火灾报警系统安装施工方案

火灾报警系统安装施工方案
火灾报警系统安装施工方案

拜耳异氰酸酯和聚醚项目TDI联合装置-基础设施BAYER ISOCYANATE & PET PROJECT TDI TRAIN – INFRASTRUCTURE

火灾报警系统和广播呼叫系统施工方案Work Method of Fire Alarm System

And Public Address System

编制:Compiled by:

审核:Reviewed by:

目录

CONTENT

1.工程概况GENERAL STATEMENT (1)

2.编制依据COMPOSE BASIS (4)

3.施工方法MAIN METHOD (4)

4施工方法、技术措施CONSTRUCTION PLAN AND TECHNICAL MEASURE (6)

5.质量保证措施、质量通病及治理QUALITY ASSURANCE MEASURES (8)

6.主要施工机具一览表MAIN TOOLS (9)

7.劳动力计划MANPOWER PLAN (9)

8.安全技术措施及HSE管理SAFETY MEASURE (9)

1.工程概况:General Statement

1.1火灾报警和广播呼叫系统包含C581PCS楼、B551楼建筑物和C593柴油发电机部分,B301新增35/10KV变压器室部分以及该区域的水喷雾系统监控。The fire alarm system and public address system

include PCS Building C581, B551 Buildings and Diesel Generator C593. B301 New 35/10KV transformer room and its water spray monitoring system are also included.

1.2 C581&C593火灾报警系统为拜耳TDI联合装置的一个子系统火警系统。C581&C593火警系统设备接入变电所C581楼主接线盘P691SS02。B551火灾报警和广播呼叫系统工程为拜耳TDI联合装置的一个子系统。B551火警系统设备接入变电所B551楼主接线盘P661SS02。Fire alarm system of

C581&C593 is a sub-project of BAYER ISOCY ANA TE & PET PROJECT TDI TRAIN. The fire alarm system of C581 &C593 is to be connected to PJB P691SS02 of C 581 substation. Fire alarm & Public system of B551 is a sub-project of BAYER ISOCY ANA TE & PET PROJECT TDI TRAIN. The fire alarm system of B551 is to be connected to PJB P691SS02 of C 551 substation

1.3 C581、B551建筑物内全部采用智能型火灾报警控制设备,包括烟感探测器,手动报警按钮,信号模块和控制模块等。C593柴油发电机采用温感探测器和手动报警按钮保护。The system for C581&B551 adopts intelligent devices including smoke detectors, manual call points, input signal modules and output control modules etc. Diesel Generator C593 is protected by heat detectors& manual call points.

1.4 B301新增火警系统设备接入新增现场接线箱E421SF01VK303,通过信号和电源总线接入B301

变电所原有现场接线箱E421SF01VK301。新增火警设备包括烟感探测器、手动报警按钮、感温电缆、信号模块、控制模块和地址模块等。

New 301 fire alarm system equipment is to be connected to new on-site wiring boxes E421SF01VK303 and to the existing on-site substation B301 junction box E421SF01VK301 through the signal and power bus. New fire equipments include smoke detectors, manual call points, temperature cables, input signal modules and output control modules module addresses etc.

1.5火灾报警系统联动设备的控制输出采用24V直流电源信号或干接点信号,最大接点容量为30V/1A,反馈输入采用干接点信号。火灾报警控制器由UPS消防电源专用回路直接供电。在失电情况下,控制器内置电源将能维持8小时操作。所有火灾报警控制盘、柜应可靠接地,接地电阻小于1Ω。Fire Alarm System linkage devices adopt 24V DC power control output signal or dry contact signals. The maximum contact capacity 30V/1A and feedback input adopts dry contact signal. Primary power supply of fire alarm control panel requires UPS power. FACP shall be equipped with a standby battery, rated to maintain operation for 8 hours after main power supply failure. All the panels and boxes shall be well earthed; the resistance shall be less than 1Ω.

1.6 C581&C593广播喇叭接入广播呼叫分线箱P691WL04,占用一路广播回路线。B551广播喇叭接入广播呼叫分线箱P661WL03,占用一路广播回路线。各楼层广播喇叭连接至垂直IT桥架旁的接线盒。广播系统功率放大器至广播喇叭采用恒压100V输出馈线方式。在屋顶安装无线对讲天线并固定于围栏上,通过同轴电缆接入广播系统盘中的无线对讲基站。在每套柴油发电机房内设1个频闪灯,在消防报警时点亮。The public address systems of C581& C593 building will be connected to junction box

P691WL04 and occupy one speaker loop. The public address systems of B551 building will be connected to junction box P691WL03 and occupy one speaker loop. Speakers on the same floor shall be connected in field junction box beside the vertical IT cable tray. The output of digital amplifier to speakers will be constant voltage 100V. Radio antenna shall be clamped on the hand rail on the edge of top PCS building. It will be connected to the radio base station which is located in PA central panel via coaxial cable. A set of beacon shall be set up for each generator room to alarm in case of fire.

2.编制依据compose basis

2. 1施工图Drawings

CAO-SCH-C581-0-EFIRE-001_L1,CAO-SCH-C581-0-EPASP-001_L1,

CAO-LAY-C581-1-EFIRE-001_L1,CAO-LAY-C581-2-EFIRE-001_L1,

CAO-LAY-C581-3-EFIRE-001_L1,CAO-LAY-C581-M-EFIRE-001_L1,

CAO-LAY-C581-M-EFIRE-002_L1,CAO-LAY-C593-1-EFIRE-001_L1,

CAO-LAY-C593-1-EPASP-001_L1,CAO-SCH-B551-0-EFIRE-001_L1,

CAO-SCH-B551-0-EPASP-001_L1,CAO-LAY-B551-1-EFIRE-001_L1,

CAO-LAY-B551-2-EFIRE-001_L1,CAO-LAY-B551-3-EFIRE-001_L1,

CAO-LAY-B551-4-EFIRE-001_L1,CAO-LAY-B551-4-EFIRE-001_L1,

CAO-LAY-B301_MV-1-EFIRE-001-35_10kV_L1,CAO-LAY-C403-1-EFIRE-001_L1

2.1.2火灾报警和广播呼叫系统安装应遵照图纸设计和施工规范要求,根据现场实际情况施工。

The installation of the fire alarm system and public address system shall conform to the requirements of drawing design and construction spec, as well as the reality.

3.施工方法Main method

3.1设计图规定的位置和标高要与工程实际情况核对,MEP各专业之间必须协调,避免发生矛盾。Check location and elevation between design and actual situation. Various professions of MEP must be coordinated to avoid conflicts.

3.2各区域终端器、模块接线箱接线盒及接线箱的安装,其箱体固定牢固,标高统一,进出电缆及电线接口合理顺直。进入箱体内电缆及电线应用扎带固定并及时做好安装记录备查。箱体安装水平偏差不大于5mm,垂直高度偏差不大于1.5mm。The installation of regional terminal device and the module junction boxes shall be firmly fixed, the elevation shall be uniform, and cables and wires interface shall be neat. Cables and wires into the cabinets shall be fixed with straps and be recorded timely. Cabinet installation level deviation is less than 5mm and vertical height deviation is less than 1.5mm.

3.3电气管路敷设要求Electrical pipe pulling requirements

火灾报警系统施工方案

施工组织设计 投标单位(盖章): 法定代表人(盖章): 编制时间:

目录 1、工程概况┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈2 2、系统介绍┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈2 3、编制依据┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈3 4、施工现场管理┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈3 5、施工人员要求┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈4 6、进度控制┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈4 7、施工工序┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈4 8、质量保证措施┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈18 9、危险源、危险点分析及预防┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈19 10、施工现场文明施工环保的要求┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈┈20 1、工程概况:

本工程名称: 地点: 2系统介绍: 本消防系统包含了火灾自动报警系统、漏电保护系统、消防广播系统、消防、组成; 2.1、火灾自动报警系统由电感烟探测器、手动报警按钮、各类模块、分机、插孔、扬声器、消火栓按钮、可燃气体探测器、模块箱等设备;本系统设消防控制室。室集中设置自动报警监控、消防及紧急广播设备,消防控制室设置一台火灾报警控制器,其消防及紧急广播系统接入消防控制室消防及紧急广播系统。消火栓启泵线引至一期消防水泵房启动水泵。火灾自动报警系统采用总线制控制中心报警系统,外部设备的全部报警信号送至报警控制器上,经分析判断及确认后,自动或手动发出经编码的联动信号,通过总线及模块启停相应的消防联动设备,同事接收状态反馈信号;系统供电采用220VAC消防电源,及在线式不间断电源供电,由业主提供; 2.2、消防广播系统在消防控制室设置消防广播机柜,在所有防火分区设置消防广播扬声器。在火灾时,可以手动或按程序自动启动消防广播系统; 2.3、消防在手动报警按钮上设有插孔,可直接与消防中心通话,配电室设有专用火警分机; 2.4、消火栓系统在各层消火栓箱设消火栓破碎玻璃按钮,当任一层发生火灾时有人破碎玻璃后,可直接启动消防按纽,并向消防控制中心发出信号;确认火灾后由主机启动消防水泵。 3、编制依据: 3.1、依据:《火灾自动报警系统设计规》GB50116-98 《自动喷水灭火系统施工及验收规》GB50261-2005 《气体灭火系统施工及验收规》GB50166-2007 3.2、依据有关的国家及部颁施工标准及验收技术规 4、施工现场管理组 临建:现场库房及现场加工车间的确定:根据现场的实际情况,经甲方指定我单位的临时

火灾报警系统安装施工工艺标准

火灾报警系统安装施工工艺 1 施工准备 2 引用标准 GB50339-2003《智能建筑工程质量验收规范》 GB50166-2007《火灾自动报警系统施工及验收规范》 3 材料设备要求 3.1 钢管、接线盒、桥架、控制及通讯线缆的规格型号、材质及阻燃、耐火特性符合设计要求,通过消防产品专业认证,材质检测报告、合格证等齐全。 3.2 火灾探测器:感烟、感温探测器、可燃气体探测器、红外光束探测器、缆式探测器等应有3C认证、型式认可证书、产品质量正面书等。 3.3 手报、消防电话、模块箱。 3.4 控制台、消防报警主机、计算机、不间断电源、打印机等。 4 主要机具 4.1 施工机具:电钻、砂轮、电焊机、电锤。 4.2 测量器具:水平尺、钢卷尺、钢直尺、万用表、摇表、对线器。 4.3 调试仪器:专用消防报警系统综合调试仪器。 5 作业条件 5.1 预埋管路、接线盒、地面线槽及预留孔洞符合设计要求。 5.2 主机房内土建、装饰作业完工,抗静电地板安装完毕,温、湿度达到使用要求。 5.3 机房内接地端子箱安装完毕。 6 安装工艺 6.1工艺流程: 6.2 钢管、金属线槽及线缆敷设 钢管、金属线槽及线缆敷设请参照进行,火灾自动报警系统中钢管和金属线槽敷设及穿线的还应满足下列要求: 6.2.1 火灾自动报警系统线缆敷设等应根据《智能建筑工程质量验收规范》的规定,对线缆的种类、电压等级进行检查。 6.2.2 对每回路的导线用500V 的兆欧表测量绝缘电阻,其对地绝缘电阻值不应小于20M Ω。 6.2.3 不同类型、不同系统、不同电压等级的消防报警线路不应穿入同一根管内或线槽的同

一槽孔内。 6.2.4 埋入非燃烧体的建筑物、构筑物内的电线保护管与建筑物、构筑物墙面的距离不应小于30mm。 6.2.5 如因条件限制,强电和弱电线路同用一竖井时,应分别布置在竖井的两侧。 6.2.6 在建筑物的吊顶内必须采用金属管、金属线槽。金属线槽和钢管明配时,应按设计要求采取防火保护措施。 6.2.7 暗装消火栓配管时应从侧面进线,接线盒不应放在消火栓箱的后侧。 6.2.8 管线与线槽的的接地应符合设计要求和有关规范的规定。 6.2.9 火灾自动报警系统的传输线路应采用铜芯绝缘线或铜芯电缆,阻燃耐火性能符合设计要求,其电压等级不应低于交流250V。 6.2.10 火灾报警器的传输线路应选择不同颜色的绝缘导线,探测器的“+”线为红色,“-”线应为蓝色,其余线应根据不同用途采用其它颜色区分。但同一工程中相同用途的导线颜色应一致,接线端子应有标号。 6.3 火灾探测器安装要求 6.3.1 火灾探测器安装应符合图纸设计要求。 6.3.2 探测器宜水平安装,当必须倾斜安装时,倾斜角不应大于45°。 6.3.3 探测器的底座应固定可靠。 6.3.4 探测器的连接导线必须可靠压接或焊接,当采用焊接时不得使用带腐蚀性的助焊剂,外接导线应有0.15m 的余量,入端处应有明显标志。 6.3.5 探测器确认灯应面向便于人员观察的主要入口方向。 6.3.6 探测器底座的穿线孔宜封堵,安装时应采取保护措施(如装上防护罩)。 6.3.7 在电梯井、升降机井设置探测器时其位置宜在井道上方的机房顶棚上。 6.3.8 探测器至墙壁、梁边的水平距离,不应小于0.5m探测器周围0.5m 内,不应有遮挡物。 6.3.9 探测器至空调送风口边的水平距离不应小于1.5m;至多孔送风顶棚孔口的水平距离不应小于0.5m。 6.3.10 在宽度小于3m 的内走道顶棚上设置探测器时,宜居中布置。感温探测器的安装间距不应超过10m;感烟探测器的安装间距不应超过15m。探测器距端墙的距离不应大于探测器安装间距的一半。 6.3.11 可燃气体探测器的安装位置和安装高度应依据所探测气体的性质而定: a 当探测的可燃气体比空气重时,探测器安装在下部。可燃气体探测器应安装在距煤气灶4m 以内,距离地面应为0.3m。 b 当探测的可燃气体比空气轻时,探测器安装在上部。当梁高大于0.6m 时,探测器应安装在有煤气灶梁的一侧。 c 在室内梁上设置可燃气体探测器时,探测器与顶棚距离应在0.3m 以内。 6.3.12 红外光束探测器的安装应符合以下要求: a 发射器和接收器应安装在一条直线上。 b 光线通路上应避免出现运动物体,不应有遮挡物。 c 相邻两组红外光束感烟探测器水平距离应不大于14m,探测器距侧墙的水平距离不应大于7m,且不应小于0.5m。 d 探测器光束距顶棚一般为0.3~0.8m,且不得大于1m。 e 探测器发出的光束应与顶棚水平,远离强磁场,避免阳光直射,底座应牢固地安装在墙上。 6.4 缆式探测器的安装应符合以下要求:

火灾自动报警系统方案设计

火灾自动报警系统方案 ●本系统采用控制中心型智能消防报警系统,具有火灾报警、联动控制等功能。系统包括以下内 容:手动报警按钮、感烟探测器、感温探测器、警铃和水流指示器等报警装置,系统同时监视 消火栓按钮、报警阀、压力开关、水流指示器及信号阀等的动作信号。 ●为了便于控制和管理,所有消防信号将显示于总控制屏上,以便一旦发生火灾时,可迅速报告 消防局。 ●消防总控制室内有以下设备:消防系统主机(工作站)、火灾视屏显示屏(LED)、火灾自动报警 系统总控制屏、消防联动控制盘、消防专用电话主机、应急电源配电盘和UPS电源、消防系统 运行记录打印机等。消防控制室可监听所有消防电源设备的状态。另外,消防总控制室内设置 一部直拨消防单位的外线电话,并同时提供与消防电话插孔匹配的手提电话。 (1)火灾报警系统保护目标 ●快速火灾探测 ●准确定位火灾地点 ●及时发出火灾报警信号 ●警示相关人员以实现: ●快速疏散建筑物内人群 ●通知相关部门采取救援措施 ●指示相关消防设备动作以实现: ●自动启动消防泵、喷淋泵等水系统灭火设备 ●联动火灾隔断手段如关闭防火卷帘门和防火阀等 ●开启排烟风机、正压风机等防排烟设备 ●开启应急广播、应急照明和疏散指示系统 (2)系统设计原则 ●系统应符合中国有关法律法规,符合消防管理条例和标准。 ●遵照安全第一、预防为主的原则,火灾自动报警系统应严格保证设备可靠性和系统可靠性,避 免误报。 ●系统应具有先进性和适用性:系统的技术性能和质量指标均达到国际先进水平,且在安装调试、 软件编程和操作使用各方面均简便易行,并适合建筑特点,达到最佳的性能价格比。 ●在系统设计时应明确与建筑设备监控系统、安防系统之间的接口界面,且系统的各项技术规范 均符合相应要求。 ●在设计火灾自动报警系统时应预留该系统与综合信息共享管理系统之间信息数据交换接口,系 统的各项技术规范均符合相应要求。 ●在系统设计时应尽量优化设备配置,考虑了整个建筑全系统的统筹配置,避免设备的重复购置 和管线的混乱局面。 在系统设计时应保留足够的冗余度:探测点与控制点的容量上及回路卡的设置上均应保留不少于20%的扩展余地。报警系统施工主要程序:

消防报警施工方案

最新资料,word文档,可以自由编辑!! 精 品 文 档 下 载 【本页是封面,下载后可以删除!】

火灾自动报警系统施工方法要求及调试 1.施工顺序 2.管路疏通 根据现场图纸及实际施工管路进行管路疏通,用钢丝绑上擦布来回拉数次,检查预埋管线通阻,将管内或槽内的积水及杂物清除干净,必要时使用压缩空气吹扫、干燥。用压缩空气时用压力约0.25Mpa的压缩空气,吹入已预埋好的钢管中,以此来除去管内残留的灰土和水分,清扫后,随即向管内吹入滑石粉,并在接线盒处将钢管端口加装护口,再进行穿线。 3.管内穿线 (1)管内穿线应在建筑物抹灰及地面工程结束后进行,用铁丝引线或利用原旧电线进行引线。 (2)穿线前应对导线的种类、电压等级及是否有断线进行检查,合格后方可使用。火灾自动报警系统的线路应采用铜芯绝缘导线或铜芯电缆。额定工作电压不超过50V时,导线的电压等级不应低于交流250V,额定工作电压超过50V时,导线的电压等级不应低于交流500V。

(3)不同用途的导线,应采用不同颜色加以区分,并作好标识,但同种用途的导线颜色应一致。 (4)导线在管内或线槽内不得有接头或扭绞,其接头在接线盒内用焊接或端子连接。在管口处应加护口,以防损伤导线。 (5)管路敷设经过建筑物的变形缝(包括沉降缝、伸缩缝、抗震缝等)时应采取补偿措施。 (6)横向敷设的报警系统传输线路如采用穿管布线时,不同防火分区的线路不宜穿入同一根管内。 (7)弱电线路的电缆竖井,与强电线路的电缆竖井分别设置。如受条件限制必须合用时,弱电与强电线路应分别布置在竖井两侧。 (8)穿管绝缘导线或电缆的总截面积,不应超过管内截面积的40%。 (9)探测器的连接导线必须可靠,用压接或焊接。当采用焊接时,不得使用带腐蚀性的助焊剂。 探测器的“+”线应为红色,“-”线应为蓝色,其余线应根据不同用途采用其它颜色区分,但同一工程中相同用途的导线颜色应一致。其余线色标参照中国建筑工业出版社出版的《建筑安装工程施工图集》第1册中“消防系统线路颜色选用表XFI-4。” (10)手动火灾报警按钮的外接导线,应留有不小于10cm的余量,且在其端部应有明显标志。 (11)引入消防报警控制器的电缆或导线,应符合下列要求: ①配线应整齐,避免交叉,并应固定牢靠; ②电缆芯线和所配导线的端部,均应标明编号,并与图纸一致,字迹清晰不易褪色; ③端子板的每个接线端,接线不得超过两根; ④电缆芯和导线,应留有不小于20cm的余量; ⑤导线应绑扎成束; ⑥导线引入线穿线后,在进线管处应封堵。 ⑦控制器的主电源引入线,应直接与消防电源连接,严禁使用电源插头。 (12)消防控制设备的外接导线,当采用金属软管作套管时,其长度不宜大于1m,并应采用管卡固定,其固定点间距不应大于0.5m。 (13)消防控制设备外接导线的端部,应有明显标志。 (14)系统接地线与保护接地线,必须分开设置,保护接地导体不得利用金属软管。 (15)配线结束后,应进行绝缘电阻检查,其对地绝缘电阻不得低于20兆欧。 (16)导线连接的接头不应增加电阻值,受力导线不应降低原机

火灾自动报警系统施工方案.doc

火灾自动报警系统施工方案 1-1 编制依据及原则 1.编制依据 1.1根据业主提供的北京市城建设计研究院的设计图纸。 1.2根据国家有关的设计施工规范和建筑质量检验评定标准: 1、《地铁设计规范》(GB50157-2003) 2、《火灾自动报警系统设计规范》(GB50116-1998) 3、《火灾自动报警系统施工及验收规范》(GB50166-2007) 4、《电气装置安装工程施工及验收规范》 5、《建筑设计防火规范》(GB50016-2006) 6、《人民防空工程设计防火规范》(GB50098-98)(2001年版) 7、《高层民用建筑设计防火规范》(GB50045-95)2005年版) 8、《点型感烟火灾探测器》(GB4715-2005) 9、《点型感温火灾探测器》(GB4716-2005) 10、《手动火灾报警按钮》(GB19880-2005) 11、《火灾报警控制器》(GB4717-2005) 12、《线型光束感烟火灾探测器》(GB14003) 13、《线型感温火灾探测器》(GB16280-2005) 14、《电气火灾监控系统》(GB14287-2005) 15、《固定灭火系统驱动、控制装置通用技术条件》(GA61-2002) 16、《消防联动控制系统》 (GB16806-2006) 17、《电子计算机机房设计规范》(GB50174-93) 18、《工业控制用软件评定准则》(GB/T13423-1992) 2.工程概况及特点 2.1工程概况 南京地铁一号线南延线工程PPP项目火灾自动报警及气体灭火控制系统,工程建设包含地下车站8座,分别为宁丹路站(含小行车辆基地区间工程)、共青团路站、花

火灾报警系统安装施工方案1

拜耳异氰酸酯和聚醚项目TDI联合装置-基础设施BAYER ISOCYANATE & PET PROJECT TDI TRAIN – INFRASTRUCTURE 火灾报警系统和广播呼叫系统施工方案Work Method of Fire Alarm System And Public Address System 编制:Compiled by: 审核:Reviewed by:

目录 CONTENT 1.工程概况GENERAL STATEMENT (2) 2.编制依据COMPOSE BASIS (4) 3.施工方法MAIN METHOD (4) 4施工方法、技术措施CONSTRUCTION PLAN AND TECHNICAL MEASURE (6) 5.质量保证措施、质量通病及治理QUALITY ASSURANCE MEASURES (8) 6.主要施工机具一览表MAIN TOOLS (9) 7.劳动力计划MANPOWER PLAN (9) 8.安全技术措施及HSE管理SAFETY MEASURE (9)

1.工程概况:General Statement 1.1火灾报警和广播呼叫系统包含C581PCS楼、B551楼建筑物和C593柴油发电机部分,B301新增35/10KV变压器室部分以及该区域的水喷雾系统监控。The fire alarm system and public address system include PCS Building C581, B551 Buildings and Diesel Generator C593. B301 New 35/10KV transformer room and its water spray monitoring system are also included. 1.2 C581&C593火灾报警系统为拜耳TDI联合装置的一个子系统火警系统。C581&C593火警系统设备接入变电所C581楼主接线盘P691SS02。B551火灾报警和广播呼叫系统工程为拜耳TDI联合装置的一个子系统。B551火警系统设备接入变电所B551楼主接线盘P661SS02。Fire alarm system of C581&C593 is a sub-project of BAYER ISOCY ANA TE & PET PROJECT TDI TRAIN. The fire alarm system of C581 &C593 is to be connected to PJB P691SS02 of C 581 substation. Fire alarm & Public system of B551 is a sub-project of BAYER ISOCY ANA TE & PET PROJECT TDI TRAIN. The fire alarm system of B551 is to be connected to PJB P691SS02 of C 551 substation 1.3 C581、B551建筑物内全部采用智能型火灾报警控制设备,包括烟感探测器,手动报警按钮,信号模块和控制模块等。C593柴油发电机采用温感探测器和手动报警按钮保护。The system for C581&B551 adopts intelligent devices including smoke detectors, manual call points, input signal modules and output control modules etc. Diesel Generator C593 is protected by heat detectors& manual call points. 1.4 B301新增火警系统设备接入新增现场接线箱E421SF01VK303,通过信号和电源总线接入B301 变电所原有现场接线箱E421SF01VK301。新增火警设备包括烟感探测器、手动报警按钮、感温电缆、信号模块、控制模块和地址模块等。 New 301 fire alarm system equipment is to be connected to new on-site wiring boxes E421SF01VK303 and to the existing on-site substation B301 junction box E421SF01VK301 through the signal and power bus. New fire equipments include smoke detectors, manual call points, temperature cables, input signal modules and output control modules module addresses etc. 1.5火灾报警系统联动设备的控制输出采用24V直流电源信号或干接点信号,最大接点容量为30V/1A,反馈输入采用干接点信号。火灾报警控制器由UPS消防电源专用回路直接供电。在失电情况下,控制器内置电源将能维持8小时操作。所有火灾报警控制盘、柜应可靠接地,接地电阻小于1Ω。Fire Alarm System linkage devices adopt 24V DC power control output signal or dry contact signals. The maximum contact capacity 30V/1A and feedback input adopts dry contact signal. Primary power supply of fire alarm control panel requires UPS power. FACP shall be equipped with a standby battery, rated to maintain operation for 8 hours after main power supply failure. All the panels and boxes shall be well earthed; the resistance shall be less than 1Ω. 1.6 C581&C593广播喇叭接入广播呼叫分线箱P691WL04,占用一路广播回路线。B551广播喇叭接入广播呼叫分线箱P661WL03,占用一路广播回路线。各楼层广播喇叭连接至垂直IT桥架旁的接线盒。广播系统功率放大器至广播喇叭采用恒压100V输出馈线方式。在屋顶安装无线对讲天线并固定于围栏上,通过同轴电缆接入广播系统盘中的无线对讲基站。在每套柴油发电机房内设1个频闪灯,在消防报警时点亮。The public address systems of C581& C593 building will be connected to junction box P691WL04 and occupy one speaker loop. The public address systems of B551 building will be connected to junction box P691WL03 and occupy one speaker loop. Speakers on the same floor shall be connected in field junction box beside the vertical IT cable tray. The output of digital amplifier to speakers will be

电气火灾监控报警系统施工方案

B3+262--DT+37段公路施工方案,施工组织设计,施工规范 电气火灾报警监控系统施工方案 1.电气火灾监控报警系统主要是由; 漏电火灾报警主机、互感器组成; 2.漏电火灾报警主机的安装: 2.1漏电火灾报警控制器主机为壁挂安装,其底边距地面高度为1.5m,正面操作距离不小于1. 2 m; 2.2引入监控器的电缆或导线,电缆芯线和所配导线的端部,均应标明编号,并与图纸一致,字迹清晰不易褪色; 2.3漏电火灾报警控制器主机安装在商场一层消防控制中心; 3.具体地说,漏电火灾报警系统的安装应注意以下问题; 3.1漏电流报警器标有电源侧和负荷侧时,应按规定安装接线,不得反接。 3.2安装漏电流断路器时,应按要求,在电弧喷出方向有足够的飞弧距离。 3.3安装时,必须严格区分N线和PE线,三级四线式或四极四线式电的N线应通过漏电火灾监控系统的电流互感探测器。通过漏电火灾监控系统的电流互感探测器的N线,不得作为PE线,不得重复接地或接设备外露可接近导体。PE线不得接入剩余电流保护装置。 3.4漏电火灾报警系统的电流互感探测器在配电柜(箱)内安装,要特别注意施工安全,要在断电情况下施工,并注意强弱电分开走线,单独敷设电流互感探测器信号线,并应使用带屏蔽的多芯控制线。特别注意防止接错线或搭线,造成强电串入火灾监控探测器中烧毁火灾监控探测器或联网的多个火灾监控探测器。 4漏电火灾报警控制器的调试; 4.1根据GB13955标准6.3.7要求,安装完成后必须要有如下的检验项目:按动探测控制器(报警器)上的测试试验按钮,使探测控制器输出脱扣电压,试验塑壳断路器脱扣是否灵敏。此项测试应逐一进行,用试验按钮连续试验3次,应正确动作,消防中心集中控制器应指示报警部位;带额定负荷电流分合3次,均可靠动作,不应有误报警现象;在消防中心集中控制器上手动对各配电箱进行断电测试,应正确无误。 青年人首先要树雄心,立大志,其次就要决心作一个有用的人才 D1

火灾报警系统升级改造施工方案

火灾报警系统升级改造工程施工方案 编制: 审核: 批准:

施工组织设计(施工方案)审查会签表

1编制依据及编制说明 (1) 2工程概况 (1) 2.1工程简介 (1) 2.2主要实物工作量 (1) 3施工组织 (1) 3.1组织机构网络图 (1) 3.2技术准备工作 (1) 3.3施工现场准备 (2) 3.4施工场外准备 (2) 4主要施工工艺 (2) 4.1火灾自动报警系统 (2) 4.11施工工序................................................................................................................................... 错误!未定义书签。 4.12准备工作 .................................................................................................................................. 错误!未定义书签。 4.13手动火灾报警按钮的安装 (3) 4.14 金属线管敷设 (3) 4.15线缆敷设 (3) 5施工质量管理 (3) 5.1质量目标 (3) 5.2质量控制体系 (4) 5.3工程质量控制措施 (5) 5.4施工过程质量控制点设置 (6) 5.5采用规范及标准一览表 (7) 5.6严格执行有关质量管理规定 (8) 5.7严格执行通病防治措施 (8) 6HSE管理和消防、保卫管理 (8) 6.1 HSE目标和指标 (8) 6.2 HSE保证体系 (8) 6.3项目施工HSE管理措施 (9) 6.4 HSE资源保证措施 (9) 6.5 HSE教育培训措施 (9) 6.6危险控制措施 (9) 6.7监督检查措施 (11) 6.8奖惩措施 (11) 6.9事故管理 (11) 6.10应急管理 (12) 6.11环境保护和废料管理 (13) 6.12健康保护措施 (14) 6.13现场施工HSE控制措施 (14) 7主要施工机具及措施用料 (16) 7.1主要施工机具及使用时间 (16) 7.2施工措施用料 (16) 8施工进度计划安排 (18) 9施工现场临时用电安排 (19) 10附表................................................................................................................................................... 错误!未定义书签。

火灾自动报警系统设计方案与对策

火灾自动报警系统案 ●本系统采用控制中心型智能消防报警系统,具有火灾报警、联动控制等功能。系统包括以下容: 手动报警按钮、感烟探测器、感温探测器、警铃和水流指示器等报警装置,系统同时监视消火 栓按钮、报警阀、压力开关、水流指示器及信号阀等的动作信号。 ●为了便于控制和管理,所有消防信号将显示于总控制屏上,以便一旦发生火灾时,可迅速报告 消防局。 ●消防总控制室有以下设备:消防系统主机(工作站)、火灾视屏显示屏(LED)、火灾自动报警系 统总控制屏、消防联动控制盘、消防专用主机、应急电源配电盘和UPS电源、消防系统运行记 录打印机等。消防控制室可监听所有消防电源设备的状态。另外,消防总控制室设置一部直拨 消防单位的外线,并同时提供与消防插匹配的手提。 (1)火灾报警系统保护目标 ●快速火灾探测 ●准确定位火灾地点 ●及时发出火灾报警信号 ●警示相关人员以实现: ●快速疏散建筑物人群 ●通知相关部门采取救援措施 ●指示相关消防设备动作以实现: ●自动启动消防泵、喷淋泵等水系统灭火设备 ●联动火灾隔断手段如关闭防火卷帘门和防火阀等 ●开启排烟风机、正压风机等防排烟设备 ●开启应急广播、应急照明和疏散指示系统 (2)系统设计原则 ●系统应符合中国有关法律法规,符合消防管理条例和标准。 ●遵照安全第一、预防为主的原则,火灾自动报警系统应格保证设备可靠性和系统可靠性,避免 误报。 ●系统应具有先进性和适用性:系统的技术性能和质量指标均达到国际先进水平,且在安装调试、 软件编程和操作使用各面均简便易行,并适合建筑特点,达到最佳的性能价格比。 ●在系统设计时应明确与建筑设备监控系统、安防系统之间的接口界面,且系统的各项技术规均 符合相应要求。 ●在设计火灾自动报警系统时应预留该系统与综合信息共享管理系统之间信息数据交换接口,系 统的各项技术规均符合相应要求。 ●在系统设计时应尽量优化设备配置,考虑了整个建筑全系统的统筹配置,避免设备的重复购置 和管线的混乱局面。 在系统设计时应保留足够的冗余度:探测点与控制点的容量上及回路卡的设置上均应保留不少于20%的扩展余地。报警系统施工主要程序:

火灾自动报警系统安装施工工艺标准

SGBZ-0705 火灾自动报警系统安装 施工工艺标准依据标准: 《建筑工程施工质量验收统一标准》GB50300-2001 《建筑电气工程施工质量验收规范》GB50303-2002 《建筑给水排水及采暖工程施工质量验收规范》 GB50242-2002 《建筑与建筑群综合布线系统工程验收规范》GB/T50312-2000 1、范围 本章适用于工业与民用建筑火灾自动报警系统安装工程。不适用于生产和贮存火药、炸药、弹药、火工品等有爆炸危险的场所设置的火灾自动报警系统安装工程。 2、施工准备 2.1接到施工任务后,首先应对图纸进行会审,同时熟悉结构图、建筑图、装修图及其它专业的有关图纸,找到影响施工的设计问题组织设计交底,解决设计施工方面存在的问题,办理好技术变更洽商,确定施工方法和配备相应的劳动力、设备、材料、机具等。同时配备配套的生活、生产临时设施。 2.2主要设备材料: 2.2.1一般火灾自动报警系统的主要设备材料选用应符合6-1“消防工程安装的通用要求”的有关内容。 2.2.2主要设备(见图2.2.2) 图2.2.2 区域火灾报警控制器;

集中报警控制设备; 消防中心控制设备; 图象显示与打印操作设备; 消防备用电源; 火灾探测器(感烟、感温、燃气等); 手动火灾报警按钮; 声光显示报警器; 各类模块(中继器); 各种联动控制及信号反馈设备; 消防通讯设备(如消防电话); 消防广播设备。 2.2.3一般常用的材料: 管材、型钢、线槽、电线、电缆、金属软管、防火涂料、异型塑料管、阻燃塑料管、接线盒、管箍、根母、护口、管卡子、焊条、氧气、乙炔、钢丝、铅丝、防锈漆、膨胀螺栓、胀塞、成套螺丝、焊油、焊锡、电池、机油、锯条、记号笔、绑带等。 2.3主要机具: 套丝机、套丝板、液压煨弯器、手动煨弯器、电焊机、气焊工具、台钻、手电钻、砂轮锯、电锤、开孔器、压线钳子、射钉枪、钢锯、手锤、活扳手、水平尺、直尺、角尺、钢卷尺线坠、电烙铁、电炉子、锡锅、扁锉、圆锉、压力案子、压力钳子、电工工具、高凳、工具袋、工具箱、万能表、兆欧表、试铃、对讲电话、步话机、试烟器、手提电吹风机等机具。 2.4劳动力配备: 根据工程工期要求,合理安排施工进度和劳动力计划,作到保工期、保质量、保安全、配备的施工员、电工、焊工等应持证上岗。 2.5编写施工方案和技术交底,组织施工人员根据工程特点进行交底和培训,使每个操作者应熟知技术、质量、安全消防的要求。 2.6应按设计要求,在施工现场配备用的规程规范、图册、工艺要求、质量记录、表格及各种有关文件。 3、操作工艺 3.1工艺流程: 钢管内导线敷设线槽配线——火灾自动报警设备安装——检调试——钢管和金属线槽安装——测验收交付使用。 3.2钢管和金属线槽安装主要要求: 3.2.1进场管材、型钢、金属线槽及其附件应有材质证明或合格证,并应检查质量、数量、 建筑设备安装分项工程施工工艺标准—智能建筑部分 规格型号是否与要求相符合,填写检查记录。钢管要求壁厚均匀,焊缝均匀,无劈裂和砂眼棱刺,无凹扁现象,镀锌层内外均匀完整无损。金属线槽及其附件,应采用经过镀锌处理的定型产品。线槽内外应光滑平整,无棱刺不应有扭曲翅边等变形现象。 3.2.2配管前应根据设计、厂家提供的各种探测器、手动报警器、广播喇叭等设备的型号、规格,选定接线盒,使盒子与所安装的设备配套。 3.2.3电线保护管遇到下列情况之一时,应在便于穿线的位置增设接线盒: 管路长度超过30m,有弯曲时; 管路长度超过20m,有一个弯曲时;

火灾自动报警系统工程施工组织方案

专业资料 自动火灾报警系统施工方案 (一)配管及管内穿线工程 1、总则认真消化、熟悉图纸,所有配管工程必须以设计图纸为 依据,严格按图施工,不得随意改变管材质、设计走向主连 接位置。如必须改变位置和走向,除在图上标示清楚外,同 时办理有关变更手续。 2、暗配管需沿最近路线敷设,尽量减少弯头数。埋入墙和地面 混凝土中的管个壁离结构表面的净距不应小于30 mm,进 入落地式电柜的管线应排列整齐,高度一致,管口应高出基 础面不小于50mm。 3、所有穿线钢管均采用冷弯法,弯曲半径暗配管不得小于其外 径的10倍,明配管不得小于管外径的6倍。管材弯曲处严 禁有折皱、凹凸、裂缝等现象,管子弯扁度不得大于管径的 10%。 4、管路长度超过一定距离时,管路中间应加装过路接线盒或把 管径放大一级: 管子长度每超过45m,无弯曲时; 管子长度每超过30m,有一个弯曲时; 管子长度每超过20m,有二个弯曲时; 管子长度每超过12m,有三个弯曲时。 5、加装接线盒的位置奕便于穿线与检修维护,不宜在潮湿有腐 蚀性介质场所加装接线盒。管子入盒时,盒外侧应套锁母,

内侧应装护口,在吊顶内敷设时,盒的内外侧均应套锁母。 6、管内或线槽的穿线,应在穿线前应将管、槽内的积水及杂物 清除干净。 7、不同系统、不同电压等级、不同电流类别的线路,不应穿在 同一管内或线槽的同一孔内。导线在管、槽内,不应有接头 或扭结。导线的接头应在接线盒内焊接或用端子连接。敷设 在地下室等潮湿或多尘场所管路的管口和管子连接处,均应 作密封处理。 (二)线槽安装 1、在吊顶内敷设的各类管路和线槽需采用单独的卡具 吊装或支持物固定,不要依附在吊顶支架上。 2、线槽的直线段应每隔1.0~1.5m设置吊顶或支点。 在下列部位也设置支、吊点:线槽接头处;距接线盒 0.2m处;线槽走向改变或转弯处。 3、吊装线槽的吊杆直径不小于6mm。 4、管线径过建筑物的变形缝(包括沉降、伸缩缝、抗 震缝)处,应采取补偿措施。导线跨越变形缝的两侧应 固定,并留有适当余量。 5、火灾自动报警系统导线敷设后,应对每路导线用 500兆欧表测量绝缘电阻,其对地绝缘电阻值不小于 20兆欧。 (三)火灾自动触发装置

火灾自动报警系统维护保养与方案

、系统维护方案 1、系统故障分析及对策 根据火灾自动报警系统的构成情况,通过对本项目的详细分析, 我方将火灾自动报警系统的故障分为四类;

2、故障处理流程 针对本项目,我方将专门委派3名具有丰富工作经验的人员负 责,以便能对系统运行过程中出现的故障进行及时处理,当遇到专职人员不能排除的故障时,我方技术服务部将尽快由总工到过现场处理。

3、维护服务计划 定期派员到现场进行系统检查并进行如下维护工作: 1)每月对贵方的消防控制室值班记录及建筑消防设施巡视检查记录作 详细分析并提出合理化建议,发现问题及时处理。 2)每月分期分批试验探测器的报警及确认灯显示。 3)每月分期分批试验火灾报警装置的声光显示功能。 4)每月分期分批对喷头进行一次外观检查,发现有不正常的喷头及 时更换;当喷头上有异物时及时清除。 5)每月分期分批用自动或手动检查大楼消防联动的控制设备和消防通 讯设备的控制和显示功能。 6)每月检查消防水泵接合器的接口及附件,保证接口完好、无渗漏、 闷盖齐全。 7)每月对灭火剂贮存容器、选择阀、液体单向阀、高压软管、集流 管、管网与喷嘴等全部系统进行外观检查。确保系统组件无碰撞变 形及其它机械性损伤,表面无锈蚀,保护涂层完好,铭牌清晰,手 动操作装置的防护罩、铅封和安全标志完整等。 8)每月分期分批试验水流指示器、压力开关等设备的报警功能、信号 显示。 9)每月对备用电源进行充放电试验,主电源和备用电源自动切换试 验。 10)每月对报警阀旁的放水试验阀进行一次供水试验,验证系统的供 水能力。 11)每季度分析各个探测器的自诊断及历史记录,对需要清洗的探测

消防自动报警系统施工方案

消防自动报警系统施工方案 一、一般情况 工程名称:宁国市商之都商业广场工程 建设地点:宁国市宁阳西路华贝 建设单位:安徽省宁国市亚云房地产开发有限公司 设计单位:北京中华建规划设计研究院有限公司 勘察单位: 宣城市建筑勘察设计研究院 监理单位:安徽天翰工程咨询有限责任公司 施工单位:歌山建设集团有限公司 二、工程概况 2.1本工程由安徽宁国亚云房地产开发有限公司开发 ,整个工程均由1#楼、2#楼及地下车库组成。其中1#楼地下一层为地下车库, 一层地下室室层高—4.5M。一~五层为商场,其中一层层高为5.10M;二~三层层高为4.80M;四~五层层高为4.50M;六~十六层为住宅楼,各层层高为 3.00M。地下一层地上十六层为框剪结构,室外地坪以上建筑总高度60.60米;其中2#楼地下一层为地下车库, 一~十八层为住宅楼。地下一层地上十八层框剪结构,室外地坪以上建筑总高度59.48米本工程规划用地总面积为11277 M2;建筑总面积为57793 M2 ,其中地上建筑面积为51799 M2 ;其中地下建筑面积为5994 M2 。建筑总面积其中住宅用房建筑面积为31085 M2;其中商业用房建筑面积为20714 M2。其中1#楼总建筑面积为37888㎡;地下室建筑面积为4280.1㎡;地上建筑面积为33608.2㎡ 2.2.本工程1、2#楼地块位于宁国市宁阳西路南侧,原华贝服饰有限公司内。 2.3.建筑首层±0.000相当于黄海高程绝对标高55.880M。 2.4.本工程为商场住宅楼, 大楼采用智能型火灾报警控制器,联动控制柜,通讯柜。联动操作包括:停止进、排风机;起动有关声光讯响器;起动有关加压风机,排风兼排烟风机;强迫电梯降止首层;控制防火卷帘下降;关闭发生火灾层及上下相邻层送风口、切断非消防电源。水流指示器,报警阀信号均到达控制室后,经确认后启动自喷泵。 2.5. 适用范围:适用于宁国市商之都商业广场消防自动报警工程 2.6. 编制依据的标准及规范 火灾自动报警系统施工及验收规范(GBJ50166) 三、施工准备 3.1 接到施工任务后,首先应对图纸进行会审,同时熟悉结构图、建筑图、装修图及其它专业的有关图纸,找到影响施工的设计问题组织设计交底,解决设计施工方面存在的问题,办理好技术变更洽商,确定施工方法和配备相应的劳动力、设备、材料、机具等。同时配备配套的生活、生产临时设施。 3.2 主要设备材料: 3.2.1 一般火灾自动报警系统的主要设备材料选用应符合6-1“消防工程安装的通用要

火灾报警施工方案

火灾自动报警系统安装 1.范围 地下二层及地上二十七层的火灾自动报警系统及联动系统、消防电话及广播系统的安装。 2.施工准备 2.1 接到施工任务后,首先应对图纸进行会审,同时熟悉结构图、建筑图、装修图及其它专业的有关图纸,找到影响施工的设计问题组织设计交底,解决设计施工方面存在的问题,办理好技术变更洽商,确定施工方法和配备相应的劳动力、设备、材料、机具等。同时配备配套的生活、生产临时设施。 2.2 主要设备材料: 2.2.1 一般火灾自动报警系统的主要设备材料选用应符合6-1“消防工程安装的通用要求”的有关内容。 2.2.2主要设备(见图6-1)

图6-1 区域火灾报警控制器; 集中报警控制设备; 消防中心控制设备; 图象显示与打印操作设备; 消防备用电源; 火灾探测器(感烟、感温、燃气等); 手动火灾报警按钮; 声光显示报警器; 各类模块(中继器); 各种联动控制及信号反馈设备; 消防通讯设备(如消防电话); 消防广播设备。 2.2.3 一般常用的材料: 管材、型钢、线槽、电线、电缆、金属软管、防火涂料、异型塑料管、阴燃塑料管、接线盒、管箍、根母、护口、管卡子、焊条、氧气、乙炔、钢丝、铅丝、防锈漆、膨胀螺栓、胀塞、成套螺丝、焊油、焊锡、电池、机油、锯条、记号笔、绑带等。 2.3 主要机具:

套丝机、套丝板、液压煨弯器、手动煨弯器、电焊机、气焊工具、台钻、手电钻、砂轮锯、电锤、开孔器、压线钳子、射钉枪、钢锯、手锤、活扳手、水平尺、直尺、角尺、钢卷尺、线坠、电烙铁、电炉子、锡锅、扁锉、圆锉、压力案子、压力钳子、电工工具、高凳、工具袋、工具箱、万能表、兆欧表、试铃、对讲电话、步话机、试烟器、手提电吹风机等机具。 2.4 劳动力配备: 根据工程工期要求,合理安排施工进度和劳动力计划,做到保工期、保质量、保安全、配备的施工员、电工、焊工等应持证上岗。 2.5 编写施工方案和技术交底,组织施工人员根据工程特点进行交底和培训,使每个操作者应熟知技术、质量、安全消防的要求。 2.6 应按设计要求,在施工现场配备使用的堆积规范、图册、工艺要求、质量、表格及各种有关文件。 3.施工工艺 3.1 工艺流程: 3.2 钢管和金属线槽安装主要要求: 3.2.1 进场管材、型钢、金属线槽及其附件应有材质证明或合格证,并应检查质量、数量、规格型号是否与要求相符合,填写检查记录。钢管要求壁厚均匀,焊缝均匀,无

火灾自动报警系统施工专项方案(2)

北京市海淀区苏家坨镇北安河 西区定向安置房项目西区17地块火灾报警及消防联动系统 施 工 方 案 北京城建天宁消防有限责任公司 2015年11月1 日

—、工程概况....................................................................... 3 ___ 二、编制依据 (3) 三、工程范围 (3) 三、施工准备 (8) 四、施工程序 (8) 五、施工管理、配合与协调措施 (8) 六、专业施工方法及技术措施 (16) 七、施工进度计戈卩及保证工期的措施 (24) 八、质量保证体系及措施 (26) 九、安全、文明施工保证措施 (29)

一、工程概况本工程为北京市海淀区苏家坨镇北安河西区定向安置房项目其中的17 地块,17 地块总用地面积44257.56 平方米,总建筑面积为188364 平方米。其中地上总建筑面积110640 平方米,地下建筑面积77724 平方米。总停车数为1299 辆(其中地上31辆,地下1268 辆)。本地块北临北安河三街,南临北安河五街,西邻北安河路,东邻北安河东一路。抗震等级为8 度,地上建筑为二类高层建筑、多层建筑,耐火等级为二级,楼座范围内地下建筑,耐火等级为一级,车库建筑耐火等级为一级。使用年限为50 年。人防等级为核6 级,平时用途为汽车库,战时用途分别为二等人员掩蔽所和人防物资库。 二、编制依据 建筑设计防火规范( GB50016-2006 ) 智能建筑设计标准( GB/T50314-2006 ) 高层民用建筑设计防火规范( 50045-95 )(2005 年版) 火灾自动报警系统设计规范( GB50016 -98 ) 火灾自动报警系统施工及验收规范( GB 50166- 2007 ) 智能建筑工程质量验收规范(GB 50339-2013) 三、工程范围 1、火灾自动报警和消防联动控制系统 1.1 火灾自动报警保护等级及系统组成: 1) 本工程采用集中报警控制系统。消防控制室设在2# 居服首层,各楼层的报警及联动等消防回路由封闭式金属防火线槽引至地库并引上至2# 居服首层消防控制室。 2) 系统构成:采用智能二总线型式,本系统由火灾探测器、带电话插孔的手动火灾报警按钮、水流指示器、火灾报警控制器、消防联动控制盘、电梯运行监控盘、火灾应急广播主机和消防通信主机、记录、显示和打印设备 、UPS 电源设备等组成。 系统应具有对自动灭火装置及相关设备等进行自动控制;控制室远程控制、现场手动控

相关文档
最新文档