毕业设计外文翻译---控制系统介绍

合集下载

毕业设计外文翻译 西门子公司的提升机控制系统的特点

毕业设计外文翻译 西门子公司的提升机控制系统的特点

英文原文SIEMENSSiemens to enhance the characteristics of control system1. the controller division of labor in differentSpecificity for the mining industry, Siemens PLC + FM458 proposed control system architecture. Logic control in part by the S7-400 PLC to implement, process control achieved in part by the FM458 controller.Siemens S7-400 PLC series of high-end production company, and its processing time, processing accuracy, fault tolerance, failure rate, expansion capability, communications capability, ease of use, etc. all have a certain superiority. PLC logic chain is mainly used to implement control and protection functions.FM458 is for certain sectors of the automation and process control requirements are relatively high situation developed under the 64-bit processors. The traditional way is PLC scan process control, cycle time, with the program scan the length and structure of the program changes. FM458 program function block is fixed scan operation, the program processing time is fixed. PLC's computing power of ordinary floating-point capability is not particularly strong, FM458 high floating point operations and procedures, fixed-time processing capability to fully meet the mining industry on the accuracy of process control and real-time requirements. FM458 mainly used to implement process control, such as location, shaft switch signal detection, stroke control, speed control, process control.Other common PLC control system to use more direct control. PLC's CPU need of a large number of operations that control the system precision, accuracy, control response on both deficiencies.2. electrical signals transmitted in different waysControl system will enhance the high-pressure tank, pressure cabinets, transformers, borehole signal, loading / unloading signal, console, electric motors, fans and other equipment for signal collection and chain of control.Siemens to all the remote signal acquisition and control were conducted using Profibus communications, placed in the remote station ET200 device. This distributed network control wiring is simple, topological expansion is convenient, reduces the field wiring, easy maintenance and low failure rate, and troubleshooting for the equipment for a lot of time and manpower. S7-400 PLC scalable Ethernet communications, scheduling and information company focused on providing a convenient centralized display.Other control systems to use more hard-line connections. Increased maintenance costs and maintenance time, extend it will increase a lot of wiring.3. position, speed, torque the three closed-loop controlSiemens control for the mining industry, the particularity and complexity, enhance the development of mine-specific process control function block, just a simple parameter setting, we can achieve a variety of conditions to enhance process control.Position control: control the process to enhance the location determines the speed, position setpoint determines the speed reference value. Through the shaft encoder position signal fed back by the actual, real-time adjustment of speed reference value, to ensure the lifts running in full accordance with the design curve. At the same time the position back based on feedback to determine when the value of parking, accurate parking.Speed control: Siemens to enhance the system to full digital control, closed-loop variable speed. As inclusion of the momentum value (acceleration derivative) control, making the speed of the corner of the smooth realization of the absolute changes, reduce wire rope and mechanical equipment on the impact and wear. Accurate detection and closed-loop speed control to achieve a speed of 0 in the case of the work of gate parking facilities, changing the traditional way by parking under the parking switch, parking brake by grinding.Torque Control: Siemens high-performance gear to ensure that the static accuracy and dynamic torque response. Torque preset function will not guarantee the winch started to fall, start smooth. Feature to ensure zero torque to maintain speed when the winch brake parking facilities will not slip down. Reduce the time of start and stop the impact and shoe machinery and equipment wear.Three closed-loop control mode enables the system to run in strict accordance with set curves, all-digital closed-loop control to stop position is accurate, do not rely on parking switch parking, reducing points of failure, high degree of automation, reducing the system is running in manual .Many other control systems used by the hardware switch to achieve speed, parking, Shi gate, control precision of the method is not high, the reliability is poor, large machinery and equipment damage.4. the three control loops: the safety circuit, electrical parking loop, closed loopThe severity level of the signal is different from the fault into three segments, clear, easy to find and eliminate the actual fault.Safety circuit: fault occurred, the elevator brake immediately implement mechanical brake, hoist can not be started until the fault is reset.Electrical stop circuits: fault occurs, the system will immediately implement electric car. After the elevator will not start until the fault is reset.Closed circuit:fault, still allow the elevator to finish this upgrade. However, after the completion of this cycle, hoist will be closed, can not start until the fault is reset.Many other control signal classification system is chaotic, to fault find and eliminate trouble.5. double-master PLC control and monitoring systemElevator control complex process, more chain between devices on the real-time and high security requirements. Siemens to enhance the safety and reliability of control system in the first place.All field devices and safety signals related respectively to the main control and monitoring system for chain compared to any found in a system fault signal immediately take appropriate measures to effectively prevent the occurrence of a single PLC system may collect the signal error, CPU error, etc. their own operations failure.Master PLC, PLC control system, process control functions in the implementation of dual-independent signal acquisition, the state judge, real-time computing, control command generator, etc., and then compared to each other the way to ensure control of each step is safe.Many other control systems for the single signal acquisition mode, to achieve some important signals can not be two-way protection. Some even single PLC control, with more than double when the PLC control can not be achieved between the double-PLC mutual monitoring, in terms of security there are some hidden dangers.6. dual detection sensor signalsSiemens digital control system to enhance the control must be accurate and reliable and accurate signal acquisition, real-time premise, high-performance S7-400 PLC and FM458 as signal acquisition, transmission, processing to provide a guarantee.Shaft encoder: Siemens Company Location (roller shaft locations), speed (at the outer edge of drum), slip rope (days Axle Division) detection were set up a dual high-precision encoder output signal respectively to the main control and monitoring system. The three encoder feedback data to compare, to ensure that every operation in accuracy of the data.Shaft Switches: Siemens sophisticated manufacturing process to improve the life of the switch shaft, image stabilization treatment reduced the malfunction. Shaft directly into the control system switch signal, the middle does not use relays, greatly reducing the hardware delay is not caused by the control accuracy. Shaft into the main control switch signal and control systems, respectively, forming a two-way protection.Many other control systems using two encoders, the lack of data between the encoder comparison. Switching signal in the low speed shaft prone to malfunction, there is no two-way protection.7. the elevator control-specific function blocks and process control proceduresControl of any system there own particularity, Siemens developed with independent intellectual property rights of private elevator control block. Position, velocity, acceleration, momentum (acceleration derivative), reptiles and other curve parameters can be set only needs to be changed, saving development time programming, labor costs, testing time. Enhance the function block to ensure optimal processing time, reduce unnecessary crawling time.Process control envelope is added to the speed, point by point speed, continuous speed, speedmonitoring; heavy promotion, heavy decentralization, enhance the overload, slippery rope, mutagenesis, speeding, over-roll and other software protection.Enhance the control of all process parameters are input parameters of function blocks the way to the future maintenance and diagnosis of the advantage.FM458's CFC (continuous function chart) programming environment to generate their own library, the library file for the compiled binary files, not to decompile, complete with independent intellectual property rights protection algorithms and procedures.Many other control systems and then manually fill in the value of the calculated curve the way, when conditions change, modify the difficulties and increase the debugging time, makes it difficult to maintain. Process control and more do not have the full protection.8. the elevator control software development SpecificSiemens in the design of electric control system, taking into account not just the starting point of electrical control, but more eyes on the electrical control from the perspective of how to extend the service life of mechanical systems devices, such as wire rope, plate-type brake brake shoes and so on.Siemens design system, it is also considering lifting height, maximum lifting speed, the maximum enhance acceleration, deceleration, under the premise remains the same, by a significant reduction in vibration of wire rope, making the whole upgrade cycle, the shortest time, thus improving the upgrade system efficiency, improve the user output in unit time.中文译文:SIEMENS西门子公司的提升机控制系统的特点1、控制器分工不同针对矿山行业的特殊性,西门子公司提出PLC+FM458构架的控制系统。

OPINIONS-ON-INTERNAL-CONTROL关于内部控制的意见大学毕业论文外文文献翻译及原文

OPINIONS-ON-INTERNAL-CONTROL关于内部控制的意见大学毕业论文外文文献翻译及原文

毕业设计(论文)外文文献翻译文献、资料中文题目:关于内部控制的意见文献、资料英文题目:OPINIONS ON INTERNAL CONTROL 文献、资料来源:文献、资料发表(出版)日期:院(部):专业:班级:姓名:学号:指导教师:翻译日期: 2017.02.14LNTU---Acc附录A关于内部控制的意见如果要证明功能扩展到包含内部控制的有效性,那么报告准则则必须制定,若干基本问题必须被解决。

随着日益频繁增长,审计员听取了他们应该发表的一个效力于客户的内部控制制度建议的意见。

这一证明功能扩展的主张者迅速指出,目前已经有了实例如独立审计师的报告公开他们的客户的内部控制制度和一些政府机构的成效,包括一些空置中的美国证券和交易委员会,都需要一个报告。

这些证实类型的反对者公布了任何关于内部控制的有效性,他们认为,目前有显着性差异监管机构的报告要求和提出意见的内部控制将会误导公众。

本文综述了目前报告的做法,考虑到理想状态相关的危害的特点,并最后提出了一些在任何给与最后判决之前必要的予以回答的问题。

现状报告虽然审计员的报告中的一些情况提及了内部控制的性质,但作出的本质陈述还有很大不同的效应。

大型银行。

关于对内部控制的观点事实上出现在一些大型银行和看法发行的年度报告中。

有时这些意见是被董事会要求的。

例如,下面的主张出现在1969年年度报告的一个大型纽约银行中,作为第3款的独立会计师的标准短形式的报告:我们的审核工作包括评价有效性,大块的内部会计控制,其中还包括内部审计。

我们认为,在于程序的影响下,再加上银行内部审计工作人员所进行的审核,这些构成一个有效的系统的内部会计控制。

意见被提供给几个其他银行,但它们基本上引用的意见是一样的。

美国证券交易委员会的规定。

美国证券交易委员会表格X-17A-5,要求独立审计师作出某些有关的内部控制陈述,并必须在每年的大多数成员国家与每一个证券经纪或注册的交易商根据1934年证券交易法第15条进行交流时。

本科毕业设计外文翻译(中文)

本科毕业设计外文翻译(中文)

本科生毕业设计(论文)外文翻译外文原文题目:Real-time interactive optical micromanipulation of a mixture of high- and low-index particles中文翻译题目:高低折射率微粒混合物的实时交互式光学微操作毕业设计(论文)题目:阵列光镊软件控制系统设计姓名:任有健学院:生命学院班级:06210501指导教师:李勤高低折射率微粒混合物的实时交互式光学微操作Peter John Rodrigo Vincent Ricardo Daria Jesper Glückstad丹麦罗斯基勒DK-4000号,Risø国家实验室光学和等离子研究系jesper.gluckstad@risoe.dkhttp://www.risoe.dk/ofd/competence/ppo.htm摘要:本文论证一种对于胶体的实时交互式光学微操作的方法,胶体中包含两种折射率的微粒,与悬浮介质(0n )相比,分别低于(0L n n <)、高于(0H n n >)悬浮介质的折射率。

球形的高低折射率微粒在横平板上被一批捕获激光束生成的约束光势能捕获,捕获激光束的横剖面可以分为“礼帽形”和“圆环形”两种光强剖面。

这种应用方法在光学捕获的空间分布和个体几何学方面提供了广泛的可重构性。

我们以实验为基础证实了同时捕获又独立操作悬浮于水(0 1.33n =)中不同尺寸的球形碳酸钠微壳( 1.2L n ≈)和聚苯乙烯微珠( 1.57H n =)的独特性质。

©2004 美国光学学会光学分类与标引体系编码:(140.7010)捕获、(170.4520)光学限制与操作和(230.6120)空间光调制器。

1 引言光带有动量和角动量。

伴随于光与物质相互作用的动量转移为我们提供了在介观量级捕获和操作微粒的方法。

过去数十年中的巨大发展已经导致了在生物和物理领域常规光学捕获的各种应用以及下一代光学微操作体系的出现[1-5]。

温度控制系统外文翻译--光刻投影镜头多闭环温度控制系统

温度控制系统外文翻译--光刻投影镜头多闭环温度控制系统

毕业设计(论文)外文资料翻译学院:机械工程学院专业:机械设计制造及其自动化姓名:学号:指导老师:附件: 1.外文资料翻译译文;2.外文原文。

附件1:外文资料翻译译文光刻投影镜头多闭环温度控制系统聂宏飞1,李晓平1,*,何艳2。

1国家重点实验室,数字制造装备与工艺,华中科技大学,武汉430074,中国大学2天华学院,上海师范大学,上海201815,中国2008年5月27日收稿; 2009年1月8日修订; 2009年1月22日定稿;2009年2月6日电子出版摘要:图像质量是光学光刻工具的最重要指标之一,尤其易受温度、振动和投影镜头(PL)污染的影响。

本地温度控制的传统方法更容易引入振动和污染,因此研发多闭环温度控制系统来控制PL内部温度,并隔离振动和污染的影响。

一个新的远程间接温度控制(RITC)方案,提出了利用冷却水循环完成对PL的间接温度控制。

嵌入温度控制单元(TCU)的加热器和冷却器用于控制冷却水的温度,并且,TCU必须远离PL,以避免震动和污染的影响。

一种包含一个内部级联控制结构(CCS)和一个外部并行串联控制结构(PCCS)的新型多闭环控制结构被用来防止大惯性,多重迟滞,和RITC系统的多重干扰。

一种非线性比例积分(PI)的算法应用,进一步提高收敛速度和控制过程的精度。

不同的控制回路和算法的对比实验被用来验证对控制性能的影响。

结果表明,精度达到0.006℃规格的多闭环温度控制系统收敛率快,鲁棒性强,自我适应能力好。

该方法已成功地应用于光学光刻工具,制作了临近尺寸(CD)100纳米的模型,其性能令人满意。

关键词:投影镜头,远程间接温度串级控制结构,并行串连控制结构,非线性比例积分(PI)的算法1简介由于集成电路缩小,更小的临界尺寸(CD)要求,生产过程的控制越来越严格。

作为最重要的制造工艺设备,先进的光学光刻工具需要更严格的微控制环境[1],如严格控制其温度、洁净度、气压、湿度等。

温度波动,特别是导致图像失真和平面图像转变,成为了光学光刻工具对图像质量影响的一个关键因素。

机器人自动寻迹控制系统-外文翻译【范本模板】

机器人自动寻迹控制系统-外文翻译【范本模板】

南京理工大学毕业设计(论文)外文资料翻译学院(系):机械工程学院专业:机械工程及其自动化姓名:陆建学号:0701500122外文出处:IEEE/IEE Electronic(用外文写)library(IEL)附件:1。

外文资料翻译译文;2.外文原文。

注:请将该封面与附件装订成册。

附件1:外文资料翻译译文导电胶粘剂机器人—一种新型,健壮,电力可控制附着技术的爬墙机器人Harsha Prahlad, Ron Pelrine,Scott Stanford,John Marlow, and Roy Kornbluh摘要本文介绍了一种新型夹紧称为兼容电胶合技术,同时也是第一次将这种技术应用于爬墙机器人.正如其名称所示电胶合是一种电气控制粘连技术,它涉及到采用电源连接到适合机器人移动的顺滑板来诱导墙体表面的静电荷。

立足于移动机人,夹紧力高(1平方厘米的夹紧表面承受0.2-1.4牛顿的力,力的具体大小取决于基板)已经在各种各样的常见的建筑基质中得到证实,无论是在粗糙还是光滑抑或是导电体还是绝缘体中都得到证实,与传统的粘合剂或干燥粘合剂不同,它可以为了符合流动性或配合清洗而被调制或关掉,该技术利用数量非常小的力量(大约20微瓦/牛顿的承受力量)并且展示了能重复地夹在有大量灰尘或其他杂物覆盖在基板的墙中的能力,通过使用这项技术,国际斯坦福研究所展示了各种各样的爬墙机器人包括跟踪和腿机器人。

I 引言最近的事件,诸如自然灾害,军事行动,或公众安全的威胁,强大的侦察机器人已经得到越来越多的重视,而能在三维空间里穿越地形复杂的城市的机器人更加受到重视。

创新地机器人具有良好的净空能力,通常使用很多模式的移动,如轮式或跟踪运动,腿运动,跳跃运动的机器人。

然而,它的攀爬或者停在垂直的表面建筑物及其他设施的能力,对其在军事用途提供了独特的应用空间.如城市侦察,传感器部署,建立城市网络节点,以及在民事搜索和救援行动.其垂直机动性和在高处栖息方面的能力也有众多的商业应用,如管道和槽罐检查或访问够不着的场合,如窗口区域清洁。

中英文文献翻译pid控制器--大学毕业设计论文

中英文文献翻译pid控制器--大学毕业设计论文

附件1:外文原文PID controllerZuo Xin and Sun Jinming(Research Institute ofAutomation, University of Petroleum,Belting 102249,China)Received April 2,2005Abstract:Performance assessment of a proportional-integral-derivative(PID)controller is condueted using the PID achievable minimum variance as abenchmark.When the process model is unknown,we carl estimate the P/D·achievable minimum variance and the corresponding parameters by routine closed-loop operation data.Simulation results show that the process output variance is reduced by retuning controller parameters.Key words:Performance assessment,PID control,minimum varianceA proportional–integral–derivative controller (PID controller) is a generic .control loop feedback mechanism widely used in industrial control systems.A PID controller attempts to correct the error between a measured process variable and a desired setpoint by calculating and then outputting a corrective action that can adjust the process accordingly.The PID controller calculation (algorithm) involves three separate parameters; the Proportional, the Integral and Derivative values. The Proportional value determines the reaction to the current error, the Integral determines the reaction based on the sum of recent errors and the Derivative determines the reaction to the rate at which the error has been changing. The weightedsum of these three actions is used to adjust the process via a control element such as the position of a control valve or the power supply of a heating element.By "tuning" the three constants in the PID controller algorithm the PID can provide control action designed for specific process requirements. The response of the controller can be described in terms of the responsiveness of the controller to an error, the degree to which the controller overshoots the setpoint and the degree of system oscillation. Note that the use of the PID algorithm for control does not guarantee optimal control of the system or systemstability.Some applications may require using only one or two modes to provide the appropriate system control. This is achieved by setting the gain of undesired control outputs to zero. A PID controller will be called a PI, PD, P or I controller in the absence of the respective control actions. PI controllers are particularly common, since derivative action is very sensitive to measurement noise, and the absence of an integral value may prevent the system from reaching its target value due to the control action.Note: Due to the diversity of the field of control theory and application, many naming conventions for the relevant variables are in common use.1.Control loop basicsA familiar example of a control loop is the action taken to keep one's shower water at the ideal temperature, which typically involves the mixing of two process streams, cold and hot water. The person feels the water to estimate its temperature. Based on this measurement they perform a control action: use the cold water tap to adjust the process. The person would repeat this input-output control loop, adjusting the hot water flow until the process temperature stabilized at the desired value.Feeling the water temperature is taking a measurement of the process value or process variable (PV). The desired temperature is called the setpoint (SP). The output from the controller and input to the process (the tap position) is called the manipulated variable (MV). The difference between the measurement and the setpoint is the error (e), too hot or too cold and by how much.As a controller, one decides roughly how much to change the tap position (MV) after one determines the temperature (PV), and therefore the error. This first estimate is the equivalent of the proportional action of a PID controller. The integral action of a PID controller can be thought of as gradually adjusting the temperature when it is almost right. Derivative action can be thought of as noticing the water temperature is getting hotter or colder, and how fast, and taking that into account when deciding how to adjust the tap.Making a change that is too large when the error is small is equivalent to a high gain controller and will lead toovershoot. If the controller were to repeatedly make changes that were too large and repeatedly overshoot the target, this control loop would be termed unstable and the output would oscillate around the setpoint in either a constant, growing, or decaying sinusoid. A human would not do this because we are adaptive controllers, learning from the process history, but PID controllers do not have the ability to learn and must be set up correctly. Selecting the correct gains for effective control is known as tuning the controller.If a controller starts from a stable state at zero error (PV = SP), then further changes by the controller will be in response to changes in other measured or unmeasured inputs to the process that impact on the process, and hence on the PV. Variables that impact on the process other than the MV are known as disturbances and generally controllers are used to reject disturbances and/or implement setpoint changes. Changes in feed water temperature constitute a disturbance to the shower process.In theory, a controller can be used to control any process which has a measurable output (PV), a known ideal value for that output (SP) and an input to the process (MV) that will affect the relevant PV. Controllers are used in industry to regulate temperature, pressure, flow rate, chemical composition, speed and practically every other variable for which a measurement exists. Automobile cruise control is an example of a process which utilizes automated control.Due to their long history, simplicity, well grounded theory and simple setup and maintenance requirements, PID controllers are the controllers of choice for many of these applications.2.PID controller theoryNote: This section describes the ideal parallel or non-interacting form of the PID controller. For other forms please see the Section "Alternative notation and PID forms".The PID control scheme is named after its three correcting terms, whose sum constitutes the manipulated variable (MV). Hence:Where Pout, Iout, and Dout are the contributions to the output from the PID controller from each of the three terms, as defined below.2.1. Proportional termThe proportional term makes a change to the output that is proportional to the current error value. The proportional response can be adjusted by multiplying the error by a constant Kp, called the proportional gain.The proportional term is given by:WherePout: Proportional outputKp: Proportional Gain, a tuning parametere: Error = SP − PVt: Time or instantaneous time (the present)Change of response for varying KpA high proportional gain results in a large change in the output for a given change in the error. If the proportional gain is too high, the system can become unstable (See the section on Loop Tuning). In contrast, a small gain results in a small output response to a large input error, and a less responsive (or sensitive) controller. If the proportional gain is too low, the control action may be too small when responding to system disturbances.In the absence of disturbances, pure proportional control will not settle at its target value, but will retain a steady state error that is a function of the proportional gain and the process gain. Despite the steady-state offset, both tuning theory and industrial practice indicate that it is the proportional term that should contribute the bulk of the output change.2.2.Integral termThe contribution from the integral term is proportional to both the magnitude of the error and the duration of the error. Summing the instantaneous error over time (integrating the error) gives the accumulated offset that should have been correctedpreviously. The accumulated error is then multiplied by the integral gain and added to the controller output. The magnitude of the contribution of the integral term to the overall control action is determined by the integral gain, Ki.The integral term is given by:Iout: Integral outputKi: Integral Gain, a tuning parametere: Error = SP − PVτ: Time in the past contributing to the integral responseThe integral term (when added to the proportional term) accelerates the movement of the process towards setpoint and eliminates the residual steady-state error that occurs with a proportional only controller. However, since the integral term is responding to accumulated errors from the past, it can cause the present value to overshoot the setpoint value (cross over the setpoint and then create a deviation in the other direction). For further notes regarding integral gain tuning and controller stability, see the section on loop tuning.2.3 Derivative termThe rate of change of the process error is calculated by determining the slope of the error over time (i.e. its first derivative with respect to time) and multiplying this rate of change by the derivative gain Kd. The magnitude of the contribution of the derivative term to the overall control action is termed the derivative gain, Kd.The derivative term is given by:Dout: Derivative outputKd: Derivative Gain, a tuning parametere: Error = SP − PVt: Time or instantaneous time (the present)The derivative term slows the rate of change of the controller output and this effect is most noticeable close to the controller setpoint. Hence, derivative control is used to reduce the magnitude of the overshoot produced by the integral component and improve the combined controller-process stability. However, differentiation of a signal amplifies noise and thus this term in the controller is highly sensitive to noise in the error term, and can cause a process to become unstable if the noise and the derivative gain are sufficiently large.2.4 SummaryThe output from the three terms, the proportional, the integral and the derivative terms are summed to calculate the output of the PID controller. Defining u(t) as the controller output, the final form of the PID algorithm is:and the tuning parameters areKp: Proportional Gain - Larger Kp typically means faster response since thelarger the error, the larger the Proportional term compensation. An excessively large proportional gain will lead to process instability and oscillation.Ki: Integral Gain - Larger Ki implies steady state errors are eliminated quicker. The trade-off is larger overshoot: any negative error integrated during transient response must be integrated away by positive error before we reach steady state.Kd: Derivative Gain - Larger Kd decreases overshoot, but slows down transient response and may lead to instability due to signal noise amplification in the differentiation of the error.3. Loop tuningIf the PID controller parameters (the gains of the proportional, integral and derivative terms) are chosen incorrectly, the controlled process input can be unstable, i.e. its output diverges, with or without oscillation, and is limited only by saturation or mechanical breakage. Tuning a control loop is the adjustment of its control parameters (gain/proportional band, integral gain/reset, derivative gain/rate) to the optimumvalues for the desired control response.The optimum behavior on a process change or setpoint change varies depending on the application. Some processes must not allow an overshoot of the process variable beyond the setpoint if, for example, this would be unsafe. Other processes must minimize the energy expended in reaching a new setpoint. Generally, stability of response (the reverse of instability) is required and the process must not oscillate for any combination of process conditions and setpoints. Some processes have a degree of non-linearity and so parameters that work well at full-load conditions don't work when the process is starting up from no-load. This section describes some traditional manual methods for loop tuning.There are several methods for tuning a PID loop. The most effective methods generally involve the development of some form of process model, then choosing P, I, and D based on the dynamic model parameters. Manual tuning methods can be relatively inefficient.The choice of method will depend largely on whether or not the loop can be taken "offline" for tuning, and the response time of the system. If the system can be taken offline, the best tuning method often involves subjecting the system to a step change in input, measuring the output as a function of time, and using this response to determine the control parameters.Choosing a Tuning MethodMethodAdvantagesDisadvantagesManual TuningNo math required. Online method.Requires experiencedpersonnel.Ziegler–NicholsProven Method. Online method.Process upset, sometrial-and-error, very aggressive tuning.Software ToolsConsistent tuning. Online or offline method. May includevalve and sensor analysis. Allow simulation before downloading.Some cost and training involved.Cohen-CoonGood process models.Some math. Offline method. Onlygood for first-order processes.3.1 Manual tuningIf the system must remain online, one tuning method is to first set the I and D values to zero. Increase the P until the output of the loop oscillates, then the P should be left set to be approximately half of that value for a "quarter amplitude decay" type response. Then increase D until any offset is correct in sufficient time for the process. However, too much D will cause instability. Finally, increase I, if required, until the loop is acceptably quick to reach its reference after a load disturbance. However, too much I will cause excessive response and overshoot. A fast PID loop tuning usually overshoots slightly to reach the setpoint more quickly; however, some systems cannot accept overshoot, in which case an "over-damped" closed-loop system is required, which will require a P setting significantly less than half that of the P setting causing oscillation.3.2Ziegler–Nichols methodAnother tuning method is formally known as the Ziegler–Nichols method, introduced by John G. Ziegler and Nathaniel B. Nichols. As in the method above, the I and D gains are first set to zero. The "P" gain is increased until it reaches the "critical gain" Kc at which the output of the loop starts to oscillate. Kc and the oscillation period Pc are used to set the gains as shown:3.3 PID tuning softwareMost modern industrial facilities no longer tune loops using the manual calculation methods shown above. Instead, PID tuning and loop optimization software are used to ensure consistent results. These software packages will gather the data, develop process models, and suggest optimal tuning. Some software packages can even develop tuning by gathering data from reference changes.Mathematical PID loop tuning induces an impulse in the system, and then uses the controlled system's frequency response to design the PID loop values. In loops with response times of several minutes, mathematical loop tuning is recommended, because trial and error can literally take days just to find a stable set of loop values.Optimal values are harder to find. Some digital loop controllers offer a self-tuning feature in which very small setpoint changes are sent to the process, allowing the controller itself to calculate optimal tuning values.Other formulas are available to tune the loop according to different performance criteria.4 Modifications to the PID algorithmThe basic PID algorithm presents some challenges in control applications that have been addressed by minor modifications to the PID form.One common problem resulting from the ideal PID implementations is integralwindup. This can be addressed by:Initializing the controller integral to a desired valueDisabling the integral function until the PV has entered the controllable region Limiting the time period over which the integral error is calculatedPreventing the integral term from accumulating above or below pre-determined boundsMany PID loops control a mechanical device (for example, a valve). Mechanical maintenance can be a major cost and wear leads to control degradation in the form of either stiction or a deadband in the mechanical response to an input signal. The rate of mechanical wear is mainly a function of how often a device is activated to make a change. Where wear is a significant concern, the PID loop may have an output deadband to reduce the frequency of activation of the output (valve). This is accomplished by modifying the controller to hold its output steady if the change would be small (within the defined deadband range). The calculated output must leave the deadband before the actual output will change.The proportional and derivative terms can produce excessive movement in the output when a system is subjected to an instantaneous "step" increase in the error, such as a large setpoint change. In the case of the derivative term, this is due to taking the derivative of the error, which is very large in the case of an instantaneous step change.5. Limitations of PID controlWhile PID controllers are applicable to many control problems, they can perform poorly in some applications.PID controllers, when used alone, can give poor performance when the PID loop gains must be reduced so that the control system does not overshoot, oscillate or "hunt" about the control setpoint value. The control system performance can be improved by combining the feedback (or closed-loop) control of a PID controller with feed-forward (or open-loop) control. Knowledge about the system (such as the desired acceleration and inertia) can be "fed forward" and combined with the PID output to improve the overall system performance. The feed-forward value alone can often provide the major portion of the controller output. The PID controller can then be used primarily to respond to whatever difference or "error" remains between the setpoint (SP) and the actual value of the process variable (PV). Since the feed-forward output is not affected by the process feedback, it can never cause the control system to oscillate, thus improving the system response and stability.For example, in most motion control systems, in order to accelerate a mechanical load under control, more force or torque is required from the prime mover, motor, or actuator. If a velocity loop PID controller is being used to control the speed of the load and command the force or torque being applied by the prime mover, then it is beneficial to take the instantaneous acceleration desired for the load, scale that value appropriately and add it to the output of the PID velocity loop controller. This means that whenever the load is being accelerated or decelerated, a proportional amount of force is commanded from the prime mover regardless of the feedback value. The PID loop in this situation uses the feedback information to effect any increase or decrease of the combined output in order to reduce the remaining difference between the process setpoint and thefeedback value. Working together, the combined open-loop feed-forward controller and closed-loop PID controller can provide a more responsive, stable and reliable control system.Another problem faced with PID controllers is that they are linear. Thus, performance of PID controllers in non-linear systems (such as HV AC systems) isvariable. Often PID controllers are enhanced through methods such as PID gain scheduling or fuzzy logic. Further practical application issues can arise from instrumentation connected to the controller. A high enough sampling rate, measurement precision, and measurement accuracy are required to achieve adequate control performance.A problem with the Derivative term is that small amounts of measurement or process noise can cause large amounts of change in the output. It is often helpful to filter the measurements with a low-pass filter in order to remove higher-frequency noise components. However, low-pass filtering and derivative control can cancel each other out, so reducing noise by instrumentation means is a much better choice. Alternatively, the differential band can be turned off in many systems with little loss of control. This is equivalent to using the PID controller as a PI controller.6. Cascade controlOne distinctive advantage of PID controllers is that two PID controllers can be used together to yield better dynamic performance. This is called cascaded PID control. In cascade control there are two PIDs arranged with one PID controlling the set point of another. A PID controller acts as outer loop controller, which controls the primary physical parameter, such as fluid level or velocity. The other controller acts as inner loop controller, which reads the output of outer loop controller as set point, usually controlling a more rapid changing parameter, flowrate or accelleration. It can be mathematically proved that the working frequency of the controller is increased and the time constant of the object is reduced by using cascaded PID controller.[vague]7. Physical implementation of PID controlIn the early history of automatic process control the PID controller was implemented as a mechanical device. These mechanical controllers used a lever, spring and a mass and were often energized by compressed air. These pneumatic controllers were once the industry standard.Electronic analog controllers can be made from a solid-state or tube amplifier, a capacitor and a resistance. Electronic analogPID control loops were often found within more complex electronic systems, for example, the head positioning of a disk drive, the power conditioning of a power supply, or even the movement-detection circuit of a modern seismometer. Nowadays, electronic controllers have largely been replaced by digital controllers implemented with microcontrollers or FPGAs.Most modern PID controllers in industry are implemented in software in programmable logic controllers (PLCs) or as a panel-mounted digital controller. Software implementations have the advantages that they are relatively cheap and are flexible with respect to the implementation of the PID algorithm.References[1]Byung,S.K.(2000)On Performance Assessment of Feedback Control Loops.Austin:The University of Texas Austin[2]Desborough,L.and Harris,T.(1992)Performance Assessment Measures for Univariate Feedback Control. The Canadian Journal of Chemical Engineering,70(12).1186-1197[3]Ender,D.B.(1993)Process Control Performance:Not as Good as You Think.Control Engineering,40(10)[4]Harris,T(1993)Pefformance Assessment Measllres for Univariate Feedforward/Feedback Control.The Canadian Journal of Chemical Engineering,71(8),1186-1197[5]Qin,S.J.(1 998)Contr01 Performance Monitoring: A Review and Assessment.Com.Chem.Eng.,(23),173.186[6]Sun,Jinming(2004)PID Performance Assessment and Parameters Tuning.Beijing:China University of Petroleum[7]Xu,Xi;Li,Tao and Bo,Xiaochen(2000)Matlab Toolbox Application--Control Engineering.Bering:Electron Industry Press附件2:外文资料翻译译文PID控制器左信孙金明(石油大学自动化研究所,北京,102249,中国)发表于2005.4.2摘要:一个比例积分微分(PID)控制器的性能评价进行使用PID实现的最小方差作为参照。

汽车电子毕设设计外文文献翻译(适用于毕业论文外文翻译+中英文对照)

汽车电子毕设设计外文文献翻译(适用于毕业论文外文翻译+中英文对照)

Ultrasonic ranging system designPublication title: Sensor Review. Bradford: 1993.Vol.ABSTRACT: Ultrasonic ranging technology has wide using worth in many fields, such as the industrial locale, vehicle navigation and sonar engineering. Now it has been used in level measurement, self-guided autonomous vehicles, fieldwork robots automotive navigation, air and underwater target detection, identification, location and so on. So there is an important practicing meaning to learn the ranging theory and ways deeply. To improve the precision of the ultrasonic ranging system in hand, satisfy the request of the engineering personnel for the ranging precision, the bound and the usage, a portable ultrasonic ranging system based on the single chip processor was developed.Keywords: Ultrasound, Ranging System, Single Chip Processor1. IntroductiveWith the development of science and technology, the improvement of people’s standard of living, speeding up the development and construction of the city. Urban drainage system have greatly developed their situation is construction improving. However, due to historical reasons many unpredictable factors in the synthesis of her time, the city drainage system. In particular drainage system often lags behind urban construction. Therefore, there are often good building excavation has been building facilities to upgrade the drainage system phenomenon. It brought to the city sewage, and it is clear to the city sewage and drainage culvert in the sewage treatment system.Co mfort is very important to people’s lives. Mobile robots designed to clear the drainage culvert and the automatic control system Free sewage culvert clear guarantee robots, the robot is designed to clear the culvert sewage to the core. Control system is the core component of the development of ultrasonic range finder. Therefore, it is very important to design a good ultrasonic range finder.2. A principle of ultrasonic distance measurementThe application of AT89C51:SCM is a major piece of computer components are integrated into the chip micro-computer. It is a multi-interface and counting on the micro-controller integration, and intelligence products are widely used in industrial automation. and MCS-51 microcontroller is a typical and representative.Microcontrollers are used in a multitude of commercial applications such as modems, motor-control systems, air conditioner control systems, automotive engine and among others. The high processing speed and enhanced peripheral set of these microcontrollers make them suitable for such high-speed event-based applications. However, these critical application domains also require that these microcontrollers are highly reliable. The high reliability and low market risks can be ensured by a robust testing process and a proper tools environment for the validation of these microcontrollers both at the component and at the system level. Intel Plaform Engineering department developed an object-oriented multi-threaded test environment for the validation of its AT89C51 automotive microcontrollers. The goals of this environment was not only to provide a robust testing environment for the AT89C51 automotive microcontrollers, but to develop an environment which can be easily extended and reused for the validation of several other future microcontrollers. The environment was developed in conjunction with Microsoft Foundation Classes(AT89C51).1.1 Features* Compatible with MCS-51 Products* 2Kbytes of Reprogrammable Flash MemoryEndurance: 1,000Write/Erase Cycles* 2.7V to 6V Operating Range* Fully Static operation: 0Hz to 24MHz* Two-level program memory lock* 128x8-bit internal RAM* 15programmable I/O lines* Two 16-bit timer/counters* Six interrupt sources*Programmable serial UART channel* Direct LED drive output* On-chip analog comparator* Low power idle and power down modes1.2 DescriptionThe AT89C2051 is a low-voltage, high-performance CMOS 8-bit microcomputer with 2Kbytes of flash programmable and erasable read only memory (PEROM). The device is manufactured using Atmel’s high density nonvolatile memory technology and is compatible with the industry standard MCS-51 instruction set and pinout. By combining a versatile 8-bit CPU with flash on a monolithic chip, the Atmel AT89C2051 is a powerful microcomputer which provides a highly flexible and cost effective solution to many embedded control applications.The AT89C2051 provides the following standard features: 2Kbytes of flash,128bytes of RAM, 15 I/O lines, two 16-bit timer/counters, a five vector two-level interrupt architecture, a full duplex serial port, a precision analog comparator, on-chip oscillator and clock circuitry. In addition, the AT89C2051 is designed with static logicfor operation down to zero frequency and supports two software selectable power saving modes. The idle mode stops the CPU while allowing the RAM, timer/counters, serial port and interrupt system to continue functioning. The power down mode saves the RAM contents but freezer the oscillator disabling all other chip functions until the next hardware reset.1.3 Pin Configuration1.4 Pin DescriptionVCC Supply voltage.GND Ground.Prot 1Prot 1 is an 8-bit bidirectional I/O port. Port pins P1.2 to P1.7 provide internal pullups. P1.0 and P1.1 require external pullups. P1.0 and P1.1 also serve as the positive input (AIN0) and the negative input (AIN1), respectively, of the on-chip precision analog comparator. The port 1 output buffers can sink 20mA and can drive LED displays directly. When 1s are written to port 1 pins, they can be used as inputs. When pins P1.2 to P1.7 are used as input and are externally pulled low, they will source current (IIL) because of the internal pullups.Port 3Port 3 pins P3.0 to P3.5, P3.7 are seven bidirectional I/O pins with internal pullups. P3.6 is hard-wired as an input to the output of the on-chip comparator and is not accessible as a general purpose I/O pin. The port 3 output buffers can sink 20mA. When 1s are written to port 3 pins they are pulled high by the internal pullups and can be used as inputs. As inputs, port 3 pins that are externally being pulled low will source current (IIL) because of the pullups.Port 3 also serves the functions of various special features of the AT89C2051 as listed below.1.5 Programming the FlashThe AT89C2051 is shipped with the 2 Kbytes of on-chip PEROM code memory array in the erased state (i.e., contents=FFH) and ready to be programmed. The code memory array is programmed one byte at a time. Once the array is programmed, to re-program any non-blank byte, the entire memory array needs to be erased electrically.Internal address counter: the AT89C2051 contains an internal PEROM address counter which is always reset to 000H on the rising edge of RST and is advanced applying a positive going pulse to pin XTAL1.Programming algorithm: to program the AT89C2051, the following sequence is recommended.1. power-up sequence:Apply power between VCC and GND pins Set RST and XTAL1 to GNDWith all other pins floating , wait for greater than 10 milliseconds2. Set pin RST to ‘H’ set pin P3.2 to ‘H’3. Apply the appropriate combination of ‘H’ or ‘L’ logic to pins P3.3, P3.4, P3.5,P3.7 to select one of the programming operations shown in the PEROM programming modes table.To program and Verify the Array:4. Apply data for code byte at location 000H to P1.0 to P1.7.5.Raise RST to 12V to enable programming.5. Pulse P3.2 once to program a byte in the PEROM array or the lock bits. The byte-write cycle is self-timed and typically takes 1.2ms.6. To verify the programmed data, lower RST from 12V to logic ‘H’ level and set pins P3.3 to P3.7 to the appropriate levels. Output data can be read at the port P1 pins.7. To program a byte at the next address location, pulse XTAL1 pin once to advance the internal address counter. Apply new data to the port P1 pins.8. Repeat steps 5 through 8, changing data and advancing the address counter for the entire 2 Kbytes array or until the end of the object file is reached.9. Power-off sequence: set XTAL1 to ‘L’ set RST to ‘L’Float all other I/O pins Turn VCC power off2.1 The principle of piezoelectric ultrasonic generatorPiezoelectric ultrasonic generator is the use of piezoelectric crystal resonators to work. Ultrasonic generator, the internal structure as shown, it has two piezoelectric chip and a resonance plate. When it’s two plus pulse signal, the frequency equal to the intrinsic piezoelectric oscillation frequency chip, the chip will happen piezoelectric resonance, and promote the development of plate vibration resonance, ultrasound is generated. Conversely, it will be for vibration suppression of piezoelectric chip, the mechanical energy is converted to electrical signals, then it becomes the ultrasonic receiver.The traditional way to determine the moment of the echo’s arrival is based on thresholding the received signal with a fixed reference. The threshold is chosen well above the noise level, whereas the moment of arrival of an echo is defined as the first moment the echo signal surpasses that threshold. The intensity of an echo reflecting from an object strongly depends on the object’s nature, size and distance from the sensor. Further, the time interval from the echo’s starting point to the moment when it surpasses the threshold changes with the intensity of the echo. As a consequence, a considerable error may occur even two echoes with different intensities arriving exactly at the same time will surpass the threshold at different moments. The stronger one will surpass the threshold earlier than the weaker, so it will be considered as belonging to a nearer object.2.2 The principle of ultrasonic distance measurementUltrasonic transmitter in a direction to launch ultrasound, in the moment to launch the beginning of time at the same time, the spread of ultrasound in the air, obstacles on his way to return immediately, the ultrasonic reflected wave received by the receiverimmediately stop the clock. Ultrasound in the air as the propagation velocity of 340m/s, according to the timer records the time t, we can calculate the distance between the launch distance barrier(s), that is: s=340t / 23. Ultrasonic Ranging System for the Second Circuit DesignSystem is characterized by single-chip microcomputer to control the use of ultrasonic transmitter and ultrasonic receiver since the launch from time to time, single-chip selection of 875, economic-to-use, and the chip has 4K of ROM, to facilitate programming.3.1 40 kHz ultrasonic pulse generated with the launchRanging system using the ultrasonic sensor of piezoelectric ceramic sensorsUCM40, its operating voltage of the pulse signal is 40kHz, which by the single-chip implementation of the following procedures to generate.puzel: mov 14h, # 12h; ultrasonic firing continued 200msHere: cpl p1.0; output 40kHz square wavenop;nop;nop;djnz 14h, here;retRanging in front of single-chip termination circuit P1.0 input port, single chip implementation of the above procedure, the P1.0 port in a 40kHz pulse output signal, after amplification transistor T, the drive to launch the first ultrasonic UCM40T, issued 40kHz ultrasonic pulse, and the continued launch of 200ms. Ranging the right and the left side of the circuit, respectively, then input port P1.1 and P1.2, the working principle and circuit in front of the same location.3.2 Reception and processing of ultrasonicUsed to receive the first launch of the first pair UCM40R, the ultrasonic pulse modulation signal into an alternating voltage, the op-amp amplification IC1A and after polarization IC1B to IC2. IC2 is locked loop with audio decoder chip LM567, internal voltage-controlled oscillator center frequency of f0=1/1.1R8C3, capacitor C4 determinetheir target bandwidth. R8-conditioning in the launch of the high jump 8 feet into a low-level, as interrupt request signals to the single-chip processing.Ranging in front of single-chip termination circuit output port INT0 interrupt the highest priority, right or left location of the output circuit with output gate IC3A access INT1 port single-chip, while single-chip P1.3 and P1.4 received input IC3A, interrupted by the process to identify the source of inquiry to deal with, interrupt priority level for the first left right after. Part of the source code is as follows:Receivel: push pswpush accclr ex1; related external interrupt 1jnb p1.1, right; P1.1 pin to 0, ranging from right to interrupt service routine circuitjnb p1.2, left; P1.2 pin to 0, to the left ranging circuit interrupt service routinereturn: SETB EX1; open external interrupt 1pop accpop pswretiright: …; right location entrance circuit interrupt service routineAjmp Returnleft: …; left ranging entrance circuit interrupt service routineAjmp Return3.3 The calculation of ultrasonic propagation timeWhen you start firing at the same time start the single-chip circuitry within the timer T0, the use of timer counting function records the time and the launch of ultrasonic reflected wave received time. When you receive the ultrasonic reflected wave, the receiver circuit output a negative jump in the end of INT0 or INT1 interrupt request generates a signal, single-chip microcomputer in response to external interrupt request, the implementation of the external interrupt service subroutine, read the time difference, calculating the distance. Some of its source code is as follows:RECEIVE0: PUSH PSWPUSH ACCCLR EX0; related external interrupt 0MOV R7, TH0; read the time valueMOV R6, TL0CLR CMOV A, R6SUBB A, #0BBH; calculate the time differenceMOV 31H, A; storage resultsMOV A, R7SUBB A, # 3CHMOV 30H, ASETB EX0; open external interrupt 0\POP ACCPOP PSWRETIFor a flat target, a distance measurement consists of two phases: a coarse measurement and a fine measurement:Step 1: Transmission of one pulse train to produce a simple ultrasonic wave.Step 2: Changing the gain of both echo amplifiers according to equation, until the echo is detected.Step 3: Detection of the amplitudes and zero-crossing times of both echoes.Step 4: Setting the gains of both echo amplifiers to normalize the output at, say 3 volts. Setting the period of the next pulses according to the: period of echoes. Setting the time window according to the data of step 2.Step 5: Sending two pulse trains to produce an interfered wave. Testing the zero-crossing times and amplitudes of the echoes. If phase inversion occurs in the echo, determine to otherwise calculate to by interpolation using the amplitudes near the trough. Derive t sub m1 and t sub m2.Step 6: Calculation of the distance y using equation.4、The ultrasonic ranging system software designSoftware is divided into two parts, the main program and interrupt service routine. Completion of the work of the main program is initialized, each sequence of ultrasonic transmitting and receiving control.Interrupt service routines from time to time to complete three of the rotation direction of ultrasonic launch, the main external interrupt service subroutine to read the value of completion time, distance calculation, the results of the output and so on.5、ConclusionsRequired measuring range of 30cm-200cm objects inside the plane to do a number of measurements found that the maximum error is 0.5cm, and good reproducibility. Single-chip design can be seen on the ultrasonic ranging system has a hardware structure is simple, reliable, small features such as measurement error. Therefore, it can be used not only for mobile robot can be used in other detection system.Thoughts: As for why the receiver do not have the transistor amplifier circuit, because the magnification well, integrated amplifier, but also with automatic gain control level, magnification to 76dB, the center frequency is 38k to 40k, is exactly resonant ultrasonic sensors frequency.6、Parking sensor6.1 Parking sensor introductionReversing radar, full name is "reversing the anti-collision radar, also known as" parking assist device, car parking or reversing the safety of assistive devices, ultrasonic sensors(commonly known as probes), controls and displays (or buzzer)and other components. To inform the driver around the obstacle to the sound or a moreintuitive display to lift the driver parking, reversing and start the vehicle around tovisit the distress caused by, and to help the driver to remove the vision deadends and blurred vision defects and improve driving safety.6.2 Reversing radar detection principleReversing radar, according to high-speed flight of the bats in thenight, not collided with any obstacle principles of design anddevelopment. Probe mounted on the rear bumper, according to different price and brand, the probe only ranging from two, three, four, six, eight,respectively, pipe around. The probe radiation, 45-degree angle up and downabout the search target. The greatest advantage is to explore lower than the bumper of the driver from the rear window is difficult to see obstacles, and the police, suchas flower beds, children playing in the squatting on the car.Display parking sensor installed in the rear view mirror, it constantlyremind drivers to car distance behindthe object distance to the dangerous distance, the buzzer starts singing, allow the driver to stop. When the gear lever linked into reverse gear, reversing radar, auto-start the work, the working range of 0.3 to 2.0 meters, so stop when the driver was very practical. Reversing radar is equivalent to an ultrasound probe for ultrasonic probe can be divided into two categories: First, Electrical, ultrasonic, the second is to use mechanical means to produce ultrasound, in view of the more commonly used piezoelectric ultrasonic generator, it has two power chips and a soundingboard, plus apulse signal when the poles, its frequency equal to the intrinsic oscillation frequency of the piezoelectric pressure chip will be resonant and drivenby the vibration of the sounding board, the mechanical energy into electrical signal, which became the ultrasonic probe works. In order to better study Ultrasonic and use up, people have to design and manufacture of ultrasonic sound, the ultrasonic probe tobe used in the use of car parking sensor. With this principle in a non-contactdetection technology for distance measurement is simple, convenient and rapid, easyto do real-time control, distance accuracy of practical industrial requirements. Parking sensor for ranging send out ultrasonic signal at a givenmoment, and shot in the face of the measured object back to the signal wave, reversing radar receiver to use statistics in the ultrasonic signal from the transmitter to receive echo signals calculate the propagation velocity in the medium, which can calculate the distance of the probe and to detect objects.6.3 Reversing radar functionality and performanceParking sensor can be divided into the LCD distance display, audible alarm, and azimuth directions, voice prompts, automatic probe detection function is complete, reversing radar distance, audible alarm, position-indicating function. A good performance reversing radar, its main properties include: (1) sensitivity, whether theresponse fast enough when there is an obstacle. (2) the existence of blind spots. (3) detection distance range.6.4 Each part of the roleReversing radar has the following effects: (1) ultrasonic sensor: used tolaunch and receive ultrasonic signals, ultrasonic sensors canmeasure distance. (2) host: after the launch of the sine wave pulse to the ultrasonic sensors, and process the received signal, to calculate the distance value, the data and monitor communication. (3) display or abuzzer: the receivinghost from the data, and display the distance value and provide differentlevels according to the distance from the alarm sound.6.5 Cautions1, the installation height: general ground: car before the installation of 45 ~55: 50 ~ 65cmcar after installation. 2, regular cleaningof the probe to prevent the fill. 3, do not use the hardstuff the probe surface cover will produce false positives or ranging allowed toprobe surface coverage, such as mud. 4, winter to avoid freezing. 5, 6 / 8 probe reversing radar before and after the probe is not free to swap may cause the ChangMing false positive problem. 6, note that the probe mounting orientation, in accordance with UP installation upward. 7, the probe is not recommended to install sheetmetal, sheet metal vibration will cause the probe resonance, resulting in false positives.超声测距系统设计原文出处:传感器文摘布拉福德:1993年超声测距技术在工业现场、车辆导航、水声工程等领域具有广泛的应用价值,目前已应用于物位测量、机器人自动导航以及空气中与水下的目标探测、识别、定位等场合。

毕业设计(论文)外文资料翻译(学生用)

毕业设计(论文)外文资料翻译(学生用)

毕业设计外文资料翻译学院:信息科学与工程学院专业:软件工程姓名: XXXXX学号: XXXXXXXXX外文出处: Think In Java (用外文写)附件: 1.外文资料翻译译文;2.外文原文。

附件1:外文资料翻译译文网络编程历史上的网络编程都倾向于困难、复杂,而且极易出错。

程序员必须掌握与网络有关的大量细节,有时甚至要对硬件有深刻的认识。

一般地,我们需要理解连网协议中不同的“层”(Layer)。

而且对于每个连网库,一般都包含了数量众多的函数,分别涉及信息块的连接、打包和拆包;这些块的来回运输;以及握手等等。

这是一项令人痛苦的工作。

但是,连网本身的概念并不是很难。

我们想获得位于其他地方某台机器上的信息,并把它们移到这儿;或者相反。

这与读写文件非常相似,只是文件存在于远程机器上,而且远程机器有权决定如何处理我们请求或者发送的数据。

Java最出色的一个地方就是它的“无痛苦连网”概念。

有关连网的基层细节已被尽可能地提取出去,并隐藏在JVM以及Java的本机安装系统里进行控制。

我们使用的编程模型是一个文件的模型;事实上,网络连接(一个“套接字”)已被封装到系统对象里,所以可象对其他数据流那样采用同样的方法调用。

除此以外,在我们处理另一个连网问题——同时控制多个网络连接——的时候,Java内建的多线程机制也是十分方便的。

本章将用一系列易懂的例子解释Java的连网支持。

15.1 机器的标识当然,为了分辨来自别处的一台机器,以及为了保证自己连接的是希望的那台机器,必须有一种机制能独一无二地标识出网络内的每台机器。

早期网络只解决了如何在本地网络环境中为机器提供唯一的名字。

但Java面向的是整个因特网,这要求用一种机制对来自世界各地的机器进行标识。

为达到这个目的,我们采用了IP(互联网地址)的概念。

IP以两种形式存在着:(1) 大家最熟悉的DNS(域名服务)形式。

我自己的域名是。

所以假定我在自己的域内有一台名为Opus的计算机,它的域名就可以是。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

英文原文Introductions to Control SystemsAutomatic control has played a vital role in the advancement of engineering and science. In addition to its extreme importance in space-vehicle, missile-guidance, and aircraft-piloting systems, etc, automatic control has become an important and integral part of modern manufacturing and industrial processes. For example, automatic control is essential in such industrial operations as controlling pressure, temperature, humidity, viscosity, and flow in the process industries; tooling, handling, and assembling mechanical parts in the manufacturing industries, among many others.Since advances in the theory and practice of automatic control provide means for attaining optimal performance of dynamic systems, improve the quality and lower the cost of production, expand the production rate, relieve the drudgery of many routine, repetitive manual operations etc, most engineers and scientists must now have a good understanding of this field.The first significant work in automatic control was James Watt’s centrifugal governor for the speed control of a steam engine in the eighteenth century. Other significant works in the early stages of development of control theory were due to Minorsky, Hazen, and Nyquist, among many others. In 1922 Minorsky worked on automatic controllers for steering ships and showed how stability could be determined by the differential equations describing the system. In 1934 Hazen, who introduced the term “ervomechanisms”for position control systems, discussed design of relay servomechanisms capable of closely following a changing input.During the decade of the 1940’s, frequency-response methods made it possible for engineers to design linear feedback control systems that satisfied performance requirements. From the end of the 1940’s to early 1950’s, the root-locus method in control system design was fully developed.The frequency-response and the root-locus methods, which are thecore of classical theory, lead to systems that are stable and satisfy a set of more or less arbitrary performance requirements. Such systems are, in general, not optimal in any meaningful sense. Since the late 1950’s, the emphasis on control design problems has been shifted from the design of one of many systems that can work to the design of one optimal system in some meaningful sense.As modern plants with many inputs and outputs become more and more complex, the description of a modern control system requires a large number of equations. Classical control theory, which deals only with single-input-single-output systems, becomes entirely powerless for multiple-input-multiple-output systems. Since about 1960, modern control theory has been developed to cope with the increased complexity of modern plants and the stringent requirements on accuracy, weight, and industrial applications.Because of the readily available electronic analog, digital, and hybrid computers for use in complex computations, the use of computers in the design of control systems and the use of on-line computers in the operation of control systems are now becoming common practice.The most recent developments in modern control theory may be said to be in the direction of the optimal control of both deterministic and stochastic systems as well as the adaptive and learning control of complex systems. Applications of modern control theory to such nonengineering fields as biology, economics, medicine, and sociology are now under way, and interesting and significant results can be expected in the near future.Next we shall introduce the terminology necessary to describe control systems.Plants. A plant is a piece of equipment, perhaps just a set of machine parts functioning together, the purpose of which is to perform a particular operation. Here we shall call any physical object to be controlled (such as a heating furnace, a chemical reactor, or a spacecraft) a plant.Processes. The Merriam-Webster Dictionary defines a process to be a natural, progressively continuing operation or development marked by a series of gradual changes that succeed one another in a relatively fixedway and lead toward a particular result or end; or an artificial or voluntary, progressively continuing operation that consists of a series of controlled actions or movements systematically directed toward a particular result or end.Here we shall call any operation to be controlled a process. Examples are chemical, economic, and biological process.Systems. A system is a combination of components that act together and perform a certain objective. A system is not limited to abstract, dynamic phenomena such as those encountered in economics. The word “system” should, therefore, be interpreted to imply physical, biological, economic, etc., system.Disturbances. A disturbance is a signal which tends to adversely affect the value of the output of a system. If a disturbance is generated within the system, it is called internal, while an external disturbance is generated outside the system and is an input.Feedback control.Feedback control is an operation which, in the presence of disturbances, tends to reduce the difference between the output of a system and the reference input (or an arbitrarily varied, desired state) and which does so on the basis of this difference. Here, only unpredictable disturbance (i.e., those unknown beforehand) are designated for as such, since with predictable or known disturbances, it is always possible to include compensation with the system so that measurements are unnecessary.Feedback control systems. A feedback control system is one which tends to maintain a prescribed relationship between the output and the reference input by comparing these and using the difference as a means of control.Note that feedback control systems are not limited to the field of engineering but can be found in various nonengineering fields such as economics and biology. For example, the human organism, in one aspect, is analogous to an intricate chemical plant with an enormous variety of unit operations.The process control of this transport and chemical-reaction network involves a variety of control loops. In fact, human organism is an extremely complex feedback control system.Servomechanisms. A servomechanism is a feedback control systemin which the output is some mechanical position, velocity, or acceleration. Therefore, the terms servomechanism and position- (or velocity- or acceleration-) control system are synonymous. Servomechanisms are extensively used in modern industry. For example, the completely automatic operation of machine tools, together with programmed instruction, may be accomplished by use of servomechanisms.Automatic regulating systems. An automatic regulating system is a feedback control system in which the reference input or the desired output is either constant or slowly varying with time and in which the primary task is to maintain the actual output at the desired value in the presence of disturbances.A home heating system in which a thermostat is the controller is an example of an automatic regulating system. In this system, the thermostat setting (the desired temperature) is compared with the actual room temperature. A change in the desired room temperature is a disturbance in this system. The objective is to maintain the desired room temperature despite changes in outdoor temperature. There are many other examples of automatic regulating systems, some of which are the automatic control of pressure and of electric quantities such as voltage, current and frequency.Process control systems. An automatic regulating system in which the output is a variable such as temperature, pressure, flow, liquid level, or pH is called a process control system.Process control is widely applied in industry. Programmed controls such as the temperature control of heating furnaces in which the furnace temperature is controlled according to a preset program are often used in such systems. For example, a preset program may be such that the furnace temperature is raised to a given temperature in a given time interval and then lowered to another given temperature in some other given time interval. In such program control the set point is varied according to the preset time schedule. The controller then functions to maintain the furnace temperature close to the varying set point. It should be noted that most process control systems include servomechanisms as an integral part.译文:控制系统介绍自动控制在工程学和科学的推进扮演一个重要角色。

相关文档
最新文档