用电负荷计算书《民用建筑电气设计规范》JGJ 16-2008:参考手册:《工业与民用配电设计手册》第三版:AP1:负荷:【计算公式】:Pc = Kp * ∑(Kd * Pn)Qc = kq * ∑(Kd * Pn * tgΦ)Sc = √(Pc * Pc + Qc * Qc)Ic = Sc / (√3 * Ur)【输出参数】:进线相序 : 三相有功功率Pc: 207.36无功功率Qc: 128.51视在功率Sc: 243.95有功同时系数kp:0.60无功同时系数kq:0.60计算电流Ic: 370.65总功率因数: 0.85【计算过程(不计入补偿容量)】:Pc = Kp * ∑(Kd * Pn)=207.36(kW)Qc = kq * ∑(Kd * Pn * tgΦ)=128.51(kvar)Sc = √(Pc * Pc + Qc * Qc)=243.95(kVA)Ic = Sc / (√3 * Ur)=370.65(A)AP2.AP3:负荷:【计算公式】:Pc = Kp * ∑(Kd * Pn)Qc = kq * ∑(Kd * Pn * tgΦ) Sc = √(Pc * Pc + Qc * Qc)Ic = Sc / (√3 * Ur)【输出参数】:进线相序 : 三相有功功率Pc: 66.72无功功率Qc: 67.40视在功率Sc: 94.84有功同时系数kp:0.80无功同时系数kq:0.80计算电流Ic: 144.09总功率因数: 0.70【计算过程(不计入补偿容量)】:Pc = Kp * ∑(Kd * Pn)=66.72(kW)Qc = kq * ∑(Kd * Pn * tgΦ) =67.40(kvar)Sc = √(Pc * Pc + Qc * Qc) =94.84(kVA)Ic = Sc / (√3 * Ur)=144.09(A)JXS:负荷:【计算公式】:Pc = Kp * ∑(Kd * Pn)Qc = kq * ∑(Kd * Pn * tgΦ) Sc = √(Pc * Pc + Qc * Qc)Ic = Sc / (√3 * Ur)【输出参数】:进线相序 : 三相有功功率Pc: 104.00无功功率Qc: 64.46视在功率Sc: 122.36有功同时系数kp:0.75无功同时系数kq:0.75计算电流Ic: 185.90总功率因数: 0.85【计算过程(不计入补偿容量)】:Pc = Kp * ∑(Kd * Pn)=104.00(kW)Qc = kq * ∑(Kd * Pn * tgΦ) =64.46(kvar)Sc = √(Pc * Pc + Qc * Qc) =122.36(kVA)Ic = Sc / (√3 * Ur)=185.90(A)。

用电负荷计算书

用电负荷计算书

用电负荷计算书工程名:《民用建筑电气设计规范》JGJ 16-2008:参考手册:《工业与民用配电设计手册》第三版:用电负荷统计表:变压器S1的回路:北教学楼、综合楼、南教学楼、实验楼、室外、消防设备、中心机房用电S1负荷:【计算公式】:Pc = Kp * ∑(Kd * Pn)Qc = kq * ∑(Kd * Pn * tgΦ)Sc = √(Pc * Pc + Qc * Qc)Ic = Sc / (√3 * Ur)【输出参数】:进线相序 : 三相有功功率Pc: 333.45无功功率Qc: 158.77视在功率Sc: 369.32有功同时系数kp:0.90无功同时系数kq:0.97计算电流Ic: 561.12总功率因数: 0.83有功负荷系数α:0.80无功负荷系数β:0.80补偿前功率因数COSφ1: 0.83补偿后功率因数COSφ2: 0.92计算补偿容量QC1: 66.87(kvar)实际补偿容量QC2: (kvar)【计算过程(加入补偿容量)】:Pc = Kp * ∑(Kd * Pn)=333.45(kW)Qc = kq * ∑(Kd * Pn * tgΦ) - QC1 =158.77(kvar)Sc = √(Pc * Pc + Qc * Qc)=369.32(kVA)Ic = Sc / (√3 * Ur)=561.12(A)【补偿容量】:COSφ1 =1/√[1+(β* Qc/α* Pc)2] =0.83COSφ2=0.92QC1=α* Pc*(tgφ1- tgφ2)=66.87【变压器容量】:变压器系列:SCB11 10系列负荷率:70额定容量:630(kW)负荷计算表变压器S1的回路:S1负荷:【计算公式】:Pc = Kp * ∑(Kd * Pn)Qc = kq * ∑(Kd * Pn * tgΦ)Sc = √(Pc * Pc + Qc * Qc)Ic = Sc / (√3 * Ur)【输出参数】:进线相序 : 三相有功功率Pc: 395.44无功功率Qc: 192.20视在功率Sc: 439.68有功同时系数kp:0.80无功同时系数kq:0.80计算电流Ic: 668.02总功率因数: 0.85有功负荷系数α:0.85无功负荷系数β:0.80补偿前功率因数COSφ1: 0.86补偿后功率因数COSφ2: 0.92计算补偿容量QC1: 52.87(kvar)实际补偿容量QC2: (kvar)【计算过程(加入补偿容量)】:Pc = Kp * ∑(Kd * Pn)=395.44(kW)Qc = kq * ∑(Kd * Pn * tgΦ) - QC1 =192.20(kvar)Sc = √(Pc * Pc + Qc * Qc)=439.68(kVA)Ic = Sc / (√3 * Ur)=668.02(A)【补偿容量】:COSφ1 =1/√[1+(β* Qc/α* Pc)2] =0.86COSφ2=0.92QC1=α* Pc*(tgφ1- tgφ2)=52.87【变压器容量】:变压器系列:S11 10系列负荷率:80额定容量:630(kVA)。

用电负荷计算教学课件

用电负荷计算教学课件
详细描述
负荷是指在一定时间内,一个电力系统中所有用户所消耗的功率总和。负荷曲 线则表示电力系统中负荷随时间变化的规律,通常以图形方式表示。
负荷计算的方法
总结词
掌握负荷计算的基本方法
详细描述
负荷计算的方法包括单位面积法、单位产品耗电量法、需要系数法、利用系数法 等。这些方法根据不同的需求和场景选择使用,可以计算出准确的负荷数值。
电动机负载主要是各种电动机,如泵 、风机、压缩机等,其特点是随工艺 需求变化,通常需要变频器、软启动 器等控制设备。
照明负载主要是各种照明设备,如日 光灯、高压钠灯等,其特点是功率较 小,但数量较多,需要合理配置。
工需要系数法、利用系数法和
单位产品耗电量法等。
单位面积法
根据房屋面积和单位面积 的负荷密度来估算总功率 。
实际测量法
通过实际测量家中的电流 、电压等参数,计算实际 用电负荷。
家庭用电负荷计算实例
三口之家
假设有一家三口,居住在80平方米的房子里,有以下家用电器:2台电视、3台空调、2台 冰箱、1台洗衣机、1台电饭煲、1台电磁炉。根据设备功率相加法,总功率约为5千瓦。
根据需要系数法和利用系数法分别计算该工厂的总功率,并比较两者的计算结果。
根据计算结果配置相应的变压器和电缆等电气设备,以确保工厂的正常生产和安全 运行。
01
用电负荷计算的注 意事项
考虑未来发展
未来发展
在计算用电负荷时,应考虑未来 用电设备的增加和电力需求的增 长,预留一定的余量以适应未来 的发展需求。
需要系数法是根据设备的功率 和需要系数计算总功率,适用 于设备功率差异较小的场合。
利用系数法是根据设备的功率 和利用系数计算总功率,适用 于设备功率差异较大的场合。

配电箱负荷计算书

配电箱负荷计算书

配电箱负荷计算书目的针对某甲公司XX工厂电缆配套工程中的配电箱负荷进行计算,确定配电箱数量及型号规格,确保电力供应可靠、安全、稳定。

计算方法按照《规划设计电气工程基础规范》(GB 50052-2019)中标准规定,配电箱的负荷计算应按照以下步骤进行:1.确定用电设备的视在功率对于每个用电设备,根据其使用说明书或者电气参数确定其视在功率,单位为千伏安(kVA)。

如下表所示:设备名称视在功率(kVA)设备110设备220设备352.计算负载总视在功率将所有用电设备的视在功率相加,得到负载总视在功率,记做S。

S = 10 + 20 + 5 = 35 kVA3.计算负载总有功功率根据功率因数和负载总视在功率计算负载总有功功率,记做P。

选择功率因数为0.8,有功功率因数修正系数Kp = 1,无功功率因数修正系数Kq = 1。

P = Kp * S= 1 * 35 = 35 kW4.选取配电箱型号和数量根据计算结果,选取适当的配电箱型号和数量,保证其额定电流大于等于所需有功功率和所需无功功率对应的电流值,同时符合现场使用和规范标准要求。

根据工厂的实际情况,选取品牌为ABB,型号为MA-E250G和MA-E125G两款配电箱。

MA-E250G型号的额定电流为250A,最大容纳40个开关-c灭弧室插件或20个断路器;MA-E125G型号的额定电流为125A,最大容纳10个开关-c灭弧室插件或5个断路器。

根据以上信息,选择MA-E250G型号1个,MA-E125G型号2个。

结论针对某甲公司XX工厂电缆配套工程中的配电箱负荷进行计算,确定需要1个MA-E250G型号配电箱和2个MA-E125G型号配电箱,可以满足所需负载的安全、稳定、可靠供电要求。

参考文献•《规划设计电气工程基础规范》(GB 50052-2019)备注本文档是计算书格式范例,具体计算必须依据实际情况进行,仅供参考。

用电设备荷载及导线计算书

用电设备荷载及导线计算书

1、确定用电负荷:(1)、插入式振动器K x = 0.3 Cos y = 0.7 tg y = 1.02P js= 0.3X18 = 5.4 kWQ js= P js X tg y=5.4x1.02 = 5.508 kvar(2)、电焊机:(取暂载率J1=0.60 功率因素COS W =0.87)P电焊=si* J EC OS W X 10二20X7060X0.87X4=28.9KWK x = 0.65 Cos y = 0.7 tg y = 1.02P js= 0.65X28.9 = 18.785kWQ js= P js X tg y=18.785x1.02 = 19.161 kvar(3)、木工圆锯机K x = 0.65 Cos y = 0.7 tg y = 1.02P js = 0.65X1.5 = 0.975 kWQ js= P js X tg y=0.975x1.02 = 0.995 kvar(4)、钢筋弯曲机K x = 0.65 Cos y = 0.7 tg y = 1.02P js = 0.65X5.5 = 3.575 kWQ js = P js X tg y=3.575X1.02 = 3.647 kvar(5)、钢筋套丝机K x = 0.65 Cos y = 0.7 tg y = 1.02P js = 0.65X8 = 5.2 kWQ js = P.s X tg^=2.6X1.02 = 5.304 kvar (6)、钢筋切断机K x = 0.65 Cos y = 0.7 tg y = 1.02P.s = 0.65X15 = 9.75 kWQ js = P.s X tg y=9.75X1.02 = 9.945 kvar(7)、钢筋调直机K x = 0.65 Cos y = 0.7 tgy = 1.02P js = 0.65X15 =9.75 kWQ js = P js X tg y=9.75x1.02 = 9.945 kvar (8)、卤化灯K x = 1.0 Cos y = 0.7 tg y = 1.02P js = 1.0X20=20 kWQ js = P js X tg y=20x1.02 = 20.4 kvar (9)、三相污水泵K x = 0.65 Cos y = 0.7 tg y = 1.02P js= 0.65X3 =1.95 kWQ js = P js X tg y=1.95x1.02 =1.989 kvar (10)、其他K x= 0.65 Cos y = 0.7 tg y = 1.02P js= 0.65X10 =6.5kWQ js = P js X tg y=6.5x1.02 =6.63 kvar(11)总的计算负荷计算,总配电箱同期系数取Kx = 0.9总的有功功率:Pjs = KxX Z Pjs =0.9x(5.4+18.785+0.975+3.575+5.2+9.75+9.75+20+1.95+6.5)=73.70 kW总的无功功率Q js二K x X Z Q.s =0.9x(5.508+19.161+0.995+3.647+5.304+9.945+9.945+20.4+1.989+6.63) = 75.08 kvar总的视在功率S js= ( P js2+Q js2 )1/2 = (73.702+75.082)1/2 = 105.208KVA总的计算电流计算I js= S j s/(1.732XU e)= 105.208/(1.732X0.38) = 159.85A2、第一项目部1#总配电线路上导线截面及分配箱、开关箱内电气设备选择:2.1用电设备到开关箱及分配箱内电器设备选择在选择前应对照平面图和系统图先由用电设备至开关箱计算,再由开关箱至分配箱计算,选择导线及开关设备。

电力负荷计算书

电力负荷计算书

20
一期病房楼2BF1重F~要W科D弱室电(常间) 用电 1-2APzyks/40kW
40
(常)
1-B1APrd/25kW
25
一期病房楼B1F1消F无防线控覆制盖中机心房安(保常) 1-B1APwxfg/30kW
30
(常)
1-1APab/80kW
80
一期病房楼1F通信网络机房(常) 1-1APtx/100kW
30
1
0.8 0.75
240
33.8 22.5 180.0
56.3 37.5 300.0
85.5 57.0 455.8
125 Q-BTLY(F)-3×50+1×25+E25 80 Q-BTLY(F)-3×25+1×16+E16 600 Q-BTLY(F)-2(3×185+1×95+E95)
30
(常)
1-1APExf/20kW
20
1
0.9 0.48
53
1
0.9 0.48
45
0.5 0.6 1.33
15
0.9 0.8 0.75
18
25.7
58.9
89.5 160 Q-BTLY(F)-4×70+E35
21.8
50.0
76.0 160 Q-BTLY(F)-4×70+E35
20.0
25.0
76.0 100 Q-BTLY(F)-3×35+1×16+E16
三级负荷 一期病房楼B1F~6F一般照明 一期病房楼7F~WD一般动力 一期病房楼泛光照明 一期病房楼屋顶风冷热泵机组1 一期病房楼屋顶风冷热泵机组2 一期病房楼7F~WD一般照明 一期病房楼B1F~6F一般动力 一期病房楼总体预留 一期病房楼屋顶空调水泵 一期病房楼屋顶风冷热泵机组3 一期病房楼屋顶风冷热泵机组4 一期病房楼B1F洗衣间用电 一期病房楼B1F热水泵

配电箱负荷计算书

配电箱负荷计算书

10.6
2.5
c1
0.08 15 1.2 1 1.2 0.55
9.9
2.5
c2
0.08 15 1.2 1 1.2 0.55
9.9
2.5
计算结果 同期系数
5.0
4.96
11 20 10 20
4.96 0.80
4 0.37
8 16
8 16 10
箱号 :cfm
回路名称编 号
单台 容 量 KW
设备 数量
回路容 量KW
需要 系数 Kc
计算容 功率系 计算电 计算电 计算电 量KW 数cosf 流A/a 流A/b 流A/c
计算 电流
A
导线 选择 mm2
母线 选择
A
M1
0.08 18 1.4 1 .08 14 1.1 1 1.12 0.55
9.3
2.5
M3
0.08 18 1.4 1 1.44 0.55
2.5
M2
0.08 14 1.1 1 1.12 0.55
9.3
2.5
M3
0.08 14 1.1 1 1.12 0.55
9.3
2.5
M4
0.08 5 0.4 1 0.4 0.55 3.3
2.5
M5
0.08 15 1.2 1 1.2 0.55
9.9
2.5
M6
0.08 15 1.2 1 1.2 0.55
9.9
7.68 0.80
6 0.52
18
15
17 18 10
箱号 :sm3
回路名称编 号
单台 容 量 KW
设备 数量
回路容 量KW
需要 系数 Kc

用电负荷计算课件PPT

用电负荷计算课件PPT

详细描述
首先了解工厂的生产设备和工艺流程,掌握主要设备的功率和运行时间。然后根 据设备的数量、功率和运行时间,可以计算出工厂的总用电负荷。同时需要考虑 工厂的生产班次和设备利用率,以更准确地反映实际用电负荷。
06
结论与展望
结论总结
研究方法
本研究采用问卷调查和实地访谈相结合的方法,对用电负荷计算的相关问题进行了深入探 讨。通过问卷调查,收集了大量关于用户用电行为和用电负荷的数据;实地访谈则帮助我 们深入了解用户需求和行业发展趋势。
详细描述
单位指标法是根据设备的单位能耗或单位产量来推算负荷的方法。这种方法适用于工艺流程较为固定的设备和场 所,可以通过对同类设备的能耗或产量进行比较,来较为准确地计算设备的负荷。在计算过程中,需要选择合适 的单位能耗或单位产量指标,并考虑设备运行过程中的变化因素。
逐级计算法
总结词
逐级计算法是一种自下而上的负荷计算方法,通过从底层设备开始逐级向上计算负荷, 最终得到总负荷。
研究结果
研究发现,随着经济的发展和人民生活水平的提高,用电负荷呈现出快速增长的趋势。同 时,用户对用电服务的需求也日益多样化,对供电可靠性和服务质量提出了更高的要求。 针对这些情况,本研究提出了一系列有效的用电负荷计算方法和优化策略。
实践意义
本研究成果对于供电企业优化资源配置、提高供电可靠性、满足用户需求具有重要的指导 意义。同时,也为政府制定相关政策提供了科学依据。
详细描述
逐级计算法是从底层设备开始,逐级向上计算负荷的方法。这种方法能够较为准确地反 映设备的实际负荷情况,尤其适用于设备数量较多、工艺流程复杂的场所。在计算过程 中,需要详细了解设备的运行状态和工艺流程,并逐级汇总设备的负荷,最终得到总负
  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

用电负荷计算书
工程名:
计算者:
计算时间:
参考手册:《民用建筑电气设计计算及示例》12SDX101-2
《民用建筑电气设计规范》JGJ 16-2008:
《工业与民用配电设计手册》第四版等
【计算公式(不加入补偿容量)】:
负荷容量:若不全为三相且不存在单相且进线相序为三相且∑(单相、L1相、L2相、L3相的负荷) <= 0.15 * ∑(三相的负荷),则计算负荷= ∑(三相的负荷) +∑(单相、L1相、L2相、L3相的负荷),否则计算负荷= ∑(三相的负荷) + max(∑(L1相的负荷),∑(L2相的负荷),∑(L3相的负荷)) * 3。

有功功率Pc = K∑p * ∑(Kd * Pn)
无功功率Qc = k∑q * ∑(Kd * Pn * tgΦ)
视在功率Sc = √(Pc * Pc + Qc * Qc
计算电流Ic = Sc / (√3 * Ur)
补偿前功率因数COSφ1 = 1/√{1+[(βav* Qc)/(αav* Pc)]²}
【已知参数】:
进线相序 : 三相
有功同时系数k∑p:1.00
无功同时系数k∑q:1.00
有功负荷系数αav:0.75
无功负荷系数βav:0.80
负荷:
【计算过程(不加入补偿容量)】:
计算负荷: 71.00
有功功率Pc = K∑p * ∑(Kd * Pn)
= 56.80
无功功率Qc = k∑q * ∑(Kd * Pn * tgΦ)
= 42.60
视在功率Sc = √(Pc * Pc + Qc * Qc
= 71.00
计算电流Ic = Sc / (√3 * Ur)
= 107.87
补偿前功率因数COSφ1 = 1/√{1+[(βav* Qc)/(αav* Pc)]²} = 0.78。