•All installations should comply with local regulations•For detectors approved to UL268refer to NFPA72for installation guidance.In such installations,it is advised that the maximum distance of Detector and Reflector from the ceiling must be 10%of the distance between floor and ceiling•For installations covering less than 18m,the Short Range Mask must be used•Position beam as high as possible,but with a minimum distance of 0.5m from Detector and Reflector to ceiling.•Mount Detector and Reflector directly opposite each other•Do NOT position Detector where personnel or objects can enter the beam path •Do NOT position 2Detectors facing each other •Detector LED indicator must face downward•Do NOT install the Detector or Reflector in environments where condensation or icing are likely tooccur18—50m =150—100m =48—18m =1Use Short RangeMaskEnsure clear line ofsight from Detector to ReflectorMount on solid surfaces (structural wall or girder)1.General Information2.Fitting the ProductClip PCB intobaseInsert DetectorcableLED indicator must face downward3.Wiring DiagramsWiring two Detectors onto two Zones:To Detector 1To Detector 2EOL EOLDET 1DET 2N/OCOMN/CN/OCOMN/CN/OCOMN/CN/OCOMN/C14V -36V DC123123123Con C Zone 1-Zone 1+Zone 2+Zone 2-Supply +Ext Reset Supply -Con A Con B see note 1see note 1ExtReset123Con D •Note 1:This component is the fire resistor.Its value is specified by the Fire Control Panel manufacturer.For U.S.installations it is typically a short circuit •ALWAYS use a separate 2-core cable for each Detector head•CAUTION:For system monitoring -Do not use looped wire under any terminals.Break wire run to provide monitoring of connections •Components not supplied:•End Of Line ('EOL')component -supplied by Fire Control Panel manufacturer •Fire Resistor•After installation,check operation of Fire and Fault connection on Fire Panel•Apply a voltage of 5V to 40V to ‘Ext Reset’contact for at least 2seconds to clear a latched fire conditionFireFaultFire Fault3.Wiring Diagrams (continued)Relay connections for wiring the two Detectors of one Controller onto one Zone:For wiring to other types of Fire Control Panel,or to wire multiple Controllers onto one Zone,refer to additional installation instructions supplied with the productEOLN/O COM N/C N/O COM N/CN/OCOMN/CN/OCOMN/C123123123Con C Zone 1-Zone 1+Con A Con B see note 1123Con D Fire Fault FireFault5seconds5secondsNOTE:One System Controller can be used to control and monitor up to two Detector heads.The ‘#’symbol in this guide is used to represent the number of the Detector currently selected (1or 2).4.Apply power•Commissioned system:•Detectors have been found but the selected Detector is not aligned:•Detector is connected butnot ‘Found’(normal on uncommissionedsystem):•Communications fault,or no Detector connected:Pressfor Pass Codescreen:•Default PassCode:1234•Change digit •Move between digits •Accept•An incorrect Pass Code will return the display to the Pass Code entry screen•Three incorrect attempts will lock access for three minutes5.Enter Pass Code to Access Engineering Menu6.Find Detectors•Press to enable ‘Found’Detectors at any point during 60s countdown•Any unused Detector channels are switched off •Press to re-scan if number is incorrect•‘Find’is automatically displayed the first time this process is run.‘Find’can also be accessed in the System Controller settings menu.Find must be performed when adding or removing a detector to an already ‘Found’system.•In‘Hi A’mode(default),during normal operation the system will take5.5mA if one Detector is connected or8mA if two Detectors are connected. During Laser targeting,Auto, Hand and Home functions,the system will take36mA.•In‘Lo A’mode(selected via the System Controller settings menu),the system will take 5.5mA or8mA in ALL modes of operation.The Detector will move more slowly during Align, Laser targeting and Home,so it is recommended to leave the system set to‘Hi A’if the current isavailable.7.Select Power Mode8.Select Detector•Select Detector to be accessed•All Detectors need to be aligned separately•Steps9to129.Select Distance between Detector and Reflector •Select8-50m(default)or100m(Set for eachDetector)SER TargetingThe system will signal Fault while in this modeThe LASER is used to align the Detector with the Reflector.It is an approximate alignment tool only.After Auto-Align the LASERwill not necessarily be pointing on the Reflector •Use to move the LASER as close to the Reflector as possible •One press of an arrow key results in one movement of the Detector head •Press or to turn off the LASER and return to the Settings menu•Refer to Additional Detector Information for troubleshooting if LASER is not visible11.‘Auto’Alignment•Select ‘Auto’to automatically align the infrared beam •Signal Strength will be shown during Alignment•If the LASER is turned on it will not necessarily be pointing on the Reflector after ‘Auto’is run -this is normal•If ‘Auto’ends with an error code ‘E-’,refer to troubleshootingHiA:2minutes LoA:25minutes•When ‘Set’is displayed press whilst the Reflector is still uncovered•When ‘S-00’is displayed,cover the Reflector with a non-reflective material and leave covered,then press•When ‘S-01’is displayed,uncover the Reflector and leave uncovered,then press •Repeat Steps 8to 12for any other Detectors found during the ‘Find’process12.‘Set’0/100(Calibrate)13.System is Aligned•Green LED on Detector will flash every 10seconds,and Signal Strength should be between 99%and 101%•Default values:35%Fire Threshold,10second delay to Fire and Fault,Non-Latching mode14.Manual Fire and Fault TestsAfter installation or cleaning,it is recommended that a manual Fire and Fault test is performed:Fire Test:Cover the Reflector slowly so that it takes longer than 5seconds to cover.The System Controller will signal Fire to the Fire Control Panel after the delay to fire has expired (10s default)Fault Test:Cover the Reflector completely within 2seconds.The System Controller will signal Fault back to the Fire Control Panel after the delay to fault has expired (10s default)Detector Fire LED Test Detector will signal Fire,System Controller will stay Normal.Press to exitwithout performing the testRelay/Controller Wiring Test System Controller signals ‘Fire’to Fire Control Panel Press or to exitIt is possible to perform a Fire Test from the System Controller,to test the wiring to the Fire Control PanelNOTE:The Remote Fire Test is acceptable for Fire Authority Acceptance and Routine Maintenance per UL268-515.Remote Fire TestThis setting is the threshold at which the Detector will detect a fire Default factorysetting=35%(Set for each Detector)16.Fire ThresholdComplies with EN54-12for sensitivity levels between 25%and 35%with a maximum delay to fire of 20seconds•Sensitivity can be adjusted in 1%steps by pressing up or down keys •Press to accept setting EN Approved Sensitivity Ranges:to move between icons in theDetector Menu,shownDelay 1(Fire)These settings are the delays that the System Controller uses before signalling a FIRE or FAULT condition respectively to the Fire Control Panel.Default factory setting=10seconds Delay 2(Fault)In Latching Mode the system will stay in Fire condition after the fire clears.In Non-Latching Mode the system will automatically return to normal condition after the fire clears(Set for each Detector)17.Fire/Fault Delaytching/Non-Latching ModeTo clear a latched fire,apply 5-40V to the External Reset terminal,enter the passcode,or power cycle for 20s(Set for each Detector)19.Cleaning the SystemThe system will automatically compensate for dust build-up by changing the Compensation Level.However,it is recommended that the Detector lenses and the Reflector are cleaned periodically with a soft lint-free cloth.If the Compensation Level for a particular Detector remains above130for several days,this indicates that cleaning should take place on that Detector.The system should be isolated from the Fire Control Panel before cleaning takes place.After cleaning,verify that the system is operating normally:If the Signal Strength is between92%and108%-leave the system to compensate back to100%(this should take no more than12hours)If the Signal Strength is above108%-reduce Compensation Level until Signal Strength is92—108%,and wait for system to compensate back to100%If the Signal Strength is below92%-perform LASER Targeting,Auto-Align,and Set.How to change Compensation Level:20.Troubleshooting21.1.Multiple Zone WiringWhen using more than one System Controller on a single zone of a conventional Fire Control Panel (FCP),it is important to choose the correct method of wiring.Incorrect wiring may result in a Controller isolating subsequent devices on that zone if it enters a Fault condition,and may prevent these subsequent devices signalling a Fire condition back to the FCP .If the FCP monitors for point detector removal,it is possible to use the following wiring diagrams which use diodes to provide zone continuity in the event of a Fault state on any Controller.Two Detectors connected to Controller:Single Detector connected to Controller on “Det 1”:Note 1–This component is the Fire Resistor.Its value is specified by the FCP manufacturer,and is not supplied with the System Controller.For U.S.installations it is typically a short circuit.Note 2–Recommended diode type:Schottky,60Volt,1Amp;must be UL listed for installations meeting NFPA72.Con C Fire Con D FaultFire Con A Fault Con BCon C Fire Con D FaultFire Con A Fault Con B1.Multiple Zone Wiring(continued)If the FCP does not monitor for detector removal,it is recommended that the following wiring diagram be used.For installations conforming to UL268and NFPA72,the following diagram MUST be used when wiring multiple Controllers onto one zone.Note1–This component is the Fire Resistor.Its value is specified by the FCP manufacturer, and is not supplied with the System Controller.For U.S.installations it is typically a short circuit.EOL–End of Line component.This is supplied with the FCP,and not supplied with the System Controller.Do NOT wire to any unused relay pairs.Con A and Con B are the relay outputs for Detector1;Con C and Con D are the relay outputs for Detector2.2.Event LoggerThe System Controller contains a logging function which will store information for the most recent 50events on each Detector.For each Fire or Fault activation,the controller will store:If there have been power-cycle events on the controller,all timing information will be lost for those events that occurred prior to the most recent of the power-cycles.To erase and restart the event logger,press and hold ‘left’and ‘right’keys together when displaying any of the event log entries.Press ‘tick’when prompted by ‘SurE’.To access the event log,press tick on the Event Logger icon when the relevant detector is highlighted:Event Number01is the most recent event 02is the event before 0103is the event before 02,and so on•The event code –This is the same as the error code (E-__)that would be displayed during the Fault,or one of the following:•99-Log erased •98-Power cycle •97-Fire Detected•96-Remote Fire Test initiated •95-AUTO initiated •94-LASER activated •93-‘Home’initiated•The elapsed time since the event occurred •The duration of the event•The signal strength when the event occurred (if applicable)•The AGC value when the event occurred (if applicable)2.Event Logger(continued)Press left to access olderevents,and right to accessnewer events.When therelevant event is selected,press down to accessfurther information about theevent.Time elapsed since eventstarted.‘—‘will be displayedif the event occurred prior tothe most recent power cycle.Duration of event.‘—‘will bedisplayed if the event is stilloccurring,or if a power cycleoccurred while the eventwas in progress,or if thereis no duration associatedwith the event type(e.g.power-on)Signal strength when theevent occurred.If the signalstrength could not be readduring the event‘—‘will bedisplayed.AGC value when the eventoccurred.If the AGC valuecould not be read during theevent‘—‘will be displayed.3.Troubleshooting-LASER not visibleIf it is not possible to see the LASER because of the installation environment(for example,if you cannot see the Reflector from the System Controller or there is high ambient light)then use‘Hand’Alignment.This option displays the signal strength value returned by the Detector, and allows the user to move the beam1.Start‘Auto’Alignment and press after two seconds to exit.(this will maximise infrared power)2.Select‘Hand’alignmente to steer the beam until the signal strength is above800.There is no auto-repeat function on any key.To move the motor in any given direction more than once, press the key multiple times4.Cover the Reflector.If the Signal Strength does not drop by more than half,the beam is not aligned to the Reflector,so repeat Step35.Perform‘Auto’alignment,followed by‘Set’4.Troubleshooting-HOMEIf it is not known where the beam is pointing,use Home Position to automatically steer the infrared beam to approximately the centre of its range of movement.•Press or to exit this function•This will take up to3minutes to complete•When complete the display will return to the Engineering Menu5.Display and Indicators -LCD Icon LayoutD e g r e e s F i r e T r a n s m S i g n a l R e c e i v S i g n a l %/VS y s t e F i r e L A S E R S e t B a r G r a p hS y s t e m L o c k e d /U n l o c k e dW a r n i n gB u s yM e t r e s6.Display and Indicators -Detector and System ControllerStatus Indicators123•PressinthismenutoenterthePassCode•PresstoputthesystemintoSleep ControllerStatusSystemControllerSoftwareVersionDetectorSoftwareVersionDetectorStatus8—5mor5—1m8.Menu Layout -Engineering Menu•T h e P a s s C o d e m u s t b e e n t e r e d t o a c c e s s t h e E n g i n e e r i n g M e n u •T h e m e n u i s n a v i g a t e d b y u s i n g k e y s t o m o v e t h e c u r s o r .•I t e m s a r e s e l e c t e d b y u s i n g •P r e s s i n g e x i t s t h i s m e n u a n d r e t u r n s t h e s y s t e m t o a ‘l o c k e d ’s t a t eS e t t i n g s E v e n t L o g F i r e T e s t D e l a y9.**Gain**1% SetDetector10.System Controller SettingsCodePower Mode•Change Pass Code Use to access each digit Use to change the digit Press to save the new Pass Code and return to the settings menu Press to cancel the change and return to the Engineering menuDetectors。

光电感烟火灾探测器安装使用说明书

光电感烟火灾探测器安装使用说明书

1、概述
JTY-GD-XY(Ⅱ)型点型光电感烟火灾探测器是依据GB4715-2005《点型感烟火灾探测器》利用红外光散射原理探测烟雾,从而预报初期火灾。

本产品因采用超薄型结构,表面安装技术,使用红外传感器,因而不含放射性,环境适应性好,不易误报,使用更加安全可靠。

2、产品特点
.二总线,可编址。

.微功耗,环境适应性好。

.通用底座,超薄造型。

.防风尘,防昆虫。

.报警确认灯:巡检时红色闪亮,报警时红色常亮,故障时灯熄灭。

3、技术指标
电源电压:DC24V
静态电流:<0.4mA。

报警电流:<2.0 mA。

外型尺寸:101.5*48(含底座)。

安装孔距:62-73 mm
全部重量:200g。

4、接线方法
5、安装调试
安装探测器底座时,应注意使报警确认灯位于房间内外便于观察的方向。

在安装接线正确无误后,方可通电加烟试验。

在足够的烟进入探测器后,一般应在
10秒内报警。

6、使用维护
探测器的应用设计(保护面积、应用场合、使用环境、安装位置、选用导线等)应符合GBJB6-88火灾报警系统设计规范。

系统正常运行后,每季度应进行现场喷烟检查,发现失灵者应及时更换。

每年清除迷宫及纱网上的灰尘一次。

线型感温探测器设计安装要求

线型感温探测器设计安装要求

线型感温探测器设计安装要求线型感温探测器具有超出其它类型探测器的独特优点,是应用于高风险易燃区和多种类型的工业、商业环境中的理想选择,特别是在具有安装困难和恶劣的条件下使用时,更能体现出传统的点式火灾探测器所不具备的优越性能。

线型感温探测器应根据设置场所的情况选择适宜的类型和安装方式,它是火灾自动报警系统有效和可靠运行的基础,因此线型感温探测器在使用时,必须有专业的设计、安装和完善的管理。

本文以下内容谨做参考。

1.1在设计前应做以下准备工作(1)环境温度的变化范围线型感温探测器具有多种温度等级,以适应正常的或周围环境产生的温度差。

选择合适的温度等级的探测器可以有效的、准确的探测火灾。

(2)线型感温探测器的探测分区和使用长度设定探测器防火分区的目的是为了迅速而准确的探测出被保护区域内发生火灾的部位,如果线型感温探测器的敷设跨越了探测分区,就无法准确的区分报警位置,甚至当一个分区的线型感温探测器出现了故障,会导致其它区域的火灾报警系统无法工作,降低了火灾报警系统的可靠性。

尤其是对于设有自动灭火系统的情况,更加要求准确报出发生火灾的部位,以便启动灭火系统进行火灾扑灭。

这就要求线型感温火灾探测器的一个回路不应跨越2个及以上的探测分区。

探测分区的长度可根据探测区域的重要程度、复杂程度、敷设电缆的特性确定,一般在70m~100m之间设定。

线型感温探测器的每个探测回路长度不宜大于120m。

1.2关于探测器的安装间距和保护范围线型感温探测器敷设区域火灾发生的过程,一般是温度升高→蓄热(受热)→产生可燃气体→产生烟雾→产生明火的过程,火灾早期探测的关键在于温度升高的阶段。

一般线型感温探测器在2m范围内可以对火灾的温度变化快速反应,即线型感温探测器的保护宽度为电缆周围±2m,如超出此范围,线型感温探测器对火灾温度的反应相对变慢,因此设计时应考虑线型感温探测器的保护范围。

另外,如果感温电缆的安装间距过大,也不能快速有效的探测中间区域,因此建议两根感温电缆之间的安装间距不应超过5m,如增大感温电缆的安装间距,必须充分考虑由此带来的不安全因素。

线型感温探测器设计安装要求

线型感温探测器设计安装要求

精心整理线型感温探测器设计安装要求线型感温探测器具有超出其它类型探测器的独特优点,是应用于高风险易燃区和多种类型的工业、商业环境中的理想选择,特别是在具有安装困难和恶劣的条件下使用时,更能体现出传统的点式火灾探测器所不具备的优越性能。

线型感温探测器应根据设置场所的情况选择适宜的类型和安装方式,它是火灾自动报警系统有效和可靠运行的基础,因此线型感温探测器在使用时,必须有专业的设计、安装和完善的管理。

本文以下内容谨做参考。

1.1(1(21.2另外,如果感温电缆的安装间距过大,也不能快速有效的探测中间区域,因此建议两根感温电缆之间的安装间距不应超过5m ,如增大感温电缆的安装间距,必须充分考虑由此带来的不安全因素。

1.3线型感温探测器安装的基本原则(1)线型感温探测器是一种感温火灾探测器,探测器必须以连续方式安装,不能抽头或分支,必须符合国家规范。

(2)线型感温探测器由感温电缆、微机调制器(或接线盒)、终端处理器(或终端盒)组成,三部分必须配套使用。

(3)在感温电缆与微机调制器(或接线盒)连接困难时,可以采用信号电缆进行中间连接,信号电缆的绝缘电阻应大于1500M Ω,信号电缆的内阻不大于100Ω。

当使用此种连接方式时,必须得到我们的认可,以确保使用的安全性。

1.4线型感温探测器安装的基本要求线型感温探测器是一种性能先进的火灾探测器,它所具有的功能可满足易燃区的任何防火要求。

虽然线型感温探测器有很强的抗机械损伤能力,当线型感温探测器在安装时还是应避免机械损伤,在线型感温探测器安装过程中的部分损伤很难从探测器的外表进行分辨,但运行一段时间后可能出现不正常的报故障或报警情况,因此线型感温探测器安装时必须注意:(1)避免将感温电缆上压敷重物;(2(3(4在货架中应用时,可将感温电缆安装在天花板下,沿货架过道中心线布置,也可以和喷水灭火系统管道在一起附设,同时将感温电缆固定在竖立的通风道空间。

货架内有比较危险物品时,感温电缆应安装在每一货架内,但不能影响货架的正常工作,以免存取货物破坏感温电缆。

感温电缆敷设

感温电缆敷设

感温电缆敷设JTW-LD-L805线型感温火灾探测器安装使用说明书JTW-LD-L805可恢复缆式线型定温火灾探测器L805可恢复式缆式线型定温火灾探测器是由接口盒L805AIB、终端盒L805ATB以及感温电缆三部分共同组成。

本探测器属于可恢复式线型定温报警器,有70℃、85℃、105℃三种温度规格,有金属屏蔽规格。

电缆缆线添加有防鼠咬的特殊添加剂,特别适用于电缆隧道内的动力电缆及控制电缆的火警早期预报,可在发电厂、变电站、钢厂、化工厂、古建筑物等场合使用。

产品符合GB16280-2005及1号修改单相关要求。

功能特点●感温电缆可多次重复使用;●探测精度高,一致性好;●不会因长期使用引起材料老化导致的探测精度变化;●专利探测原理,潮湿环境下使用不会出现误报警;●抗干扰能力强,可应用于强电磁干扰场所;JTW-LD-L805线型感温火灾探测器安装使用说明书●结构稳定可靠,抗拉性强,抗震动性强,防鼠咬;●感温电缆标准长度为200m,可根据实际需要进行扩展(<1000m);●感温电缆可应用于室内、室外、防爆场所;●接口盒(信号解码器)内置火警和故障继电器开关量输出;●方便连接各种工业控制系统、火灾报警系统。

典型应用场所1.发电厂及电力行业:电缆桥架、电缆隧道、电缆沟及电缆竖井2.锅炉前膛-燃烧炉保护及冷却塔3.煤粉输送机-轴承过热4.变配电室、变压器及输电设施5.控制室和计算机室——底板夹层6.轨道交通行业:地铁隧道,站点以及自动扶梯7.电缆桥架、电缆接头及电池保护8.机车车辆:挠性联轴节与排气总管9.动力装置及泵保护10.冶金及制造业:钢架、管道工程11.电缆桥架、电缆接头及变流装置12.控制室、货架仓库、物品储存库13.轧机输送设备、混合器14.军事与军工:雷达设备、通讯设备及发电机15.导弹仓库、弹药库及配件库16.石油化工:化工装置、井口保护及油气储罐浮顶17.电缆槽盒以及油槽车保护18.其它:吸尘管道、过滤器及活性炭仓19.食品行业筒仓、干燥机及冷冻设备20.食品及轻工行业输送机可恢复缆式定温火灾探测器产品优势项目可恢复缆式定温火灾探测器(感温电缆)探测温度可70℃、85℃、105℃工作原理线上敷设专利测温器件,有专利保护最小受热长1米(与国标要求一致)满足国家标GB16280-2005及1号修改单抗老化、日晒及高低温度不怕日晒、不老化,长时间使用探测温度不受环境影响。

缆式线型定温探测器

缆式线型定温探测器

JTW-LD3开关量缆式线型定温火灾探测器应用设计与安装说明书上海浦东乐韵电器配件厂一.概述JTW-LD3缆式线型定温探测器是为了满足市场需求,更进一步提高国内同类产品研制和生产的技术条件,保证在特殊环境条件下国家财产的消防安全而研制的缆式线型定温探测器,与火灾报警控制器配套,可广泛用于电站、油库、石华工厂、飞机库、冶金、矿山等等工矿企业电缆隧道、传输带、电控设备以及室内外大型易爆堆垛的火灾探测器报警。

该探测器已通过国家消防产品质量监督检测中心的检测,符和GB16280-2005《线型感温火灾探测器技术要求及实验方法》的技术要求。

二.特点JTW-LD3缆式线型火灾探测器1.由热敏缆线、接线盒、终端盒组成;2.敏感元件为一种特殊电缆,简称热敏电缆,电缆由两根包有热敏绝缘材料的弹性钢丝、普通导线、紧箍带和护套组成;3.当其保护的某一部位或某一点的温度上升到热敏电缆的额定动作温度时,两钢丝间绝缘状态产生变化,产生报警信号;4.工程成本低廉、安装方便灵活,可直接和保护物体接触,其保护距离长、范围广;5.该探测器的报警距离时间适当,动作温度稳定可靠;6.该电缆可长期在水林条件下使用,且具有较好的耐酸、耐碱、耐油和抗腐蚀性能,可应用于粉尘、油烟、腐蚀气体、电磁干扰强、风速大、空气潮湿等恶劣环境。

三.缆式线型火灾探测器产品型号分类1.探测器型号为:2.盒体型号为:四.主要技术性能指标1.J TW-LD3型缆式线型火灾探测器热敏电缆2。

JTW-LD3/J,JTW-LD3/Z型缆式线型火灾探测器接线盒与终端盒五.探测器的安装与使用5.1探测器的结构探测器包括接线盒、热敏电缆和终端盒组成。

具体结构如图1、图2所示图 1 热敏缆线结构图图2 防水型接线盒a,终端盒b端子示意图5.2应用设计说明JTW-LD3缆式线型定温探测器可根据实际工程的应用需要,与各种火灾报警控制器配套,构成各种报警应用模式。

5.2.1二芯电缆应用模式将三芯热敏电缆当作二芯热敏电缆方式使用,即只使用三芯电缆中的两根报警导线(线一、线二),回线不用。

火灾探测器的安装方法

火灾探测器的安装方法

火灾探测器的安装方法一、工艺流程根据图纸和现场确认点位T设备检查T根据设计图标注探测器地址码T探测器按地址号编码T探测器底座安装T探测器接线T探测器安装在底座上T通电运行调试二、操作工艺1、安装前应首先检查外壳是否完好无损,标识是否齐全;按照施工图标注的探测器地址号,按要求对探测器编码;使用螺钉将配套底座固定在指定的位置上,确认底座已安装牢靠;2、按产品要求进行接线,底座与导线连接必须可靠压接或焊接,探测器底座的连接导线,应留有不小于150mm的余量,且在其端部应有明显标志,探测器底座的穿线孔宜封堵;3、将探测器插入底座,按要求旋转探测器,直至探测器锁定到位;探测器报警确认灯应朝向便于人员观察的主要入方向。

4、探测器的底座应固定牢靠,其导线连接必须可靠压接或焊接,当采用焊接时,不得使用带腐蚀性的助焊剂。

5、同一工程中的导线,应根据不同用途选不同颜色加以区分,相同用途的导线颜色应一致。

电源线正极应为红色,负极应为蓝色或黑色。

6、探测器底座的穿线孔宜封堵,安装完毕后的探测器底座应采取保护措施。

7、探测器在即将调试时方可安装,在安装前应妥善保管,并应采取防尘,防潮,防腐蚀措施。

三、安装要求1、探测器至墙壁、梁边得水平距离不应小于0.5米;2、探测器周围水平距离0.5米内,不应有遮挡物;3、探测器至空调送风最近边的水平距离,不应小于1.5米;至多孔送风顶棚孔的水平距离,不应小于0.5米;4、在宽度小于3米的内走道顶棚上安装探测器时,宜居中安装。

点型感温火灾探测器的安装间距不应超过10米;点型感烟火灾探测器的安装间距,不应超过15米。

探测器至墙壁的距离,不应大于安装间距的一半;5、探测器宜水平安装,当确需倾斜安装时,倾斜角度不应大于45°。

6、线型火灾探测器和可燃气体探测器等有特殊安装要求的探测器,应符合现行有关国家标准的规定。

四、监视状态检验1、将1uA电流表工装的两组输入端子分别与稳压源的两组输出端子连接,稳压源的两组电压分别调为9V和30V。

缆式线型感温火灾探测器安装使用说明书

缆式线型感温火灾探测器安装使用说明书

一、概述缆式线型感温火灾探测器(以下简称探测器)分为可恢复式和不可恢复式,报警温度分别为定温85℃和105℃。

探测器由信号处理单元、终端处理器、线型温度传感器三部分构成。

探测器采用两总线制连接方式,可与泰和安火灾报警控制器直接连接,实现火警及故障信号上传;也可独立使用,报警时由信号线输出火警状态,报故障时由探测器信号线输出故障状态。

探测器主要应用于以下场所:✧电缆设施:电缆隧道、电缆竖井、电缆夹层,电缆桥架等。

✧电力设施:配电装置、开关设备、变压器,电抗器等。

✧皮带传输设施:运煤、运料皮带,自动化生产线等。

探测器产品分类:二、特点1.两总线:直接接入火灾报警总线,不需外接模块。

2.报警准确、不误报:智能算法,有效识别火灾。

3.总线与电缆电气隔离,减少干扰。

4.可恢复式,可重复使用,降低使用成本。

5.支持独立工作:具备火警、故障触点输出。

6.高防护,环境适应能力强。

三、技术参数1.工作电压:额定电压DC 24V (15V ~28V )2.工作电流:监视电流:1.5mA 报警电流:2mA3.报警温度:85℃:JTW-LDM-TX3LF01/85、JTW-LDM-TX3L01/85105℃:JTW-LDM-TX3LF02/105、JTW-LDM-TX3L02/1054.探测器类别:缆式、定温、探测型、可恢复式:JTW-LDM-TX3LF01/85、JTW-LDM-TX3LF02/105缆式、定温、探测型、不可恢复式:JTW-LDM-TX3L01/85、JTW-LDM-TX3L02/1055.使用长度:≤200m :6.防护等级:IP667.环境温度:JTW-LDM-TX3LF01/85编码型、可恢复式、定温85℃JTW-LDM-TX3LF02/105编码型、可恢复式、定温105℃JTW-LDM-TX3L01/85编码型、不可恢复式、定温85℃JTW-LDM-TX3L02/105编码型、不可恢复式、定温105℃-10~+50℃(JTW-LDM-TX3LF01/85,JTW-LDM-TX3L01/85)-10~+70℃(JTW-LDM-TX3LF02/105,JTW-LDM-TX3L02/105)8.状态指示:运行指示灯绿色,正常工作时闪亮,火警指示灯红色,火警时常亮,故障指示灯黄色,线型温度传感器短路、断路时常亮。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

JTW-LD-85-8687线型定温火灾探测器安装使用说明书
1.概述
JTW-LD-85-8687开关量式线型定温探测器(以下简称探测器)为开关量的感温探测器,报警温度为85℃;该探测器由传感电缆、末端盒两部分组成,该探测器满足GB16280-2005标准,可方便地与其它厂家的火灾报警控制器配套使用。

2.主要技术指标
◆环境温度:-30℃~55℃;
◆最大长期工作湿度:90%~98%,短期可达100% ;
◆工作电压:DC18-32V ;
◆末端盒防护等级IP65。

3.探测器安装
A.基本原则
◆传感电缆必须以连续的无抽头或分支的连接布线方式安装,并严
格按照国家规范要求进行,,如确需中间接头时,必须使用专用的
密封接线盒;
◆探测分区的划分依据规范进行,结合探测区域的特征和环境温
度,决定传感电缆使用长度和回路数;
◆可以方便地与其它厂家的火灾报警控制器配套使用。

B.传感电缆的报警温度等级
根据生产工艺的不同,探测器的报警阀值可以在工厂调定,对于特定的区域选择合适的报警阀值主要取决于以下几个因素:
◆根据防护区域可燃物的燃烧特性,确定和选择报警的温度等级;
◆确定传感电缆使用环境的最高环境温度,以确定不动作温度。

C.传感电缆的布设位置
传感电缆的布设原则上应尽可能靠近防护对象,对于要求探测器在火灾发生以前或产生的热导致设备失灵之前,就能够检测出其温度逐步上升或过热的现象,则更应该采用直接接触式布设。

4.系统接线方式
与报警控制器相接时,接至其输入模块的监视端,接线示意图如下(终端电阻视不同厂家的要求而定);
通用接线方式图。