UNC motor mount bolts 250 1/4 - 20 UNC fan panel bolts100 1/4 - 20 UNC fan guard self tapping screws 100 #10 - 24 UNC louver blade screws28DescriptionHHP2-30Part NumberCore assembly Due to the many variations in core configurations and sizes, fluid connection types, and coat-ings, please contact factory with heater model and serial number.Top/Bottom panel HHP2-30-20-001 Side panel HHP2-30-20-002 Fan panel HUH1-30-22 Motor baseHHP2-30-20-007 Left side motor bracket HUH2-36-20-006 Right side motor bracket HUH2-36-20-005 Fan blade HHP2-30-FBMotor (56C frame)Specify motor voltage, phase, frequency, horsepower & type of enclosure (totally enclosed or explosion-proof)Speed Reducer HUH2-36-SD Speed Reducer Shim HUH2-36-20-010 Fan guard (2 pieces) HUH1-30-20-008 Louver blade kitHHP2-30-20-003-KTop/Bottom panel screw kit HHP-TB-SK Side motor bracket screw kit HUH2-36-MB-SKMotor bolt kit HH-MB-SKCore screw kit HHP-CM-SKMotor base bolt kit HH-MM-SK Speed reducer screw kit HUH2-36-GB-SKFan guard screw kit HH-FG-SK Louver screw kitHHP2-30-LB-SK*** Please have model & serial number of heater available before calling ***HHP2 (30 inch model)— Maintenance Program —Regular inspection, based on a schedule determined by the amount of dirt in the atmosphere, assures maximum operating economy and heating capacity.Annual Inspection (before each heating season)1. Check all terminal connections and electrical conductors for damage, looseness, defects, fraying, etc. andreplace or tighten where applicable.2. Check for fluid leakage from heat-exchanger core. If fluid leakage occurs, remove heater from service andhave the heat-exchanger core replaced by a factory replacement unit. Refer to “Repair and Replacement”section for complete details. Note: This heat-exchanger core is covered by the Safety Codes Act and therefore is not field repairable.3. Check electrical junction box. Inside of enclosure must be clean, dry, and free from any foreign materials.The cover must also be completely on and tight.4. Check motor shaft bearing play. Replace motor if play is excessive or if motor does not run quietly andsmoothly. Motor bearings are permanently lubricated.5. On HHP2-30 models, speed reducer is maintenance free . Check for excessive noise and vibration.6. Check fan. Replace immediately if cracked or damaged.7. Check louvers. Louver screws should be tight. Louvers are not to be set less than 15 degrees of the closedposition.8. Check the tightness of all hardware. All nuts and bolts, including mounting hardware, must be tightened totorque settings on Page 9.9. Turn heater motor on for a minimum of 10 minutes. Check for air exiting heater through louvers and smoothrunning of motor.10. Ensure periodic cleaning of complete heater is done.Periodic Maintenance (before and as required during heating season)1. Clean the following (remove dust using compressed air):∙ Finned tubes∙ Fan∙ Fan Guard∙ Motor∙ Louvers∙ cabinet2. Check the following:∙ Motor (and speed reducer on HHP2-30) for smooth and quiet operation∙ Louvers at proper angle and tightness∙ Electrical junction box covers are secureHEATER MAINTENANCE RECORDHeater Model: _________________________ Serial No.: ______________________________Date of Maintenance PerformedByMaintenance PerformedPRINTED IN CANADA©Copyright 2015The information contained in this manual has been carefully checked and verified for accuracy. Specifica-tions subject to change withoutnotice.Hazloc Heaters is a trademark ofHazloc Heaters Inc.#1, 666 Goddard Ave. NE Calgary, Alberta T2K 5X3 CanadaTel.: +1-403-730-2488 Fax: +1-403-730-2482Customer Toll Free (U.S. & Canada): +1-866-701-Heat (4328) Limited 18-Month WarrantyHazloc Heaters TM warrants all HHP2 series of heat-exchanger unit heaters against defects in materials and workmanship under normal conditions of use for a period of eighteen (18) months from date of purchase based on the following terms:1. The heater must not be modified in any way.2. The heater must be stored, installed and used only in accordance with the owner’s manual and attached data plate information.3. Replacement parts will be provided free of charge as necessary to restore any unit to normal operating condition, provided that the defective parts be returned to us freight prepaid and that the replacement parts be accepted freight collect.4. The complete heater may be returned to our manufacturing plant for repair or replacement (at our discretion), freight charges prepaid.5. Components damaged by contamination from dirt, dust, etc. or corrosion will not be considered as defects.6. This warranty shall be limited to the actual equipment involved and, under no circumstances, shall include or extend to installation or removal costs, or to consequential damages or losses.。
H-28H多输出电子压力开关说明书

0 to 200 bar
PSW3000-6K-I
750
0 to 6000 psig
0 to 400 bar
PSW3000-9K-I
790
0 to 9000 psig
0 to 600 bar
FOUR SWITCHES PLUS 0 to 10 Vdc ANALOG OUTPUT, 1⁄4 FNPT FITTING
Status Display: S1 to S4 on LCD
Digital Display
Display Height: Green, 8-digit, 14-segment LCD, 12.7 mm (0.5")
H-28
MULTI OUTPUT ELECTRONIC PRESSURE SWITCH
to PSW3001. No additional charge for metric fitting.
Ordering Examples: PSW3000-150-I, pressure switch, 0 to 10 bar (0 to 150 psig) pressure range, 4 switching outputs and 4 to 20 mA analog output, $750.
0 to 200 bar
PSW3000-6K-V
775
0 to 6000 psig
0 to 400 bar
PSW3000-9K-V
820
0 to 9000 psig
0 to 600 bar
Comes complete with connector and operator’s manual.
To order switch with G 1⁄4 female metric pressure fitting change model number from PSW3000
局部放电测试仪说明书

局部放电测试仪说明书尊敬的顾客感谢您购买本公司HTJF-H局部放电检测系统。
在您初次使用该仪器前,请您详细地阅读本使用说明书,将可帮助您熟练地使用本仪器。
我们的宗旨是不断地改进和完善公司的产品,因此您所使用的仪器可能与使用说明书有少许的差别。
如果有改动的话,我们会用附页方式告知,敬请谅解!您有不清楚之处,请与公司售后服务部联络,我们定会满足您的要求。
由于输入输出端子、测试柱等均有可能带电压,您在插拔测试线、电源插座时,会产生电火花,小心电击,避免触电危险,注意人身安全!◆慎重保证本公司生产的产品,在发货之日起三个月内,如产品出现缺陷,实行包换。
一年(包括一年)内如产品出现缺陷,实行免费维修。
一年以上如产品出现缺陷,实行有偿终身维修。
◆安全要求请阅读下列安全注意事项,以免人身伤害,并防止本产品或与其相连接的任何其它产品受到损坏。
为了避免可能发生的危2险,本产品只可在规定的范围内使用。
只有合格的技术人员才可执行维修。
—防止火灾或人身伤害使用适当的电源线。
只可使用本产品专用、并且符合本产品规格的电源线。
正确地连接和断开。
当测试导线与带电端子连接时,请勿随意连接或断开测试导线。
产品接地。
本产品除通过电源线接地导线接地外,产品外壳的接地柱必须接地。
为了防止电击,接地导体必须与地面相连。
在与本产品输入或输出终端连接前,应确保本产品已正确接地。
注意所有终端的额定值。
为了防止火灾或电击危险,请注意本产品的所有额定值和标记。
在对本产品进行连接之前,请阅读本产品使用说明书,以便进一步了解有关额定值的信息。
请勿在无仪器盖板时操作。
如盖板或面板已卸下,请勿操作本产品。
使用适当的保险丝。
只可使用符合本产品规定类型和额定值的保险丝。
避免接触裸露电路和带电金属。
产品有电时,请勿触摸裸露的接点和部位。
在有可疑的故障时,请勿操作。
如怀疑本产品有损坏,请本公司维修人员进行检查,切勿继续操作。
请勿在潮湿环境下操作。
武汉市华天电力自动化有限责任公司请勿在易爆环境中操作。
[精品]FX-H375手操器使用说明书范文
[精品]FX-H375手操器使用说明书范文-1-一使用指南1.1简介F某-H375HART手持器是支持HART协议设备的手持通信器,它可以对所有符合HART协议的设备进行配置、管理和维护。
见图1。
图1.F某-H375HART手持器F某-H375手持器可以方便的接入4~20mAHART协议仪表电流回路中,与HART协议仪表进行通信,配置HART仪表的设定参数(如量程上下限等),读取仪表的检测值、设定值,可以对仪表进行诊断和维护等等。
该手持器支持HART协议的第一主设备(HART网桥等),也支持HART协议的点对点和多点通信方式。
-2-F某-H375HART协议手持通信器1.2手持器连接F某-H375手持器可以在远端控制室或仪表就地接入单独对HART仪表进行通信操作。
连接如图3所示,手持器可以并联在HART协议设备上,也可以并联在其负载电阻(250Ω)上。
连接时不必考虑引线的极性。
图2.后连接面板图3.手持器连接图-3-注意:为保证手持器通信正常,在回路中必须有最小值为250Ω的负载电阻。
手持器不直接测量回路电流。
1.3打开手持器首先检查手持器已经装好了电池,检查如图3中的仪表回路供电正常后,按下手持器的键打开手持器(再按一次关闭手持器),手持器启动后大约5秒,手持器将自动在4-20mA回路上寻找轮询地址为零的HART设备。
如果没有找到,手持器会显示“Nodevicefoundataddre0,Poll”的提示。
如果找到了HART协议设备,手持器将显示在线主菜单,如图4。
Online(某某某某某某某某)Deviceetup1ProceVariable2Diag/Service3Baicetup4Detailedetup 图4.在线主菜单-4-F某-H375HART协议手持通信器1.4常用功能指导1.4.1监视变量(读取检测值)在线状态时,选择第一项ProceVariable并按右箭头键,即可进入监视变量功能。
合泰ph说明书
HOTEC INSTRUMENTS CO.,LTD IS0-9001 认证合格厂廠使用前注意事項(一)錯誤的接線將導致儀器故障及觸電,請熟讀操作說明書後再自行安裝。
(二)背面接地點(E點)必須確實接好(如圖說明)。
(三)當電源是三相(3ψ)AC220V時,請注意火線,以避免干擾。
(四)监测分析仪安装现场必须选择通风良好,避免阳光直射。
1酸硷度在线监测分析仪操作说明书一.酸硷度在线监测分析仪介绍(PH-101) :HOTEC监测分析仪為國人自行研製設計之精密监测分析仪,可適用於任何場合,採用較大型LCD液晶顯示(0.8〞)可耐溫至90℃不變黑。
型號歸類如下:Model:PH Analyzers PH-101HOTEC监测分析仪使用的電極來自美國BJC公司,為目前歐美電極種類最多、品質最佳的工業電極,可適用於各種場合,如廢水槽、發酵槽、本公司生產之监测分析仪為高阻抗輸入型,可適用任何廠牌工業用電極。
二.使用前安裝程序:1.核對配件是否齊全。
2.安裝組合電極。
3.安裝监测分析仪。
4.連接電極線、訊號線、及傳送器。
5.確定操作範圍接上電源。
6.校正使用標準液。
2三.規格及特征:1、主机2、传输距离:分析仪(主机)至电极距离达30m;4-20mA信号传输可达1000。
3、电极(美国BJC电极)特点:环状陶瓷孔,耐高污染,不易阻塞,清洗容易,HT3蓝色玻璃头抗紫外线干扰;填充液为内压式;适用温度:-5 to 100℃。
耐压能力≥30psig4、接线盒/IP管抗干扰:抗紫外线干扰;防水等级:IP65。
3四.面板說明(TABLE1):A:型號HOTEC PH -101TABLE1B.型號:PH-101功能鍵說明(1)【POWER 】鍵:電源開關(2)【STDBY 】鍵:電源釋能開關(3)【MODE 】鍵:功能選擇開關,按MODE鍵則設定順序如下:pΗ→Lo→Hi→pΗ(4)CALIB旋鈕:pΗ7.00校正鈕或mV零點調整鈕。
HTHB-HRF-RF 双喷嘴冷水字体说明书
Contour™ Refrigerated Fountainswith Double-Bubbler™ and HydroBoostNOTE: It is common practice to ground electrical hardware such as telephones, computers and other devices to available water lines. This can, however, cause electrical feedback in the plumbing circuit, which0000001062 (Rev. F - 04/18 )Page 10000001062 (Rev.FE - 04/18 )Page 20000001062 (Rev. F - 04/18 )Page 30000001062 (Rev.FE - 04/18 )Page 4CHILLER INLETCHILLER OUTLET7STRAINERTO BUBBLER7TO BOTTLEFILLERFigure 4 – HTHBWF-HRF-RF Filter Mounting(not required with HTHB-HRF-RF)0000001062 (Rev. F - 04/18 )Page 5Figure 7 – Fountain InstallationFigure 8 – Lower Panel Installation72NutNut3,4,5,6,71Reset Switch10. Install fountains with (4) 5/16-18 HHMS, (4) 5/16-18 nuts (from original installation) (Fig. 7). Connect the ¼” water lines from the fountain to the remaining opening on the tee at the remote chiller (cut lines to fit as needed), (Test fit refrigerated panel to make sure there is a tight joint between it & the main panel before fully tightening mounting screws.)11. Attach waste tubes (1-1/4” O.D.) to 1-1/4” O.D. slip trap. Trap on the bottle filler side must be 1-1/2” O.D. (Traps and connec- tion fittings provided by others).12. Drill a 5/32” (.156”) diameter mounting hole in right hand frame to secure the lower right corner of the upper panel.• Center the hole in tab opening.• Secure the panel to the frame with (screw in kit Item 7).13. Make final water supply connections. Turn on water supply, check for leaks. Repair leaks as required.• These products are designed to operate on 20-105 PSI supply line pressure. If inlet pressure is above 105 PSI, a pressure regulator must be installed in the supply line. • (Caution: Any damage caused by connecting these products to a supply line with pressure lower than 20 PSI or higher than 105 PSI IS NOT covered under warranty.)14. Make electrical connections to the bottle filler and remote chiller. The LCD Bottle counter should illuminate. Refer toBF11 Program instructions for additional details on Bottle Filler setup.15. Verify proper dispensing from the bottle filler by placing a cup, hand or any opaque object in front of sensor area and verify water dispenses. Note: the first initial dispenses might have air in the line which may cause a sputter. This will be eliminated once all air is purged from the line. A steady stream of water assures all air is removed. The sensor has a 20 second maxi- mum ON time. It may be necessary to step away from the beam a few times to purge all air. Check for leaks. 16. Reconfirm the installation has no leaks. Install the lower (louver) panel.7 See Note 12NOTE: The following items are not used with the converted installation: – One Fountain Assembly – Wall Frame - Left Side – Upper Panel – Lower (Louver) PanelVERIFY CONTROL BOARD SOFTWARE1) To verify the software program of the control board the unit willneed to be shut down and restarted. The chiller (if present) doesnot need to be shut down and restarted.2) Shut down the unit by unplugging the power cord from the walloutlet or switching off the circuit breaker to the unit.3) Restart the unit by plugging the power cord back into the walloutlet or by switching on the circuit breaker to the unit.4) Upon start up, the bottle count display will show the softwaredesignation of BF11 or BF12.ACCESSING THE PROGRAMMING BUTTON1) To access the program button, remove the bottom lower louveredpanel (Fig. 7) by removing the lower panel screws. Reset button is located on the mounting bracket.RESET THE FILTER MONITOR1) Instructions apply to filtered units only.2) Depress the program button for approximately 2 seconds until thedisplay changes then release. The display will change and scrollthrough two messages:“RST FLTR” – Reset Filter Monitor“SETTINGS” – System Settings Sub MenuIf the program button is not pushed again the display will scroll through the two messages above for three cycles and then default back to bottle count and be back in run mode.3) When the display changes to “RST FLTR”, depress the buttonagain. The display will change to show “FLTR =”. Depress thebutton again and the display will show “FLTR =0”4) The Green LED should be illuminated indicating that the visual filtermonitor has been reset.SETTING RANGE OF THE IR SENSOR WHERE APPLICABLE 1) Depress the program button for approximately 2 seconds until thedisplay changes then release. The display will change and scroll through two messages:“RST FLTR” – Reset Filter Status LED“SETTINGS” – System Settings Sub MenuIf the program button is not pushed again the display will scroll through the two messages above for three cycles and then default back to bottle count and be back in run mode.2) When the display changes to “SETTINGS”, depress the buttonagain. The display will change to show“RNG SET” - Range set for IR sensor.“UNIT TYP” - Type of unit (REFRIG or NON-RFRG)“FLT SIZE” - Select filter capacity“RST BCNT” - Reset bottle count3) When display shows “RNG SET” push program button once thedisplay will show current value (can be 1 – 10) e.g. “RNG = 3”.4) Once display shows current value push the program button to scrollthrough value of 1 – 10. Select the desired range setting, "1" being closest to sensor and "10" being farthest away.5) Once range is selected allow approximately 4 seconds to pass andthen the display will go back to bottle counter and be in run mode. 6) Test bottle filler by placing bottle or hand in front of sensor to makesure water is dispensed.SETTING UNIT TYPE1) Depress the program button for approximately 2 seconds until thedisplay changes then release. The display will change and scroll through two messages:“RST FLTR” – Reset Filter Status LED“SETTINGS” – System Settings Sub MenuIf the program button is not pushed again the display will scrollthrough the two messages above for three cycles and then default back to bottle count and be back in run mode.2) When the display changes to “SETTINGS”, depress the buttonagain.The display will change to show“RNG SET” - Range set for IR sensor.“UNIT TYP” - Type of unit (REFRIG or NON-RFRG)“FLT SIZE” - Select filter capacity“RST BCNT” - Reset bottle count Continued from below:3) W hen display shows “UNIT TYPE” push program button once thedisplay will show current value. C an be REFRIG or NON-RFRG4) Push button once to change value. Once value is s elected the display will show the new value. (Can be REFRIG or NON-RFRG) “REFRIG“ - stands for refrigerated product. In this setting the flow rate is estimated at 1.0 gallon per minute.“NON-RFRG“ - stands for nonrefrigerated product. In this setting theflow rate is estimated at 1.5 gallons per minute. Both “REFRIG“ and“NON-RFRG“ simulate 1 bottle equal to 20 oz.5) A llow approximately 4 seconds to pass and the display will return to bottle counter and be in run mode.RESETTING BOTTLE COUNT1) Depress the program button for approximately 2 seconds until thedisplay changes then release. The display will change and scrollthrough two messages:“RST FLTR” – Reset Filter Status LED“SETTINGS” – System Settings Sub MenuIf the program button is not pushed again the display will scroll through the two messages above for three cycles and then default back to bottle count and be back in run mode.2) When the display changes to “SETTINGS”, depress the button again. The display will change to show:“RNG SET”- Range set for IR sensor.“UNIT TYP” - Type of unit (REFRIG or NON-RFRG)“FLT SIZE” - Select filter capacity“RST BCNT” - Reset bottle countIf the button is not pushed again the display will scroll through the four messages above for three cycles and return to run mode.3) W hen display shows “RST BCNT” push program button once thedisplay will show current value, e.g. “0033183”.4) Once display shows current value push the program button once more to reset back to 0. The display will show BTLCT = 0 for approximately 2 seconds and then return to run mode showing 00000000 bottles. NOTE: Once the bottle count is reset to zero there is no way to return to the previous bottle count.5) T esting the bottle counter:REFRIG units: Place bottle or hand in front of sensor for approximately9 seconds to see bottle counter count 00000001,(This is based on filling a 20 oz. bottle).NON-RFRG units: Place bottle or hand in front of sensor for approximately 6 seconds to see bottle counter count 00000001,(This is based on filling a 20 oz bottle).SETTING FILTER CAPACITY1) Depress the program button for approximately 2 seconds until thedisplay changes then release. The display will change and scroll through two messages:“RST FLTR” – Reset Filter Status LED“SETTINGS” – System Settings Sub MenuIf the program button is not pushed again the display will scroll through the two messages above for three cycles and then default back to bottle count and be back in run mode.2) When the display changes to “SETTINGS”, depress the button again. The display will change to show:“RNG SET“- Range set for IR sensor.“UNIT TYP“ - Type of unit (REFRIG or NON-RFRG)“FLT SIZE” - Select filter capacity“RST BCNT“ - Reset bottle countIf the button is not pushed again the display will scroll through the four messages above for three cycles and return to run mode.3) W hen display shows “FLT SIZE” push program button once. The display will show current value. Can be 3000GAL or 6000GAL.4) Push program button again to display the desired “FLT SIZE”.5) Allow approximately 4 seconds to pass and the display will return tobottle counter and be in run mode.BF11 - BF12 PROGRAMSETTING THE CONTROL BOARD0000001062 (Rev.FE - 04/18 )Page 62222 CAMDEN COURT OAK BROOK, IL 60523 630.574.3500Figure 11 – Water Supply ConnectionsNOTE: WATER FLOWDIRECTIONSERVICE STOP(NOT FURNISHED)1/4” O.D. TUBE3/8” O.D. UNPLATEDNote: Screw the locknut hand tight to sealFigure 12 – Super Seal ConnectionsDO NOTActuation of Quick Connect Water Fittings: Cooleris provided with lead-free connectors which utilize ano-ring water seal. To remove tubing from the fitting,relieve water pressure, push in on the gray collar whilepulling on the tubing. (See Fig. 13) To insert tubing,0000001062 (Rev. F - 04/18 ) Page 7。
HAWE Hydraulik DRH 双通道压力关闭阀说明书
Releasable twin check valve type DRH Product documentationOperating pressure p max: 500 barFlow rate Q max: 140 lpmD 6110© by HAWE Hydraulik SE.The reproduction and distribution of this document as well as the use and communication of its contents to others without explicit authorisation is prohibited.Offenders will be held liable for the payment of damages.All rights reserved in the event of patent or utility model applications.Brand names, product names and trademarks are not specifically indicated. In particular with regard to registered and protected names and trademarks, usage is subject to legal provisions.HAWE Hydraulik respects these legal provisions in all cases.Printing date / document generated on: 17.01.2018Contents1Overview of releasable twin check valve type DRH (4)2Available versions, main data (5)3Parameters (7)4Dimensions (9)5Assembly, operation and maintenance recommendations (13)5.1Intended use (13)5.2Assembly information (13)5.3Operating instructions (14)5.4Maintenance information (14)6Circuit examples (15)1Overview of releasable twin check valve type DRHCheck valves with hydraulic release are a type of check valve. They block one or both hydraulic consumer lines or are used as a hydraulically actuated drain or circulation valve.In the closed state the check valve type DRH has zero leakage. It is a twin check valve for double-acting consumers. Available with hydraulic release. Hydraulic release suppresses relief surges that can occur at high pressure and with a large consumer volume.Features and bene ts:■Pressures up to 500 bar■with hydraulic release for smooth switchingIntended applications:■Blocking of leak-free hydraulic cylindersVersions:■Pipe connection■Manifold mountingReleasable twin check valve type DRHCheck valves■Used in all customary applications in which a consumer is controlled via a directional spool valve with a blocked or free pump through- ow or when several consumers are selectively actuated via directional spool valves in a parallel circuit. See Chapter 6, "Circuit examples". To release the pressure blocked at A or B, approximately 0.4 times the pressure is required on the other side.Versions with integrated pressure-limiting valves enable use in conjunction with hydraulic motors, pivoting or rotating cylinders (type DRHS or DRHCS with shock valves), or with miniature pressure-limiting valves make it possible to avoid slow pressure build-upse.g. by expansion of volume with a rise in temperature (type DRH..SS).Check valves with drain port■For all applications where several consumers are actuated in series with the P d R pump through- ow. If a downstream direction-al spool valve is actuated, all upstream spool valves are loaded with the system pressure of the actuated consumer in the P d R through- ow, so that leakage oil slowly penetrates into the consumer connections and lines (see Chapter 6, "Circuit examples").The continuous drainage of leakage oil via the separate leakage line prevents a gradual pressurisation with uncontrolled release and possible drifting of the consumers. The leakage outlet is closed when the check valve is in the released position.Check valves with hydraulic release■For applications where the basic version cannot be released due to unfavourable area or load ratios at the hydraulic cylinder (rod side). Relieving the hydraulic release takes approx. 0.1 times the pressure on the opposing side. The hydraulic release can be single-sided (type DRH..V) or on both sides (type DRH.. VV).2Available versions, main dataCircuit symbol:DRH 1DRH 2DRH 3DRH 3 L DRH 4 LDRH 5 LDRH 1 PDRH 3 PDRH 3 PG...DRH 3 LSS-..DRHS 2..DRH 3 SS-..DRHCS 2DRH 2 ADRH 2 MAOrder coding example:Shock valve pressure setting (bar); see Chapter 3, "Parameters"Table 1 Basic type, size, functionTable 1 Basic type, size, function3Parameters General informationCharacteristic curvesOil viscosity approx. 50 mm 2/sCurve 1:C d AD d BCurve 2: A d C B d D(released)Δp ow resistance (bar); Q ow rate (lpm)Δp ow resistance (bar); Q ow rate (lpm)Pilot pressure p St (bar) on the feed side (reference value)To release:p St, 0.4 p A(B) + 3p A(B)Pressure (bar) on the blocked side Aor BHydraulic release for release:p StV, 0.1 p A(B) + 12To keep open: 1p St , 0.5 Δp A(B) + p C(D) + kΔp A(B)Flow resistance curve 2 at released port A or Bp C(D)Pressure (bar) on the out ow side C or Dk, 6 DRH 1 and DRH 2, 4 DRH 3, 3 DRH 4 and DRH 5WeightType DRH 1= approx. 0.5 kg DRH 2= approx. 1.2 kg DRHS 2= approx. 1.5 kg DRHCS 2= approx. 1.8 kg DRH 3= approx. 1.6 kg DRH 4= approx. 2.9 kg DRH 5= approx. 5.5 kg1A (dragging) load in the direction of the consumer movement may cause utter at the check valve. This can be prevented by installing a restrictor check valve between the check valve and consumer. Suitable for this purpose are types QR, QV according to D 7730 or type RD according to D 7540. Alternatively use type DRHCS ...4DimensionsAll dimensions in mm, subject to change.DRH 1 ... 5 (L, V, VV)1Port L for type DRH..L onlyConnections (ISO 228-1)A, B, C, D LDRH 1G 1/4 (BSPP)--DRH 2G 3/8 (BSPP)--DRH 2 JIS G 3/8-JIS (BSPP)--DRH 2 M M16x1.5--DRH 3--DRH 3LG 1/2 (BSPP)G 3/8 (BSPP) DRH 4--DRH 4LG 3/4 (BSPP)G 1/2 (BSPP) DRH 5--DRH 5LG 1 (BSPP)G 3/4 (BSPP)Type L B H SW a b c e e1e2g DRH 17045201410218502854M6 DRH 2896030221326.510633673M8 DRH 3DRH 3L1156030271739.513813699M10DRH 4DRH 4L1507040322247.515.510655134M10DRH 5DRH 5L19580504127.5651714065179M10DRH 1 P (VV)1O-ring 7.65x1.78 NBR 90 ShDRH 1 PG VV1O-ring 7.65x1.78 NBR 90 ShDRHS 2Pressure adjustment for type DRHS 2:After undoing the tapped plug and loosening the grub screw,the pressure can be adjusted with a threaded washer within the respective pressure range (monitor the pressure gauge!):Connections (ISO 228-1) (BSPP)A, B, C, DG 3/8DRHCS 21Shock valve B2Pre-load valve A3Pre-load valve B4Shock valve APressure adjustment for type DRCHS 2:Identical for shock and pre-load valve (monitor the pressure gauge!):Connections (ISO 228-1) (BSPP)A, B, C, D G 3/8DRH 3 SS (V, VV)DRH 3 LSS (V, VV)1Port L only for type DRH 3 L...Connections (ISO 228-1) (BSPP) A, B, C, D G 1/2L G 3/8DRH 3 P (V, VV)1O-ring 15 x 2.5 NBR 90 Sh5Assembly, operation and maintenance recommendations5.1 Intended useThis valve is exclusively intended for hydraulic applications ( uid engineering).The valve demands high technical safety standards and regulations for uid engineering and electrical engineering.The user must observe the safety measures and warnings in this documentation.Essential requirements for the product to function correctly and safely:–All information in this documentation must be observed. This applies in particular to all safety measures and warnings.–The product must only be assembled and put into operation by quali ed personnel.–The product must only be operated within the speci ed technical parameters. The technical parameters are described in detail in this documentation.–The operating and maintenance manual of the speci c complete system must also always be observed.If the product can no longer be operated safely:1.Remove the product from operation and mark it accordingly✓It is then not permissible to continue using or operating the product5.2 Assembly informationThe product must only be installed in the complete system with standard and compliant connection components (screw ttings, hoses, pipes, etc.).The hydraulic power pack must be shut down correctly prior to dismounting; this applies in particular to power packs with hydraulic accumulators.5.3 Operating instructionsProduct configuration and setting the pressure and ow rateThe statements and technical parameters in this documentation must be strictly observed.The instructions for the complete technical system must also always be followed.Purity and ltering of the hydraulic uidFine contamination can significantly impair the function of the hydraulic component. Contamination can cause irreparable damage.Examples of ne contamination include:–Metal chips–Rubber particles from hoses and seals–Dirt due to assembly and maintenance–Mechanical debris–Chemical ageing of the hydraulic uidPay attention to the cleanliness level of the hydraulic uid in order to maintain faultless operation.(Also see cleanliness level in Chapter 3, "Parameters").5.4 Maintenance informationThis product is largely maintenance-free.Conduct a visual inspection at regular intervals, but at least once per year, to check if the hydraulic connections are damaged. If external leakages are found, shut down and repair the system.Clean the device surface of dust deposits and dirt at regular intervals, but at least once per year.6Circuit examplesExample 1:General application with directional spool valve1Cylinder type P.. according to D 2055/12Type DRH 33Directional spool valve4Pump type R according to D 6010 HExample 2:Application in shipbuilding with directional spool valves connected in series1Pump type R according to D 6010 H2Pressure-limiting valve type MV 6.. according to D 7000/13Type DRH 5L4Separate leakage line5Directional spool valve type SG 5 LS according to D 5650/10 - D R H - 09-2015-1.2.1HAWE Hydraulik SE Einsteinring 17 | 85609 Aschheim/München | Postfach 11 55 | 85605 Aschheim | Germany Tel+4989379100-1000|Fax+4989379100-91000|************| Further information Additional versions■Releasable check valve type RH: D 6105■Check valve type CRK, CRB and CRH: D 7712■Releasable check valve type HRP: D 5116■Releasable check valve type RHC and RHCE: D 7165Application■Proportional directional spool valve, type PSL and PSV size 2: D 7700-2■Proportional directional spool valve, type PSL, PSM and PSV size 3: D 7700-3■Proportional directional spool valve, type PSL, PSM and PSV size 5: D 7700-5■Proportional directional spool valve type PSLF, PSVF and SLF size 3: D 7700-3F ■Proportional directional spool valve type PSLF, PSVF and SLF size 5: D 7700-5F ■Directional spool valve bank type SWS: D 7951。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
HTJF-H局部放电检测系统的使用
尊敬的顾客
感谢您购买本公司HTJF-H局部放电检测系统。
在您初次使用该仪器前,请您详细地阅读本使用说明书,将可帮助您熟练地使用本仪器。
我们的宗旨是不断地改进和完善公司的产
品,因此您所使用的仪器可能与使用说明书有
少许的差别。
如果有改动的话,我们会用附页
方式告知,敬请谅解!您有不清楚之处,请与
公司售后服务部联络,我们定会满足您的要求。
由于输入输出端子、测试柱等均有可能带电压,您在插拔测试线、电源插座时,会产生电火花,小心电击,避免触电危险,注意人身安全!
◆慎重保证
本公司生产的产品,在发货之日起三个月内,如产品出现缺陷,实行包换。
一年(包括一年)内如产品出现缺陷,实行免费维修。
一年以上如产品出现缺陷,实行有偿终身维修。
◆安全要求
请阅读下列安全注意事项,以免人身伤害,并防止本产品或与其相连接的任何其它产品受到损坏。
为了避免可能发生的危
险,本产品只可在规定的范围内使用。
只有合格的技术人员才可执行维修。
—防止火灾或人身伤害
使用适当的电源线。
只可使用本产品专用、并且符合本产品规格的电源线。
正确地连接和断开。
当测试导线与带电端子连接时,请勿随意连接或断开测试导线。
产品接地。
本产品除通过电源线接地导线接地外,产品外壳的接地柱必须接地。
为了防止电击,接地导体必须与地面相连。
在与本产品输入或输出终端连接前,应确保本产品已正确接地。
注意所有终端的额定值。
为了防止火灾或电击危险,请注意本产品的所有额定值和标记。
在对本产品进行连接之前,请阅读本产品使用说明书,以便进一步了解有关额定值的信息。
请勿在无仪器盖板时操作。
如盖板或面板已卸下,请勿操作本产品。
使用适当的保险丝。
只可使用符合本产品规定类型和额定值的保险丝。
避免接触裸露电路和带电金属。
产品有电时,请勿触摸裸露的接点和部位。
在有可疑的故障时,请勿操作。
如怀疑本产品有损坏,请本公司维修人员进行检查,切勿继续操作。
请勿在潮湿环境下操作。
请勿在易爆环境中操作。
保持产品表面清洁和干燥。
-安全术语
警告:警告字句指出可能造成人身伤亡的状况或做法。
小心:小心字句指出可能造成本产品或其它财产损坏的状况或做法。
HTJF-H局部放电检测系统
一、概述:
局部放电试验是电力设备绝缘的主要试验项目,是根据国际及国内目前最新技术进展而开发的HTJF-H局部放电检测系统,它集计算机控制,数字采样,显示及打印技术与一体。
以崭新的二维及三维图形显示局部放电图谱信息,HTJF-H系统可单路或双路输入信号,双路输入方式使其具备平衡回路检测、脉冲极性鉴别检测功能。
HTJF-H系统就其检测方法、测量回路、技术性能参数完全符合GB7354-87及ICE-270局部放电测量标准要求。
纯程控工作方式;全汉字菜单提示;任意存贮、打印;自动生成试验报告;二维及三维局部放电图谱显示;采用数字开窗技术,抗干扰能力强;双通道测量及数字差分技术,可同时测量两个试品或一个试品两个测量点的局部放电信号,可方便地分析局部放电信号的来源。
本产品系国家“七五”重点科技攻关项目和电力部“八五”重点
推广项目。
先后在葛州坝50kV开关站,武汉凤凰山500kV变电站,沈阳变压器厂等对数百台变压器进行测试,工作可靠,操作方便。
二、系统原理:
HTJF-H系统采用的检测方法是世界上目前最广泛采用的直接法、电桥平衡法、电流脉冲法,其基本原理:试品产生一次局部放电时,试品Cx两端产生瞬时的电压变化ΔU,经过一耦合电容Ck耦合到检测阻抗Zm,回路中会产生一脉冲电流I,将此脉冲电流I经检测阻抗Zm产生的脉冲电压进行采样,放大和显示处理,就可以测定局部放电的视在放电量等参数。
脉冲电流法主要利用局部放电信号频谱中的较低频部分,可避免无线电干扰。
HTJF-H系统配置RLC型检测阻抗,他测量局部放电产生的脉冲信号,并抑制实验电源的工频及其它低频干扰信号。
HTJF-H系统为脉冲峰值指示形式测试系统,具有计算机程控滤波、放大、采样、存储及显示等功能。
数据采集与试验电压同步进行。
能够用直接法、电桥平衡法、复率n、平均放电电流I、平方率D,可作各种图谱:q-n、q-ф、q-ф-t等,整套测量系统能检测出小于1000pC局部放电量的超声信号。
其软件具备测试结果的统计评估和局部放电数据为基础的局部放电故障自动识别功能,自动生成报告;虚拟示波器有线性、椭圆2维、3维图形显示方式。
该装置适合GIS、电缆、110KV及以上电压等级的电力变压器、35KV及以上电压等级的电力互感器、套管、避雷器、耦合电容器等电力设备的局部放电试验。
二、系统配置:
1.硬件系统:
A.工控机:
a.放大器、滤波器
b.零标电路
c.A/D转换器
d.RAM存储器
B.显示器(17寸液晶彩显)
C.打印机:24针式打印机
D.检测阻抗4只
E.HTJF-301校准脉冲发生器
F.测量屏蔽电缆(50米、20米同轴信号电缆)
G.101键盘
H.铝合金包装箱
2.软件系统配置:
A.数据采集与网络通信软件
B.图形显示及处理软件
C.系统工作方式控制软件
D.局部放电信号分析软件
三、系统技术指标:
1.计算机:工控机、256M内存、3寸软驱、2M电子盘、高速缓存型
显卡、通信接口、LP打印机接口、RS232接口、WIN XP界面、INTER 2G以上的处理器、80G硬盘、8M显存、40倍速光驱、VGA图卡。
2.程控滤波器:低频带10、20、40KHZ
高频带100、200、300KHZ
3.放大器:其中手动粗调放大器增益调节范围(-40dB~60dB),
程控微调放大器增益调节范围16档24 dB。
输入阻抗1MΩ
输入端子噪音小于5μV
3dB频带10HZ-300KHZ
各量程档位20%标尺-100%标尺,线性度误差小于10%
各量程档位脉冲低重复率误差小于10%
4.A/D转换器:A/D转换器采样速率:0.1μs/点
A/D转换器采样精度:8位±1/2LSB
5.RAM存储器:每路128K
6.显示器:17寸液晶彩显
7.打印机: 24针打印机
8.HTJF-301校准脉冲发生器:
输出校准脉冲电压值5档可调:0.5V、1V、2.5V、5V、10V
校准电容值5档可调:10pF、20pF、50pF、100pF、200pF
输出阻抗小于100Ω、频率1000HZ、校准脉冲值误差小于1.5%
校准脉冲电压波形上升时间小于60ns
校准脉冲电压波形衰减时间大于100μs
工作电源为可充电蓄电池,工作电压DC12V。
9.测量通道:2个10.工作环境:
温度:-5℃~45℃
湿度:≤90%
海拔高度: <1000m 地震强度:≤7级
适合户内及户外使用。