表1 在监视方向上的过程信息类型标识=UI8[1..8]<0..44> <0> := 未定义<1> := 单点信息M_SP_NA_1<2> := 带时标的单点信息M_SP_TA_1<3> := 双点信息M_DP_NA_1<4> := 带时标的双点信息M_DP_TA_1<5> := 步位置信息M_ST_NA_1<6> := 带时标的步位置信息M_ST_TA_1<7> := 32 比特串M_BO_NA_1<8> := 带时标的32 比特串M_BO_TA_1<9> := 测量值, 规一化值M_ME_NA_1<10> := 测量值,带时标的规一化值M_ME_TA_1<11> := 测量值, 标度化值M_ME_NB_1<12> := 测量值, 带时标的标度化值M_ME_TB_1<13> := 测量值, 短浮点数M_ME_NC_1<14> := 测量值, 带时标的短浮点数M_ME_TC_1<15> := 累计量M_IT_NA_1<16> := 带时标的累计量M_IT_TA_1<17> := 带时标的继电保护设备事件M_EP_TA_1<18> := 带时标的继电保护设备成组启动事件M_EP_TB_1<19> := 带时标的继电保护设备成组输出电路信息M_EP_TC_1<20> := 带变位检出的成组单点信息M_PS_NA_1<21> := 测量值, 不带品质描述词的规一化值M_ME_ND_1<22..29> := 为将来兼容定义保留<30> := 带CP56Time2a 时标的单点信息M_SP_TB_1<31> := 带CP56Time2a 时标的双点信息M_DP_TB_1<32> := 带CP56Time2a 时标的步位置信息M_ST_TB_1<33> := 带CP56Time2a 时标的32 比特串M_BO_TB_1<34> := 带CP56Time2a 时标的测量值, 规一化值M_ME_TD_1<35> := 带CP56Time2a 时标的测量值, 标度化值M_ME_TE_1<36> := 带CP56Time2a 时标的测量值, 短浮点数M_ME_TF_1<37> := 带CP56Time2a 时标的累计量M_IT_TB_1<38> := 带CP56Time2a 时标的继电保护设备事件M_EP_TD_1<39> := 带CP56Time2a 时标的继电保护设备成组启动事件M_EP_TE_1<40> := 带CP56Time2a 时标的继电保护设备成组输出电路信息M_EP_TF_1<41..44> := 为将来兼容定义保留表2 在控制方向的过程信息类型标识=UI8[1..8]<45..69>CON<45>:= 单点命令C_SC_NA_1 CON<46>:= 双点命令C_DC_NA_1 CON<47>:= 步调节(升降)命令C_RC_NA_1 CON<48>:= 设定值(设点)命令, 规一化值C_SE_NA_1 CON<49>:= 设定值(设点)命令, 标度化值C_SE_NB_1 CON<50>:= 设定值(设点)命令, 短浮点数C_SE_NC_1CON<51>:= 32 比特串C_BO_NA_1 <52..57> := 为将来兼容定义保留CON<58> := 带时标CP56Time2a 的单命令C_SC_NA_1 CON<59> := 带时标CP56Time2a 的双命令C_DC_NA_1 CON<60> := 带时标CP56Time2a 的升降命令C_RC_NA_1 CON<61> := 带时标CP56Time2a 的设点命令,规一化值C_SE_TA_1 CON<62> := 带时标CP56Time2a 的设点命令,标度化值C_SE_TB_1 CON<63> := 带时标CP56Time2a 的设点命令,短浮点数C_SE_TC_1 CON<64> := 带时标CP56Time2a 的32 比特串C_BO_NA_1 <65..69> := 为将来兼容定义保留表3 在监视方向的系统命令类型标识=UI8[1..8]<70..99><70> := 初始化结束M_EI_NA_1<71..99>:= 为将来兼容定义保留表4 在控制方向的系统命令类型标识=UI8[1..8]<100..109>CON<100>:= 总召唤命令C_IC_NA_1 CON<101>:= 电能脉冲召唤命令C_CI_NA_1 CON<102>:= 读命令C_RD_NA_1 CON<103>:= 时钟同步命令C_CS_NA_1 CON<104>:= 测试命今C_TS_NA_1 CON<105>:= 复位进程命令C_RP_NA_1 CON<106>:= 延时获得命今C_CD_NA_1 CON<107>:= 带时标CP56Time2a 的测试命令C_TS_NA_1 <108..109>:= 为将来兼容定义保留表5 在控制方向的参数命令类型标识=UI8[1..8]<110..119>CON<110>:= 测量值参数, 规一化值P_ME_NA_1 CON<111>:= 测量值参数, 标度化值P_ME_NB_1 CON<112>:= 测量值参数, 短浮点数P_ME_NC_1 CON<113>:= 参数激活P_AC_NA_1 <114..119>:= 为将来兼容定义保留表6 文件传输类型标识=UI8[1..8]<120..127><120> := 文件淮备就绪F_FR_NA_1 <121> := 节淮备就绪F_SR_NA_1 <122> := 召唤目录, 选择文件, 召唤文件,召唤节F_SC_NA_1 <123> := 最后的节,最后的段F_LS_NA_1 <124> := 确认文件,确认节F_AF_NA_1 <125> := 段F_SG_NA_1 <126> := 目录F_DR_T A_1 <127> := 为将来兼容定义保留注在控制方向上具有CON标记的ASDU,在监视方向上可以传送同样的报文内容,只是传送原因会不相同,在监视方向上这些ASDU用作肯定或否定确认。

积成IEC-104规约报文格式2004-01版

积成IEC-104规约报文格式2004-01版

鲁能积成(福建)IEC-104规约报文格式2003年12月一、应用规约控制信息(APCI) 的定义3二、模块已实现的ASDU 41.在监视方向实现的ASDU: (4)2.在控制方向实现的ASDU: (5)3.类型标识1:M_SP_NA_1 (5)4.类型标识13:M_ME_NC_1 (7)5.类型标识21:M_ME_ND_1 (8)6.类型标识2:M_SP_TA_1 (传送SOE事项) (9)7.类型标识100:C_IC_NA_1 (10)8.类型标识30:M_SP_TB_1 (12)9.类型标识14:M_ME_TC_1 (12)10.类型标识15:M_IT_NA_1 (电度) (13)11.类型标识16:M_IT_TA_1 (15)12.类型标36:M_ME_TF_1 (16)13.类型标37:M_IT_TB_1 (17)14.自定义CON<53> : = 多点控制方案命令C_MC_NA_1 (18)15.类型标识46:C_DC_NA_1 (19)16.类型标识47:C_RC_NA_1 (20)17.类型标识103:C_CS_NA_1 (20)18.类型标识100:C_IC_NA_1 (21)19.类型标识61:M_CH_NA_1 (参考类型标识1:M_SP_NA_1) (22)20.类型标识62:M_CH_ND_1 (传送系统通道标号) (24)三、104规约转发保护信息方案 (26)附录A: 传送原因 (30)附录B: 信息对象地址(本地址定义引用之IEC-101 2002年版) (31)附录C: 组号分配 (31)一、应用规约控制信息(APCI) 的定义传输接口(TCP到用户)是一个面向流接口,它没有为IEC 60870-5-101中的ASDU 定义任何启动或者停止机制。

为了检出ASDU的启动和结束,每个APCI包括下列的定界元素:一个启动字符,ASDU的规定长度,以及控制域(见图4)。

iec101-104规约各种标识

iec101-104规约各种标识
名称
品质描述关键词
初始化原因(COI)
召唤限定词(QOI)
计数量召唤命令限定词 (QCC)
测量值参数限定词 (QPM)
参数激活限定词(QPA)
复位进程命令限定词 (QRP)
命令限定词(QOC)
FBP=固定测试字
解释
QDS :=CP8{OV,RES,BL,SB,NT,IV} OV :=BS1[1] <0..1> ,(Type 6),<0> :=未溢出, <1> RES =RESERVE :=BS3[2.<0..1> (Type 6),<0> :=未被闭锁,<1> SB :=BS1[6]<0..1> (Type 6),<0> :=未被取代,<1> NT :=BS1[7]<0..1> (Type 6),<0> :=当前值, <1> IV :=BS1[8]<0..1> (Type 6),<0> :=有效, <1> :=溢出 :=被闭锁 :=被取代 :=非当前值 :=无效
<32..63> := 为特定使用保留(专用范围) FRZ = 冻结,:=UI2[7..8]<0..63> ,(Type 1.1) <0> :=读(无冻结或复位) <1> :=计数量冻结不带复位(被冻结的值为累计量) <2> :=计数量冻结带复位(被冻结的值为增量信息) <3> :=计数量复位 QPM :=CP8{KPA,LPC,POP} KPA = 参数类别 :=UI6[1..6]<0..63> (Type 1.1) <0> :=未用 <1> :=门限值 <2> :=平滑系数(滤波时间常数) <3> :=传送测量值的下限 <4> :=传送测量值的上限 <5..31> :=为本配套标准的标准定义保留(兼容范围) <32..63>:= 为特定使用保留(专用范围) LPC = 当地参数改变 :=BS1[7]<0..1> ,(Type 6) <0> :=未改变 <1> :=改变 POP = 参数在运行 :=BS1[8]<0..1>, (Type 6) <0> :=运行 <1> :=未运行 QPA :=UI8[1..8]<0..255> (Type 1.1) <0> :=未用 <1> :=激活/仃止激活这之前装载的参数(信息对象地址=0) <2> :=激活/仃止激活所寻址信息对象的参数1) <3> :=激活/仃止激活所寻址的持续循环或周期传输的信息对象 <4..127> :=为本配套标准的标准定义保留(兼容范围) <128..255> := 为特定使用保留(专用范围) 注: 激活/仃止激活在传输原因中定义。 QRP :=UI8[2..7]<0..255> (Type 1.1) <0> :=未采用 <1> :=进程的总复位 <2> :=复位事件缓冲区等待处理的带时标的信息 <3..127> :=为本配套标准的标准定义保留(兼容范围) <128..255> := 为特定使用保留(专用范围) QOC:=CP6{QU,S/E} QU :=UI5[3..7]<0..31> (Type 1.1) 2) <0> :=无另外的定义 <1> :=短脉冲持续时间(断路器),持续时间由被控站内的系统参数所确定 <2> :=长脉冲持续时间,持续时间由被控站内的系统参数所确定 <3> :=持续输出 <4..8> :=为本配套标准的标准定义保留(兼容范围) 3) <9..15> :=为其他预先定义的功能选集保留 <16..31> :=为特定使用保留(专用范围) S/E:=BS1[8]<0..1> (Type 6) <0> :=执行 <1> :=选择 注:在被控站内预先确定所寻址的控制功能的属性(即脉冲持续时间等)时采用,不由控制站选择 注:采用在被控站内预先定义固定属性的控制功能

104规约讲解

104规约讲解

RTU须逐条回答
报文类型标识(五) (Type Identification)
参数命令 《110》归一化测量值参数 《111》标度化测量值参数 《112》短浮点测量值参数 《113》参数激活 文件传输 《120》文件准备就绪 《121》节准备就绪 《122》召唤/选择目录、文件 《123》最后的节、段 《124》认可文件、节 《125》段 《126》目录 P-ME-NA-1 P-ME-NB-1 P-ME-NC-1 P-AC-NA-1 F-FR-NA-1 F-SR-NA-1 F-SC-NA-1 F-LS-NA-1 F-AF-NA-1 F-SG-NA-1 F-DR-NA-1
报文类型标识(二) (Type Identification)
《33》带CP56时标的32比特串 《34》带CP56时标的归一化测量值 《35》带CP56时标的标度化测量值 《36》带CP56时标的短浮点测量值 《37》带CP56时标的累计量 《38》带CP56时标的继电保护设备事件 《39》带CP56时标的继电保护设备成组启动事件 《40》带CP56时标的继电保护设备成组输出信息 《70》站端初始化结束 M-BO-TB-1 M-ME-TD-1 M-ME-TE-1 M-ME-TF-1 M-IT-TB-1 M-EP-TD-1 M-EP-TE-1 M-EP-TF-1 M-EI-NA-1
以上都是RTU向主站上送的报文类型 以上都是RTU向主站上送的报文类型 RTU
报文类型标识(三) (Type Identification)
控制命令
《45》单点命令 《46》双点命令 《47》步调节命令 《48》归一化设定值命令 《49》标度化设定值命令 《50》短浮点设定值命令 《51》32比特串命令 《58-64》带长时标的命令 C-SC-NA-1 C-DC-NA-1 C-RC-NA-1 C-SE-NA-1 C-SE-NB-1 C-SE-NC-1 C-BO-NA-1

104是什么意思

104是什么意思

104是什么意思什么是104规约?104规约国家电力设备通信的一种标准协议,版本目前分为iec104 1997和2002两个版本,在流程上没有什么变化,02版只是在97版上扩展了遥测、遥信等信息体地址,区别如下:类别1997版基地址2002版基地址遥信1h----400h1h----4000h遥测701h----900h4001h----5000h遥控b01h----b80h6001h----6100h设点b81h----c00h6201h----6400h电度c01h----c80h6401h----6600h二、104规约帧格式分析104规约帧格式:①.控制域格式有三种:1)u格式:不计数的控制功能类型,用于传输控制命令的报文。

u格式的apdu只包含apci,帧长6字节。

2)i格式:信息传输格式类型,用于传输含有信息体的报文和确认对方i格式的信息报文。

i格式的apdu包含apci和asdu3)s格式:计数的监视功能类型,用于传输对站端的确认的报文。

s格式的apdu只包含apci,帧长6字节。

可知s格式的apdu的帧内容为如下6个字节:68 04 01 00 98 53 前四个字节固定,后两个字节表示接收序号。

s帧和i 帧结合使用,用于信息确认,主站和子站可以按频率发送,比如接收8帧i帧回答一帧s帧,也可以要求接收一帧i帧就应答一帧s帧。

②.104规约asdu:数据单元标识符:1)数据单元类型:类型标识(typ):1字节可变结构限定词(vsq):1字节2)传送原因(cot):2字节3)asdu公共地址(adr):2字节4)信息对象地址(infoadr):3字节常用的类型标识(typ):可变结构限定词(vsq):占1个字节,最高位为是否连续标志(1:连续,0:不连续),后7位表示信息对象个数。

当可变结构限定词最高位为1表示连续时,对应n个信息对象中,第一个信息对象中含有信息体地址(3个字节)表示从这个规约地址开始,第二个信息对象中不再包含信息体地址,第二个信息对象地址是在第一信息对象中的信息体地址递增。

104规约解读

104规约解读

104规约解读一、104规约报文分3种类型,称U格式、S格式、I格式。

激活帧生效:680407000000激活帧确认:68040B000000测试帧生效:680443000000测试帧确认:680483000000停止帧生效:680413000000如S帧确认:6804010002003、I格式:一般带有ASDU报文,传输各种数据、命令,如YX、YC数据总召唤、读命令、YK、对时等。

二、通讯报文实例:68 04 07 00 00 00 /* U格式启动帧 */68 04 0B 00 00 00 /* 响应帧 */68 0E 00 00 02 00 64 01 06 00 01 00 00 00 0014/* I格式总召帧 */ 68 0E 44 00 02 00 64 01 07 00 01 00 00 00 0014/* 总召激活帧 *//* 总召遥信帧 */68 8C 46 00 02 00 01 FF 14 00 01 00 01 00 00 00 00 01 01 00 01 01 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 80 00 01 01 00 01 01 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 01 00 00 01 00 00 00 00 00信息字个数为:FF-80,当信息字个数小于80时为非连续数据,应给出每个信息字的地址68 8C 48 00 02 00 01 FF 14 00 01 00 80 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 80 00 01 00 00 0000 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 0001 00 00 00 00 01 00 00 00 00 01 01 01 01 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 01 01 00 01 00 00 00 00 00 00 00 00 01 00 01 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00/* 总召遥测帧 */68 8D 5C 00 02 00 15 C0 14 00 01 00 01 40 00 0B 04 0D 04 09 04 69 00 79 00 67 00 40 FD EC FF CE FF AA 06 0C 04 09 04 09 04 27 02 21 02 3D 02 4B F8 F0 FE B6 FF AA 06 0B 04 0B 04 09 04 00 00 00 00 00 00 00 00 00 00 00 00 0B 04 0C 04 09 04 00 00 02 07 01 07 00 07 1F 06 1A 06 77 04 4B 04 EA 04 12 05 00 00 00 00 00 00 00 00 00 00 73 05 75 05 58 05 5A 05 37 01 12 01 1B 01 00 00 00 00 00 00 E5 03 DF 03 F0 03 10 00 C4 06 C3 06 BC 0668 8D 5E 00 02 00 15 C0 14 00 01 00 41 40 00 E9 03 D0 03 F2 03 22 00 BD 06 BE 06 BD 06 0A 04 0C 04 0A 04 54 02 4B 02 52 02 3E 07 0E 01 7C 00 E6 03 DF 03 EF 03 D6 03 D6 03 DB 03 84 07 C3 01 A2 00 0B 04 0B 04 09 04 9A 02 96 02 99 02 67 07 37 01 7E 00 E8 03 D0 03 F3 03 4D 04 4B 04 46 04 A6 07 01 02 9A 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 8D 01 94 01 98 01 96 07 BC 0068 0E 64 00 02 00 64 01 0A 00 01 00 00 00 0014/* 总召激活终止帧 *//* 对时报文 */68 14 08 00 04 00 67 01 0600 01 00 00 00 0020 00 1E 08 18 0A 0668 14 0A 00 04 00 67 0107 00 01 00 00 00 0020 00 1E 08 18 0A 06|> |-------------| | | |-----| |-----| |---------| |--------------------------| 长度帧计数 | 个数原因主站地址信息地址 CP56Time2a时标按乘2变化类型毫秒L-毫秒H-分-时-日-月-年68 04 43 00 00 00 /* 链路测试报文 */68 04 83 00 00 00 /* 响应帧 *//* 变化遥测帧 */68 AA 64 00 02 00 15 20 03 00 01 00 01 40 0005 04 02 40 0005 04 03 40 00 18 04 07 40 00 24 FD 0F 40 00 26 02 3E 40 00 C4 06 3F 40 00 BD 06 4C 40 00 51 02 50 40 00 81 00 55 40 00 DC 03 66 40 00 59 04 81 40 00 42 00 95 40 00 56 03 97 40 00 5307 9A 40 00 C9 01 9B 40 00 C8 01 9C 40 00 C6 01 9E 40 00 D3 00 A2 40 00 ED 01 A7 40 00 2E 02 A8 40 00 2C 02 AA 40 00 11 01 AC 40 00 37 02 AD 40 00 2C 02 B8 40 00 35 00 B9 40 00 47 00 BB 40 00 71 FE C7 40 00 B9 FD CA 40 00 3E 02 CB 40 00 3E 02 CC 40 00 41 02 D6 40 00 86 06/* 变位遥信帧 */68 16 0E 00 0A 00 01 03 0300 01 00 01 00 00 01 02 00 00 01 03 00 00 01| |-------------| | | |-----| |-----| |---------| | |---------| | |--------| | 长度帧计数类型个数原因主站地址遥信地址值遥信地址值遥信地址值/* SOE事件帧 */68 15 10 00 0C 00 1E 01 0300 01 00 01 00 00 01 01 62 3A 08 18 0A 06|> |-------------| | | |-----| |-----| |---------| | |-------------------------| 长度帧计数 | 个数原因主站地址遥信地址值 CP56Time2a时标类型毫秒L-毫秒H-分-时-日-月-年68 0E 12 00 0E 00 2E 01 0600 01 00 01 60 0081/* 双点遥控分选择 */68 0E 12 00 0E 00 2E 01 07 00 01 00 01 60 0081 /* 遥控返校 */|> |-------------| | | |-----| |-----| |---------| |长度帧计数 | 个数原因主站地址信息地址双命令类型68 0E 12 00 0E 00 2E 01 0600 01 00 01 60 0001/* 双点遥控分执行 */68 0E 12 00 0E 00 2E 01 07 00 01 00 01 60 0001 /* 遥控返校 */68 0E 12 00 0E 00 2D 01 0600 01 00 01 60 0080/* 单点遥控分选择 */68 0E 12 00 0E 00 2D 01 07 00 01 00 01 60 0080 /* 遥控返校 */68 0E 14 00 10 00 2D 01 06 00 01 00 01 60 0000/* 单点遥控分执行 */68 0E 14 00 10 00 2D 01 07 00 01 00 01 60 0000 /* 遥控返校 */|> |-------------| | | |-----| |-----| |---------| |长度帧计数 | 个数原因主站地址信息地址单命令类型68 0E 14 00 10 00 2D 01 08 00 01 00 01 60 0080/* 单点遥控分撤销 */68 0E 14 00 10 00 2D 01 09 00 01 00 01 60 0080 /* 遥控返校 */68 10 34 00 00 00 30 01 06 00 01 00 01 62 00 64 00 80/*单点AGC选择*/|> |-------------| | | |-----| |-----| |---------| | |长度帧计数 | 个数原因主站地址信息地址 YT值单命令类型68 0E 40 00 00 00 65 01 06 00 01 00 00 00 0045/* I格式总召YM*/68 10 36 00 00 00 30 01 06 00 01 00 01 62 00 64 00 00/*单点AGC执行*/68 04 01 00 12 00 /* S格式计数帧 */|> |-----| |------|长度 S格式帧接收序号注:收到5、6帧以后,主站发一次确认帧,可以以此判断通道状况三、信息体地址的问题前面说101对YX、YC、YK都有规定的信息体起始地址。

104规约类型标识

104规约类型标识

104规约类型标识1:单点信息2:带短时标的单点信息3:双点信息4:带短时标的双点信息5:步长位置信息6:带短时标的步长位置信息7:32比特串8:带短时标的32比特串9:测量值,归一化值10:带短时标的测量值,归一化值11:测量值,标度化值12:带短时标的测量值,标度化值13:测量值,短浮点数14:带短时标的测量值,短浮点数15:累计值16:带短时标的累计值17:带时标的保护设备事件18:带时标的继电保护装置成组启动事件19:带时标的继电保护装置成组输出电路信息20:具有状态变位检出的成组单点信息21:测量值,不带品质描述的归一化值30:带CP56Time2a时标的单点信息31:带CP56Time2a时标的双点信息32:带CP56Time2a时标的步位置信息33:带CP56Time2a时标的32比特串34:带CP56Time2a时标的测量值规一化35:带CP56Time2a时标的测量值标度化36:带CP56Time2a时标的测量值短浮点37:带CP56Time2a时标的累计量38:带CP56Time2a时标的继电保护装置39:带CP56Time2a时标的继电保护装置成组启动事件40:带CP56Time2a时标的继电保护装置成组输出电路信息41~44:为将来的兼容定义保留45:单命令46:双命令47:步调节命令48:设点命令,归一化值49:设点命令,标度化值50:设点命令,浮点数值51:32比特串52~57:为将来的兼容定义保留58:带CP56Time2a时标的单命令59:带CP56Time2a时标的双命令60:带CP56Time2a时标的步调节命令61:带CP56Time2a时标的设点命令,归一化值62:带CP56Time2a时标的设点命令,标度化值63:带CP56Time2a时标的设点命令,浮点数值64:带CP56Time2a时标的32比特串65~69:为将来的兼容定义保留70:初始化结束71~99:为将来的兼容定义保留100:总召唤101:电能脉冲召唤命令102:读命令103:时钟同步命令104:测试命令105:复位进程命令106:延时获得命令107:带CP56Time2a时标的测试命令108~109:为将来的兼容定义保留110:规一化值的参数111:比例系数的参数112:浮点数值的参数113:参数的激活114~119:为将来的兼容定义保留120:文件准备就绪121:节准备就绪122:召唤目录,选择文件,召唤文件,召唤节123:最后节,最后段124:确认文件,确认节125:段126:目录127:为将来的兼容定义保留。

iec104类型标识

iec104类型标识

iec104类型标识IEC 104类型标识IEC 104是一种通信协议,用于在电力系统自动化中实现远程监控和控制。

它定义了一种标准化的数据传输方式,使得不同厂商的设备可以互相通信和交互。

IEC 104类型标识是在通信过程中对数据进行分类和标记的关键指示。

IEC 104协议中,类型标识用于指示信息对象的类型和数据格式。

通过类型标识,接收端可以准确地解析数据,确定其含义和用途。

IEC 104定义了多种类型标识,每种类型标识都对应着特定的数据类型和功能。

其中,常见的IEC 104类型标识包括:1. 单点信息(Single-Point Information,SI):用于表示开关状态的单个位信息。

比如,可以用来表示设备的开关状态(合闸/分闸)。

2. 双点信息(Double-Point Information,DI):用于表示开关状态的两个位信息。

比如,可以用来表示设备的开关状态(合闸/分闸)以及中间状态(动作中/停止中)。

3. 步位置信息(Step Position Information,SP):用于表示设备的位置信息,通常用于表示开关的位置。

比如,可以用来表示开关的合闸位置或分闸位置。

4. 命令信息(Command Information,CI):用于表示控制命令的信息。

比如,可以用来发送控制命令,实现对设备的远程控制。

5. 测量值标度化参数(Measured Value Scaled Parameter,MV):用于表示测量值的参数信息。

比如,可以用来表示电流、电压、功率等物理量的测量值。

6. 归一化测量值(Normalized Measured Value,NMV):用于表示归一化测量值的信息。

归一化测量值是通过对实际测量值进行归一化处理得到的,通常用于表示电流、电压等模拟量的测量值。

7. 标度化测量值(Scaled Measured Value,SMV):用于表示标度化测量值的信息。

标度化测量值是通过对实际测量值进行标度化处理得到的,通常用于表示电流、电压等模拟量的测量值。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

表1 在监视方向上的过程信息
类型标识=UI8[1..8]<0..44> <0> := 未定义
<1> := 单点信息M_SP_NA_1
<2> := 带时标的单点信息M_SP_TA_1
<3> := 双点信息M_DP_NA_1
<4> := 带时标的双点信息M_DP_TA_1
<5> := 步位置信息M_ST_NA_1
<6> := 带时标的步位置信息M_ST_TA_1
<7> := 32 比特串M_BO_NA_1
<8> := 带时标的32 比特串M_BO_TA_1
<9> := 测量值, 规一化值M_ME_NA_1
<10> := 测量值,带时标的规一化值M_ME_TA_1
<11> := 测量值, 标度化值M_ME_NB_1
<12> := 测量值, 带时标的标度化值M_ME_TB_1
<13> := 测量值, 短浮点数M_ME_NC_1
<14> := 测量值, 带时标的短浮点数M_ME_TC_1
<15> := 累计量M_IT_NA_1
<16> := 带时标的累计量M_IT_TA_1
<17> := 带时标的继电保护设备事件M_EP_TA_1
<18> := 带时标的继电保护设备成组启动事件M_EP_TB_1
<19> := 带时标的继电保护设备成组输出电路信息M_EP_TC_1
<20> := 带变位检出的成组单点信息M_PS_NA_1
<21> := 测量值, 不带品质描述词的规一化值M_ME_ND_1
<22..29> := 为将来兼容定义保留
<30> := 带CP56Time2a 时标的单点信息M_SP_TB_1
<31> := 带CP56Time2a 时标的双点信息M_DP_TB_1
<32> := 带CP56Time2a 时标的步位置信息M_ST_TB_1
<33> := 带CP56Time2a 时标的32 比特串M_BO_TB_1
<34> := 带CP56Time2a 时标的测量值, 规一化值M_ME_TD_1
<35> := 带CP56Time2a 时标的测量值, 标度化值M_ME_TE_1
<36> := 带CP56Time2a 时标的测量值, 短浮点数M_ME_TF_1
<37> := 带CP56Time2a 时标的累计量M_IT_TB_1
<38> := 带CP56Time2a 时标的继电保护设备事件M_EP_TD_1
<39> := 带CP56Time2a 时标的继电保护设备成组启动事件M_EP_TE_1
<40> := 带CP56Time2a 时标的继电保护设备成组输出电路信息M_EP_TF_1
<41..44> := 为将来兼容定义保留
表2 在控制方向的过程信息
类型标识=UI8[1..8]<45..69>
CON<45>:= 单点命令C_SC_NA_1 CON<46>:= 双点命令C_DC_NA_1 CON<47>:= 步调节(升降)命令C_RC_NA_1 CON<48>:= 设定值(设点)命令, 规一化值C_SE_NA_1 CON<49>:= 设定值(设点)命令, 标度化值C_SE_NB_1 CON<50>:= 设定值(设点)命令, 短浮点数C_SE_NC_1
CON<51>:= 32 比特串C_BO_NA_1 <52..57> := 为将来兼容定义保留
CON<58> := 带时标CP56Time2a 的单命令C_SC_NA_1 CON<59> := 带时标CP56Time2a 的双命令C_DC_NA_1 CON<60> := 带时标CP56Time2a 的升降命令C_RC_NA_1 CON<61> := 带时标CP56Time2a 的设点命令,规一化值C_SE_TA_1 CON<62> := 带时标CP56Time2a 的设点命令,标度化值C_SE_TB_1 CON<63> := 带时标CP56Time2a 的设点命令,短浮点数C_SE_TC_1 CON<64> := 带时标CP56Time2a 的32 比特串C_BO_NA_1 <65..69> := 为将来兼容定义保留
表3 在监视方向的系统命令
类型标识=UI8[1..8]<70..99>
<70> := 初始化结束M_EI_NA_1
<71..99>:= 为将来兼容定义保留
表4 在控制方向的系统命令
类型标识=UI8[1..8]<100..109>
CON<100>:= 总召唤命令C_IC_NA_1 CON<101>:= 电能脉冲召唤命令C_CI_NA_1 CON<102>:= 读命令C_RD_NA_1 CON<103>:= 时钟同步命令C_CS_NA_1 CON<104>:= 测试命今C_TS_NA_1 CON<105>:= 复位进程命令C_RP_NA_1 CON<106>:= 延时获得命今C_CD_NA_1 CON<107>:= 带时标CP56Time2a 的测试命令C_TS_NA_1 <108..109>:= 为将来兼容定义保留
表5 在控制方向的参数命令
类型标识=UI8[1..8]<110..119>
CON<110>:= 测量值参数, 规一化值P_ME_NA_1 CON<111>:= 测量值参数, 标度化值P_ME_NB_1 CON<112>:= 测量值参数, 短浮点数P_ME_NC_1 CON<113>:= 参数激活P_AC_NA_1 <114..119>:= 为将来兼容定义保留
表6 文件传输
类型标识=UI8[1..8]<120..127>
<120> := 文件淮备就绪F_FR_NA_1 <121> := 节淮备就绪F_SR_NA_1 <122> := 召唤目录, 选择文件, 召唤文件,召唤节F_SC_NA_1 <123> := 最后的节,最后的段F_LS_NA_1 <124> := 确认文件,确认节F_AF_NA_1 <125> := 段F_SG_NA_1 <126> := 目录F_DR_T A_1 <127> := 为将来兼容定义保留
注在控制方向上具有CON标记的ASDU,在监视方向上可以传送同样的报文内容,只是传送原因会不相同,在监视方向上这些ASDU用作肯定或否定确认。