XF 110KV变电所是地区重要变电所,是电力系统110KV电压等级的重要部分。其设计分为电气一次部分和电气二次部分设计。

一次部分由说明书,计算书与电气工程图组成,说明书和计算书包括变电所总体分析;负荷分析与主变选择;电气主接线设计;短路电流计算;电气设备选择;配电装置选择;变电所总平设计及防雷保护设计。

二次部分由说明书,计算书与电气工程图组成。说明书和计算书包括整体概述;线路保护的整定计算;主变压器的保护整定计算;电容器的保护整定计算;母线保护和所用变保护设计。

计算书和电气工程图为附录部分。其中一次部分电气AutoCAD制图六张;二次部分为四张手工制图。

本变电所设计为毕业设计课题,以巩固大学所学知识。通过本次设计,使我对电气工程及其自动化专业的主干课程有一个较为全面,系统的掌握,增强了理论联系实际的能力,提高了工程意识,锻炼了我独立分析和解决电力工程设计问题的能力,为未来的实际工作奠定了必要的基础。

关键词: Ⅰ、变电所Ⅱ、变压器Ⅲ、继电保护

Abstract

XF county 110KV substation is an important station in this distract, which is one of the extremely necessary parts of the 110KV network in electric power system.

The design of the substation can be separated in two parts: primary part and secondary part of the electric design.

The first part consists of specifications, computation book and Electrical engineering drawings about the design. The specifications has several parts which are General analysis of the station, Load analysis, The selection of the main transformer, Layout of configuration, Computation of short circuit; Select of electric

devices, Power distribution devices, General design of substation plane and the design of thunderbolt protection.

The second part also consists of specifications, computation book and electrical drawings about the design。Specifications and computation book include following section: General, The evaluation and calculate of line protection, Transformer protection, capacitor protection, Bus protection and Self-using transformer protection.

Computation book, Electrical engineering drawings and catalogue of drawings are attached in the end。There are nine drawings total, in which four are prepared by hand, others are prepared by computer in which installed the software electrical AutoCAD. From other view, it also can be classified as first part and second part.

This is a design of substation for graduation design test. It can strengthen our specified knowledge.

Key-words: Ⅰsubstation Ⅱtransformer Ⅲ Relay protection

谢辞

首先,在设计前的理论学习和实验环节中,刘宪林、王克文、陈根永、孔斌、包毅等专业课和实验指导老师的教导为我提供了丰富的专业理论知识和实践分析能力。在本次设计的近一个学期中,和极其认真负责的辅导和耐心的解答帮助我解决了一个个的难题。在此要对老师们不辞劳苦的工作和无私奉献的精神表示衷心的感谢!

在本次设计过程中,特别要感谢同寝室的同学、及同组的同学,他们的帮助让这次设计变得轻松了许多。

设计中虽然充分采纳了老师和同学们的意见,几经修改,但由于是初次设计,加之自身水平有限,设计及论述过程中难免有错误,请各位老师批评指正。

附录1:外文资料翻译

A1.1译文

变压器

1. 介绍

要从远端发电厂送出电能,必须应用高压输电。因为最终的负荷,在一些点高电压必须降低。变压器能使电力系统各个部分运行在电压不同的等级。本文我

们讨论的原则和电力变压器的应用。

2. 双绕组变压器

变压器的最简单形式包括两个磁通相互耦合的固定线圈。两个线圈之所以相互耦合,是因为它们连接着共同的磁通。

在电力应用中,使用层式铁芯变压器(本文中提到的)。变压器是高效率的,因为它没有旋转损失,因此在电压等级转换的过程中,能量损失比较少。典型的效率范围在92到99%,上限值适用于大功率变压器。

从交流电源流入电流的一侧被称为变压器的一次侧绕组或者是原边。它在铁圈中建立了磁通φ,它的幅值和方向都会发生周期性的变化。磁通连接的第二个绕组被称为变压器的二次侧绕组或者是副边。磁通是变化的;因此依据楞次定律,电磁感应在二次侧产生了电压。变压器在原边接收电能的同时也在向副边所带的负荷输送电能。这就是变压器的作用。

3. 变压器的工作原理

当二次侧电路开路是,即使原边被施以正弦电压V p,也是没有能量转移的。外加电压在一次侧绕组中产生一个小电流Iθ。这个空载电流有两项功能:(1)在铁芯中产生电磁通,该磁通在零和 φm之间做正弦变化,φm是铁芯磁通的最大值;(2)它的一个分量说明了铁芯中的涡流和磁滞损耗。这两种相关的损耗被称为铁芯损耗。

变压器空载电流Iθ一般大约只有满载电流的2%—5%。因为在空载时,原边绕组中的铁芯相当于一个很大的电抗,空载电流的相位大约将滞后于原边电压相位90o。显然可见电流分量I m= I0sinθ0,被称做励磁电流,它在相位上滞后于原边电压V P 90o。就是这个分量在铁芯中建立了磁通;因此磁通φ与I m同相。

第二个分量I e=I0sinθ0,与原边电压同相。这个电流分量向铁芯提供用于损耗的电流。两个相量的分量和代表空载电流,即

I0 = I m+ I e

应注意的是空载电流是畸变和非正弦形的。这种情况是非线性铁芯材料造成的。

如果假定变压器中没有其他的电能损耗一次侧的感应电动势E p和二次侧的感应电压E s可以表示出来。因为一次侧绕组中的磁通会通过二次绕组,依据法拉第电磁感应定律,二次侧绕组中将产生一个电动势E,即E=NΔφ/Δt。相同的磁通会通过原边自身,产生一个电动势E p。正如前文中讨论到的,所产生的电压必定滞后于磁通90o,因此,它于施加的电压有180o的相位差。因为没有电流流过二次侧绕组,E s=V s。一次侧空载电流很小,仅为满载电流的百分之几。因此原边电压很小,并且V p的值近乎等于E p。原边的电压和它产生的磁通波形是正弦形的;因此

产生电动势E p 和E s 的值是做正弦变化的。产生电压的平均值如下

E avg = turns×给定时间内磁通变化量给定时间

即是法拉第定律在瞬时时间里的应用。它遵循

E avg = N 21/(2)

m f = 4fNφm 其中N 是指线圈的匝数。从交流电原理可知,有效值是一个正弦波,其值为平均电压的1.11倍;因此

E = 4.44fNφm

因为一次侧绕组和二次侧绕组的磁通相等,所以绕组中每匝的电压也相同。因此

E p = 4.44fN p φm

并且

E s = 4.44fN s φm

其中N p 和E s 是一次侧绕组和二次侧绕组的匝数。一次侧和二次侧电压增长的比率称做变比。用字母a 来表示这个比率,如下式 a = p s

E E = p s N N 假设变压器输出电能等于其输入电能——这个假设适用于高效率的变压器。实际上我们是考虑一台理想状态下的变压器;这意味着它没有任何损耗。因此

P m = P out

或者

V p I p × primary PF = V s I s × secondary PF

这里PF 代表功率因素。在上面公式中一次侧和二次侧的功率因素是相等的;因此

V p I p = V s I s

从上式我们可以得知

p s V V = p s I I ≌ p s

E E ≌ a 它表明端电压比等于匝数比,换句话说,一次侧和二次侧电流比与匝数比成

当副边电压V s 相对于原边电压减小时,这个变压器就叫做降压变压器。如果这个电压是升高的,它就是一个升压变压器。在一个降压变压器中传输变比a 远大于1(a>1.0),同样的,一个升压变压器的变比小于1(a<1.0)。当a=1时,变压器

的二次侧电压就等于起一次侧电压。这是一种特殊类型的变压器,可被应用于当一次侧和二次侧需要相互绝缘以维持相同的电压等级的状况下。因此,我们把这种类型的变压器称为绝缘型变压器。

显然,铁芯中的电磁通形成了连接原边和副边的回路。在第四部分我们会了解到当变压器带负荷运行时一次侧绕组电流是如何随着二次侧负荷电流变化而变

化的。

从电源侧来看变压器,其阻抗可认为等于V p / I p 。从等式 p s V V = p s I I ≌ p s

E E ≌ a 中我们可知V p = aV s 并且I p = I s /a 。根据V s 和I s ,可得V p 和I p 的比例是

p p V I = /s s aV I a = 2s s

a V I 但是V s / I s 负荷阻抗Z L ,因此我们可以这样表示

Z m (primary) = a 2Z L

这个等式表明二次侧连接的阻抗折算到电源侧,其值为原来的a 2倍。我们把这种折算方式称为负载阻抗向一次侧的折算。这个公式应用于变压器的阻抗匹配。

4. 有载情况下的变压器

一次侧电压和二次侧电压有着相同的极性,一般习惯上用点记号表示。如果点号同在线圈的上端,就意味着它们的极性相同。因此当二次侧连接着一个负载时,在瞬间就有一个负荷电流沿着这个方向产生。换句话说,极性的标注可以表明当电流流过两侧的线圈时,线圈中的磁动势会增加。

因为二次侧电压的大小取决于铁芯磁通大小φ0,所以很显然当正常情况下负载电势E s 没有变化时,二次电压也不会有明显的变化。当变压器带负荷运行时,将有电流I s 流过二次侧,因为E s 产生的感应电动势相当于一个电压源。二次侧电流产生的磁动势N s I s 会产生一个励磁。这个磁通的方向在任何一个时刻都和主磁通反向。当然,这是楞次定律的体现。因此,N s I s 所产生的磁动势会使主磁通φ0减小。这意味着一次侧线圈中的磁通减少,因而它的电压E p 将会增大。感应电压的减小将使外施电压和感应电动势之间的差值更大,它将使初级线圈中流过更大的电流。初级线圈中的电流I p 的增大,意味着前面所说明的两个条件都满足:(1)输出功率将随着输出功率的增加而增加(2)初级线圈中的磁动势将增加,以此来抵消二次侧中的磁动势减小磁通的趋势。

总的来说,变压器为了保持磁通是常数,对磁通变化的响应是瞬时的。更重要的是,在空载和满载时,主磁通φ0的降落是很少的(一般在)1至3%。其需要的条件是E 降落很多来使电流I p 增加。

在一次侧,电流I p ’在一次侧流过以平衡I s 产生的影响。它的磁动势N p I p ’只停

留在一次侧。因为铁芯的磁通φ0保持不变,变压器空载时空载电流I0必定会为其提供能量。故一次侧电流I p是电流I p’与I0’的和。

因为空载电流相对较小,那么一次侧的安匝数与二次侧的安匝数相等的假设是成立的。因为在这种状况下铁芯的磁通是恒定的。因此我们仍旧可以认定空载电流I0相对于满载电流是极其小的。

当一个电流流过二次侧绕组,它的磁动势(N s I s)将产生一个磁通,于空载电流I0产生的磁通φ0不同,它只停留在二次侧绕组中。因为这个磁通不流过一次侧绕组,所以它不是一个公共磁通。

另外,流过一次侧绕组的负载电流只在一次侧绕组中产生磁通,这个磁通被称为一次侧的漏磁。二次侧漏磁将使电压增大以保持两侧电压的平衡。一次侧漏磁也一样。因此,这两个增大的电压具有电压降的性质,总称为漏电抗电压降。另外,两侧绕组同样具有阻抗,这也将产生一个电阻压降。把这些附加的电压降也考虑在内,这样一个实际的变压器的等值电路图就完成了。由于分支励磁体现在电流里,为了分析我们可以将它忽略。这就符我们前面计算中可以忽略空载电流的假设。这证明了它对我们分析变压器时所产生的影响微乎其微。因为电压降与负载电流成比例关系,这就意味着空载情况下一次侧和二次侧绕组的电压降都为零。

译自<<科技英语>>

A1.2原文

TRANSFORMER

1. INTRODUCTION

The high-voltage transmission was need for the case electrical power is to be provided at considerable distance from a generating station. At some point this high voltage must be reduced, because ultimately is must supply a load. The transformer makes it possible for various parts of a power system to operate at different voltage levels. In this paper we discuss power transformer principles and applications.

2. TOW-WINDING TRANSFORMERS

A transformer in its simplest form consists of two stationary coils coupled by a mutual magnetic flux. The coils are said to be mutually coupled because they link a common flux.

In power applications, laminated steel core transformers (to which this paper is restricted) are used. Transformers are efficient because the rotational losses normally associated with rotating machine are absent, so relatively little power is lost when transforming power from one voltage level to another. Typical efficiencies are in the range 92 to 99%, the higher values applying to the larger power transformers.

The current flowing in the coil connected to the ac source is called the primary winding or simply the primary. It sets up the flux φ in the core, which varies periodically both in magnitude and direction. The flux links the second coil, called the secondary winding or simply secondary. The flux is changing; therefore, it induces a voltage in the secondary by electromagnetic induction in accordance with Lenz’s law. Thus the primary receives its power from the source while the secondary supplies this power to the load. This action is known as transformer action.

3. TRANSFORMER PRINCIPLES

When a sinusoidal voltage V p is applied to the primary with the secondary open-circuited, there will be no energy transfer. The impressed voltage causes a small current Iθ to flow in the primary winding. This no-load current has two functions: (1) it produces the magnetic flux in the core, which varies sinusoidally between zero and φm, where φm is the maximum value of the core flux; and (2) it provides a component to account for the hysteresis and eddy current losses in the core. There combined losses are

normally referred to as the core losses.

The no-load current Iθ is usually few percent of the rated full-load current of the transformer (about 2 to 5%). Since at no-load the primary winding acts as a large reactance due to the iron core, the no-load current will lag the primary voltage by nearly 90o. It is readily seen that the current component I m= I0sinθ0, called the magnetizing current, is 90o in phase behind the primary voltage V P. It is this component that sets up the flux in the core; φ is therefore in phase with I m.

The second component, I e=I0sinθ0, is in phase with the primary voltage. It is the current component that supplies the core losses. The phasor sum of these two components represents the no-load current, or

I0 = I m+ I e

It should be noted that the no-load current is distortes and nonsinusoidal. This is the result of the nonlinear behavior of the core material.

If it is assumed that there are no other losses in the transformer, the induced voltage In the primary, E p and that in the secondary, E s can be shown. Since the magnetic flux set up by the primary winding,there will be an induced EMF E in the secondary winding in accordance with Faraday’s law, namely, E=NΔφ/Δt. This same flux also links the primary itself, inducing in it an EMF, E p. As discussed earlier, the induced voltage must lag the flux by 90o, therefore, they are 180o out of phase with the applied voltage. Since no current flows in the secondary winding, E s=V s. The no-load primary current I0 is small, a few percent of full-load current. Thus the voltage in the primary is small and V p is nearly equal to E p. The primary voltage and the resulting flux are sinusoidal; thus the induced quantities E p and E s vary as a sine function. The average

value of the induced voltage given by

E avg = turns×change in flux in a given time

given time

which is Faraday’s law applied to a f inite time interval. It follows that

E avg = N

2

1/(2)

m

f

= 4fNφm

which N is the number of turns on the winding. Form ac circuit theory, the effective or root-mean-square (rms) voltage for a sine wave is 1.11 times the average voltage; thus

E = 4.44fNφm

Since the same flux links with the primary and secondary windings, the voltage per turn in each winding is the same. Hence

E p = 4.44fN pφm

and

E s = 4.44fN s φm

where E p and Es are the number of turn on the primary and secondary windings, respectively. The ratio of primary to secondary induced voltage is called the transformation ratio. Denoting this ratio by a, it is seen that a = p s

E E = p s N N Assume that the output power of a transformer equals its input power, not a bad sumption in practice considering the high efficiencies. What we really are saying is that we are dealing with an ideal transformer; that is, it has no losses. Thus

P m = P out

or

V p I p × primary PF = V s I s × secondary PF

where PF is the power factor. For the above-stated assumption it means that the power factor on primary and secondary sides are equal; therefore

V p I p = V s I s from which is obtained

p s V V = p s I I ≌ p s

E E ≌ a It shows that as an approximation the terminal voltage ratio equals the turns ratio. The primary and secondary current, on the other hand, are inversely related to the turns ratio. The turns ratio gives a measure of how much the secondary voltage is raised or lowered in relation to the primary voltage. To calculate the voltage regulation, we need more information.

The ratio of the terminal voltage varies somewhat depending on the load and its power factor. In practice, the transformation ratio is obtained from the nameplate data, which list the primary and secondary voltage under full-load condition.

When the secondary voltage V s is reduced compared to the primary voltage, the transformation is said to be a step-down transformer: conversely, if this voltage is raised, it is called a step-up transformer. In a step-down transformer the transformation ratio a is greater than unity (a>1.0), while for a step-up transformer it is smaller than unity (a<1.0). In the event that a=1, the transformer secondary voltage equals the primary voltage. This is a special type of transformer used in instances where electrical isolation is required between the primary and secondary circuit while maintaining the same voltage level. Therefore, this transformer is generally knows as an isolation transformer.

As is apparent, it is the magnetic flux in the core that forms the connecting link between primary and secondary circuit. In section 4 it is shown how the primary winding current adjusts itself to the secondary load current when the transformer supplies a load.

Looking into the transformer terminals from the source, an impedance is seen which by definition equals V p / I p . From p s V V = p s I I ≌ p s

E E ≌ a , we have V p = aV s and I p = I s /a.In terms of V s and I s the ratio of V p to I p is

p p V I = /s s aV I a = 2s s

a V I But V s / I s is the load impedance Z L thus we can say that

Z m (primary) = a 2Z L

This equation tells us that when an impedance is connected to the secondary side, it appears from the source as an impedance having a magnitude that is a 2 times its actual value. We say that the load impedance is reflected or referred to the primary. It is this property of transformers that is used in impedance-matching applications.

4. TRANSFORMERS UNDER LOAD

The primary and secondary voltages shown have similar polarities, as indicated by the “dot-making ” convention. The dots near the upper ends of the windings have the same meaning as in circuit theory; the marked terminals have the same polarity. Thus when a load is connected to the secondary, the instantaneous load current is in the direction shown. In other words, the polarity markings signify that when positive current enters both windings at the marked terminals, the MMFs of the two windings add.

Since the secondary voltage depends on the core flux φ0, it must be clear that the flux should not change appreciably if E s is to remain essentially constant under normal loading conditions. With the load connected, a current I s will flow in the secondary circuit, because the induced EMF E s will act as a voltage source. The secondary current produces an MMF N s I s that creates a flux. This flux has such a direction that at any instant in time it opposes the main flux that created it in the first place. Of course, this is Lenz ’s law in action. Thus the MMF represented by N s I s tends to reduce the core flux φ0. This means that the flux linking the primary winding reduces and consequently the primary induced voltage E p , This reduction in induced voltage causes a greater difference between the impressed voltage and the counter induced EMF, thereby

allowing more current to flow in the primary. The fact that primary current I p increases means that the two conditions stated earlier are fulfilled: (1) the power input increases to match the power output, and (2) the primary MMF increases to offset the tendency of the secondary MMF to reduce the flux.

In general, it will be found that the transformer reacts almost instantaneously to keep the resultant core flux essentially constant. Moreover, the core flux φ0 drops very slightly between n o load and full load (about 1 to 3%), a necessary condition if E p is to fall sufficiently to allow an increase in I p.

On the primary side, I p’is the current that flows in the primary to balance the demagnetizing effect of I s. Its MMF N p I p’ sets up a flux linking the primary only. Since the core flux φ0remains constant. I0must be the same current that energizes the transformer at no load. The primary current I p is therefore the sum of the current I p’ and I0.

Because the no-load current is relatively small, it is correct to assume that the primary ampere-turns equal the secondary ampere-turns, since it is under this condition that the core flux is essentially constant. Thus we will assume that I0 is negligible, as it is only a small component of the full-load current.

When a current flows in the secondary winding, the resulting MMF (N s I s) creates a separate flux, apart from the flux φ0 produced by I0, which links the secondary winding only. This flux does no link with the primary winding and is therefore not a mutual flux.

In addition, the load current that flows through the primary winding creates a flux that links with the primary winding only; it is called the primary leakage flux. The secondary- leakage flux gives rise to an induced voltage that is not counter balanced by an equivalent induced voltage in the primary. Similarly, the voltage induced in the primary is not counterbalanced in the secondary winding. Consequently, these two induced voltages behave like voltage drops, generally called leakage reactance voltage drops. Furthermore, each winding has some resistance, which produces a resistive voltage drop. When taken into account, these additional voltage drops would complete the equivalent circuit diagram of a practical transformer. Note that the magnetizing branch is shown in this circuit, which for our purposes will be disregarded. This follows our earlier assumption that the no-load current is assumed negligible in our calculations. This is further justified in that it is rarely necessary to predict transformer performance to such accuracies. Since the voltage drops are all directly proportional to the load current, it means that at no-load conditions there will be no voltage drops in either winding.

变电站外文翻译外文文献英文文献变电站的综合概述(工程科技)

附录Ⅲ 英文翻译 A comprehensive overview of substations Along with the economic development and the modern industry developments of quick rising, the design of the power supply system become more and more completely and system. Because the quickly increase electricity of factories, it also increases seriously to the dependable index of the economic condition, power supply in quantity. Therefore they need the higher and more perfect request to the power supply. Whether Design reasonable, not only affect directly the base investment and circulate the expenses with have the metal depletion in colour metal, but also will reflect the dependable in power supply and the safe in many facts. In a word, it is close with the economic performance and the safety of the people. The substation is an importance part of the electric power system, it is consisted of the electric appliances equipments and the Transmission and the Distribution. It obtains the electric power from the electric power system, through its function of transformation and assign, transport and safety. Then transport the power to every place with safe, dependable, and economical. As an important part of power’s transport and control, the transformer substation must change the mode of the traditional design and control, then can adapt to the modern electric power system, the development of modern industry and the of trend of the society life. Electric power industry is one of the foundations of national industry and national economic development to industry, it is a coal, oil, natural gas, hydropower, nuclear power, wind power and other energy conversion into electrical energy of the secondary energy industry, it for the other departments of the national economy fast and stable development of the provision of adequate power, and its level of development is a reflection of the country's economic development an important indicator of the level. As the power in the industry and the importance of the national economy, electricity transmission and distribution of electric energy used in these areas is an indispensable component.。Therefore, power transmission and distribution is critical. Substation is to enable superior power plant power plants or power after adjustments to the lower load of books is an important part of power transmission. Operation of its functions, the capacity of a direct impact on the size of the lower load

(完整版)110KV变电站及其配电系统设计_毕业设计

河南机电职业学院毕业论文(实习报告) 题目:110KV变电站及其配电系统设计 所属系部:电子工程系 专业班级:输变电工程12-1 学生姓名:刘康 指导教师:梁家裴 2015年6月6日

毕业论文(实习报告)任务书

指导教师签字:教研室主任签字: 年月日 毕业论文(实习报告)评审表

摘要

本文主要进行110KV变电站设计。首先根据任务书上所给系统及线路和所有负荷的参数,通过对所建变电站及出线的考虑和对负荷资料分析,满足安全性、经济性及可靠性的要求确定了110KV、35KV、10KV侧主接线的形式,然后又通过负荷计算及供电范围确定了主变压器台数、容量、及型号,从而得出各元件的参数,进行等值网络化简,然后选择短路点进行短路计算,根据短路电流计算结果及最大持续工作电流,选择并校验电气设备,包括母线、断路器、隔离开关、电压互感器、电流互感器等,并确定配电装置。根据负荷及短路计算为线路、变压器、母线配置继电保护并进行整定计算。本文同时对防雷接地及补偿装置进行了简单的分析,最后进行了电气主接线图及110KV配电装置间隔断面图的绘制 关键词:变电站设计,变压器,电气主接线,设备选择

目录 摘要 ..................................................................................................................... I I 1 变电站的介绍. (1) 1.1 变电站的作用 (1) 1.2 我国变电站及其设计的发展趋势 (2) 1.3 变电站设计的主要原则和分类 (4) 2 电气主接线设计 (4) 2.1 电气主接线设计概述 (5) 2.2 电气主接线的基本形式 (7) 2.3 电气主接线选择 (7) 3 变电站主变压器选择 (10) 3.1 主变压器的选择 (10) 3.2 主变压器选择结果 (11) 4 短路电流计算 (13) 4.1 短路的危害 (13) 4.2 短路电流计算的目的 (13) 4.3 短路电流计算方法 (13) 5 继电保护的配置 (14) 5.1 继电保护的基本知识 (14) 5.2 110kv线路的继电保护配置 (14) 5.3 变压器的继电保护 (14) 5.4 母线保护 (15) 5.5 备自投和自动重合闸的设置 (16)

110kV变电站设计开题报告

110kv变电站110kv线路保护及主系统设计 1课题来源 本课题为某110kv中心变电站110kv线路保护记主系统设计课题。该变电站是最末一个梯级电站,装机容量600万千瓦,年发电量301亿千瓦时,用地总面积为8070.1374公顷。向家坝水电站110kV中心变电站为向家坝水电站提供施工供电电源和电站建成以后作为厂用电备用电源的一座变电站。设计容量为3 50MVA,电压等级为110/35/10kV, 110kV进出线有5条,中压35kV侧有10 回出线,低压10kV侧有20 回出线. 2 设计的目的和意义 110kV变电所是电力配送的重要环节,也是电网建设的关键环节。变电所设计质量的好坏,直接关系到电力系统的安全、稳定、灵活和经济运行。它是联系发电厂和用户的中间环节,起着变换和分配电能的作用。电气主接线是发电厂变电所主要环节,电气主接线连接直接影响运行的可靠性、灵活性。它的拟定直接关系着全厂电气设备的选择、配电装置的布置、继电保护、自动装置和控制方式的确定。 随着变电所综合自动化技术的不断发展与进步,变电站综合自动化系统取代或更新传统的变电所二次系统,继而实现“无人值班”变电所已成为电力系统新的发展方向和趋势。 3 国内外的现状和发展趋势 目前,我国小城市和西部地区经济的不断发展对电能资源的要求也越来越高,西部主要是高原地带,在高海拔的条件下,农村现有的变电技术远达不到经济的快速发展,这也在一定程度上影响了西部地区和中小城市变电技术的推广和应用技术的深化。因此,一方面需要创造条件有针对性地提高对小城市以及农村的变电站的建设,加强专业知识的培训来提高变电技术;另一方面,可以通过媒介积极开展技术交流,通过实践去体验、探索。 当今世界各方面因素正冲击着全球电力工业,在国外变电所技术有十分剧烈的竞争,而世界范围内的变电所都采用了新技术; 其次,不同的环境要求给所有的电力供应商增加了额外的责任,使电力自动化设备尤其是高压大功率变电站的市场开发空间大大拓展。另外高压变电所的最终用户对变电站的自动控制、节能、

变电站设计外文翻译 毕业设计

外文文献一 General Requirements to Construction of Substation Substations are a vital element in a power supply system of industrial enterprises.They serve to receive ,convert and distribute electric energy .Depending on power and purpose ,the substations are divided into central distribution substations for a voltage of 110-500kV;main step-down substations for110-220/6-10-35kV;deep entrance substations for 110-330/6-10Kv;distribution substations for 6-10Kv;shop transformer substations for 6-10/0.38-0.66kV.At the main step-down substations, the energy received from the power source is transformed from 110-220kV usually to 6-10kV(sometimes 35kV) which is distributed among substations of the enterprise and is fed to high-voltage services. Central distribution substations receive energy from power systems and distribute it (without or with partial transformation) via aerial and cable lines of deep entrances at a voltage of 110-220kV over the enterprise territory .Central distribution substation differs from the main distribution substation in a higher power and in that bulk of its power is at a voltage of 110-220kV;it features simplified switching circuits at primary voltage; it is fed from the power to an individual object or region .Low-and medium-power shop substations transform energy from 6-10kV to a secondary voltage of 380/220 or 660/380. Step-up transformer substations are used at power plants for transformation of energy produced by the generators to a higher voltage which decreases losses at a long-distance transmission .Converter substations are intended to convert AC to DC (sometimes vice versa) and to convert energy of one frequency to another .Converter substations with semiconductor rectifiers are convert energy of one frequency to another .Converter substations with semiconductor rectifiers are most economic. Distribution substations for 6-10kV are fed primarily from main distribution substations (sometimes from central distribution substations).With a system of

110KV降压变电所设计_毕业设计论文

《发电厂电气部分》结业论文 110KV降压变电所设计 课程名称:发电厂电气部分 任课教师:姜新通 所在学院:信息技术学院 专业:电气工程及其自动化 中国·大庆 2012 年 5 月 毕业设计(论文)原创性声明和使用授权说明

原创性声明 本人郑重承诺:所呈交的毕业设计(论文),是我个人在指导教师的指导下进行的研究工作及取得的成果。尽我所知,除文中特别加以标注和致谢的地方外,不包含其他人或组织已经发表或公布过的研究成果,也不包含我为获得及其它教育机构的学位或学历而使用过的材料。对本研究提供过帮助和做出过贡献的个人或集体,均已在文中作了明确的说明并表示了谢意。 作者签名:日期: 指导教师签名:日期: 使用授权说明 本人完全了解大学关于收集、保存、使用毕业设计(论文)的规定,即:按照学校要求提交毕业设计(论文)的印刷本和电子版本;学校有权保存毕业设计(论文)的印刷本和电子版,并提供目录检索与阅览服务;学校可以采用影印、缩印、数字化或其它复制手段保存论文;在不以赢利为目的前提下,学校可以公布论文的部分或全部内容。 作者签名:日期:

学位论文原创性声明 本人郑重声明:所呈交的论文是本人在导师的指导下独立进行研究所取得的研究成果。除了文中特别加以标注引用的内容外,本论文不包含任何其他个人或集体已经发表或撰写的成果作品。对本文的研究做出重要贡献的个人和集体,均已在文中以明确方式标明。本人完全意识到本声明的法律后果由本人承担。 作者签名:日期:年月日 学位论文版权使用授权书 本学位论文作者完全了解学校有关保留、使用学位论文的规定,同意学校保留并向国家有关部门或机构送交论文的复印件和电子版,允许论文被查阅和借阅。本人授权大学可以将本学位论文的全部或部分内容编入有关数据库进行检索,可以采用影印、缩印或扫描等复制手段保存和汇编本学位论文。 涉密论文按学校规定处理。 作者签名:日期:年月日 导师签名:日期:年月日

110kV变电所毕业设计说明书

目录 第一章原始资料分析 (2) 第二章变电所接入系统设计 (3) 第三章变电所地方供电系统设计 (4) 第四章主变压器的选择 (6) 第五章所用变压器的选择 (14) 第六章主接线的设计 (16) 第七章变电所电器设备的选择 (19) 第八节继电保护的配置 (24) 参考资料 (27)

第一章原始资料分析 一、原始资料 1、待建110KV降压变电所从相距30km的110KV东郊变电站受电。 2、待建110KV降压变电所年负荷增长率为5%,变电站总负荷考虑五年发展规划。 3、地区气温: ?1?年最高气温35℃,年最低气温–15℃。 ?2?年平均气温15℃。 4、待建110KV降压变电所各电压级负荷数据如下表: 二、对原始资料的分析计算 为满足电力系统对无功的需要,需要在用户侧装设电容器,进行无功补偿,使用户的功率因数提高,35kV线路用户功率因数提高到0.9为宜,10kV线路用户功率因数应不低于0.9。 根据原始资料中的最大有功及调整后的功率因数,算出最大无功,可得出以下数据:

第二章变电所接入系统设计 一、确定电压等级 输电线路电压等级的确定应符合国家规定的标准电压等级。选择电压等级时,应根据输送容量和输电距离,以及接入电网的额定电压的情况来确定,输送容量应该考虑变电所总负荷和五年发展规划。因此待建110KV变电所的最高电压等级应为110kV。 二、确定回路数 该110KV变电所建成后,所供用户中存在Ⅰ、Ⅱ类重要负荷,因此110KV变电所应采用双回110KV线路接入系统。 三、确定110KV线路导线的规格、型号 由于该待建110KV变电所距离受电110KV东郊变电站30KM,处于平原河网地区,因此应采用架空线路,导线选择LGJ型。 四、110KV线路导线截面选择 导线截面积选择的一般方法是:先按经济电流密度初选导线标称截面积,然

110kV变电站设计

110KV变电所电气设计说明 所址选择: 首先考虑变电所所址的标高,历史上有无被洪水浸淹历史;进出线走廊应便于架空线路的引入和引出,尽量少占地并考虑发展余地;其次列出变电所所在地的气象条件:年均最高、最低气温、最大风速、覆冰厚度、地震强度、年平均雷暴日、污秽等级,把这些作为设计的技术条件。 主变压器的选择: 变压器台数和容量的选择直接影响主接线的形式和配电装置的结构。它的确定除依据传递容量基本原始资料外,还应依据电力系统5-10年的发展规划、输送功率大小、馈线回路数、电压等级以及接入系统的紧密程度等因素,进行综合分析和合理选择。 选择主变压器型式时,应考虑以下问题:相数、绕组数与结构、绕组接线组别(在电厂和变电站中一般都选用YN,d11常规接线)、调压方式、冷却方式。 由于本变电所具有三种电压等级110KV、35KV、10KV,各侧的功率均达到变压器额定容量的15%以上,低压侧需装设无功补偿,所以主变压器采用三绕组变压器。为保证供电质量、降低线路的损耗此变压器采用的是有载调压方式,在运行中可改变分接头开关的位置,而且调节范围大。由于本地区的自然地理环境的特点,故冷却方式采用自然风冷却。 为保证供电的可靠性,该变电所装设两台主变压器。当系统处于最大运行方式时两台变压器同时投入使用,最小运行方式或检修时只投入一台变压器且能满足供电要求。 所以选择的变压器为2×SFSZL7-31500/110型变压器。 变电站电气主接线: 变电站主接线的设计要求,根据变电站在电力系统中的地位、负荷性质、出线回路数等条件和具体情况确定。 通常变电站主接线的高压侧,应尽可能采用短路器数目教少的接线,以节省投资,随出线数目的不同,可采用桥形、单母线、双母线及角形接线等。如果变电站电压为超高压等级,又是重要的枢纽变电站,宜采用双母线带旁母接线或采用一台半断路器接线。变电站的低压侧常采用单母分段接线或双母线接线,以便于扩建。6~10KV馈线应选轻型断路器,如SN10型少油断路器或ZN13型真空断路器;若不能满足开断电流及动稳定和热稳定要求时,应采用限流措施。在变电站中最简单的限制短路电流的方法,是使变压器低压侧分列运行;若分列运行仍不能满足要求,则可装设分列电抗器,一般尽可能不装限流效果较小的母线电抗器。 故综合从以下几个方面考虑: 1 断路器检修时,是否影响连续供电; 2 线路能否满足Ⅰ,Ⅱ类负荷对供电的要求; 3大型机组突然停电对电力系统稳定运行的影响与产生的后果等因素。 主接线方案的拟定: 对本变电所原始材料进行分析,结合对电气主接线的可靠性、灵活性及经济性等基本要求,综合考虑。在满足技术、经济政策的前提下,力争使其技术先进,供电可靠,经济合理的主接线方案。此主接线还应具有足够的灵活性,能适应各

10kv变电站毕业设计

毕业设计(论文)任务书 一、题目:10kv变电所设计 指导思想和目的: 1、灵活运用本专业所学的基础和专业知识。 2、培养学生的专业技术知识和技能,能运用所学理论知识和技能解决生产第一线的运行、维护、检修及技术管理等实际工作,具有分析解决一般技术和业务问题的能力。 3、对学生进行一次高级人才基本技能的综合训练,培养学生分析和解决本专业技术实际问题的能力,包括技术经济政策的理解能力;查阅和综合分析各种文献资料、掌握使用工程技术规范和手册、图表等技术资料的能力;计算机应用能力;绘图和设计说明书(论文)的撰写等方面的能力。 4、培养学生树立严肃认真的工作作风,实事求是、严谨论证的科学态度,团结勤奋、协同作战的优良作风和应有的职业道德。 二.设计任务或主要技术指标: 1.设计任务 要求根据用电负荷实际情况,并适当考虑发展。按照安全可靠、技术先进、经济合理的要求,确定变电所的位置与形式,确定变电所主变压器的参数、容量与类型。选择变电所主接线方案及高低压设备和进出线,确定二次回路方案,选择整定继电保护装置、确定防雷和接地装置,最后按要求写出设计说明书,绘制设计图纸。 二、设计进度与要求: 第1周:收集10kv降压变电所资料。 第2周:了解掌握10kv降压变电站的基本组成。 第3周:根据设计背景计算变电所负荷。 第4周:短路电流计算。 第5周:电气主接线选择与校验。 第6周:继电保护预防雷保护的设计。 弟7周:制作10kv降压变电站设计报告。 弟8周:答辩 三、主要参考书及参考资料: [1]刘介才编著.《工厂供电》,第4版,机械工业出版社,2005 [2]雷振山编著.《中小型变电所实用设计手册》,第1版,中国水利水电出版社,2000。 [3]雷振山编著.《实用供配电技术手册》,第1版,中国水利水电出版社,2002。 [4]王子午编著.《常用供配电设备选型手册》,第一版,煤炭工业出版社,1998。 [5]徐泽植编著.《10kV及以下供配电设计与安装》,第一版,煤炭工业出版社,2002。 教研室主任(签名):系(部)主任(签名):2012年2月21日

(完整版)110kv变电站一次系统设计毕业设计

以下文档格式全部为word格式,下载后您可以任意修改编 辑。 沧州职业技术学院 毕业设计 《110kv变电站一次系统设计》

目录 引言................................................................................................................................... - 1第1章概述..................................................................................................................... - 2第2章负荷计算及变压器选择..................................................................................... - 4 2.1负荷计算................................................................................................................. -4 2.1.1 计算负荷的目的.............................................................................................. - 4 2.1.2 负荷分析.......................................................................................................... - 4 2.2主变压器的选择..................................................................................................... -5 2.2.1 主变压器台数和容量的确定.......................................................................... - 5 2.2.2 变压器型号的选择.......................................................................................... - 5 2.3本变电站站用变压器的选择................................................................................. -6 2.4小结......................................................................................................................... -7第3章无功补偿装置的选择......................................................................................... - 8 3.1补偿装置的意义..................................................................................................... -8 3.2无功补偿装置类型的选择..................................................................................... -8 3.2.1 无功补偿装置的类型...................................................................................... - 8 3.2.2 常用的三种补偿装置的比较及选择.............................................................. - 8

110KV变电所毕业设计毕业设计

“发电厂及电力系统”专业大学毕业设计任务书 设计题目:区域电力网及降压变电所设计 毕业设计任务书 一、区域电网的设计内容 1、根据负荷资料,待设计变电所的地理位置。据已有电厂的供电情况。作出功率平衡。 2、通过技术经济综合比较,确定电网供电电压、电网接线方式及导线截面。 3、进行电网功率分布及电压计算,评定调压要求,选定调压方案。 4、评定电网接线方案。 二、在区域电网设计的基础上,设计110 kV;kV A降压变电所的电气部分。具体要求如下: 1、对B 变电所在系统中的地位作用及所供用户的分析。 2、选择变电所主变压器的台数、容量、型式。 3、分析确定高低压主接线方式及配电装置型式。 4、分析确定所用电接线方式。 5、进行继电保护及互感器的配置。 6、进行选择设备所必须的短路电流计算。 7、选择变电所高低压侧回路的断路器、隔离开关。 8、选择10kV 硬母线。 9、进行防雷及保护接地的规划。 三、设计文件及图纸要求: 1、设计说明书一份; 2、计算书; 3、图纸(2号)。 (1)区域电网接线图; (2)变电所一次接线图;

原 始 资 料 一、区域电网设计的有关原始资料 1、发电厂、变电所及新选定变电所地理位置(见附图一):D 图; 2、原有发电厂、变电所主接线图及设备规范(见附图二); 3、新变电所有关资料; 变电所 编 号 最大负荷 MW 功率因数 COSφ 二次侧 电压kV 调 压 要 求 负荷曲线 性 质 重要负荷 % A 20 0.92 10 顺 A 60 B 23 0.9 10 逆 B 51 C 27 0.9 10 逆 B 60 D 20 0.92 10 常 A 70 4、典型日负荷曲线 典型日负荷曲线(A ) % 100 90 80 70 60 50 40 30 20 10 0 2 4 6 8 10 12 14 16 18 20 22 24

110kv变电站安全距离110kv变电站设计规范.

110kv变电站安全距离110kv变电站设计规范 110kv变电站安全距离 国家《电磁辐射管理办法》规定100千伏以上为电磁强辐射工程,第二十条规定:在集中使用大型电磁辐射设备或高频设备的周围,按环境保护和城市规划要求,在规划限制区内不得修建居民住房、幼儿园等敏感建筑。 不过,据环保部门介绍,我国目前对设备与建筑物之间的距离有一定要求。比如一般10KV —35KV变电站,要求正面距居民住宅12米以上,侧面8米以上;35KV以上变电站的建设,要求正面距居民住宅15米以上,侧面12米以上;箱式变电站距居民住宅5米以上。 北京市规划委(2004规意字0638号)110千伏的地下高压变电站工程项目,明确要求距离不得少于300米。 35~110KV变电站设计规范 第一章总则 第1.0.1条为使变电所的设计认真执行国家的有关技术经济政策,符合安全可靠、技术先进和经济合理的要求,制订本规范。 第1.0.2条本规范适用于电压为35~110kV,单台变压器容量为5000kV A及以上新建变电所的设计。 第1.0.3条变电所的设计应根据工程的5~10年发展规划进行,做到远、近期结合,以近期为主,正确处理近期建设与远期发展的关系,适当考虑扩建的可能。 第1.0.4条变电所的设计,必须从全局出发,统筹兼顾,按照负荷性质、用电容量、工程特点和地区供电条件,结合国情合理地确定设计方案。 第1.0.5条变电所的设计,必须坚持节约用地的原则。 第1.0.6条变电所设计除应执行本规范外,尚应符合现行的国家有关标准和规范的规定。第二章所址选择和所区布置 第2.0.1条变电所所址的选择,应根据下列要求,综合考虑确定: 一、靠近负荷中心; 二、节约用地,不占或少占耕地及经济效益高的土地; 三、与城乡或工矿企业规划相协调,便于架空和电缆线路的引入和引出; 四、交通运输方便; 五、周围环境宜无明显污秽,如空气污秽时,所址宜设在受污源影响最小处; 六、具有适宜的地质、地形和地貌条件(例如避开断层、滑坡、塌陷区、溶洞地带、山区风口和有危岩或易发生滚石的场所),所址宜避免选在有重要文物或开采后对变电所有影响的矿藏地点,否则应征得有关部门的同意; 七、所址标高宜在50年一遇高水位之上,否则,所区应有可靠的防洪措施或与地区(工业企业)的防洪标准相一致,但仍应高于内涝水位; 八、应考虑职工生活上的方便及水源条件; 九、应考虑变电所与周围环境、邻近设施的相互影响。 第2.0.2条变电所的总平面布置应紧凑合理。 第2.0.3条变电所宜设置不低于2.2m高的实体围墙。城网变电所、工业企业变电所围墙的高度及形式,应与周围环境相协调。 第2.0.4条变电所内为满足消防要求的主要道路宽度,应为3.5m。主要设备运输道路的宽度可根据运输要求确定,并应具备回车条件。 第2.0.5条变电所的场地设计坡度,应根据设备布置、土质条件、排水方式和道路纵坡确定,

10KV变电所毕业设计(论文)

10KV变电所毕业设计 1 变电所总体设计及供配电系统分析 1.1 变电所设计原则 进行变电所设计时须遵照变电所设计规范所规定的原则。 根据《35—10kV变电所设计规范》要求: 第1.0.3条变电所的设计应根据工程的5—10年发展规划进行,做到远近结合、以近为主,正确处理近期建设与远景发展的关系,适当考虑扩建的可能性。 第1.0.4条变电所的设计必须从全局出发、统筹兼顾,按照负荷性质、用电容量、工程特点和地区供电条件,结合国情合理地确定设计方案。 第1.0.5条变电所的设计,必须节约用地的原则。 1.2 变电所设计目的与任务 毕业设计是本专业教学计划中的重要环节。此次毕业设计的目的是通过变电所设计实践,综合运用所学知识,贯彻执行我国电力工业有关方针政策,理论联系实践,锻炼独立分析和解决电力工程设计问题的能力,为未来的实际工作奠定必要的基础。 1.3 PG新校区供电需求分析 PG新校区10KV变电所为位于PG新校的变电所,由系统S1、系统S2向PG 新校区供电,来供给该校教学、实验、施工及生活用电,PG新校区变电所的建立可保障新校区的正常用电,提高供电质量和供电可靠性。PG新校区变电所变电压等级为10/0.4KV,是以向终端用户供电为主的变电所,全所停电后将对该校中断供电。 1.4 变电所总体分析 1.4.1 建站必要性与建站规模 1 建站必要性 PG新校区10KV变电所为终端变电所,在系统中主要起变配电作用,全所停电将造成全校停电,它供给该校教学、实验、施工及生活用电。故为满足该校用电要求决定建设本变电站。 2 建站规模

PG新校区10KV变电所电压等级为10/0.4KV 线路回路数: 近期6回,远期2回; 近期最大负荷4627KW。 1.4.2 所址概况与所址条件 1 所址概况 PG新校区10KV变电所位于该校图书馆周围,西部电源和东部电源进线先通过10kV变电所高压侧开关站进行电能分配,然后馈出六回线分配给两个独立变电所和四个箱式变电站,独立变电所和箱式变电站经过变压后供给其所带负荷用电。 2 所址条件 依据《10kV及以下变电所设计规范》GB50053-94 第2.0.1条,变电站所址的选择,应根据下列要求经技术、经济比较确定: 一、接近负荷中心; 二、进出线方便; 三、接近电源侧; 四、设备运输方便; 五、不应设在有剧烈振动或高温的场所; 六、不宜设在多尘或有腐蚀性气体的场所,当无法远离时,不应设在污染源盛行风向的下风侧; 七、不应设在厕所、浴室或其他经常积水场所的正下方,且不宜与上述场所相贴邻; 八、不应设在有爆炸危险环境的正上方或正下方,且不宜设在有火灾危险环境的正上方或正下方,当与有爆炸或火灾危险环境的建筑物毗连时,应符合现行国家标准《爆炸和火灾危险环境电力装置设计规范》的规定; 九、不应设在地势低洼和可能积水的场所。 PG新校区10KV变电所建在该校内部,为节约用地、接近负荷中心、进出线方便,故采用建立两个独立变电所和四个箱式变电站的方针。 1.5 负荷分析 1.5.1 负荷的分类与重要性 1一级负荷: 对供电要求最高,要求不断电或可极短时间断电。必须有两个独立电源供电,且当任何一个电源断开后,能保证对全部一级负荷不间断供电; 2 二级负荷: 对供电要求较高,要求基本不断电或可短时间断电。一般要有

变电站外文翻译外文文献英文文献变电站的综合概述

附录Ⅲ 英文翻译 A prehensive overview of substations Along with the economic development and the modern industry developments of quick rising, the design of the power supply system bee more and more pletely and system、Because the quickly increase electricity of factories, it also increases seriously to the dependable index of the economic condition, power supply in quantity、Therefore they need the higher and more perfect request to the power supply、Whether Design reasonable, not only affect directly the base investment and circulate the expenses with have the metal depletion in colour metal, but also will reflect the dependable in power supply and the safe in many facts、In a word, it is close with the economic performance and the safety of the people、The substation is an importance part of the electric power system, it is consisted of the electric appliances equipments and the Transmission and the Distribution、It obtains the electric power from the electric power system, through its function of transformation and assign, transport and safety、Then transport the power to every place with safe, dependable, and economical、As an important part of power’s transport and control, the transformer substation must change the mode of the traditional design and control, then can adapt to the modern electric power system, the development of modern industry and the of trend of the society life、 Electric power industry is one of the foundations of national industry and national economic development to industry, it is a coal, oil, natural gas, hydropower, nuclear power, wind power and other energy conversion into electrical energy of the secondary energy industry, it for the other departments of the national economy fast and stable development of the provision of adequate power, and its level of development is a reflection of the country's economic development an important indicator of the level、As the power in the industry and the importance of the national economy, electricity transmission and distribution of electric energy used in these areas is an indispensable ponent、。Therefore, power transmission and distribution is critical、Substation is to enable superior power plant power plants or power after adjustments to the lower load of books is an important part of power transmission、Operation of its functions, the capacity of a direct impact on the size of the lower load power, thereby affecting the industrial production and power consumption、Substation system if a link

BY市110kv降压变电所设计--牛

BY市110kv降压变电所设计--牛

课程设计 电气工程及其自动化_专业班级 题目BY市110kV降压变电所设计 姓名 学号 指导教师 二О年月日

一.变电站概括 1.1变电站总体分析 BY市变电站位于市边缘,供给城市和近郊工业、农业及生活用电,是新建地区变电所。变电站做为电力系统中起着重要的连接作用,是联系发电厂与负荷的重要环节。本课程设计主要是关于本变电站的一次设计,为了是变电站的一次设计能够很好的接入电力系统,使电力系统安全可靠的运行,下面对本变电站做初步分析的原始数据进行分析。 1.变电站类型:110KV地方降压变电站 2.电压等级:110/10KV 3.线路回数:110KV:2回,备用2回;10KV:13回,备用2回; 4.地理条件:平均海拔100m,地势平坦,交通方便,有充足水源,属轻地震区。年最高气温+42℃,年最低气温-18℃,年平均温度+16℃,最热月平均最高温度+32℃。最大风速35m/s,主导风向西北,覆冰厚度。5.负荷情况:主要是一、二级负荷,市内负荷主要为市区生活用电、棉纺厂、印染厂等工业用电;郊区负荷主要为郊区变电站及其他工业用电。 6.系统情况:根据任务书中电力系统简图可以看到,本变电站位于两个电源中间,有两个发电厂提供电

能,进而经过该变电站降压后用于工业、农业等负荷用电,需要一定的可靠性。 1.2 负荷分析及主变压器的选择 负荷计算的目的: 计算负荷是供电设计计算的基本依据,计算负荷确定得是否正确合理,直接影响到电器和导线电缆的选择是否经济合理。如计算负荷确定过大,将使电器和导线选得过大,造成投资和有色金属的消耗浪费,如计算负荷确定过小又将使电器和导线电缆处子过早老化甚至烧毁,造成重大损失,由此可见正确确定计算负荷重要性。 负荷分析 10KV 侧: 近期负荷:P 近=(2+2+1+1+2+3+2+1.5+1.5+1.5)MW=17.5MW 远期负荷: P 远=(3+3+1.5+1.5+3+4.5+3.5+2+2+2+2+2)=30MW ∑=n i Pi 1=17.5MW+30MW=47.5MW 综合最大计算负荷计算公式: S js =Kt*1 cos n i i i P φ =∑*(1+α%) (注:Kt:同时系数,取85%; %:线损,取5%) S js 近=Kt*max 1cos n i i i P ? =∑近 *(1+α%)