来宾电厂改扩建2*300MW燃煤火电组工程第五批辅机设备采购项目名称:220kV电缆及辅助设备采购招标编号:JC(2)2005152技术资料文件宝胜比瑞利电缆有限公司二00五年十一月附录 B:电缆载流量的计算220 kV 800 mm2 single-core XLPE cableCu Milliken conductorCorrugated seamless aluminium sheathPVC servingTrefoil touching, XB/SPB bondingAir rating in open trough of 4 circuits shielded from solar radiationMax DC resistance at 20℃ 22.10 μΩ/m Conductor outside diameter 34.8 mmConductor screen diameter 39.2 mmInsulation outside diameter 89.2 mmInsulation screen outside diameter 91.2 mmCore binder outside diameter 98.60 mmSheath inside diameter 99.60 mmSheath trough outside diameter 104.4 mmSheath crest outside diameter 116.4 mmServing crest outside diameter 126.4 mmInsulation TR 3.5 K.m/WRelative permittivity 2.5Tan delta 0.0010Sheath clearance TR 10.0 K.m/WServing TR 6.0 K.m/WFrequency 50 Hz2-1 Table 2 Air T4 constants Z, E, g 0.960 1.250 0.2002-1 2.2.6.2 Effective length of trough perimeter 3500 mmAir temperature 40.0 ℃Maximum conductor temperature 90.0 ℃IEC 287 1994-51-1 2.1.1 DC resistance at rating 28.180 μΩ/m 1-1 2.1.2 Skin effect ks, ys 0.4125 0.01741-1 2.1.4.1 Proximity effect kp, yp 0.3500 0.00401-1 2.1 AC resistance at rating 28.782 μΩ/m 1-1 2.2 Nominal capacitance 168.92 pF/m1-1 2.2 Dielectric loss per circuit 2.57 W/m2-1 2.1.1.1 Thermal resistance T1 0.6893 K.m/W2-1 2.1.3 Thermal resistance T3 0.1292 K.m/W1-1 2.4.1 Sheath/non-magnetic layers resistance 42.92 μΩ/m 1-1 2.3.6.1 'Sheath' loss factor (all metal layers) 0.32322-1 2.2.1.1 T4 0.4973 K.m/W2-1 2.2.6.2 Air temperature rise within trough 28.4 KSheath temperature 77.2 ℃Cable surface temperature 74.0 ℃Conductor loss per circuit 54.33 W/m'Sheath' loss per circuit 17.56 W/mTotal losses per circuit 74.5 W/m1-1 1.4.1.1 Rated current 854 A附录C 电缆蛇形敷设时轴向推力及径向位移的计算 C1、根据GB50217 轴向应力的表达式这里式中: B -蛇形敷设正负波幅总幅宽(mm ) B=1.2D L -蛇形半个节距(mm) n -蛇形幅宽的变位量(mm ) EI -电缆的弯曲刚性(kg.m 2) α-电缆的线膨胀系数(1/℃) 16.5×10-6 t -温升(℃)取40℃ μ-电缆的摩擦系数 1 W -电缆单位重量(kg/m ) 18.4 D -电缆外径(mm)126.4E -金属护套的有效系数MN/m 2 取15750 d 0-铝护套波峰外径(mm ) 116.4 d i -铝护套波谷内径(mm ) di= d 0-2t n t n -铝护套标称厚度(mm )t n =2.4将上述有关数据代入得: F =1061.05 kgC2、电缆蛇形敷设时的偏移距离()()()kg n B WL n B t EI B t EI F +++-=28.02828222μααB tL B n -+=226.1α21000244.0⎪⎪⎭⎫⎝⎛=Wd EIL ()()444064mm d d I i ⎪⎪⎭⎫ ⎝⎛-=πgg c c c c T T D T f ∆⋅-∆⋅-∆⋅⋅∆⋅⋅≥-ααεαmax 30102式中: c α=导体热膨胀系数,1/K ;(0.5×10-4)c T ∆ =导体温度变化,取70︒Cg α=金属护套热膨胀系数,1/K ;(0.7×10-4)g T ∆ =金属护套温度变化,取70︒C ;D =金属护套平均外径,mm ;m ax ε∆ =金属护套最大允许的应力变化,铝护套取0.45%;计算得:0f ≥ 0.26(m)附录 D 电缆金属护套感应电压计算D1根据招标文件附图电缆在电缆沟中三相呈三角形敷设,且紧密接触故根据感应电压公式计算: Xm= 2ωln(2S/D)×10-7=0.871×10-4(Ω/m)S:相间距为2DD:电缆金属护套外径金属护套上的感应电压数值为:E=Us1= Us2=Us3= I × XsI 为电缆中流过的电流,考虑电缆系统要求通过的最大负荷电流415A,则Us1= Us2=Us3=0.036(V/m)根据招标文件所述最长电缆通道400m,另加电缆两端终端高度(假设10米高)20米,制作附件所需两端各5米,则总长为430米,裕量按10%计,则电缆最大长度为473m,则电缆在运行过程中产生的最大感应电压0.036× 473=17 V:D2 当电缆三相短路时,根据招标文件中53KA/3S的要求:则产生的感应电压为E=I×0.871×10-4×473=53000×0.435×10-4×473m=2181(V)D3 当电缆单相短路时,根据招标文件中25KA/3S的要求:则产生的感应电压为E=I×0.435×10-4×473=25000×0.871×10-4×473 m=1028.8(V)附录E电缆的敷设和安装注意事项1.最小弯曲半径皱纹铝护套220kV交联电缆的最小弯曲半径为:安装时20 Dc安装后15 Dc注:其中Dc为电缆外径2.侧壁压力在安装时,允许的侧壁压力是5000N/m (500kg/m),SWP=F/R其中SWP ──侧壁压力,为N/m(或kg/m)F ──拉力,为N(或kg)R──弯曲半径,为米3.最大允许拉力铜芯电力电缆在安装时承受的最大拉力不许超过导体截面的70N/mm2.4.最低允许安装温度电缆安装时的最低温度取决于电缆所用外护套材料,应遵循下列原则:PVC 最低环境温度0℃PE 最低环境温度-15℃如需在更低环境温度下敷设时,请与电缆制造商商议。

长期载流量计算书

长期载流量计算书

长期载流量计算书:电缆导体上所通过的电流叫做电缆的载流量,有时也叫做电缆的“负载”或“负荷”。

电缆允许(长期)连续载流量是指电缆的负载为连续恒定电流(100%负载率)时的最大允许量。

电缆所允许的连续载流量,可用导体高于环境温度的稳态温升推导出来。

从电缆的等效热路图(图1)按热路欧姆定律,得:△θ= (W c+21W d)T1+[W c(1+λ1)+ W d]n T2 +[W c(1+λ1+λ2)+ W d]n (T3+ T4)进一步整理公式,可求得电缆长期载流量I:I={)T)(TnR(1)TnR(1RT)Tn(TT21W43212114321d++++++⎢⎢⎣⎡⎥⎥⎦⎤+++-λλλθ△(A)式中:△θ=θ-θa ———高于环境温度的导体温升(℃);θ——电缆(导体)的最高允许长期工作温度(℃);θa——环境温度(℃);W c=I2R——单位长度电缆的每相导体损耗(W/m);W d———单位长度电缆的每相介质损耗(W/m);I———电缆的允许连续工作电流(连续载流量)(A);R——在长期工作温度下每米电缆每相的导体交流有效电阻(Ω/m);T1 、T2 、T3 、T4———单位长度电缆的绝缘热阻、内衬层、外被层、周围媒质热阻(K·m/W);n——电缆的芯数;λ1、λ2———电缆的护套及铠装损耗系数。

从公式可以看出决定电缆载流量的因素有: 1.导电线芯损耗的影响导体的交流电阻的大小与其载流量有密切关系,导体交流电阻的大小取决于导体半径和导体的电导率,为了提高导体的传输容量,必须减少导体的杂质,提高纯度。

当然增大导体的截面对提高电缆的载流量有直接的影响。

一般电缆应在2.5A/mm 2的经济电流密度范围为宜。

2.介质损耗的影响对于10kV 及以下的低压系统,介质损耗占的比重较小,可忽略不计。

但随电压等级的提高,介质损耗W i =U 02ωCtg δ因有电压平方的关系,故其影响会随电压的增加而增大,即便tg δ较小的变化也引起介质损耗较大的变化。

高压电缆截面选择计算书

高压电缆截面选择计算书

电缆截面选择计算1.计算条件A.环境温度:40℃。

B.敷设方式:●穿金属管敷设;●金属桥架敷设;●地沟敷设;●穿塑料管敷设。

C.使用导线:铜导体电力电缆●6~10kV高压:XLPE(交联聚乙烯绝缘)电力电缆。

●380V低压:PVC(聚氯乙烯绝缘)或XLPE电力电缆。

2.导线截面选择原则2.1导线的载流量1)载流量的校正A.温度校正K1=√(θn-θa)/(θn-θc)式中:θn:导线线芯允许最高工作温度,℃;XLPE绝缘电缆为90℃,PVC绝缘电缆为70℃。

θa:敷设处的环境温度,℃;θc:已知载流量数据的对应温度,℃。

2)敷设方式的校正国标《电力工程电缆设计规范》GB50217-94中给出了不同敷设方式的校正系数。

综合常用的几种敷设方式的校正系数,并考虑到以往工程的经验及经济性,取敷设方式校正系数K2=0.73)载流量的校正系数K=K1×K22.2电力电缆载流量表表1 6~10kV XLPE绝缘铜芯电力电缆载流量表表2 0.6/1kV PVC绝缘电力电缆载流量表表3 0.6/1kV XLPE绝缘电力电缆载流量表2.3短路保护协调1)6~10kV回路电力电缆短路保护协调S≥I×√t×102/C式中:S:电缆截面,mm2;I:短路电流周期分量有效值,A;t:短路切除时间,秒。

C:电动机馈线C=15320;其他馈线C=13666 2)380V低压回路电力电缆短路保护协调●配电线路的短路保护协调S≥I×√t/K式中:S:电缆截面,mm2;I:短路电流有效值(均方根值),A;t:短路电流持续作用时间,秒。

K:PVC绝缘电缆K=115;XLPE绝缘电缆K=143●380V电动机回路短路保护协调电缆的允许电流大于线路短路保护熔断器熔体额定电流的40%。

2.4电缆的最小截面A.6~10kV电力电缆:根据铜冶炼厂实际使用经验,采用断路器时,最小截面70~95 mm2。

(在新设计的工程中应根据短路电流数据进行计算)B.低压电力电缆:最小截面:4 mm2。

直流电缆计算书

直流电缆计算书

励磁直流电缆计算书
一、发电机组的励磁参数
励磁电压:231.6V 励磁电流:817.1A
二、直流电缆
1、采用单芯交联电缆。

2、根据励磁电流的大小及考虑到1.1倍电流下长期运行等因素,直流电缆
单极总载流量:817.1×1.1=898.8A。

3、估计每极采用两根单芯电缆,则每根载流量为898.8/(2×1.00×1.00)
=449.4A(注:“1.00”为环境温度系数,“1.00”为敷设电缆时的校正系
数),
4、对于采用铜芯单芯交联电缆,其截面为150mm2时,载流量为479A,故每
极可采用两根150mm2截面的电缆,每根载流量为479A,总载流量为2×
479=958A〉898.8A,满足1.1倍额定励磁电流状态长期运行的要求。

5、额定电压:4×231.6V=926.4V,可取1000V。

6、最终型号:YJV-150mm2单芯交联电缆,额定电压:1000V。

7、数量:每套装置整流桥输出的正负极各两根。

高压电缆截面选择计算书

高压电缆截面选择计算书

高压电缆截面选择计算书(总10页)--本页仅作为文档封面,使用时请直接删除即可----内页可以根据需求调整合适字体及大小--电缆截面选择计算1.计算条件A.环境温度:40℃。

B.敷设方式:穿金属管敷设;金属桥架敷设;地沟敷设;穿塑料管敷设。

C.使用导线:铜导体电力电缆6~10kV高压:XLPE(交联聚乙烯绝缘)电力电缆。

380V低压:PVC(聚氯乙烯绝缘)或XLPE电力电缆。

2.导线截面选择原则导线的载流量1)载流量的校正A.温度校正K1=√(θn-θa)/(θn-θc)式中:θn:导线线芯允许最高工作温度,℃;XLPE绝缘电缆为90℃,PVC绝缘电缆为70℃。

θa:敷设处的环境温度,℃;θc:已知载流量数据的对应温度,℃。

2)敷设方式的校正国标《电力工程电缆设计规范》GB50217-94中给出了不同敷设方式的校正系数。

综合常用的几种敷设方式的校正系数,并考虑到以往工程的经验及经济性,取敷设方式校正系数K2=3)载流量的校正系数K=K1×K2电力电缆载流量表表1 6~10kV XLPE绝缘铜芯电力电缆载流量表表2 1kV PVC绝缘电力电缆载流量表表3 1kV XLPE绝缘电力电缆载流量表短路保护协调1)6~10kV回路电力电缆短路保护协调S≥I×√t×102/C式中:S:电缆截面,mm2;I:短路电流周期分量有效值,A;t:短路切除时间,秒。

C:电动机馈线C=15320;其他馈线C=136662)380V低压回路电力电缆短路保护协调配电线路的短路保护协调S≥I×√t/K式中:S:电缆截面,mm2;I:短路电流有效值(均方根值),A;t:短路电流持续作用时间,秒。

K:PVC绝缘电缆K=115;XLPE绝缘电缆K=143380V电动机回路短路保护协调电缆的允许电流大于线路短路保护熔断器熔体额定电流的40%。

电缆的最小截面A.6~10kV电力电缆:根据铜冶炼厂实际使用经验,采用断路器时,最小截面70~95 mm2。

电气专业计算书

电气专业计算书

电气专业计算书住宅楼电气专业计算书选用箱式变电站。

变压器Se:400KV AI js=23A进户电缆选用:YJV22-3x70mm2进户负荷开关:FLN36-12D/125A-20电流互感器:50/5A低压部分:(0.4仟伏)一、变压器的选择:住宅用电负荷: Pe=482KW Kc=0.4 Pjs=193KW其他用电负荷: Pe=132KW Kc=0.8 Pjs=106KW用电总负荷: ∑Pjs=298KW电容器补偿:Q补=120Kvar补偿后:COSφ=0.94 Sjs=298÷0.94=316KV A选择1台SC9-10KV/0.4KV-400KV A变压器变压器的负载率:η=316÷400=79%二、应急发电机的选择:用电负荷: Pe=133KW Kc=0.8 Pjs=106KW 选择一台DY100B 双电源切换开关选择:BYQ2-225配出电缆:ZR-YJV-0.6KV-3x70+1x35 SC80三、低压母线配电回路的选择:(正常母线)1、1单元2~7层住宅用电(WL1):Pe= 126KW Kc=0.6 COSφ=0.8 Ijs=144A断路器选择:NZM6-200电流互感器:200/5A出线选择:YJV-0.6KV- 3x70+1x35 SR,FC,SC80 2、1单元8~14层住宅用电(WL2):Pe= 115KW Kc=0.6 COSφ=0.8 Ijs=131A断路器选择:NZM6-200电流互感器:200/5A出线选择:YJV-0.6KV- 3x70+1x35 SR,FC,SC80 3、消防泵(WL3):Pe= 30KW Kc=1 COSφ=0.8 Ijs=61A断路器选择:NZM6-125电流互感器:100/5A出线选择:ZR-YJV-0.6KV-3x35+1x16 SC80 4、2单元2~7层住宅用电(WL5):Pe= 126KW Kc=0.6 COSφ=0.8 Ijs=144A断路器选择:NZM6-200电流互感器:200/5A出线选择:YJV-0.6KV- 3x70+1x35 SR,FC,SC80 5、2单元8~14层住宅用电(WL6):Pe= 115KW Kc=0.6 COSφ=0.8 Ijs=131A断路器选择:NZM6-200电流互感器:200/5A出线选择:YJV-0.6KV- 3x70+1x35 SR,FC,SC80 6、1单元电梯(WL7):Pe= 20KW Kc=1 COSφ=0.55 Ijs=55A断路器选择:NZM6-80电流互感器:100/5A出线选择:ZR-YJV-0.6KV-5x16 SR,FC,SC80 7、2单元电梯(WL8):Pe= 20KW Kc=1 COSφ=0.55 Ijs=55A断路器选择:NZM6-80电流互感器:100/5A出线选择:ZR-YJV-0.6KV-5x16 SR,FC,SC80 8、1单元屋顶用电(WL9):Pe= 7KW Kc=1 COSφ=0.8 Ijs=14A断路器选择:NZM4-32电流互感器:50/5A出线选择:ZR-YJV-0.6KV-5x6 SR,FC,SC50 9、2单元屋顶用电(WL10):Pe= 4KW Kc=1 COSφ=0.8 Ijs=10A断路器选择:NZM4-25电流互感器:50/5A出线选择:ZR-YJV-0.6KV-5x6 SR,FC,SC50 10、潜污泵(WL11):Pe= 8KW Kc=1 COSφ=0.8 Ijs=15A断路器选择:NZM4-32电流互感器:50/5A出线选择:ZR-YJV-0.6KV-5x6 SR,FC,SC50 11、消防控制室(WL12):Pe= 4KW Kc=1 COSφ=0.8 Ijs=10A断路器选择:NZM4-25电流互感器:50/5A出线选择:ZR-YJV-0.6KV-5x6 SR,FC,SC50 应急母线1、生活泵(WE1):Pe= 37KW Kc=1 COSφ=0.8 Ijs=72A断路器选择:NZM6-125电流互感器:100/5A出线选择:ZR-YJV-0.6KV-3x35+1x16 SC80 2、消防泵(WE2):Pe= 30KW Kc=1 COSφ=0.8 Ijs=61A断路器选择:NZM6-125电流互感器:100/5A出线选择:ZR-YJV-0.6KV-3x35+1x16 SC80 3、1单元电梯(WE3):Pe= 20KW Kc=1 COSφ=0.55 Ijs=55A断路器选择:NZM6-80电流互感器:100/5A出线选择:ZR-YJV-0.6KV-5x16 SR,FC,SC80 4、2单元电梯(WE4):Pe= 20KW Kc=1 COSφ=0.55 Ijs=55A断路器选择:NZM6-80电流互感器:100/5A出线选择:ZR-YJV-0.6KV-5x16 SR,FC,SC80 5、室外园林照明(WE5):Pe= 20KW Kc=1 COSφ=0.8 Ijs=38A断路器选择:NZM6-63电流互感器:100/5A6、楼梯间及架空层照明(WE6):Pe=12KW Kc=1 COSφ=0.8 Ijs=23A断路器选择:NZM4-32电流互感器:50/5A出线选择:ZR-YJV-0.6KV-3x6 SR,FC,SC32 7、潜污泵(WE7):Pe= 8KW Kc=1 COSφ=0.8 Ijs=15A断路器选择:NZM4-32电流互感器:50/5A出线选择:ZR-YJV-0.6KV-5x6 SR,FC,SC50 8、2单元屋顶用电(WE8):Pe= 4KW Kc=1 COSφ=0.8 Ijs=10A断路器选择:NZM4-25电流互感器:50/5A出线选择:ZR-YJV-0.6KV-5x6 SR,FC,SC50 9、1单元屋顶用电(WE9):Pe= 7KW Kc=1 COSφ=0.8 Ijs=14A断路器选择:NZM4-32电流互感器:50/5A出线选择:ZR-YJV-0.6KV-5x6 SR,FC,SC50 10、消防控制室(WE10):Pe= 4KW Kc=1 COSφ=0.8 Ijs=10A断路器选择:NZM4-25电流互感器:50/5A出线选择:ZR-YJV-0.6KV-5x6 SR,FC,SC50 其他配电箱负荷计算见相应系统图。

132kV高压充油电缆

132kV高压充油电缆

9326
CYZQ241
铜芯纸绝缘铅包不锈钢带径向加强镀锌 GB 钢丝铠装、纤维绳外护层充油电力电缆 9326
电缆的型号及结构
型号
名称
参考标 准
备注
CYZQ102(103 铜芯纸绝缘铅包铜带径向加强聚氯乙烯 GB
)
(聚乙烯)护套充油电力电缆
9326
CYZQ102(103 铜芯纸绝缘铅包不锈钢带径向加强聚氯 GB
)
乙烯(聚乙烯)护套充油电力电缆
9326
CYZQ141
铜芯纸绝缘铅包铜带径向加强镀锌钢丝 GB
铠装、纤维绳外护层充油电力电缆
高压充油电缆
132kV 高压充油电缆产品在荷兰(KEMA)实验室经过检验认 可,并向卡拉奇供电公司(KESC)的 132kV 电缆工程项目提供 160 公 里高压充油电缆、配套附件及工程技术服务,向塞浦路斯供电局(EAC)、 香港中华电力公司、印度尼西亚雅加达电力公司等提供高压充油电缆,
配பைடு நூலகம்附件及工程技术服务。

1323311kV变配电工程估算编制说明

1323311kV变配电工程估算编制说明

****132/33/11kV变配电工程估算编制说明1. 编制依据:1.依据****132kV电网项目开展前期工作的批复。

2.****公司2013年(第一批)集中招标采购可研和勘测设计招标、中标通知书。

3. ****电网“关于印发****等132kV输变电工程接入系统方案的批复”。

4. ****国家电网公司“两型一化”变电站建设设计导则5. ****国家电网公司132kV变电站“两型一化”建设实施细则6.现场踏勘、勘察资料2.工程建设规模:(1)****132kV变电站终期规模:主变压器(三相三绕组有载调压降压变压器)终期3×50MVA,本期 2×50MVA;132kV出线终期2回,本期一次建成;33kV出线终期 ** 回,本期 **回;10kV出线终期 6 回,本期 5 回。

132kV 线路自西侧架空引进站内,33kV出线和10kV出线采用经站内电缆沟方式引出站外,园区内设10KV箱式变电站20个。

(2)****132kV变电站主接线型式:132kV 终期采用扩大内桥接线,本期一次建成;33kV 终期采用单母线三分段接线,本期采用单母线分段接线;10kV采用单母线三分段接线,本期采用单母线分段接线。

(3)****132kV变电站配电装置:主变压器采用户内布置,132kV配电装置采用GIS设备户内布置;35kV设备采用户内开关柜;10kV设备采用户内开关柜。

(4)建议****132kV变电站主变压器参数:采用三相三绕组有载调压降压变压器,额定电压和调压范围选择为(5)建议****132kV变电站短路水平:132kV按照 31.5kA设计,33kV按照 25kA设计,10kV按照 25kA设计。

(6)建议****132kV变电站无功补偿装置配置:本期每台主变10kV侧配备2组并联电容器组,容量为2×6Mvar。

2.2土建部分2.2.1站内建筑物为一座地上二层生产综合楼,建筑面积为1440m2,总高度15.35m,室内外高差0.45m。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

- 1 -1、绝缘厚度计算书及对各系数取值的依据。

a.按AC 计算lacac E K K K U t '3'2'13⨯⨯⨯=式中:U -系统工频电压;K 1 -温度系数,取 K 1=1.2;K 2 -老化系数 ;K 3 -裕度系数 ,取K 3=1.1;E 1ac -工频电压下的最小击穿场强,取 E 1ac =30kV/mm;老化系数 K 2的确定:对于交联聚乙烯电缆,其V -t 特性为:V nt =C 式中:V -绝缘体上施的电压,kV; T -电缆寿命 N -寿命指数;n=9; C -常数则,K 2 =(30年×360天/年×24小时/天)1/9=4;110kV 最小工频击穿绝缘厚度为:13.42(mm) b. 按冲击电压计算计算公式impimp E K K K BIL t 321⨯⨯⨯=式中:BIL -基准冲击水平,取BIL =650kV ; K 1-温度系数,取K 1=1.25; K 2-老化系数,取K 2=1.1; K 3-裕度系数,取K 3=1.1;E imp -雷电冲击过电压下的最小击穿场强,取 E imp =60kV/mm ;110kV 最小冲击击穿绝缘厚度为:16.39mmc.确定绝缘厚度110kV 交联电缆最小绝缘厚度:t = max (13.42,16.39) = 16.39mm 取绝缘的标称厚度为18.0mm ,能满足电气性能的要求。

2、电缆电场梯度、电容、电感计算书。

a. 圆形导体电缆绝缘的电场强度(通常称为电场应力)按下式计算。

⎪⎪⎭⎫ ⎝⎛=120ln r r r U E式中: E - 绝缘层中半径为r 处的电场强度,MV/m ; U 0 - 电缆对地额定电压,kV ; r - 所求电场强度处的半径,mm ; r 1 - 包括屏蔽层的导体半径,mm ;r 2 - 不包括绝缘屏蔽的绝缘半径,mm;计算最大电场应力时,绝缘半径取最小值(导体标称外径+绝缘最小平均厚度),导体半径取标称值.可知: 导体屏蔽表面电场应力: ⎪⎪⎭⎫ ⎝⎛=1210ln rr r U E =6.07MV/m绝缘表面电电场应力: ⎪⎪⎭⎫ ⎝⎛=1220ln rr r U E =3.07MV/mb.电缆电容计算 910ln 18-⨯⎪⎪⎭⎫ ⎝⎛=cir dD C ε式中:C - 电缆电容,F/m ;ε - 绝缘介电常数,交联聚乙烯 ε=2.3D i - 内半导电屏蔽层直径(包括内半导电层厚度〕,mm;d c - 绝缘外径,mm;可知:电缆电容值: 0.187μF/kmc.电感计算 cg r S K L 2ln2.0+=式中:L - 三相电缆的每相电感,μΩ/m ; ω - 频率,rad/s ; K - 自感因数,0.050;S g - 电缆间平均几何间距,mm ;r c - 导体外径,mm ;三角形排列时Sg 等于电缆轴间距离, 平行排列时Sg 等于电缆轴间距离的1.26倍。

可知电缆电感为: 0.6339mH/km(电缆平行敷设,间距:250mm)3、短期过载能力曲线,说明全年过载时间为多少不至于影响电缆寿命。

紧急过负荷时导体允许工作温度为105︒C ,电缆年平均允许过负荷时间72小时, 整个运行期限内不超过1500小时。

4、电缆载流量计算书。

持续(100%负荷率)运行载流量(计算循依IEC287等公认标准方法);)(*])1([*])1([*)5.0(4321221212T T n W R I nT W R I T W R I d d d +++++++++=∆λλλθ式中:从上述等式得出载流量计算公式:21))(1()1()](5.0[43212114321⎩⎨⎧⎭⎬⎫+++++++++-∆=T T nR T nR RT T T T n T W I d λλλθA. 损耗计算 A.1 导体AC 电阻)1(p s y y R R ++'=式中R - 最高工作温度温度导体的交流电阻,Ω/m R '- 最高工作温度温度导体的直流电阻,Ω/m ; y s – 集肤效应因数; y p – 邻近效应因数()[]201200-+='θαR R式中R 0 - 20︒C 时导体的DC 电阻,Ω/m448.0192sss x x y +=s s k Rfx 72108-⨯=π⎥⎥⎥⎥⎥⎦⎤⎢⎢⎢⎢⎢⎣⎡+++⎪⎭⎫ ⎝⎛⨯⎪⎭⎫ ⎝⎛+=27.08.019218.1312.08.0192442244p p c c ppp x x s d s d x x yp p k R fx 72108-⨯'=πA.2. 介质损耗δωtg CU W d 20=式中0U - 对地电压,V ;δtg - 在电源系统和工作温度下绝缘损耗因数; C - 单位长度电缆电容;µF/km ;910ln 18-⨯⎪⎪⎭⎫ ⎝⎛=cidD c εA.3.护套损耗因数"+'=111λλλ式中'1λ为环流损耗因数;"1λ 为涡流损耗因数;A.3.1涡流损耗护套单点接地或交叉互联连接的单芯电缆涡流损耗因数()()⎥⎥⎦⎤⎢⎢⎣⎡⨯+∆+∆+=''1241210110121s s st g RR βλλ 式中()6.11013174.1-⎪⎪⎭⎫ ⎝⎛+=-ssss D Dt g βsρπωβ71104=R s - 在工作温度时金属护套的电阻, Ω/km;R - 在工作温度时导体电阻, Ω/km;s ρ - 工作温度下金属护套材料的电阻率, ohm.m;s D - 电缆金属护套外径, mm; s t - 金属护套厚度, mm;ω - 2πf;三根单芯电缆呈三角形排列:2220213⎪⎭⎫ ⎝⎛⎪⎪⎭⎫ ⎝⎛+=s d m m λ ()()66.192.045.21233.014.1+⎪⎭⎫ ⎝⎛+=∆m s d m02=∆三根单芯电缆平面排列 中间电缆:2220216⎪⎭⎫ ⎝⎛⎪⎪⎭⎫ ⎝⎛+=s d m m λ ()7.04.108.31286.0+⎪⎭⎫⎝⎛=∆m s d m02=∆超前相外侧电缆2220215.1⎪⎭⎫ ⎝⎛⎪⎪⎭⎫ ⎝⎛+=s d m m λ ()216.07.0127.4+⎪⎭⎫⎝⎛=∆m s d m()06.547.13.32221+⎪⎭⎫⎝⎛=∆m S d m滞后相外侧电缆2220215.1⎪⎭⎫ ⎝⎛⎪⎪⎭⎫ ⎝⎛+=s d m m λ ()()()125.0123.02274.0+⎪⎭⎫⎝⎛-++=∆m s d m m m()27.32292.0+⎪⎭⎫⎝⎛=∆m S d mA.3.2环流损耗在金属护套单点互连或交叉互联接地且每个大段都分成电性相同的三个小段场合下, 单芯电缆环流损耗'1λ=0.B 电缆热阻计算B.1 电缆绝缘的热阻T 1⎪⎪⎭⎫⎝⎛+=c Td t T 1121ln 2πρ式中T ρ—绝缘材料系数,K•m/W ;c d —导体直径,mm ;1t —导体和金属套间的绝缘厚度,;对于皱纹金属护套1ts ocit t D D t -+=21 B.2金属护套与铠装之间的热阻T 2⎪⎪⎭⎫⎝⎛=s T D t T 222ln 2πρ式中 2t —内衬层厚度,mm ;s D —金属套外径,mm ;输出 2T =0B.3皱纹金属金属铝护套非铠装电缆外护层热阻3T 为()⎥⎥⎥⎦⎤⎢⎢⎢⎣⎡+++=s it oc oc T t D D t D T 22ln 233πρ式中3t —外护层厚度,mm ; s t —铝护套厚度,mm ;B.4 电缆外部热阻a) 空气中电缆外部热阻4T()4141s e h D T θπ∆***=式中E D Zh e+=s θ∆—超过环境温度以上的电缆表面温升,K 。

对于皱纹金属套 ()33102-⨯+=t D D oc e b)管道中电缆的外部热阻4T4444T T T T '''+''+'=式中4T '—管道和电缆之间的热阻; em D Y V UT )(1.014θ++='U 、V 和Y 是与敷设有关的系数;e D —电缆外径,mm ;m θ—电缆与管道之间的介质平均温度,℃;4T ''—管道本身的热阻;⎪⎪⎭⎫⎝⎛=''d T D D T 04ln 21ρπ()⎪⎭⎪⎬⎫⎪⎩⎪⎨⎧⎥⎥⎦⎤⎢⎢⎣⎡⎪⎪⎭⎫ ⎝⎛++-+='''212421ln 1ln 2s L u u T T πρ c) 埋地电缆的外部热阻4T()⎪⎭⎪⎬⎫⎪⎩⎪⎨⎧⎥⎥⎦⎤⎢⎢⎣⎡⎪⎪⎭⎫ ⎝⎛++-+=212421ln 1ln 2s L u u T Tπρ式中 T ρ— 土壤热阻系数,K•m/W ;1s —相邻电缆之间的轴心距离,mm ; eD Lu 2=L —电缆轴线至地表面的距离,mm ;e D —电缆外径,mm ;5、金属护套厚度计算书。

金属护套标称厚度取2.0mm ,经过(6)短路电流计算符合系统短路要求。

6、电缆导体以及金属套的短路热稳定校验。

采用IEC60949中绝热过程短路电流计算公式计算在任何起始温度条件下的短路电流。

⎪⎪⎭⎫ ⎝⎛++⨯⨯=⨯βθβθi f adS K t Iln 222, 其中 ()20121020ρβσ-⨯+=c K式中:S 电缆或金属屏蔽的标称截面,mm 2;I ad 导体或屏蔽的短路电流(绝热过程),A ;t短路时间,s ;β 温度系数的倒数; θf 最终短路温度; θi 起始短路温度;σc 20℃时导体的比热,J/m 3K ;ρ20 20℃时导体的电阻率;导体在非绝热状态下允许的短路:非绝热因素的计算:⎪⎭⎫ ⎝⎛++=S t Y S t X1ε 取X = 0.41 (mm 2/s)1/2 ,Y = 0.12 mm 2/s ,则导体允许的短路电流为:金属护套电气截面:t S oc it ⨯=2式中: S 金属护套电气截面,mm 2d it 皱纹铝护套波谷外径,mm;d oc 皱纹铝护套波峰外径,mm; t 金属护套厚度,mm. 金属屏蔽非绝热因素的计算:()()320043.0069.061.01t M tM t M +-+=ε 其中:F M ⨯⨯+=-313322102δσρσρσ 式中: t 短路持续时间,s;F 热性不完善接触因素,取0.7; σ2, σ3屏蔽层四周媒质比热,J/K.m 3; σ1, 屏蔽层比热,J/K.m 3;ρ2, ρ3, 屏蔽层四周媒质的热阻,K.m/W; δ 屏蔽层的厚度 mm. ε 非绝热因素金属护套短路电流能力。

相关文档