某小区给水工艺毕业设计完整版-精品
小区给水排水设计毕业设计说明书

摘要文景小区住宅楼采用剪力墙结构,地上建筑高度54.00m,市政水压为30m 水柱;地下室为丙二类库房,地上18层,标准层两梯4户,共有2种户型,一种为三室两厅两卫一厨,另外一种为两室两厅一卫一厨。
本楼建筑设计等级为二类高层建筑。
本建筑各给排水系统介绍如下:1.给水系统:据设计资料以及规范中的要求并结合该楼的功能分区,将该建筑在竖向上分为2个供水区,低区为1~5层;高区为6~18层。
低区利用市政给水管网供水压力直接供水;高区采用变频水泵加压供水。
本设计采用高区6~14层均设减压阀的供水方式。
阀后压力在0.2MPa左右,使供水达到最大舒适度。
2.热水系统:本建筑热水系统热水由每户自家的热水器供给,用户自理。
3.消防系统:包括消火栓系统和自动喷水灭火系统。
本设计建筑总高度54m 的高层建筑楼,属于中危险级,二类高层建筑类别。
本建筑消火栓系统采用不分区室内消防给水系统;本建筑为住宅楼,内设消火栓系统,自喷系统采用湿式自动喷水灭火系统,其中地下室属于丙二类库图,其他楼层属于中危险级Ⅰ级。
4.排水系统:包括生活污水系统和雨水系统。
本建筑内部生活污水采用合流方式排出;屋面雨水采用外排水方式,设计重现期为一年。
关键词:给水系统高层建筑建筑类别消防系统排水ABSRACTWenjing distric residential buildings withshear wall structure, the ground54.00m high buildings municipal water pressure for the 30m column; basement for C two class storehouse, on the ground 18, standard layer two staircase 4 households, a total of 2Apartment layout, for3 rooms two hall two defend one hutch, another two rooms two hall defend one hutch. The building design of grade two class of high-rise building.The building of the water supply and drainage system are as follows:1.water supply system: according to the design and specification requirements and the floor of the partition function, the buildings under vertical is divided into 2water supply area, low area is 1 ~5layer; high is 6~ 18 layer. Zone of low utilization of municipal water supply pipe network water supply pressure to supply water directly; high use frequency conversion pump pressurized water supply. This design uses the high6~14layer are provided with pressure reducing valve water supply mode. After the pressure valve in the water about 0.2MPa, reaching the maximum comfort.2.the hot water system of building hot water system with hot water from every home water heater supply, the users themselves.3.fire fighting system: including fire hydrant systems and automatic sprinkler fire extinguishing system. The design of the total height of the building54m tall building, belongs to dangerous levels, two types of high-rise buildings category. The present building fire hydrant system using partition indoor fire water supply system for residential building; the building, equipped with fire hydrant system, automatic sprinkler system with automatic sprinkler fire extinguishing system, which belongs to the C class library of basement two, other floor belongs to dangerous grade level.4.drainage system: including sewage systems and rainwater system. The construction of internal domestic wastewater using combined method to discharge; roof rainwater using external drainage pattern, design return period of one year.Key words:water supply system in high-rise building fire system drainage construction category.目录第一篇设计任务及资料 (5)1.设计题目: (5)2.设计任务: (5)3.工程概况 (5)4.设计内容: (5)第二章设计说明书 (6)1.给水方案的确定 (6)1.1方案比较确定 (6)1.2分区方式及系统组成 (6)1.2.1给水系统竖向分区的必要性 (6)1.2.2给水系统竖向分区的要求 (7)1.2.3本建筑给水竖向分区情况 (7)2.消防系统的确定 (7)3.自喷系统的确定 (8)4.排水系统的确定 (9)5.雨水系统确定 (9)6.热水系统确定 (9)7.管道及设备安装要求 (9)7.1给水管道及设备安装要求 (9)7.2消防管道及设备安装要求 (10)7.2.1消火栓的安装 (10)7.2.2自动喷洒灭火系统 (10)第三篇设计计算书 (11)1.建筑冷水给水工程设计计算 (11)1.1生活给水用水量标准与参数确定 (11)2.贮水池容积计算 (11)2.1调节容积 (11)2.2消防用水量 (12)2.2.1消火栓用水量 (12)2.2.2自喷用水量 (12)2.2.3消防总用水量 (12)2.3安全储备水量 (12)2.4高位水箱容积计算 (13)3.管道水力计算 (13)3.1低区给水管网水力计算 (13)3.1.1低区生活给水系统所需压力 (17)3.1.2水表的选择 (17)3.2高区生活给水系统计算 (18)3.2.1高区压力计算 (20)3.2.2校核水箱安装高度 (21)3.2.3高区底层给水支管的减压 (21)3.2.4高区水表选择 (21)3.2.5水泵的选择 (22)4.热水系统计算 (23)4.1 热水系统水力计算依据 (23)4.2热水系统水力计算 (24)5.消火栓给水系统的计算 (25)5.1消火栓的保护半径应为: (25)5.2消防水箱贮水量计算 (26)5.3消火栓喷嘴压力及流量 (26)5.4消火栓口所需的水压 (27)5.5消防泵选择 (30)5.6减压阀及减压孔板的设计计算 (30)6.自喷给水系统的计算 (30)6.1基本设计参数 (30)6.2设计计算 (31)6.3自喷选泵 (34)7.排水管路水力计算 (34)7.1排水当量 (35)7.2其他说明 (42)8.雨水系统计算 (43)8.1设计参数 (43)8.2设计暴雨强度q的确定 (43)8.3汇水面积F (43)8.4雨水管路水力计算: (43)8.5其他说明 (44)参考文献 (45)谢辞 (46)第一篇设计任务及资料1.设计题目:文景小区住宅楼建筑给水排水工程设计2.设计任务:设计文景小区住宅楼的建筑给水、排水、消防给水和雨水系统。
某给水工程毕业设计说明书--优秀完整版

摘要E市给水工程,是为了满足该区近期和远期用水量增长的需要而新建的。
该工程分为两组,最终的供水设计规模为3.1万m3/d,整个工程包括取水工程,净水工程和输配水工程三部分。
其工艺流程如下:水源取水头自流管一级泵房自动加药设备机械搅拌澄清池普通快滤池清水池配水池二级泵房配水管网用户同时,本设计课题还包括:水厂占地面积,人员配备,厂内建筑物布置和管线定位等。
整个工艺流程中主要构筑物的设计时间为机械搅拌澄清池池:1.28h普通快滤池冲洗时间:6min普通快滤池的滤速为:13.3m/h目录第一章概述第一节城市自然条件第二节城市建设规划第三节工程设计第二章设计水量第一节设计用水量第二节设计水量第三章给水水源及取水工程第一节给水水源第二节取水构筑物第三节取水泵站(一级泵站)第四章净水厂第一节机械搅拌澄清池第二节普通快滤池第三节清水池第四节配水池第五节送水泵站(二级泵站)第六节加矾加氯间第五章自动化设计第一节净水厂的自动化设计第六章净水厂总体布置第一节净水厂的流程及平面布置第二节附属建筑第三节净水厂绿化与道路第一章概述第一节城市自然条件一、地下水E市基本无地下水可以开采利用。
二、地表水碧流河贯通E市全境,其水文情况为:历年最大流量为952m3/s,最小流量为8.25m3/s,最高水位66.82m(P=1%),最小水位59.98m(P=97%),平均水位62.84m。
浪高1.1m.碧流河水质符合《生活饮用水水源水质标准》二级标准。
该市有东风水库、万福水库。
其中,离市区最近的无金矿污染的为距离市区30公里,万福水库上游2.5公里。
水库水量充足,水质好。
三、气象该市属亚热带湿润气候,年平均气温18摄氏度,最高气温39摄氏度,最低气温零下9摄氏度,最高月平均气温29.2摄氏度,最低月平均气温5.6摄氏度。
日照时速1850小时,无霜期260天左右,有冰雹、暴雨、干旱等灾害气候影响。
降雨量:多年平均降雨量为1600-2000mm左右,最高降雨量2672.5mm,最小降雨量1432.6mm.境内气候湿润温和,四季分明。
毕业设计住宅小区给水排水管网综合设计精编版

毕业设计住宅小区给水排水管网综合设计公司内部编号:(GOOD-TMMT-MMUT-UUPTY-UUYY-DTTI-学号:08434125常州大学毕业设计(论文)(2012届)题目常州市聚湖半岛住宅小区给水排水管网综合设计学生杨秋荣学院环境与安全工程学院专业班级给水082校内指导教师彭明国专业技术职务高工校外指导老师专业技术职务二○一二年六月常州聚湖半岛小区给排水管网综合设计摘要:给水排水工程是城市主要基础设施之一,随着社会经济和城市建设的不断发展,城市基础设施及功能的不断完善,城市发展对给水排水工程的设计和建设提出了更高要求。
课题主要研究常州市聚湖半岛小区室外给水、污水和雨水管线的综合设计,建立该住宅小区完善的给水排水管网系统。
结合常州市城市规划有关规范,进行给水管网布置、管网定线的优化设计及管网的技术经济计算,建立污水管网和雨水管网水力模型,计小区给排水水量,进行可靠的水力计算及校核,完善给水、污水及雨水的平面和主干管纵剖面布置,合理选用给排水管道材料,综合好城市地下管线。
提出了一套完整的住宅小区给水排水综合管网方案,并进行了给水排水管网工程设计和运行管理的优化,确保了小区给水排水管网的安全、环保和可持续发展。
关键词:常州市、给排水、管网、小区。
The integrated design of community water supply and drainage pipe network together in Changzhou lake peninsulaAbstract: water supply and drainage engineering is one of the main city infrastructure, along with the social economy and the continuous development of city construction, the city infrastructure and the continuous improvement of the function, development of city water and wastewater engineering design and construction raised taller requirement. The main research topic a district of changzhou city water supply, sewage and outdoor rain pipeline integrated design, build the residential area perfect water pipe network system. Combined with changzhou city planning related codes, water distribution network, and the pipeline layout for the optimization design of the line and network technology economic calculation, building up sewagepipe network and the rain hydraulic model, plan of water supply and drainage area, reliable hydraulic calculation and checking, improve water supply, sewage and rainwater plane and ZhuGanGuan ZongPouMianlayoutKeywords: changzhou, water supply and drainage, and the pipeline, the village.目录1 引言11.1 工程概况 (1)1.2 设计说明 (1)1.2.1 设计依据 (1)1.2.2 设计内容 (2)1.2.3 设计目标 (2)2 给水管网设计32.1 给水管网设计说明 (3)2.1.1 给水系统基本概念 (3)2.1.2 给水方式的确定 (3)2.1.3 给水管网布置形式 (3)2.1.4 给水管网定线 (4)2.2 给水管材选择和接口形式 (5)2.2.1 给水管材选择 (5)2.2.2 接口形式 (5)2.3 给水管道的布置与敷设 (6)2.4 给水管网设计计算 (6)2.4.1 设计用水量 (6)2.4.2 沿线流量 (8)2.4.3 节点流量 (9)2.4.4 给水管的管径计算 (12)2.4.5 消防校核 (14)3 污水管网设计173.1 排水管网设计说明 (17)3.1.1 排水系统的体制选择 (17)3.1.2 排水系统的布置形式 (18)3.1.3 排水管道定线 (19)3.2 排水管材选择和污水管道衔接 (19)3.2.1 排水管材选择 (19)3.2.2 污水管道的衔接 (20)3.2.3 污水检查井的设置 (20)3.3 污水管道的布置与敷设 (20)3.4 污水管网设计计算 (21)3.4.1 生活污水设计流量的确定 (21)3.4.2 比流量的确定 (22)3.4.3 污水管道水力计算设计参数 (22)3.4.4 干管设计流量计算 (24)3.4.5 干管水力计算 (24)4 雨水管网设计284.1 雨水管网设计说明 (28)4.1.1 雨水管渠设计内容 (28)4.1.2 雨水管渠系统平面布置原则 (28)4.1.3 雨水管渠系统的设计步骤 (28)4.2 雨量分析的几个要素 (28)4.2.1 降雨量 (28)4.2.2 降雨历时 (28)4.2.3 暴雨强度 (28)4.2.4 降雨面积和汇水面积 (28)4.2.5 暴雨强度公式 (28)4.3 雨水管渠设计流量的确定 (28)4.3.1 设计流量公式 (28)4.3.2 径流系数Ψ 的确定 (28)4.3.3 设计重现期 P的确定 (28)4.3.4 集水时间 t 的确定 (28)4.4 雨水管网设计计算 (28)4.4.1 雨水管渠水力计算的设计参数 (28)4.4.2 汇水面积的确定 (28)4.4.3 雨水干管水力计算 (28)5 给排水管道平面图和纵剖面图的绘制286 结论281 引言随着现代城市建设高速发展,人民生活水平的不断提高,人们对环境的要求越来越高,除了人车分流的基本要求外,小桥流水、鸟语花香已成为小区景观建设的基本元素,对于给排水的要求也是如此,好的环境能改善一个人的心情,当然包括给排水管网,而且大型小区的设备用房往往面积大,布置复杂,且绝大部分都设置在地下。
给水工程毕业设计完整版(城镇管网+给水厂)

摘要随着我国经济的进步,人民生活水平有了极大的改善,使得人们对生活、饮用水质和水量的要求也有所提高。
与之相反的是,伴随着经济发展所导致的环境污染也使得自然水质降低,这就要求给水排水工程设计人员对城市给水工程有更专业和更合理的规划和设计。
本设计为XX省XX镇给水工程初步设计,设计的主要内容包括取水工程、净水工程、输水管渠、城市管网、泵站以及其它调节构筑物。
结合设计规范以及实际情况,本设计采用如下净水流程:管式静态混合——隔板絮凝池——斜管沉淀池——清水池。
关键词水质,水量,给水工程,净水工程,城市管网ABSTRACT With the rapid development of China's economy, people's living standards have greatly improved, and makes people's life, the requirement of the drinking water quality and water volume is increased. By contrast, with the economic development caused by the pollution of the environment also makes the natural water quality decreased, which requires the water supply and drainage engineering design personnel is more professional and more reasonable for urban water supply engineering planning and design.This design for the XXX province XXX town water supply engineering preliminary design, the design of the main content includes water engineering, water purification, water pipe canal, city piping systems and pumping stations, and other structures adjustment.Combining with the design specification and the actual situation, this design USES the following water purification process, tubular static mixed - clapboard flocculation pool - inclined tube sedimentation tank - clear water reserviors.KEY WORDS water quality, water quantity, water supply engineering, water engineering, urban pipe network目录第1章绪论 (6)1.1前言 (6)1.2设计原始资料 (6)1.2.1设计题目 (6)1.2.2原始资料 (6)1.2.3毕业设计内容 (9)第2章管网计算 (9)2.1供水方案的确定 (9)2.1.1设计后的工程要求 (9)2.1.2可行性方案的确定 (10)2.2城市管网设计计算 (10)2.2.1城市最高日用水量计算 (10)2.2.2最高日最大时用水量计算 (12)2.2.3消防用水量计算 (12)2.2.4绘制全市最高日用水量变化曲线 (13)2.3管网定线 (15)2.3.1布置原则 (15)2.3.2管网布置要点 (15)2.3.3输水管定线 (16)2.3.4配水管定线 (16)2.4方案管网水力计算 (17)2.4.1统一供水管网水力计算 (17)2.4.2方案二管网水力计算 (24)2.5方案的管网经济技术比较 (31)2.5.1统一供水方案管网预算 (31)2.5.2并联分区管网预算 (32)2.5.3给水管网方案确定 (33)2.6绘制等水压线图 (33)2.6.1控制点的确定方法和节点地面标高 (33)第3章取水工程设计 (35)3.1进水间设计 (35)3.1.1一泵站设计水量 (35)3.1.2格栅的设计 (36)3.1.3格网的设计 (37)3.2取水头部及尺寸计算 (38)3.2.1 取水头部及高程计算 (38)3.2.2 进水间平面尺寸及吸水间平面尺寸的计算 (38)3.2.3格栅起吊高度计算 (39)3.3取水泵房的设计 (39)3.3.1 泵设计扬程的确定 (39)3.3.2选择水泵和机组 (40)3.3.4吸水管路和压水管路的计算 (41)3.3.5水泵机组和道路布置 (41)3.3.6吸水管在吸水间布置 (43)3.3.7水泵安装高度的确定 (43)3.3.8吸水管中的水头损失 (44)3.3.9 压水管路水头损失∑h d (44)3.3.10水泵实际扬程 (45)3.4泵房设计及附属设备的选择 (45)3.4.1附属设备的选择计算 (45)3.4.2 泵房高度计算 (47)第4章净水构筑物的计算 (48)4.1设计供水量 (48)4.2配水井计算 (48)4.3投药系统计算 (49)4.3.1用药量计算 (50)4.3.2加药间和仓库 (50)4.3.3 混合设备(管式静态混合器) (51)4.4絮凝设备 (51)4.4.1设计参数 (51)4.4.2絮凝池参数的确定 (52)4.4.3设计计算 (52)4.5斜管沉淀池的计算 (54)4.5.1斜管沉淀池的设计要点 (54)4.5.2设计计算 (54)4.6普通快滤池计算 (59)4.6.1滤池的设计计算 (59)4.7液氯消毒系统的计算 (63)4.7.1加氯量 (63)4.7.2加氯设备 (64)4.7.3加氯间 (64)4.8清水池设计 (65)4.8.1清水池容积计算 (65)4.8.2清水池设计计算 (66)4.9吸水井 (68)4.9.1设置吸水井的原因 (68)4.9.2吸水井计算 (68)4.10二级泵站扬程的确定 (69)4.10.1计算水泵扬程 (69)4.10.2管道特性曲线 (70)4.10.3泵型号的选择 (70)4.10.4机组基础尺寸的确定 (71)4.10.5水泵的有关设计计算和校核 (72)第5章水厂平面布置 (76)5.2水厂平面和高程布置 (77)5.2.1平面布置 (77)5.2.2高程布置 (78)第6章给水工程经济概算 (79)6.1工程总概算 (79)6.1.1取水部分 (79)6.1.2净水厂部分 (79)6.1.3输配水部分 (79)6.1.4附属构筑物部分 (80)6.2制水成本计算 (81)6.2.1 计算资料: (81)6.2.2 制水成本计算 (82)总结 (85)参考文献 (86)附录1 (87)附录2 (88)附录3 (89)附录4 (90)附录5 (92)附录6 (94)附录7 (96)附录8 (97)附录9 (98)附录10 (99)附录11 (100)附录12 (101)第1章绪论1.1前言XX镇,坐落XX省XX地区的一座正在开发发展的城市,在城市的中央有一条河流由东南方向流向西北方向,并有一条自西向东延伸的铁路。
给水工程毕业设计模板

给水工程毕业设计12020年4月19日目录目录 (1)中文摘要 (2)英文摘要 (3)1 绪论.................................................................................. 错误!未定义书签。
2 概述.................................................................................. 错误!未定义书签。
2.1 毕业设计的主要内容与基本要求.................................. 错误!未定义书签。
2.2 毕业设计成果 ................................................................. 错误!未定义书签。
2.3 设计缘由......................................................................... 错误!未定义书签。
2.4 设计要求......................................................................... 错误!未定义书签。
3 取水工程........................................................................... 错误!未定义书签。
3.1 设计用水量的确定 ......................................................... 错误!未定义书签。
3.2 取水装置设计 ................................................................. 错误!未定义书签。
【精品】毕业设计-某小区高楼变频恒压供水系统设计

某小区高楼变频恒压供水控制系统设计摘要随着我国社会经济的发展,城市建设发展十分迅速,同时也对基础设施建设提出了更高的要求。
城市供水系统的建设是其中的一个重要方面,供水的可靠性、稳定性、经济性直接影响到用户的正常工作和生活。
随着人们对供水质量和供水系统可靠性要求的不断提高,利用先进的自动化技术、控制技术以及通讯技术,设计出高性能、高节能、能适应供水厂复杂环境的恒压供水系统成为必然趋势。
本文首先根据管网和水泵的运行特性曲线,阐明了供水系统的变频调速节能原理;具体分析了变频恒水压供水的原理及系统的组成结构,通过研究和比较,得出结论:变频调速是当今国际上一项效益最高、性能最好、应用最广、最有发展前途的电机调速技术。
因此本文以采用变频器和PLC 组合构成系统的方式,以某居民小区水泵电动机控制系统为对象,逐步阐明如何实现水压恒定供水。
进行了控制系统的主电路设计,控制电路设计。
对输入输出点进行了统计,共有13个输入输出点,根据PLC的选型原则,设备选用了在生产中应用最为广泛的西门子公司生产的S7-200系列(CPU222)的PLC和MM430泵类专用的变频器,利用变频器的本身自有的软启动功能实现水泵电机的启动。
在控制过程中,电控系统由S7-200完成,PID控制由变频器的内置PID控制方式完成,根据控制系统软硬件设计和控制要求,结合变频器的功能参数表预置了相关的参数。
在介绍了PLC的编程方法的基础上,选用了适合初学者的逻辑代数编程,写出了恒压变频供水的逻辑代数,并设计了梯形图,利用PLCSIM仿真软件进行了仿真,仿真的结果表明了设计程序的正确性。
利用了WinCC组态软件设计了高楼变频恒压供水控制系统的界面,界面可动态反映水泵变频供水的工作状态。
最后对恒压供水进行了经济效益分析,分析的结果表明具有明显的节能效益。
关键词:恒压供水,变频调速,PLC,设计,仿真ABSTRACTAs China's social and economic development, urban construction and development very quickly, but also the construction of infrastructure facilities has put forward higher requirements. City water supply system construction is one of the important aspects of the water supply reliability and stability, the economy of a direct impact on the user's normal work and life. As people on the water quality and water supply systems in the continuous improvement of reliability requirements, the use of advanced automation technology, control technology and communication technology, design a high-performance, high-energy, water supply plants to adapt to the complex environment of constant pressure water supply Systems become an inevitable trendIn this paper, pipe network and pumps under the operation of the curve, clarify the water supply system for energy-saving Frequency Control Principle; specific analysis of the frequency of the principle of constant pressure water supply system and the composition of the structure, through research and comparison, concluded: Frequency Control is the highest international one-effectiveness, performance, the best and most widely, the most The future development of the Motor technology. Therefore this paper to adopt the PLC and inverter combination of a systematic approach to a small residential area pump motor control system for the target, and gradually clarified how to achieve a constant supply pressure.A control system for the main circuit design, control circuit design. The input and output points to the statistics, a total of 13 input and output, the PLC in accordance with the principle of selection, equipment selection in the production of the most widely produced by Siemens S7-200 series (CPU222) of the PLC and pumps for MM430 The converter, using its own frequency converter itself to achieve the soft-start the pump motor launch. In the control process, the electronic control system completed by the S7-200, PID control by the converter built-in PID control manner, in accordance with control system software and hardware design and control requirements, combining the functions of converter table preset parameters of the relevant parameters . After the introduction of the PLC programming methods, based on the choice of the logic of algebra for beginners programming, the constant pressure to write the logic of algebra frequency of water supply and design of the ladder, use of simulation software PLCSIM the simulation, simulation The results show thatthe correctness of the design process. WinCC use of the configuration software designed high frequency constant pressure water supply control system interface, dynamic interface may reflect the work of pumping frequency of water supply status. Finally, the constant pressure of water supply for the economic benefit analysis, analysis of the results showed that a significant energy efficiency.Keywords:Constant pressure Water Supply ,Variable velocity Variable frequency,PLC,Design,Simulation目录第一章绪论 (7)1.1引言 (7)1.2本课题产生的背景和意义 (8)1.3变频恒压供水的现况 (8)1.3.1 国内外变频供水系统现状 (8)1.3.2 变频供水系统应用范围 (9)1.4本人的主要工作 (9)第二章变频恒压供水的理论分析 (11)2.1水泵的工作原理 (11)2.2供水电机的搭配 (11)2.3水泵的调节方式 (12)2.4恒压供水系统的能耗分析 (13)2.5供水系统的安全性问题 (15)2.5.1 水锤效应 (15)2.5.3 水锤效应的消除 (16)2.5.4 延长水泵寿命的其他因素 (16)第三章变频恒压供水控制系统硬件的设计 (17)3.1变频恒压供水控制系统的构成方案 (17)3.2变频恒压供水系统的控制方案 (18)3.3供水设备的选择原则 (19)3.4参数的计算与供水设备选型 (21)3.4.1 水泵的参数计算与型号的选择 (21)3.4.2 变频器的选择 (21)3.4.3 压力传感器的选择 (23)3.4.4 水位传感器的选择 (23)3.4.5 其他低压电器的选择 (23)3.5PLC的选型 (24)3.5.1 I/O点的统计 (24)3.5.2 PLC选型的基本原则 (25)3.5.3 I/O的分配 (25)3.6系统硬件线路设计 (26)3.7PID参数的预置 (27)第四章变频恒压供水控制系统软件的设计 (29)4.1常用编程方法 (29)4.1.1 经验设计法 (29)4.1.2 翻译设计法 (29)4.1.3 逻辑代数设计法 (30)4.2编程软件的简单介绍 (32)4.3恒压供水系统梯形图的设计 (33)4.4程序的仿真与调试 (37)4.4.1 仿真软件的简介 (37)4.4.2 恒压供水系统程序的仿真调试 (38)4.5恒压变频供水系统的W IN CC界面设计 (40)4.5.1 WinCC软件简介 (40)4.5.2 恒压供水系统的WinCC界面设计 (41)4.6经济效益分析 (44)第五章总结与期望 (47)5.1总结 (47)5.2展望 (47)参考文献 (48)致谢 (49)附录语句表 (50)第一章绪论1.1 引言水是生命之源,人类生存和发展都离不开水。
某小区中水回用工艺设计毕业设计

第一部份某小区生活污水再生利用(中水)处理工艺设计(B)说明书1. 概述项目概况某地块是上海某房地产经营有限公司开发的大型住宅小区,总占地约164700m2,总建筑面积417748m2,小区共分三期建设,总绿化面积为万m2,道路约为万m2,停车车位有900个,水景面积约为3500m2。
为了充分利用水资源,响应国家节水政策,降低小区用水费用,小区开发商拟建一套生活废水(或称杂排水)处理再生利用设施,以达到《城市污水再生利用城市杂用水水质》要求回用,中水主要用于小区内的绿化浇灌、道路地面冲洗、车辆清洗等功能。
中水回用的现状与意义水是人类社会赖以生存的最重要物质条件之一,我国作为一个水资源紧缺的国家,人均水资源占有量为273立方米,仅为世界人均占有量的1/4,水资源紧缺已成为制约我国城市可持续发展的重要因素。
中水主要指城市污水或生活污水处理后达到一定的水质标准,可在一定范围内重复使用的非饮用水,其水质介于上水与下水之间,中水回用则是将城市污水进行处理后作为再生资源回用。
是水资源有效利用的一种形式。
中水回用,是解决城市水资源危机的重要途径,也是协调城市水资源与水环境的根本出路。
开发和应用投资省、见效快、运行成本低的中水回用处理技术已经成为确保社会经济可持续发展的重大课题。
设置中水回用既可以有效地利用和节约有限的、宝贵的淡水资源,又可以减少污、废水排放量,减少水环境的污染,还可以缓解城市下水道的超负荷现象,具有明显的社会效益、环境效益和经济效益。
城市污水由于水量稳定,基建投资经济,许多国家都将中水回用作为解决缺水问题的优选方案。
国际上,日本、美国等国早已开展污水处理后回用的工作。
美国加利福尼亚已实施卫生间废水处理再利用工程。
在德国的一些城市,地方政府正试验提供处理过的废水冲洗马桶。
中水回用的典型代表是日本,上世纪60年代起就开始使用中水。
1997年底,日本供建筑、建筑物群、居民小区的冲厕或其它非生活饮用的杂用水污水净化设施有1475套,回用水量为亿立方米/年,占城市总供水量(亿立方米/年)的%。
成都市某某小区给排水设计(建筑给排水毕业设计(含计算书))

市政工程系毕业设计(论文)题目:成都市某小区10#楼给水排水院系:市政工程系专业:给水排水工程班级:姓名:指导老师:完成日期:2007.6.1前言如今,我国国民经济实力的不断增强,建筑业的迅速发展,建筑物的总体建设水平不断提高。
建筑内部的给水排水工程是建筑设备中的重要组成部分,奇迹术水平及先进性直接影响建筑物的使用功能,与人们生活,环境,安全息息相关,涉及到千家万户,与社会的环境保护,水资源的合理利用,可持续性发展紧密相连。
建筑给水排水工程发展迅速,在理论和实践上都将不断地完善和发展,对建筑给水排水专业的人员,在数量和质量上都提出了更高的要求,应具有更先进的设计理念和更高的设计水平,不断引进先进技术,要切实把理论和实践相结合。
为了巩固和掌握建筑给水排水工程的理论知识和实践能力,本次毕业设计的是成都市紫藤花园小区的建筑给水排水系统。
其中包括建筑给水系统,建筑排水系统,建筑消防系统的设计。
只有用科学的方法和实践的结合,才能保证给水排水的系统的安全可靠运行,保证用户的用水需求,又可以最大限度的降低建设投资和运行成本。
在平时的学习中已经积累了一定的理论基础知识,再加上这次的建筑给水排水工程的设计实践,又加深了对理论基础知识的理解和系统化,更锻炼了动手能力,也为以后的设计奠定了坚实的基础。
只有把理论和实践相结合才能发现问题,解决问题,加深记忆。
在这次设计中参考了大量书目,其中主要参考书目附于其后。
由于高层建筑给水排水系统涉及内容和知识领域广泛,加之本人经验水平有限,在设计中难免出现一些不太合理之处,恳请各位老师批评指正。
ForewordAt now, the architecture industry development is rapid, the building overall construction level unceasingly enhances. Its technical leve land directly affect the building the use function, lives with the people, the health, the environment, the security is closely linked, involves everyone, with society's environmental protection, water resources reasonable use, but the long-enduring development close is connected.In recent years constructed for the water dewatering excavation development is rapid, in the theory and the practice all unceasingly the consummation and the development, to the construction for the water draining water specialized personnel, all proposed in the quantity and the quality a higher request, should have the more advanced design idea and the higher design level, unceasingly introduced the advanced technology, had practically unifies the theory and the practice.For making stronger and controling building water supply to drain theories knowledge and fulfillment ability of engineering, this time design of is even crest the indoor water supply of the office building of the 12 layer industry and business bureau in mountain City drain system. Include water supply system among them, catchment system, the design of fire fight system.Made reference to a great deal of bibliography in this design, among them, the main reference attach in afterward.Because the key figures construct water supply catchment system to involve contents and knowledge realm extensively, adding it oneself experience level is limited, appearing some not that reasonable place unavoidably in the design, pleading each teacher to criticize to correct.目录设计概况┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅1 引言┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅2 第1章高层建筑内部给水系统┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅81.1给水系统的设计说明┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅81.2给水管道的布置与敷设┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅91.3给水系统设计用水量┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅101.4管道水力计算┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅12 第2章高层建筑内部热水系统┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅232.1热水供应系统设计说明┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅232.2热水管道的布置与敷设┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅232.3热水系统用水量┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅242.4耗热量、热水量和加热设备供热量的计算┅┅┅┅┅┅┅┅┅252.5 管道水力计算┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅292.6 机械循环热水系统计算┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅34 第3章高层建筑内部排水系统┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅433.1排水系统的设计说明┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅433.2排水管道的布置与敷设┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅433.3排水系统的设计计算┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅443.4化粪池的设计计算┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅463.5排污泵及集水井的设计计算┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅48 第4章高层建筑内部消火栓系统┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅494.1系统选择和管道布置┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅494.2消火栓系统水力计算┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅494.3减压孔板计算┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅51 第5章自动喷淋灭火系统┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅535.1喷淋系统设计说明┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅535.2喷淋系统水力计算┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅545.3泵的选型┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅59 结束语┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅60 致谢┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅60 参考文献┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅┅61设计概况成都市紫藤花园小区建筑面积11000平方米,建筑高度81米,属于一类建筑;地上26层,地下1层;小区1、2层为商场,其余各层为住宅;在地下1层设有泵房,变压器室,空调机房,配电室,值班室,消毒室,仓库等。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
1 绪论1.1 设计任务与原始资料1.1.1原始资料H小区地处沿海地区,经济较发达,该小区常住人口约20000人。
取水源为小区附近(如图1.1所示)的湖泊(水质如表1.1所示)。
湖泊水深较浅,水位随季节变化不大,最高水位位于地平面以下0.3米,最低水位位于地平面以下0.6米;岸边地势较缓,地基条件较好。
由于工业的发展,水源遭到一定程度的污染,水质指标总体基本符合地面水质标准中类水的标准,但氨氮(3NH-N)含量超标,AOC(可同化有机碳)和的含量也较高,水厂常规处理工艺已经无法使出水符合《生活饮用水卫生标准》(GB5749-85)和卫生部颁布的《生活饮用水卫生标准>>。
表1.1 原水水质一览表1.1.2设计的主要内容本设计的任务是针对题设要求和条件,设计出适合H小区的给水处理工程。
本设计的内容包括:(1)取水构筑物及泵站设计;(2)针对原水水质,选择适宜的给水处理工艺流程,其中应当包括(或部分包括):⑴预处理工艺;⑵常规处理工艺;⑶深度处理工艺。
(3)水厂处理构筑物设计、设备的选型及运行参数确定。
(4)绘制工艺的平面布置图和高程布置图。
(5)绘制主要构筑物的加工/施工/工艺图。
图1.1 H小区地形图1.1.3设计的具体要求(1)学会收集与整理设计资料;运用已学过的理论知识,合理规划,设计小型给水处理系统;通过设计,熟悉有关技术规定和设计规范。
(2)根据任务书的要求,合理安排和规划时间,按期独立完成设计任务;设计结果应具有一定的实用价值。
1.1.4需要提交的设计成果(1)毕业设计说明和计算书一本(合订)。
(2)H小区给水工艺设计图纸一套,其中应包括:a、H小区给水系统平面布置图和高程布置图(2张);b、取水构筑物剖面图(1张);c、给水厂主要处理构筑物的加工/施工/工艺图(5-8张)。
1.2工艺流程选择近年来,随着工农业的迅速发展,城市化建设加快,城市人口膨胀,引起了城市工业生活用水量大大增加;同时,相应的污染排放量也逐年增加。
导致了饮用水水源普遍受到污染,饮用水水质恶化。
常规的工艺已经无法满足处理水有较好水质的标准。
国外也纷纷在常规工艺基础上增设预处理、深度处理,处理后的水质较好,使用安全,经济上也可运行。
针对本次设计,因为是经济发达地区,水质污染主要超标项目:可同化有机碳(有机物)和氨氮。
拟采用生物预处理+常规工艺+深度处理。
常规处理中可以选择混凝沉淀也可以选择澄清工艺将二者合为一个工艺。
通过对原水水质的分析,现拟定以下工艺流程:原水--生物预处理—絮凝沉淀—过滤--深度处理—消毒。
2 取水装置及泵站设计2.1 水量确定根据所给资料,沿海经济较发达地区。
查《给排水工程快速设计手册》表1-3,H小区地处东南沿海地区,属于第三区,即:上海浙江的全部江西安徽江苏的大部福建北部湖南湖北的东部和河南南部。
给水设备类型:室内有给水排水卫生设备并有淋浴设备和集中热水供应。
表2.1 生活用水量定额所以最高日生活用水量定额200 L/人.dk=1.4 用水普及率f=98%(1)城市或居住区的最高日生活用水量Q1Q1 =qfN= 200(L/人.d)×2000人×98%=3920m3(2)浇洒道路和大面积绿化需用水Q2浇洒道路每平方米路面每次1~1.5L大面积绿化用水1.5~2.0L/(d.㎡)。
若按面积计算,绿化及浇洒道路用水量〉生活用水量,不合理。
所以据经验估计占3%,只负责预留地及生活区的用水量。
各个工厂可自己打井供绿化浇洒道路,也不计入用水量计算。
(3)Q2=3%Q1=3%×3920=117.6约=118. m3(4)再增加相当于最高日用水量15%~25%的未预见用水量和管网漏水量。
(5)设计年限内最高日用水量Qd’=1.25(Q1+Q2) =1.25×(3920+118)=5047.5 m3/d(6)再加水厂自用水量:取设计用水量的5%则Qd=1.05Qd=1.05×5047.5 m3/d=5299.875 m3/d(7)最高日平均时用水量Qh=hmdmQd/8.22024/875.52992433===0.06 m s/3(8)最高时设计用水量Qh’=Qhα=1.4×220.8m h/3=309.12 m h/3=0.086 m s/32.2 取水装置2.2.1取水点取水点因为是湖泊取水,湖泊取水的基本要求是:(1)远离湖岸芦苇等较多的地方,这些湖区有机物丰富,水生物较多,水质较差,易发生堵塞现象。
(2)取水点应该避免选择在夏季主风向的向风面的凹岸处,因为这些地方大量浮游生物集聚并死亡,使水质恶化,水的色度增加,且产生臭味。
(3)取水头部应该远离支流的汇入点,选择水深较大,浊度较小的地点。
(4)取水头部应该建在稳定的湖岸,选择岸坡坡度较小,岸高不大的地方。
所以取水口应选在近湖泊出口处,离开支流汇入口,且须避开藻类集中滋生区。
考虑到实际地区情况,无法满足取水口在主导风向上风向这个条件,所以取离预留空地最近的湖泊边的一点,但取水头部可以取远点。
伸入湖泊78.8m.2.2.2取水方式从湖泊取水,应考虑风浪对淹没深度的影响。
(1)岸边式取水构筑物适用于湖泊岸边较陡,主流近岸,岸边有足够水深,水质和地质条件较好的情况。
(2)河床式取水构筑物在湖岸平坦,岸边水深不够或水质不好时采用。
本设计从湖泊中取水,水深较小,岸边地质条件较好,水质比较均匀,可分建或合建取水构筑物。
考虑造价问题,泵房不宜挖太深,所以选择河床分建式取水构筑物。
53.753.454.052.9取水头部自流管集水室吸水管路输水管路54.954.4758.85吸水室水泵图2.1 取水构筑物示意图河床式取水构筑物按照进水管形式的不同,河床式取水构筑物的主要类型有自流管取水,虹吸管取水,水泵直接吸水,桥墩式取水等。
(1)自流管取水:自流管淹没于水中,湖水靠重力自留,工作较可靠,但敷设自流管时,开挖土石方量较大,适用于自流管埋深不大时。
(2)虹吸管取水:虹吸管比自流管提高了卖官的高程,可以减少水下土石方量,缩短工期,节约投资。
但虹吸管对管材及施工质量要求较高,运行管理要求严格,并须保证严密不漏气,需要真空装置,工作可靠性不如自流管。
(3)水泵直接吸水:适用于水中漂浮物不多,吸水管不长的中小型泵房。
(4)桥墩式取水:造价高,适合在大河中,岸边无建泵房条件下使用。
水厂规模较小,湖泊岸边地质条件较好,地势平坦,水质稳定,水位落差不大,所以可以选择自流管取水方式,既可以减少工程造价,与虹吸管相比又可以保证供水安全,并与取水量要求相适宜。
2.2.3取水头部常见的河床式取水构筑物的取水头部主要有喇叭口取水头部、蘑菇头式取水头部、鱼形罩取水头部、箱式取水头部、斜板取水头部等。
(1)喇叭口取水头部:是设有隔栅的金属喇叭口,用桩架或支墩固定在河床上,这种头部构造简单,造价较低,施工方便,但取出漂浮污效果较差。
(2)蘑菇头式取水头部:是一个向上的喇叭口,其上再加一金属帽盖。
河水由帽盖底部流入,带入的泥沙及漂浮物较少。
缺点是头部高度较大,有求水深较大。
(3)鱼形罩取水头部:是一个两端带圆锥头部的圆筒,在圆筒表面和背水圆锥面上开设圆形进水孔。
其外形区域流线型,水流阻力小,而且进水面积大,进水孔流速小,漂浮物难于吸附在罩上,所以能减轻水草堵塞。
(4)箱式取水头部:进水孔总面积较大,能减少冰凌和泥沙进入量,适于在水深较小的情况下使用。
(5)斜板取水头部:适用于粗颗粒泥沙较多的情况。
综合各种取水头部的优缺点与适用范围,选用箱式取水头部较为合适,能满足浅水取水的条件限制,又能节省造价,施工也不太复杂。
2.2.4取水头部的进水孔与格栅面积取水头部进水孔的上缘在设计最低水位以下的浸没深度,侧面进水时不小于0.3m.进水孔一般布置在取水头部的侧面和下游方向。
取水头部至少分成两格或分设两个,以便清洗和维修。
如图,取水头部的平面尺寸为3.6×1.8m2。
图2.2 取水头部平面图进水孔流速无冰絮时为0.2~0.6m/s,本设计取0.4 m/s , 栅条直接固定在进水孔上,栅条采用扁钢,厚度s=10mm,栅条净距采用b=50mm,格栅阻塞系数k1=0.75, 栅条引起的面积减少系数k2=s b b +=105050+=0.833, 进水孔总面积,Fo=Vo K K Q 21 =4.075.0833.006.0⨯⨯=0.24㎡每个进水孔面积 f=Fo/4=24㎡/4=0.06㎡ 水流通过格栅的水头损失0.05~0.1m 取1.0m进水孔尺寸用B1×H1=0.2m ×0.3m,格栅尺寸因为太小,无法用现有的标准尺寸,自己制的尺寸为0.22m ×0.32m 。
图2.3 格栅2.2.5平板格网设在进水间内,用于拦截水中细小的漂浮物。
过网流速采用V1=0.3m/s.网眼尺寸采用5mm ×5mm ,网丝直径d=2mm,网格面积减少系数 K1=2)(d b b b +⨯ =2)25(55+⨯ =0.51 格网阻塞系数采用K2=0.5,水流收缩系数采用a=0.8,平板网格所需面积F1=121aV K K Q =3.08.05.051.006.0⨯⨯⨯=0.98㎡ 设两个格网,每个格网面积为0.245㎡,进水部分尺寸为B1×H1=0.49×0.5,同样没有这么小的标准格网,自制的尺寸为0.54m ×0.55m 。
图2.4 平板格网水头损失约0.10~0.202mH O ,取0.202mH O 。
2.2.6进水管自流管采用钢筋混凝土,出于安全性考虑,不少于两根管。
管径按正常供水时的设计水量和流速决定。
进水管设计流速不小于0.6 m/s ,本设计取0.8 m/s ,水量为0.06m 3/s ,自流管一般埋设在河床下0.5~1.0m,减少其对江河水流的影响和免受冲击。
如需要铺设在河床上,须用块石或支墩固定。
坡度和坡向河心。
A=vQ =8.003.0=0.0375㎡.D=0.218m=218mm 取250mm.从取水头部到集水间的长度为45m,集水间到一级泵房12.5m,一级泵房到水厂内处理构筑物—预处理的长度为12.5m 。
2.2.7集水间集水间的平面尺寸为2.8×3.6㎡,吸水间中最高水面标高为53.7-0.5=53.2m,最低水面标高为53.4-0.5m.=52.9 m 。
图2.5集水间平面图2.3 一级提升泵站计算2.3.1设计扬程⑴小水厂的一级泵站考虑一半或两班制运转。
按最高日的平均时流量计算。
Q=220.8m s m h /06.0/33=⑵设计扬程粗估a 静扬程通过取水计算已知在最不利情况下一条自流管检修,另一条自流管通过75%的设计流量时, 从取水头部到泵房吸水间的全部水头损失为0.5m,则吸水间中最高水面标高为53.7-0.5=53.2m,最低水面标高为53.4-0.5m.=52.9 m水泵所需静扬程 洪水位时 58.75-53.2=5.55 m枯水位时58.75-52.9=5.85mb 吸水管路水头损失为0.2m,c 输水管路中的水头损失:设计输水管为钢管,两根各长为21.25m ,管径为250mm , 则水头损失为20.3h m =。