业扩供电方案导则
10kV及以下业扩受电工程技术导则(2018版)

5.1 确定供电方案的基本原则................................................................................................. 7 5.2 供电方案的基本内容..........................................................................................................7 5.3 电力客户分类和电力负荷分类......................................................................................... 8 6 用电容量、供电电压等级及供电电源点的确定原则................................................................9 6.1 用电容量的确定..................................................................................................................9 6.2 供电电压等级的确定........................................................................................................13 6.3 供电电源点的确定............................................................................................................15 7 接入工程.......................................................................................................................................16 7.1 一般规定............................................................................................................................16 7.2 高压客户接入....................................................................................................................17 7.3 低压客户接入....................................................................................................................17 7.4 电力系统变电站配套工程............................................................................................... 19 7.5 接入工程设备技术要求................................................................................................... 19 8 客户受电工程...............................................................................................................................27 8.1 一般规定............................................................................................................................27 8.2 电气主接线及运行方式................................................................................................... 28 8.3 无功补偿............................................................................................................................29 8.4 继电保护及电气测量........................................................................................................30 8.5 电能计量............................................................................................................................31 8.6 自备应急电源配置............................................................................................................32 8.7 特殊客户的电能质量要求............................................................................................... 32 8.8 主要受电装置技术要求................................................................................................... 32 8.9 配电站................................................................................................................................35 8.10 直流屏(箱)的选用......................................................................................................37 9 防雷与接地...................................................................................................................................37 9.1 防雷要求............................................................................................................................37 9.2 10kV 接地方式..................................................................................................................38 9.3 380/220V 接地方式...........................................................................................................38
10kV及以下业扩受电工程技术导则

注:摘自 2011 年《110kV 南网配电网技术导则》(有修改)。 2)供电半径超过本级电压规定时,可按高一级电压供电。 3)具有冲击负荷﹑波动负荷、非对称负荷的客户,宜采用由系统变电站新建线路或提 高电压等级供电的供电方式。 6.2.2 10kV 电压等级 1)客户受电变压器总容量在 50kVA-10MVA 时(含 10MVA) ,宜采用 10kV 供电。城 区或高新技术(经济)开发区内的客户申请容量超过 10MVA,且附近无 35kV 供电条件时, 可采用 10kV 多回路供电。受电变压器(含直配的高压电机)总容量不宜超过 15MVA 。 (GB/50293-1999 城市电力规划规范) 2)10kV 电压等级供电的客户,当单回路电源线路容量不满足负荷需求且附近无上一 级电压等级供电时,可合理增加供电回路数,采用多回路供电。
表 6.3 电力客户供电电压等级 需用变压器容量 (kVA) 用电设备容量 (kW) 不大于 10 不大于 50 大于 50 不大于 100 大于 100 250 至 6000 6000 至 40000 40000 及以上 电力客户计算负荷 (kW) 区 0.22 0.38 10 10 110 及以上 供电电压(kV) A、B、C 类供电 D、E、F 类供电区 0.22 0.38/10 10 10、35 110 及以上
10
10kV 及以下业扩受电工程技术导则 (试行)
中国南方电网有限责任公司
2
Pc ——有功计算负荷(kW) K x ——需要系数
cos ——客户的平均功率因数
P ——客户需用设备容量总和(kW)
e
3) 变压器台数的确定 a) 变压器台数应满足用电负荷对可靠性的要求。对于重要电力客户或有一、二级负 荷的客户,选择两台或多台变压器供电。 b) 对季节性负荷或昼夜负荷变化较大客户的宜采用经济运行方式,可选择两台或多 台变压器供电。 c) 装有两台及以上变压器时,当断开一台时,其余变压器容量应满足一级负荷和二 级负荷的全部用电。 d) 配电站中单台变压器的容量不宜大于 1250kVA。当用电设备容量较大、负荷集中 且运行合理时,可选用较大容量的变压器。 e) 柱上油浸式变压器的单台容量不宜超过 500kVA。 f) 箱式变单台容量干式变压器不宜超过 800kVA,油浸式变压器不宜超过 630kVA。 6.1.2 低压供电客户 低压电力客户用电容量即为该户接装在电能计量装置内的所有用电设备额定容量 (kW) 的总和,其中也包括已接线而未用电的设备。设备的额定容量是指设备铭牌上标定的额定 kW 数。如果设备铭牌上标有分档使用,有不同容量时,应按其中最大容量计算。 6.1.3 居民客户 1) 居住区住宅用电容量的配置 a) 居住区住宅以及公共服务设施用电容量的确定应综合考虑所在城市的性质、社会 经济、气候、民族、习俗及家庭能源使用的种类。 b)居住区供电的负荷计算,一般采用负荷密度法、单位指标法和需要系数法。其单位 指标负荷或密度不宜小于表 6.2 的数值:
国家电网公司业扩供电方案编制导则

国家电网公司业扩供电方案编制导则1.范围本导则规定了业扩供电方案的编制原则和主要内容,明确了电力客户的界定和分级原则,确定了供电方式、计量方式、计费计价方式、自备应急电源配置、无功补偿、继电保护等主要技术原则。
本导则适用于国家电网公司所属各区域电网公司、省(自治区、直辖市)电力公司及供电企业对220千伏及以下供电的各类客户业扩供电方案的确定。
2 规范性引用文件下列文件对于本文件的应用是必不可少的,凡是标注日期的引用文件,仅注日期的版本适用于本文件。
凡是不标注日期的引用文件,其最新版本(包括所有的修改单)适用于本文件。
《电力供应与使用条例》《供电营业规则》GB 50052-2009《供配电系统设计规范》GB 50053-1994《10KV及以下变电所设计规范》GB 50054-1995《低压配电设计规范》GB 50059-1992《35~110KV变电所设计规范》GB 50060-2008《35~110KV高压配电装置设计规范》GB50062-2008《电力装置的继电保护和自动装置设计规范》GB/T12326-2008《电能质量电压波动和闪变》GB/T14285-2006《继电保护和安全自动装置技术规程》1GB/T 14549-1993《电能质量公用电网谐波》DL/T448-2000《电能计量装置技术管理规程》国家电力监管委员会第27号令《供电监管办法》电监安全[2008]43号《关于加强重要电力用户供电电源及自备应急电源配置监督管理的意见》国家电网营销〔2010〕119 号《关于加快用电信息采集系统建设的意见》3 术语3.1 供电方案指由供电企业提出,经供用双方协商后确定,满足客户用电需求的电力供应具体实施计划。
供电方案可作为客户受电工程规划立项以及设计、施工建设的依据。
3.2 主供电源指能够正常有效且连续为全部用电负荷提供电力的电源。
3.3 备用电源指根据客户在安全、业务和生产上对供电可靠性的实际需求,在主供电源发生故障或断电时,能够有效且连续为全部或部分负荷提供电力的电源。
20kv用户业扩工程供电方案编制导则试行20

20kV用户业扩工程供电方案编制导则(试行)浙江省电力公司2009年11月1 范围2规范性引用文件3术语和定义4编制原则5供电容量供电方式电气主接线及运行方式的确定电能计量、继电保护、二次回路及自动装置电能质量10无功补偿20kV 用户业扩工程供电方案编制导则1范围为适应浙江省经济社会和电网发展的需要,提升电网的供电能力和适应性,降低电网损耗和供电成本,节约土地资源,实现“增容、换代、升压、优化通道”的发展思路, 在中压配电网全面推广应用20kV 电压等级供电,特制定20kV 用户业扩工程供电方案编 制导则。
本导则规定了 20kV 电力用户业扩工程供电方案编制的基本原则,明确了用户业扩工程供电方式、电气主接线及运行方式、电能计量、继电保护、二次回路及自动装置、电 能质量、无功补偿等相关技术要求。
本导则适用于公司20kV 供电区域以及lOkV 、20kV 混合供电区域内电力用 户业扩 工程供电方案的编制。
本导则未涉及的内容,按现行的国家标准、规范,电力行业标准及国家电网公司和浙江省电力公司企业标准等有关规定执行。
2规范性引用文件下列文件中的条款通过本导则的引用而构成为本导则的条款。
引用文件,其随后所有的修改单(不包括勘误的内容)或修订版均不适用于本导贝然 而,鼓励根据本导则达成协议的各方研究是否可使用这些文件的最新版本。
凡是不注日期 的引用文件,其最新版本适用于本导则。
《电力供应与使用条例》 《供电营业规则》 《国家电网公司业扩供电方案编制导则(试行)》 《浙江省电力系统调度规程》GB/ T 14285-2006凡是注日期的 GB 50052-1995供配电系统设计规范 GB 50054-1995低压配电系统设计规范 GB 50062-2008电力装置的继电保护和自动装置设计规范 GB/ T 12325-2008电能质量供电电压偏差 电能质量电压波动和闪变继电保护和安全自动装置技术规程GB/ T 14549-1993电能质量公用电网谐波DL/T 448-2000 电能计量装置技术管理规程3术语和定义3・1业扩工程“业扩”是指供电方办理用户用电业务扩充管理工作的简称,业扩工程包括在屮请接电工作中涉及到接入工程、用户受电工程。
业扩报装供电编制方案

业扩报装供电编制方案一、背景业扩报装供电编制方案是指为新建、改建、扩建、迁移、停复电等业务提供电力综合服务的详细计划,目的是实现有效、安全、可靠地供电。
本方案旨在解决报装供电过程中的问题,确保业务顺利进行。
二、编制原则1.按照电力供需平衡、经济可行和资源可靠的原则,制定供电方案。
2.遵循国家有关电力发展政策、法规和标准,确保供电方案的合规性。
3.充分考虑业主的需求和用电负荷,确保供电方案的可靠性和满足性。
4.与相关部门、单位进行充分沟通和协调,确保供电方案的可行性和顺利实施。
三、编制流程1. 了解业务需求在启动报装供电编制方案之前,必须充分了解业务需求,包括新建或改建项目的用电负荷、用电特点和电力系统接入条件等。
通过与业主沟通,获取详细的用电需求信息。
2. 制定供电方案初稿根据业务需求,结合现有电力系统运行情况,制定供电方案初稿。
方案初稿应包括供电线路规划、变电站规划、设备选型、电力系统配置等内容。
3. 进行可行性分析对供电方案初稿进行可行性分析,评估方案的技术可行性、经济可行性和环境影响。
必要时,可以进行电力系统仿真分析,验证方案的可行性和合理性。
4. 完善供电方案根据可行性分析结果,对供电方案进行优化和完善。
在优化过程中,要充分考虑供电可靠性、经济性和可持续性,确保方案的综合效益最大化。
5. 编制报装方案在供电方案完善之后,根据国家相关规定,编制报装方案。
报装方案应包括供电设备清单、施工进度计划、电力设备参数等详细信息。
6. 相关手续办理根据报装方案,与相关电力部门进行联络,办理各项报装手续。
包括设备购置、线路敷设、开通手续等。
7. 方案实施和验收按照报装方案的计划,实施供电方案的建设和施工。
在完成施工后,进行供电方案的验收,确保方案实施和运行效果。
四、注意事项1.制定供电方案时,要遵循国家相关法规和规定,确保合规性。
2.要与相关电力部门进行充分沟通和协调,确保供电方案的可行性和顺利实施。
3.在方案实施过程中,要严格按照计划进行,确保供电工程的质量和安全。
10kV 及以下业扩受电工程技术导则

李晓宁 林声宏 汤德明 麦 红 陈万成 何舜徽 邓盈盈 蓝运清 王娟杨 孙帮新
I
前言
为了规范南方电网电力客户业扩受电工程建设,加强客户用电工程安全管理,缩短业扩 受电工程设计时间,提高业扩受电业务办理效率,本着“统一标准、规范管理、方便客户” 的原则,南方电网根据现行国家行业标准,制定了《10kV 及以下业扩受电工程典型设计》(试 行)(以下简称典设)。
5.1 确定供电方案的基本原则................................................................................................6 5.2 供电方案的基本内容........................................................................................................6 5.3 电力客户分类和电力负荷分类........................................................................................7 6 用电容量、供电电压等级及供电电源点的确定原则 ...............................................................8 6.1 用电容量的确定................................................................................................................8 6.2 供电电压等级的确定......................................................................................................10 6.3 供电电源点的确定.......................................................................................................... 11 7 接入工程.....................................................................................................................................12 7.1 一般规定..........................................................................................................................12 7.2 高压客户接入..................................................................................................................13 7.3 低压客户接入..................................................................................................................14 7.4 分布式电源及微电网接入..............................................................................................14 7.5 电力系统变电站配套工程..............................................................................................15 7.6 接入工程设备技术要求..................................................................................................16 8 客户受电工程.............................................................................................................................20 8.1 一般规定..........................................................................................................................20 8.2 电气主接线及运行方式..................................................................................................21 8.3 无功补偿..........................................................................................................................22 8.4 继电保护及电气测量......................................................................................................22 8.5 电能计量..........................................................................................................................23 8.6 自备应急电源配置..........................................................................................................23 8.7 特殊客户的电能质量要求..............................................................................................24 8.8 主要受电装置技术要求..................................................................................................24 8.9 配电站..............................................................................................................................26 9 防雷与接地.................................................................................................................................27 9.1 防雷要求..........................................................................................................................27 9.2 10kV 接地方式.................................................................................................................28 9.3 380/220V 接地方式..........................................................................................................28
国家电网公司业扩供电方案编制导则

国家电网公司业扩供电方案编制导则1.范围本导则规定了业扩供电方案的编制原则和主要内容,明确了电力客户的界定和分级原则,确定了供电方式、计量方式、计费计价方式、自备应急电源配置、无功补偿、继电保护等主要技术原则。
本导则适用于国家电网公司所属各区域电网公司、省(自治区、直辖市)电力公司及供电企业对220千伏及以下供电的各类客户业扩供电方案的确定。
2 规范性引用文件下列文件对于本文件的应用是必不可少的,凡是标注日期的引用文件,仅注日期的版本适用于本文件。
凡是不标注日期的引用文件,其最新版本(包括所有的修改单)适用于本文件。
《电力供应与使用条例》《供电营业规则》GB 50052-2009《供配电系统设计规范》GB 50053-1994《10KV及以下变电所设计规范》GB 50054-1995《低压配电设计规范》GB 50059-1992《35~110KV变电所设计规范》GB 50060-2008《35~110KV高压配电装置设计规范》GB50062-2008《电力装置的继电保护和自动装置设计规范》GB/T12326-2008《电能质量电压波动和闪变》GB/T14285-2006《继电保护和安全自动装置技术规程》1GB/T 14549-1993《电能质量公用电网谐波》DL/T448-2000《电能计量装置技术管理规程》国家电力监管委员会第27号令《供电监管办法》电监安全[2008]43号《关于加强重要电力用户供电电源及自备应急电源配置监督管理的意见》国家电网营销〔2010〕119 号《关于加快用电信息采集系统建设的意见》3 术语3.1 供电方案指由供电企业提出,经供用双方协商后确定,满足客户用电需求的电力供应具体实施计划。
供电方案可作为客户受电工程规划立项以及设计、施工建设的依据。
3.2 主供电源指能够正常有效且连续为全部用电负荷提供电力的电源。
3.3 备用电源指根据客户在安全、业务和生产上对供电可靠性的实际需求,在主供电源发生故障或断电时,能够有效且连续为全部或部分负荷提供电力的电源。
业扩工程供电方案设计

业扩工程供电方案设计一、项目概况随着经济的快速发展和城市化进程的加快,各种商业综合体、写字楼、大型商场等需求不断增加,作为这些项目的基础设施之一的供电系统也面临着更高的要求。
因此,本文旨在对业扩工程供电方案进行设计,以满足建筑规划和用电需求。
二、规划设计原则1. 安全可靠性供电系统应具备良好的抗干扰能力,确保设备运行的安全可靠。
对供电系统进行严格的设计与施工,保证其安全性,防范火灾、保证居民和设备的安全。
2. 经济性考虑供电系统的建设和运行成本,合理利用资源,降低建设和运行成本,确保建设后能够稳定运行。
3. 灵活性供电系统应具备较高的适应能力与灵活性,以满足不同用电需求的变化。
4. 可持续性在供电系统的设计过程中,应充分考虑可持续发展,尽量选择绿色环保的供电设备和技术,减少对环境的影响。
三、供电方案设计1. 设备选择在供电设备的选择上,应综合考虑经济性、可靠性和灵活性。
一般可采用变压器、配电箱、开关箱等传统设备,并根据实际需求考虑使用新能源设备。
2. 供电方式采用并网供电方式,由供电企业向业主提供稳定、安全的供电。
3. 供电容量根据业主的用电情况和建筑规模确定供电容量,充分考虑未来的扩建和增容需求。
4. 线路布置为了保证供电系统的可靠性和安全性,供电线路的布置应避免与其他设施冲突,采取合理的线路布置方式,进行合理的走线分布。
5. 防雷保护供电系统应做好防雷保护,采取合理的防雷措施,确保设备的正常运行。
6. 立项程序供电方案设计需经过相关部门的审批,需提供详细的设计方案、工程图纸和相关技术论证,以确保设计方案的合理性和可行性。
7. 配电系统设计在供电方案设计中,需详细设计配电系统,包括主干线、支路、用电设备等。
同时,应根据用电需求合理布置变压器、开关箱、电缆等设备。
四、实施方案1. 施工方案供电施工应按照国家规定的电气工程施工规范执行,严格按照设计方案和施工图纸进行施工,保障工程的质量。
2. 材料选用供电工程所需的设备和材料应符合国家相关标准,并应及时进行选型、采购,以保障工程的施工进度。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
国家电网公司业扩供电方案编制导则国家电网公司二○一○年九月目录1 范围 (5)2 规范性引用文件 (5)3 术语 (6)3.1 供电方案 (6)3.2 主供电源 (6)3.3 备用电源 (6)3.4 自备应急电源 (6)3.5 双电源 (7)3.6 双回路 (7)3.7 保安负荷 (7)3.8 电能计量方式 (7)3.9 用电信息采集终端 (7)3.9 电能质量 (8)3.10 谐波源 (8)3.11 大容量非线性负荷 (8)4 确定供电方案的基本原则及要求 (8)4.1 基本原则 (8)4.2 基本要求 (9)5 供电方案的基本内容 (9)5.2 低压供电客户 (10)5.3 居民客户 (10)6 电力客户分级 (11)6.1 重要电力客户的界定 (11)6.3 普通电力客户的界定 (12)7 用电容量及供电电压等级的确定 (12)7.1 用电容量的确定 (12)7.2 供电额定电压 (13)7.3 确定供电电压等级的一般原则 (13)7.4 低压供电 (14)7.5 高压供电 (14)7.6 临时供电 (15)7.7 居住区住宅用电容量配置 (15)8 供电电源及自备应急电源配置 (15)8.1 供电电源配置的一般原则 (15)8.2 供电电源点确定的一般原则 (16)8.3 自备应急电源配置的一般原则 (17)8.4 非电性质保安措施配置的一般原则 (17)9 电气主接线及运行方式的确定 (17)9.1 确定电气主接线的一般原则 (17)9.2 电气主接线的主要型式 (18)9.4 重要客户运行方式 (18)10 电能计量点及计量方式的确定 (19)10.1 电能计量点 (19)10.2 电能计量方式 (19)10.3 电能计量装置的接线方式 (20)10.4 电能计量装置的配置 (20)10.5 用电信息采集终端的配置 (21)11 电能质量及无功补偿技术要求 (21)11.1 供电电压允许偏差 (21)11.2 非线性负荷设备接入电网 (21)11.3 谐波限值 (22)11.4 电压波动和闪变的允许值 (22)11.5 无功补偿装置的配置原则 (22)11.6 功率因数要求 (22)11.7 无功补偿容量的计算 (23)12 继电保护及调度通信自动化技术要求 (23)12.1 继电保护设置的基本原则 (23)12.2 备用电源自动投入装置要求 (23)12.3 需要实行电力调度管理的客户范围 (23)12.4 通信和自动化要求 (24)附录A (25)附录B (26)1 范围本导则规定了业扩供电方案的编制原则和主要内容,明确了电力客户的界定和分级原则,确定了供电方式、计量方式、计费计价方式、自备应急电源配置、无功补偿、继电保护等主要技术原则。
本导则适用于国家电网公司所属各区域电网公司、省(自治区、直辖市)电力公司及供电企业对220千伏及以下供电的各类客户业扩供电方案的确定。
2 规范性引用文件下列文件对于本文件的应用是必不可少的,凡是标注日期的引用文件,仅注日期的版本适用于本文件。
凡是不标注日期的引用文件,其最新版本(包括所有的修改单)适用于本文件。
《电力供应与使用条例》《供电营业规则》GB 50052-2009 《供配电系统设计规范》GB 50053-1994 《10KV及以下变电所设计规范》GB 50054-1995 《低压配电设计规范》GB 50059-1992《35~110KV变电所设计规范》GB 50060-2008 《35~110KV高压配电装置设计规范》GB 50062-2008 《电力装置的继电保护和自动装置设计规范》GB/T 12326-2008《电能质量电压波动和闪变》GB/T14285-2006《继电保护和安全自动装置技术规程》GB/T 14549-1993《电能质量公用电网谐波》DL/T448-2000 《电能计量装置技术管理规程》国家电力监管委员会第27号令《供电监管办法》电监安全[2008]43号《关于加强重要电力用户供电电源及自备应急电源配置监督管理的意见》国家电网营销〔2010〕119号《关于加快用电信息采集系统建设的意见》3 术语3.1 供电方案指由供电企业提出,经供用双方协商后确定,满足客户用电需求的电力供应具体实施计划。
供电方案可作为客户受电工程规划立项以及设计、施工建设的依据。
3.2 主供电源指能够正常有效且连续为全部用电负荷提供电力的电源。
3.3 备用电源指根据客户在安全、业务和生产上对供电可靠性的实际需求,在主供电源发生故障或断电时,能够有效且连续为全部或部分负荷提供电力的电源。
3.4 自备应急电源指由客户自行配备的,在正常供电电源全部发生中断的情况下,能够至少满足对客户保安负荷不间断供电的独立电源。
3.5 双电源指由两个独立的供电线路向同一个用电负荷实施的供电。
这两条供电线路是由两个电源供电,即由来自两个不同方向的变电站或来自具有两回及以上进线的同一变电站内两段不同母线分别提供的电源。
3.6 双回路指为同一用电负荷供电的两回供电线路。
3.7 保安负荷指用于保障用电场所人身与财产安全所需的电力负荷。
一般认为,断电后会造成下列后果之一的,为保安负荷:(1)直接引发人身伤亡的;(2)使有毒、有害物溢出,造成环境大面积污染的;(3)将引起爆炸或火灾的;(4)将引起重大生产设备损坏的;(5)将引起较大范围社会秩序混乱或在政治上产生严重影响的。
3.8 电能计量方式指根据电能计量的不同对象、以及确定的客户供电方式和国家电价政策要求,确定电能计量点和电能计量装置配置原则。
3.9 用电信息采集终端指安装在用电信息采集点的设备,用于电能表数据的采集、数据管理、数据双向传输以及转发或执行控制命令。
用电信息采集终端按应用场所分为专变采集终端、集中抄表终端(包括集中器、采集器)、分布式能源监控终端等类型。
3.9 电能质量指供应到客户受电端的电能品质的优劣程度。
通常以电压允许偏差、电压允许波动和闪变、电压正弦波形畸变率、三相电压不平衡度、频率允许偏差等指标来衡量。
3.10 谐波源指向公共电网注入谐波电流或在公共电网中产生谐波电压的电气设备。
如:电气机车、电弧炉、整流器、逆变器、变频器、相控的调速和调压装置、弧焊机、感应加热设备、气体放电灯以及有磁饱和现象的机电设备。
3.11 大容量非线性负荷指接入110kV及以上电压等级电力系统的电弧炉、轧钢设备、地铁、电气化铁路牵引机车,以及单台4000kVA 及以上整流设备等具有波动性、冲击性、不对称性的负荷。
4 确定供电方案的基本原则及要求4.1 基本原则4.1.1 应能满足供用电安全、可靠、经济、运行灵活、管理方便的要求,并留有发展余度。
4.1.2 符合电网建设、改造和发展规划要求;满足客户近期、远期对电力的需求,具有最佳的综合经济效益。
4.1.3 具有满足客户需求的供电可靠性及合格的电能质量。
4.1.4 符合相关国家标准、电力行业技术标准和规程,以及技术装备先进要求,并应对多种供电方案进行技术经济比较,确定最佳方案。
4.2 基本要求4.2.1 根据电网条件以及客户的用电容量、用电性质、用电时间、用电负荷重要程度等因素,确定供电方式和受电方式。
4.2.2 根据重要客户的分级确定供电电源及数量、自备应急电源及非电性质的保安措施配置要求。
4.2.3 根据确定的供电方式及国家电价政策确定电能计量方式、用电信息采集终端安装方案。
4.2.4 根据客户的用电性质和国家电价政策确定计费方案。
4.2.5 客户自备应急电源及非电性质保安措施的配置、谐波负序治理的措施应与受电工程同步设计、同步建设、同步验收、同步投运。
4.2.6 对有受电工程的,应按照产权分界划分的原则,确定双方工程建设出资界面。
5 供电方案的基本内容5.1 高压供电客户(1)客户基本用电信息:户名、用电地址、行业、用电性质、负荷分级,核定的用电容量,拟定的客户分级。
(2)供电电源及每路进线的供电容量。
(3)供电电压等级,供电线路及敷设方式要求。
(4)客户电气主接线及运行方式,主要受电装置的容量及电气参数配置要求。
(5)计量点的设置,计量方式,计费方案,用电信息采集终端安装方案。
(6)无功补偿标准、应急电源及保安措施配置,谐波治理、继电保护、调度通信要求。
(7)受电工程建设投资界面。
(8)供电方案的有效期。
(9)其它需说明的事宜。
5.2 低压供电客户(1)客户基本用电信息:户名、用电地址、行业、用电性质、负荷分级,核定的用电容量。
(2)供电电压、公用配变名称、供电线路、供电容量、出线方式。
(3)进线方式,受电装置位置,计量点的设置,计量方式,计费方案,用电信息采集终端安装方案。
(4)无功补偿标准、应急电源及保安措施配置、继电保护要求。
(5)受电工程建设投资界面。
(6)供电方案的有效期。
(7)其它需说明的事宜。
5.3 居民客户(1)客户基本用电信息:户名、用电地址、行业、用电性质,核定的用电容量。
(2)供电电压、供电线路、公用配变名称、供电容量、出线方式。
(3)进线方式、受电装置位置、计量点的设置,计量方式,计费方案,用电信息采集终端安装方案。
(4)供电方案的有效期。
6 电力客户分级6.1 重要电力客户的界定重要电力客户是指在国家或者一个地区(城市)的社会、政治、经济生活中占有重要地位,对其中断供电将可能造成人身伤亡、较大环境污染、较大政治影响、较大经济损失、社会公共秩序严重混乱的用电单位或对供电可靠性有特殊要求的用电场所。
重要电力客户认定一般由各级供电企业或电力客户提出,经当地政府有关部门批准。
6.2 重要电力客户的分级6.2.1 根据对供电可靠性的要求以及中断供电危害程度,重要电力客户户可以分为特级、一级、二级重要电力客户和临时性重要电力客户。
6.2.1.1特级重要电力客户,是指在管理国家事务中具有特别重要作用,中断供电将可能危害国家安全的电力客户。
6.2.1.2 一级重要电力客户,是指中断供电将可能产生下列后果之一的电力客户:(1)直接引发人身伤亡的;(2)造成严重环境污染的;(3)发生中毒、爆炸或火灾的;(4)造成重大政治影响的;(5)造成重大经济损失的;(6)造成较大范围社会公共秩序严重混乱的。
6.2.1.3 二级重要客户,是指中断供电将可能产生下列后果之一的电力客户:(1)造成较大环境污染的;(2)造成较大政治影响的;(3)造成较大经济损失的;(4)造成一定范围社会公共秩序严重混乱的。
6.2.1.4 临时性重要电力客户,是指需要临时特殊供电保障的电力客户。
6.3 普通电力客户的界定除重要电力客户以外的其它客户,统称为普通电力客户。
7 用电容量及供电电压等级的确定7.1 用电容量的确定7.1.1 用电容量确定的原则综合考虑客户申请容量、用电设备总容量,并结合生产特性兼顾主要用电设备同时率、同时系数等因素后确定。