变频器说明书施奈德Atv71
施耐德ATV71变频器网络设置手册atv71_devicenet_manual_en_v1

User's manual Retain for future use Altivar 71DeviceNet card VW3 A3 309ContentsBefore you begin_____________________________________________________________________________________________ 3Documentation structure_______________________________________________________________________________________ 4Introduction_________________________________________________________________________________________________ 5 Presentation_____________________________________________________________________________________________ 5 Notation________________________________________________________________________________________________ 5Quick start__________________________________________________________________________________________________ 6Hardware setup_____________________________________________________________________________________________ 7 Receipt_________________________________________________________________________________________________ 7 Hardware description______________________________________________________________________________________ 7 Installing the card in the drive________________________________________________________________________________ 7 Coding the switches_______________________________________________________________________________________ 8Wiring to the network________________________________________________________________________________________ 10 Cable routing practices____________________________________________________________________________________ 10 Wiring the DeviceNet connector_____________________________________________________________________________ 10Configuring by the drive HMI__________________________________________________________________________________ 12 Configuring the control____________________________________________________________________________________ 12 Configuring the communication scanner______________________________________________________________________ 17 Configuring the fault management___________________________________________________________________________ 19 Configuring monitored parameters___________________________________________________________________________ 20Configuring by a network tool__________________________________________________________________________________ 21 Network tool____________________________________________________________________________________________ 21 Going online with RSNetWorx______________________________________________________________________________ 21 Creating an EDS file______________________________________________________________________________________ 21 Configuring the DeviceNet scanner__________________________________________________________________________ 22 Editing parameters of the drive______________________________________________________________________________ 27 Editing objects of the drive_________________________________________________________________________________ 32 Creating a PLC program______________________________________________________________________________________ 35 Using I/O messaging_____________________________________________________________________________________ 35 Using explicit messaging__________________________________________________________________________________ 35 Diagnostics by the drive HMI__________________________________________________________________________________ 36 Checking the node address and the data rate__________________________________________________________________ 36 Signalling LED__________________________________________________________________________________________ 37 Monitoring the control_____________________________________________________________________________________ 38 Monitoring the communication scanner_______________________________________________________________________ 39 Troubleshooting the communication fault______________________________________________________________________ 40 Troubleshooting the card fault______________________________________________________________________________ 41 DeviceNet objects___________________________________________________________________________________________ 42 Supported classes_______________________________________________________________________________________ 42 Identity object___________________________________________________________________________________________ 43 Message router object____________________________________________________________________________________ 46 DeviceNet object_________________________________________________________________________________________ 47 Assembly object_________________________________________________________________________________________ 49 Connection object________________________________________________________________________________________ 60 Motor data object________________________________________________________________________________________ 64 Control supervisor object__________________________________________________________________________________ 65 AC/DC Drive Object______________________________________________________________________________________ 67 Acknowledge handler object________________________________________________________________________________ 68 Application objects_______________________________________________________________________________________ 69 DeviceNet interface object_________________________________________________________________________________ 70 While every precaution has been taken in the preparation of this document, SchneiderElectric SA assumes no liability for any omissions or errors it may contain, nor for anydamages resulting from the application or use of the information herein.The products described in this document may be changed or modified at any time,either from a technical point of view or in the way they are operated. Their descriptioncan in no way be considered contractual.21. Before you beginRead and understand these instructions before performing any procedure with this drive.CAUTIONDAMAGED EQUIPMENTDo not install or operate any drive that appears damaged.Failure to follow this instruction can result in equipment damage.32. Documentation structureThe following Altivar 71 technical documents are available on the Web site and on the CDROM delivered with each drive.b Installation manualThis manual describes:•How to assemble the drive•How to connect the driveb Programming manualThis manual describes:•The functions•The parameters•How to use the drive HMI (integrated HMI and graphic HMI)b Communication parameters manualThis manual describes:•The drive parameters with specific information (addresses, formats, etc.) for use via a bus or communication network•The operating modes specific to communication (state chart)•The interaction between communication and local controlb Modbus, CANopen, Ethernet, Profibus, INTERBUS, Uni-Telway, DeviceNet, Modbus Plus, Fipio, etc., manualsThese manuals describe:•Connection to the bus or network•Configuration of the communication-specific parameters via the integrated HMI or the graphic HMI•Diagnostics•Software setup•The communication services specific to the protocolb Altivar 58/58F migration manualThis manual describes the differences between the Altivar 71 and the Altivar 58/58F.It explains how to replace an Altivar 58 or 58F, including how to replace drives communicating on a bus or network.43. Introduction3. 1. PresentationThe DeviceNet communication card (catalog number VW3 A3 309) is used to connect an Altivar 71 drive to a DeviceNet network.The communication card has an open-style 5-pin connector for connection to the network.Data exchanges give access to all Altivar 71 functions:•Downloading configuration and adjustment parameters,•Command,•Monitoring,•Diagnostics.DeviceNet cables and connecting accessories must be ordered separately.The graphic display terminal or the integrated display terminal can be used to access numerous functions for communication diagnostics.3. 2. NotationDrive terminal displaysThe graphic display terminal menus are shown in square brackets.Example: [1.9 COMMUNICATION].The integrated 7-segment display terminal menus are shown in round brackets.Example: (COM-).Parameter names are displayed on the graphic display terminal in square brackets.Example: [Fallback speed]Parameter codes are displayed on the integrated 7-segment display terminal in round brackets.Example: (LFF).FormatsHexadecimal values are written as follows: 16#Binary values are written as follows: 2#VocabularyDepending on DeviceNet document and tools, equivalent wordings are used. The table below shows vocabulary used in the present document and other corresponding definitions.In this document Other CommentsNode address DeviceNet address, MAC IDData rate Baud ratekbit/s kBPS, kbps, kSetpoint Reference, targetPath Object Address Class, instance, attributeThe reader should avoid mixing two terms:-DeviceNet scanner, which is the master device on the DeviceNet network.-Communication scanner, which is a function inside the Altivar drive.AbbreviationsReq. = RequiredOpt. = Optional54. Quick startThis section is provided to help experienced users quickly start using the DeviceNet card. If you are unsure how to complete a step, refer to the referenced chapter.Step Refer to1Review the safety precautions for the Altivar drive and DeviceNet card.Installation manual2Verify that the Altivar drive is properly installed.Installation manual4Install the DeviceNet card in the drive.Verify that the Altivar drive is not powered.Then, dismount the drive cover, mount the card in the drive. Finally mount the cover.Installation manual4Commission the DeviceNet card.Verify that the Altivar drive is not powered.Set a unique node address and the appropriate data rate using the switches on the card.If desired, you can disable the switches and use parameter settings instead.5. Hardware setup5Connect the drive to the DeviceNet network.Verify that the Altivar drive is not powered.Then, connect the card to the network using a DeviceNet cable.6. Wiring to the network6Apply power to the drive.The card receives power from the drive.Apply power to the drive.The status indicator should be green.If it flashes red, there is a problem(refer to 10. 2. Signalling LED).10. Diagnostics by the drive HMI7Configure the drive for your application.Select the functions and set the parameters as required by your application.Programming manual8Configure the drive behaviour and I/O interface for DeviceNet by the drive HMI.Choose the suitable assemblies for your application (refer to 7. 1. Configuring the control).If assemblies 100 or 101 are used, select the commands assigned to the control word (refer the Programming manual).Set the parameters for the following features as requiredby your application:Control and setpoint channels (refer to 7. 1. Configuring the control),If assemblies 100 or 101 are used, input and output assignments(refer to 7. 2. Configuring the communication scanner),Behaviour on communication fault (refer to 7. 3. Configuring the fault management),The parameters that you would like to monitor by the drive HMI for diagnostics(refer to 7. 4. Configuring monitored parameters).Programming manual Communication parameters manual 7. Configuring by the drive HMI9Apply power to the DeviceNet master and other devices on the network.Verify that the master and network are installed and functioning in accordance with DeviceNet standards, and then apply power to them.DeviceNet master manuals (DeviceNet cable system planning and Installation manual ...)10Configure the scanner to communicate with the drive.Use a network tool such as RSNetWorx for DeviceNet to configure the scanner on the network.Make sure to:Set up the scan list,Map the drive data to the scan list,Save your DeviceNet configuration to the scanner and a file.8. 4. Configuring the DeviceNet scanner11Configure the drive by the network tool.Set the parameters for the following features as required by your application:If the data rate switches (7 and 8) are set to 1, Node address and data rate,If you do not use default assemblies (100 or 101), select (and configure) assemblies.8. 5. Editing parameters of the drive12Create a PLC programControl the drive using I/O (assemblies).Monitor or configure the drive using Explicit Messages.9. Creating a PLC program DeviceNet master manuals65. 1. Receipt•Check that the card reference printed on the label is the same as that on the delivery note corresponding to the purchase order.•Remove the option card from its packaging and check that it has not been damaged in transit.5. 2. Hardware description5. 3. Installing the card in the driveRefer to the Installation manual.Configuration switches (data rate and node address)Bicolour LED785. 4. Coding the switchesb Switches descriptionb Overriding the switchesWhen switches 7 and 8 are set in position low (ON = 1), the data rate and the node address of the drive must be set by a network tool (refer to 8. Configuring by a network tool). Default values are 125 kbit/s and node address 63.b Coding the data rateAll devices connected to the DeviceNet network must communicate at the same data rate: 125, 250, or 500 kbit/s. The table below shows the switch settings that configure the DeviceNet data rate on the drive.Any change to the switch setting takes effect at the next power-up.b Coding the node addressAll devices connected to the DeviceNet network must have a unique address, ranging from 0 to 63 (decimal).If the data rate swithes (7 and 8) are both set to 1 (on), the switches 1 to 6 are ignored and the node address must be set by a network tool (default value = 63).The table below lists the switch setting for each valid node address.Any change to the switch setting takes effect at the next power-up.Switch 7Switch 8Data rate00125 kbit/s 01250 kbit/s 10500 kbit/s11The DeviceNet data rate and the node address of the drive must be set by a network tool.Node address Switches 12 3456Node address Switches 12 3456Node address Switches 12 3456Node address Switches 12 34560000 00001601 00003210 00004811 00000100 00011701 00013310 00014911 00010200 00101801 00103410 00105011 00100300 00111901 00113510 00115111 00110400 01002001 01003610 01005211 01000500 01012101 01013710 01015311 01010600 01102201 01103810 01105411 01100700 01112301 01113910 01115511 01110800 10002401 10004010 10005611 10000900 10012501 10014110 10015711 10011000 10102601 10104210 10105811 10101100 10112701 10114310 10115911 10111200 11002801 11004410 11006011 11001300 11012901 11014510 11016111 11011400 11103001 11104610 11106211 11101500 11113101 11114710 11116311 1111rateaddresshight = OFF = 0low = ON = 19bExamplesData rate = 250 kbit/s (switches 7 and 8 = 2#01)Node address = 25 (switches 1 to 6 = 2#01 1001)Data rate = 500 kbit/s (switches 7 and 8 = 2#10)Node address = 52 (switches 1 to 6 = 2#11 0100)106. Wiring to the network6. 1. Cable routing practicesWhen wiring Altivar 71 drives to a DeviceNet network, follow all wiring practices required by national and local electrical codes. Also observe the following guidelines:•Avoid areas of high temperature, moisture, vibration, or other mechanical stress.•Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or twisting the cable.•Use cable ducts, raceways, or other structures to protect the cable. Use these structures for signal wiring paths. They must not contain power wiring.•Avoid sources of electrical interference that can induce noise into the cable. Use the maximum practicable separation from such sources.When planning cable routing within a building, follow these guidelines:•Maintain a minimum separation of 1 m from the following equipment:-air conditioners and large blowers,-elevators and escalators,-radios and televisions,-intercom and security systems,-fluorescent, incandescent, and neon lighting fixtures.•Maintain a minimum separation of 3 m from the following equipment:-line and motor power wiring,-transformers,-generators,-alternators.When wiring in electrical equipment rooms or large electrical equipment line-ups, observe the following guidelines for cable segregation and separation of circuits:•Use metallic conduit for drive wiring. Do not run control network and power wiring in the same conduit.•Separate non-metallic conduits or cable trays used to carry power wiring from metallic conduit carrying low-level control network wiring by at least 300 mm.•Separate metallic conduits carrying power wiring or low-level control network wiring by at least 80 mm.•Cross the metallic conduits and non-metallic conduits at right angles whenever power and control network wiring cross.•Attenuate conducted emissions from the drive to the line in some installations to prevent interference with telecommunication, radio, and sensitive electronic equipment. Such instances may require attenuating filters. Consult the Altivar catalog for selection and application of these filters.6. 2. Wiring the DeviceNet connectorThe figures and the table below show the pin-outs of the card connectors. The removable DeviceNet female connector attaches to the network cable.Line termination: If the drive is the first or the last device on the DeviceNet network, a line terminator (121 Ω resistor) must be wired on the removable DeviceNet female connector, between pins 2 and 4 (CAN_L and CAN_H).DeviceNet card male connector Removable DeviceNet female connectorPin Name Color 1GND Black 2CAN_L Blue 3SHIELD Bare 4CAN_H White 5V+Red6. Wiring to the networkThe ODVA standards (Release 2.0) specify 7 types of cables for use in DeviceNet networks:•Thick cable•Thin cable•Flat cable•Cable I•Cable II•Cable IV•Cable VThe table below lists main specifications of cables. For more information, refer to the ODVA specifications.Type of cable Data conductor pair size Power conductor pair size Data impedanceThick cable18 AWG15 AWG120 Ω +/- 10 % (at 1 MHz) Thin cable24 AWG22 AWG120 Ω +/- 10 % (at 1 MHz) Flat cable16 AWG16 AWG120 Ω +/- 10 % (at 500 kHz) Cable I24 AWG22 AWG120 Ω +/- 10 % (at 1 MHz) Cable II18 AWG15 AWG120 Ω +/- 10 % (at 1 MHz) Cable IV18 AWG16 AWG120 Ω +/- 10 % (at 500 kHz) Cable V18 AWG16 AWG120 Ω +/- 10 % (at 500 kHz)The maximum permissible length of the network cable depends an the data rate and the type of cable.Type of cable Data rate125 kbit/s250 kbit/s500 kbit/sThick cable500 m (1640 ft)250 m (820 ft)100 m (328 ft)Thin cable100 m (328 ft)100 m (328 ft)100 m (328 ft)Flat cable420 m (1378 ft)200 m (656 ft)75 m (246 ft)Cable I100 m (328 ft)100 m (328 ft)100 m (328 ft)Cable II500 m (1640 ft)250 m (820 ft)100 m (328 ft)Cable IV---Cable V420 m (1378 ft)200 m (656 ft)75 m (246 ft)For maximum length of the drops refer to table, whatever type of cable:Data rate Cumulative drop Maximum drop125 kbit/s156 m (516 ft) 6 m (20 ft)250 kbit/s78 m (256 ft) 6 m (20 ft)500 kbit/s39 m (128 ft) 6 m (20 ft)7. 1. Configuring the controlb PrincipleBy the configuration of the control, it is possible to decide from what channel the drive receives its commands and setpoint, either permanently or depending on a switching command.Numerous configurations are possible. For more information, refer to the Programming manual and Communication parameters manual. The following configurations are some of the possibilities available.M Control with communication scannerIf the default assemblies (100, 101) are selected, all possibilities of Altivar 71 drive are available.It is possible to use all profiles and modes of the drive:-I/O profile,-Drivecom profiles with separate or non separate mode.By the configuration of the communication scanner, it is possible to assign any relevant parameter of the drive to the 4 input and 4 output variables of the assemblies.See the input / output interface with the PLC can be fully customised depending on the application.The use of the communication scanner is als the best way to interface with a "Controller Inside" card.M Control according to ODVA AC drive profileThe ODVA AC drive profile is activated when one of the following assemblies is selected:•20: Basic speed control output•21: Extended speed control output•22: Speed and torque control output•23: Extended speed and torque control output•70: Basic speed control input•71: Extended speed control input•72: Speed and torque control input•73: Extended speed and torque control inputThe advantage of using the ODVA drive profile standard is the interchangeability with other brands.The drive must be configured in the Drivecom profile with separate mode.The DeviceNet card translates the commands, behaviour and monitoring information from of ODVA profile (on the network) to the Drivecom profile (in the drive).M Control according to Allen-Bradley® drive profileThe Allen-Bradley® Drive profile is activated when one of the following assemblies is selected:•103: Allen-Bradley® drive output•104: Allen-Bradley® drive input•105: Allen-Bradley® drive input with parametersIf you need to replace Allen-Bradley® drives, in an existing application, this profile is a good way to minimise the modifications.The drive must be configured in the Drivecom profile with separate mode.The DeviceNet card translates the commands, behaviour and monitoring information from of Allen-Bradley® drive profile (on the network) to the Drivecom profile (in the drive).b Available configurationsM If you use the communication scanner:•100: Communication scanner output•101: Communication scanner input there is no limitation in the configuration of the control.The examples below are only possible if you use the communication scanner.M If you use the ODVA AC drive profile or Allen-Bradley® Drive profile, that is, the assemblies:•20: Basic speed control output •21: Extended speed control output •22: Speed and torque control output•23: Extended speed and torque control output •70: Basic speed control input •71: Extended speed control input •72: Speed and torque control input•73: Extended speed and torque control input •103: Allen-Bradley® drive output •104: Allen-Bradley® drive input•105: Allen-Bradley® drive input with parameters only some configurations are permitted, they are listed in the table below.Configuration via the graphic display terminal or the integrated display terminal:Case 1: Setpoint 1B is connected to the functions (Summing, PID, etc) which remain active even after switching.Case 2: Setpoint 2 is directly connected to the drive reference limit. If switching is performed, the functions that affect the reference (summing, PID, etc.) are inhibited.Note: It is not possible to configure the display terminal as a channel.To switch to the display terminal, use the function force local and assign the parameter [Forced local Ref.] to [HMI] (LCC ).Parameter Permitted valueCommentProfileDrivecom profile separate The run commands are in Drivecom profile,the command and the reference can come from different channels.Setpoint 1 configuration Network card Setpoint 1 comes from DeviceNet.Setpoint 1B configuration Terminals Setpoint 2 comes from terminals (AI1 or AI2).Setpoint 2 configuration Terminals Setpoint 2 comes from terminals (AI1 or AI2).Command 1 configuration Network card Command 1 comes from mand 2 configuration TerminalsCommand 2 comes from terminals.Setpoint switching Network card bit 12Bit 12 of the control word switches the setpoint (1 <-> 1B or 1 <-> 2).Command switchingNetwork card bit 13Bit 13 of the control word switches the command.Menu Parameter Permitted value [1.6 - COMMAND] (CtL-)[Profile] (CHCF )[Separate] (SEP )[Ref.1 channel] (Fr1)[Com. card] (nEt )[Ref.1B channel] (Fr1b )[Ref. AI1] (AI1) or [Ref. AI2] (AI2)[Cmd channel 1] (Cd1)[Com. card] (nEt )[Cmd channel 2] (Cd2)[Terminals] (tEr )[Cmd switching] (CCS )[C312] (C312)[1.7 APPLICATION FUNCT.] (F Un-)[REFERENCE SWITCH.][Ref 1B switching] (rCb )[C313] (C313)Menu Parameter Permitted value [1.6 - COMMAND] (CtL-)[1.7 APPLICATION FUNCT.] (FUn-)[REFERENCE SWITCH.][Profile] (CHCF )[Separate] (SEP )[Ref.1 channel] (Fr1)[Com. card] (nEt )[Ref.2 channel] (Fr2)[Ref. AI1] (AI1) or [Ref. AI2] (AI2)[Cmd channel 1] (Cd1)[Com. card] (nEt )[Cmd channel 2] (Cd2)[Terminals] (tEr )[Cmd switching] (CCS )[C312] (C312)[Ref. 2 switching] (rFC )[C313] (C313)b Control via DeviceNet in I/O profileNote: This configuration can only be used if the communication scanner assemblies (100 and 101) are selected.The command and the setpoint come from DeviceNet.Control is in I/O profile.Configure the following parameters:Configuration via the graphic display terminal or the integrated display terminal:b Control via DeviceNet or via the terminals in I/O profileNote: This configuration can only be used if the communication scanner assemblies (100 and 101) are selected.The command and the setpoint both come from DeviceNet or the terminals. Input LI5 at the terminals is used to switch between DeviceNet and the terminals.Control is in I/O profile.Configure the following parameters:Note: Setpoint 1B is connected to the functions (Summing, PID, etc) which remain active even after switching.Configuration via the graphic display terminal or the integrated display terminal:Parameter Value CommentProfileI/O profileThe run command is simply obtained by bit 0 of the command word.Setpoint 1 configuration Network card The setpoint comes from mand 1 configurationNetwork card The command comes from DeviceNet.MenuParameter Value[1.6 - COMMAND] (CtL-)[Profile] (CHCF )[I/O profile] (IO )[Ref.1 channel] (Fr1)[Com. card] (nEt )[Cmd channel 1] (Cd1)[Com. opt card] (nEt )Parameter Value CommentProfileI/O profile The run command is simply obtained by bit 0 of the control word.Setpoint 1 configuration Network card Setpoint 1 comes from DeviceNet.Setpoint 1B configuration Analog input 1 on the terminals Setpoint 1B comes from input AI1 on the terminals.Setpoint switching Input LI5Input LI5 switches the setpoint (1 ↔1B).Command 1 configuration Network card Command 1 comes from mand 2 configuration Terminals Command 2 comes from the mand switchingInput LI5Input LI5 switches the command.MenuParameter Value[1.6 - COMMAND] (CtL-)[Profile] (CHCF )[I/O profile] (IO )[Ref.1 chan] (Fr1)[Com. card] (nEt )[Cmd channel 1] (Cd1)[Com. card] (nEt )[Cmd channel 2] (Cd2)[Terminals] (tEr )[Cmd switching] (CCS )[LI5] (LI5)[1.7 APPLICATION FUNCT.] (FUn-)[REFERENCE SWITCH.][Ref.1B chan] (Fr1b )[AI1 ref.] (AI1)[Ref 1B switching] (rCb )[LI5] (LI5)b Control via DeviceNet in Drivecom profileNote: This configuration can only be used if the communication scanner assemblies (100 and 101) are selected.The command and the setpoint come from DeviceNet.Configure the following parameters:Parameter Value CommentProfile Separate Drivecom profile The run commands are in Drivecom profile, the command and the setpoint cancome from different channels.Setpoint 1 configuration Network card The setpoint comes from DeviceNet.Command 1 configuration Network card Command 1 comes from DeviceNet.Configuration via the graphic display terminal or the integrated display terminal:Menu Parameter Value[1.6 - COMMAND](CtL-)[Profile](CHCF)[Separate](SEP)[Ref.1 chan](Fr1)[Com. card](nEt)[Cmd channel 1](Cd1)[Com. card](nEt)b Control via DeviceNet or the terminals in Drivecom profileNote: This configuration can only be used if the communication scanner assemblies (100 and 101) are selected.The command and the setpoint both come from DeviceNet or the terminals. Input LI5 at the terminals is used to switch between DeviceNet and the terminals.Configure the following parameters:Parameter Value CommentProfile Separate Drivecom profile The run commands are in Drivecom profile, the command and thesetpoint can come from different channels.Setpoint 1 configuration Network card Setpoint 1 comes from DeviceNet.Setpoint 2 configuration Analog input 1 on the terminals Setpoint 2 comes from input AI1 on the terminals.Setpoint switching Input LI5Input LI5 switches the setpoint (1 ↔ 2) and the command.Command 1 configuration Network card Command 1 comes from DeviceNet.Command 2 configuration Terminals Command 2 comes from the terminals.Command switching Input LI5Input LI5 switches the command.Note: Setpoint 2 is directly connected to the drive reference limit. If switching is performed, the functions that affect the reference (summing, PID, etc) are inhibited.Configuration via the graphic display terminal or the integrated display terminal:Menu Parameter Value[1.6 - COMMAND](CtL-)[Profile](CHCF)[Separate](SEP)[Ref.1 chan](Fr1)[Com. card](nEt)[Ref.2 chan](Fr2)[AI1 ref.](AI1)[Ref. 2 switching](rFC)[LI5](LI5)[Cmd channel 1] (Cd1)[Com. card](nEt)[Cmd channel 2](Cd2)[Terminals](tEr)[Cmd switching](CCS)[LI5](LI5)。
施耐德变频器(ATV71L)调试说明

施耐德变频器(ATV71L)功能参数说明菜单路径:电梯()→电梯宏() →电机数据()参数 参数定义 参数设定值范围单位电机控制类型电机的控制类型异步电机闭环选同步电机闭环选电机额定功率异步电机的额定功率 按实际异步电机的额定功率KW电机额定电压异步电机的额定电压 按实际异步电机的额定电压 V电机额定电流异步电机的额定电流 按实际异步电机的额定电流 A电机额定频率异步电机的额定频率 按实际异步电机的额定频率 HZ电机额定速度异步电机的额定速度 按实际异步电机的额定速度 rpm同步电机极对数同步电机的极对数 按实际电机的极数/2同步电机额定电流同步电机的额定电流 按实际同步电机的额定电流 A同步电机额定速度同步电机的额定速度 按实际同步电机的额定速度 rpm同步电机转矩同步电机的额定转矩 按实际同步电机的额定转矩 Nm变频器电流限幅用于限制电机电流电机额定电流(乘以) x 1.8输入A自机自学习用于同步电机进行电机自整定没有进行电机自学习;进行电机自学习请求;已完成电机自学习;菜单路径:电梯()→电梯宏() →电梯数据()参数 参数定义 参数设定值范围 单位电梯额定速度电梯的额定速度 按实际电梯额定速度 m/s电机额定载重量电梯启动转矩 700 Kg加速时间电梯启动时低速加速时间 3~4 S减速时间电梯减速停车段的减速时间12~30 (12) S 加速始端圆滑系数加速斜坡开始平滑时间 50%加速未端圆滑系数加速斜坡结束平滑时间 50%减速始端圆滑系数减速斜坡开始平滑时间 40%减速未端圆滑系数减速斜坡结束平滑时间 40%斜坡2切换阀值第二段斜坡曲线开始速度设置成电梯的爬行速度(数值=SP3内的值)HZ第2加速时间第2段曲线高速段加速时间3~6 S第2减速时间第2段曲线减速段时间2.0~5 (3.0)(只适用于≤1米梯速)S菜单路径:电梯()→电梯优化() →速度环() 参数 参数定义 参数设定值范围 单位频率F环稳定性速度环比例增益,调整速度瞬变返回到稳定状态的增益20%频率环增益速度环的积分增益时间,调整速度瞬变的响应时间20%速度环滤波系数异步电机设65 同步电机设100编码器滤波激活编码器滤波常数3 ms 菜单路径:设置()参数 参数定义 参数设定值范围 单位高速频率电机的额定频率(电梯的额定速度)电机的额定频率 HZ菜单路径:电机控制()参数 参数定义 参数设定值范围 单位 最大输出频率电梯超速保护值 电机的额定频率*1.1 HZ菜单路径:电梯()→电梯功能() →预设速度()参数 参数定义 参数设定值范围 单位预设速度3爬行速度按0.06m/s的速度换算成频率HZ预设速度4SP 4多段速3(三层运行速度)按1.5m/s~1.75m/s的速度换算成频率 * 0.95HZ预设速度5检修速度按 0.2m/s的速度换算成频率 * 0.95HZ预设速度6多段速1(单层运行速度)按1.0m/s的速度换算成频率 * 0.95预设速度7多段速2(两层运行速度)按1.5m/s的速度换算成频率 * 0.95HZ预设速度8多段速4(四层运行速度)按2.0m/s的速度换算成频率 * 0.95电梯起动舒适感调整:菜单路径:电梯()→电梯优化() →起动调整()→刹车起动()参数 参数定义 参数设定值范围 单位 刹车机构释放时间刹车机构释放时间延时 1.0 S 刹车释放电流l b r刹车机构释放电流值(-5,-10,+10,+5)约30~50%额定电流值A 制动力方向刹车释放电流功能打开或关闭功能打开菜单路径:电梯()→电梯优化() →起动调整()→倒溜管理()参数 参数定义 参数设定值范围 单位 倒溜管理倒溜管理功能打开或关闭倒溜补偿倒溜补偿增益 10~200% (40)倒溜缓冲倒溜阻尼系数 30~100% (50)起始刚度补偿起始刚度补偿 功能打开或关闭激活角度启激活角度系数1~10% (1)刚度增益刚度增益 40~200% (60)电梯停止时舒适感的调整:一.电梯速度≤ 1.0m/s : 减小减速时间可以增大爬行距离;二.电梯速度>1.0m/s :单层运行冲层 减小减速时间 减速太快,有冲层现象多层运行冲层减小减速时间一.电梯速度≤1.0m/s : 增大减速时间可以减小爬行距离; 二.电梯速度>1.0m/s :单层运行爬行太长增大减速时间 减速太慢,爬行太长多层运行爬行太长增大减速时间停止有倒溜停止时有振动① 有倒溜时,增加刹车抱紧时间② 确认bECd 是否设为0.0s③停止时有提升感,加大减速时间菜单路径:电梯() → 电梯优化() → 停止调整()参数 参数定义 参数设定值范围单位 bECd零速抱闸时间 0.0 s抱闸抱紧时间0.5s★ 电梯减速时间调整方法:① 菜单路径:电梯() → 电梯功能() → 频率阀值()参数 参数定义参数设定值范围单位 频率阀值设置减速时间的切换频率单层运行的速度值 HZ备注:如电梯速度≤1.0m/s :可设置为一半的数值② 菜单路径:电梯() → 电梯功能() → 参数组切换()参数 参数定义参数设定值范围 单位 2组参数组设置切换2组参数组的内容到频率阀值 HZ选择参数SPS选择此参数组,只能用液晶操作器设定第2减速时间第1组0~频率阀值的单层速度的减速时间4.5~6 S第2组频率阀值~最高速的多层速度减速时间3~5S备注:如电梯速度≤1.0m/s 时,数值不变,为曲线段减速时间监控参数: 端子状态监控:菜单路径:监视() → 输入/输出映像()→逻辑输入LI1至LI8的状态( LI5I- )参数 参 数 说 明逻辑输入LI1~LI8状态1亮表示该信号动作,状态0亮表示该信号不动作 电机运行电流监控: 菜单路径:监视() →电流()1. 施耐德变频器(ATV71L )1.1施耐德变频器电机自学习时的故障显示:故障代码 名称 故障原因 检查措施负载不跟随 编码器反馈速度与给定值不相符1.检查主机编码器;2.重新做主机自学习;角度值误差 电机编码器角度学习不正确 1.确认变频器与电机连接线是否正确;2.确认KMY 接触器接触是否良好; 3.确认主机编码器安装是否牢固;4.重新执行电机自学习;配置错误 变频器PG 卡故障; 1.检修PG 卡接触是否良好;2.更换变频器PG 卡; 编码器故障 编码器反馈故障1.检查变频器内编码器设定的参数;2.检查编码器的连接线;过电流 负载太大电机控制()菜单中最大输出频率设定值不对1.检查负载;2.检查最大输出频率的设定值;电机短路接地短路变频器输出侧短路或接地检查变频器侧输出侧的连接线;超速 驱动负载不稳定或负载太大1.检查编码器接线和抗干扰处理是否正常;2.检查速度环的比例增益设定是否合适;3. 检查编码器是否正常;速度反馈丢失 没有编码器反馈信号 编码器连接线有干扰1.检查编码器的连接线;2.检查编码器连接线的屏蔽层接地是否良好,接到ST-1分频卡上的线接触是否良好;Brake 控制 没有达到刹车释放电流1.检查电机的动力线连接是否正确,有无虚接现象;2.检查KMY 接触器主触点接触是否良好,动力线有无虚接现象;3.检查是否由于厅门锁回路瞬间断开所致;变频器过热 变频器温度太高1.检查变频器的通风情况及周围温度;2.检查变频器的散热风扇运行是否正常;变频器过载 负载电流太大1.检查负载情况;2.检查电机热保护的设置值是否正确;输出缺1相输出缺3相变频器输出缺相1.检查变频器输出端的连接线;2.检查KMY运行接触器; 输入过电压主回路电压太高;电源不稳定有波动;输入缺相 变频器输入缺相输入欠压 变频器输入电压太低检查变频器的输入电源电源切除变频器PWR使能信号端无输入信号自由停车 变频器故障后自由停车模式检查主板到PWR端的连接线IGBT过热 变频器过载1.减小载波频率;2.检查负载情况;3.交换电机的V、W动力线,重新做主机自学习;4.检查安装主机编码器;。
施耐德ATV71变频器设置指南

施耐德ATV71变频器设置指南施耐德ATV71变频器是一种专业的电气控制设备,用于控制电动机的转速和运行。
在使用ATV71变频器之前,我们需要了解如何正确设置和调试它以确保最佳性能和安全运行。
以下是施耐德ATV71变频器的设置指南,包括安装、接线、参数设置和调试过程。
第一步:安装和接线1.根据变频器的额定功率和电压,选择适当的安装位置。
2.确保变频器周围的环境通风良好,并远离热源和湿度。
3.确保电源线和电机线接线正确,按照变频器的接线图进行连接。
在连接电源线和电机线之前,确保电源已经断开。
4.检查接线是否牢固,并避免电线交叉和短路。
第二步:参数设置1.连接电源后,按下变频器面板上的“模式”按钮,进入基本设置菜单。
2.使用上下/左右箭头键导航到所需的参数设置,按下“确定”键进行选择。
3.根据实际应用需求,设置变频器的基本参数,如额定电压、额定功率和额定电流。
4.设置电压和频率限制,以确保在变频器的额定工作范围内运行电动机。
5.根据操作手册提供的参数列表,逐个设置变频器的高级参数,如加速时间、减速时间、最大转矩和过载保护。
6.检查参数设置是否正确,并根据需要进行修改。
第三步:调试过程1.在进行调试前,确保变频器和电动机的机械连接正确,并确保电机轴与机械负载对齐。
2.提供适当的负载,并逐步增加变频器的输出频率。
3.监控电动机的运行情况,包括转速、电流和温度。
确保运行正常且没有异常情况。
4.根据需要,调整变频器的参数,以获得更好的性能和运行效果。
5.使用变频器提供的监控功能进行故障诊断和排除。
第四步:安全注意事项1.在进行任何调试和设置之前,确保电源已经关闭,并使用安全锁进行锁定,以防止误操作。
2.注意变频器的电气隔离和绝缘等级,避免触摸裸露的电线和接口。
3.在操作变频器时必须使用绝缘手套和安全鞋,以确保人身安全。
4.定期检查电源线和接线的连接情况,并确保电缆和电线的绝缘性能良好。
总结:通过正确的安装、接线、参数设置和调试过程,我们可以确保施耐德ATV71变频器的最佳性能和安全运行。
(完整版)施耐德ATV71变频器设置指南

施耐德ATV71变频器调试指南第一部分接线一.电气控制图:1.主回路2.控制回路3.编码器二.端子位置图:1.功率端子分布:ATV71-HD95N4 ATV71-HD95N4(输入电抗器)ATV71-HD45N4/ ATV71-HD55N4 ATV71-HU75N4 2.控制端子位置图:3.编码器卡安装图三.接线注意事项:1.各功率端子和控制端子一定要安装紧固;1.1 动力直流母线端子PO--PA+之间的短接铜片一定要保持紧固;1.2 控制端子的PWR--+24V之间的短接片一定要保持连接,否则变频器将显示状态PRA并且不能正常输出。
1.3 如用AI1+和AI1-做双极性给定,请去掉AI1-和com之间的短接片。
2.请可靠连接各保护地和屏蔽地。
第二部分用中文图形终端编程一.中文图形编程操作终端界面二.菜单结构1.主菜单注:所有的参数调整都在1 变频器菜单中进行,其它的主菜单都是辅助功能。
这些需要在使用中灵活掌握,慢慢积累经验。
2.变频器菜单注:变频器菜单中有关调试主要菜单是1.1 到 1.8 。
我们暂时也仅仅涉及一些主要的菜单和参数。
其它都是辅助菜单,这些需要在使用中灵活掌握,慢慢积累经验。
三.调试的步骤第一步,设置简捷的起停控制设置端子与面板切换功能键(命令菜单):在命令菜单,找到最后一个参数:F4键分配:设置其功能为T/K,即为端子控制(Terminals)与图形终端控制(Kepad)切换。
这样按F4键可以切换用端子控制起停或图形终端控制起停。
端子控制有效时,起停命令来自LI1, LI2的逻辑端子的输入,这时变频器图形终端首行显示的第二个位置显示TERM;图形终端控制激活时,按图形终端上的RUN, STOP,FWD/REV键可以控制变频器的正反转,旋转导航键(浏览鼓轮)改变频率给定这时图形终端首行显示的第二个位置显示HMI。
此设置的目的是为了便于手动试运转。
正常运行时,应采用端子控制。
(常熟工厂为设置)。
ATV71变频器操作说明

ATV71变频器操作说明一启动前的准备首先检查变频器的进线和出现正确连接到变频器,用万用表量进线和出现对地绝缘情况(电机的绝缘在连接到变频器之前应由摇表测过)。
一切正常后,由开关柜送电,量一下进线电压,确保进线电压在变频器允许范围内(380V-480V)且输入平衡。
然后闭合柜门,将刀熔开关打到闭合位置,变频器上电。
此时,柜顶风机运转且向上抽风,变频器操作面板显示正常,显示状态栏显示为RDY.二参数设值首先先记下电机铭牌上的电机额定值,然后按参数表设置参数。
参数设置完后。
进入电机控制菜单执行自整定(此时电机为空载)。
电机自整定完后可以按以下方式控制电机。
三控制每台变频器由三中控制方式:本地控制(操作面板控制启停和调速),远程控制一(电机旁就地箱控制启停),远程控制二(DCS控制启停和调速)。
1.本地操作(1)使用本地操做前要确保变频器处于本地控制模式下,具体信息应在显示面板状态显示栏即第一行第二项显示为“HMI”,第二行显示为“图形终端频率给定”。
若显示为“Term”则需要按下F4键进行切换(若在运行期间改变此参数会导致停车,请在改变此参数前确认)。
(2)显示面板第二行为频率给定,启动变频器前要确认所给频率是否符合要求,若不符可旋转旋钮来增大或减小给定值。
(3)启动变频器,按下面板左下方的RUN按键,变频器开始启动加速,加速到给定频率后,变频器处于运行状态。
启动过程中面板左上角的状态显示栏显示为RDY-ACC-RUN。
(4)停止变频器,按下面板左边的STOP/RESET键,变频器开始启动,直到减速到0HZ后,变频器处于准备状态。
停止过程中面板左上角的状态显示栏显示为RUN-DEC-RDY。
2 远程控制使用远程控制时前要确保变频器处于远程控制时模式下,具体信息应在显示面板状态显示栏即第一行第二项显示为“Term”,第二行显示为“频率给定”。
若显示为“HMI”则需要按下F4键进行切换(若在运行期间改变此参数会导致停车,请在改变此参数前确认)。
施耐德ATV71变频器设置指南

施耐德ATV71变频器调试指南第一部分接线一.电气控制图:1.主回路2.控制回路3.编码器二.端子位置图:1.功率端子分布:ATV71-HD95N4 ATV71-HD95N4(输入电抗器)ATV71-HD45N4/ ATV71-HD55N4 ATV71-HU75N42.控制端子位置图:3.编码器卡安装图三.接线注意事项:1.各功率端子和控制端子一定要安装紧固;1.1 动力直流母线端子PO--PA+之间的短接铜片一定要保持紧固;1.2 控制端子的PWR--+24V之间的短接片一定要保持连接,否则变频器将显示状态PRA 并且不能正常输出。
1.3 如用AI1+和AI1-做双极性给定,请去掉AI1-和com之间的短接片。
2.请可靠连接各保护地和屏蔽地。
第二部分用中文图形终端编程一.中文图形编程操作终端界面二.菜单结构1.主菜单注:所有的参数调整都在 1 变频器菜单中进行,其它的主菜单都是辅助功能。
这些需要在使用中灵活掌握,慢慢积累经验。
2.变频器菜单注:变频器菜单中有关调试主要菜单是1.1 到 1.8 。
我们暂时也仅仅涉及一些主要的菜单和参数。
其它都是辅助菜单,这些需要在使用中灵活掌握,慢慢积累经验。
三.调试的步骤第一步,设置简捷的起停控制设置端子与面板切换功能键(命令菜单):在命令菜单,找到最后一个参数:F4键分配:设置其功能为 T/K,即为端子控制(Terminals)与图形终端控制(Kepad)切换。
这样按F4键可以切换用端子控制起停或图形终端控制起停。
端子控制有效时,起停命令来自LI1, LI2的逻辑端子的输入,这时变频器图形终端首行显示的第二个位置显示TERM;图形终端控制激活时,按图形终端上的RUN, STOP,FWD/REV键可以控制变频器的正反转,旋转导航键(浏览鼓轮)改变频率给定这时图形终端首行显示的第二个位置显示HMI。
此设置的目的是为了便于手动试运转。
正常运行时,应采用端子控制。
(常熟工厂为设置)。
施耐德ATV变频器设置指南

施耐德ATV71变频器调试指南第一部分接线一.电气控制图:1.主回路2.控制回路3.编码器二.端子位置图:1.功率端子分布:ATV71-HD95N4 ATV71-HD95N4(输入电抗器)ATV71-HD45N4/ ATV71-HD55N4 ATV71-HU75N42.控制端子位置图:3.编码器卡安装图三.接线注意事项:1.各功率端子和控制端子一定要安装紧固;1.1 动力直流母线端子PO--PA+之间的短接铜片一定要保持紧固;1.2 控制端子的PWR--+24V之间的短接片一定要保持连接,否则变频器将显示状态PRA并且不能正常输出。
1.3 如用AI1+和AI1-做双极性给定,请去掉AI1-和com之间的短接片。
2.请可靠连接各保护地和屏蔽地。
第二部分用中文图形终端编程一.中文图形编程操作终端界面二.菜单结构1.主菜单注:所有的参数调整都在 1 变频器菜单中进行,其它的主菜单都是辅助功能。
这些需要在使用中灵活掌握,慢慢积累经验。
2.变频器菜单注:变频器菜单中有关调试主要菜单是1.1 到 1.8 。
我们暂时也仅仅涉及一些主要的菜单和参数。
其它都是辅助菜单,这些需要在使用中灵活掌握,慢慢积累经验。
三.调试的步骤第一步,设置简捷的起停控制设置端子与面板切换功能键(命令菜单):在命令菜单,找到最后一个参数:F4键分配:设置其功能为 T/K,即为端子控制(Terminals)与图形终端控制(Kepad)切换。
这样按F4键可以切换用端子控制起停或图形终端控制起停。
端子控制有效时,起停命令来自LI1, LI2的逻辑端子的输入,这时变频器图形终端首行显示的第二个位置显示TERM;图形终端控制激活时,按图形终端上的RUN,STOP,FWD/REV键可以控制变频器的正反转,旋转导航键(浏览鼓轮)改变频率给定这时图形终端首行显示的第二个位置显示HMI。
此设置的目的是为了便于手动试运转。
正常运行时,应采用端子控制。
(常熟工厂为设置)。
施耐德变频器操作说明2012年9月7日

ATV71施耐德变频器操作说明一、图形显示终端按钮功能介绍1,图形显示器;2,功能键F1,F2,F3,F4;3,STOP/RESET(停车/复位)按钮;4,RUN(运行)按钮;5,导航按钮;• 按(ENT): - 保存当前值; 1234657- 进入所选菜单或参数;• 转动CW/CCW:- 增大或减小一个值;- 转到下一行或前一行;- 增大或减小给定值,如果通过终端控制功能被激活;6,用于使电机旋转反向的按钮;7,ESC 按钮:中断一个值、一个参数或一个菜单,返回以前的选择。
※注意:如果通过终端控制功能被激活按钮3、4、5 与6 可用于直接控制变频器。
二、图形显示屏描述1,显示行。
在出厂设置模式下显示:变频器状态:如图中RDY;有效控制通道:如图中Term;频率给定值:如图中+0.00Hz;电机内电流:如图中0A。
2,菜单行。
显示当前菜单或子菜单的名称。
3,菜单、子菜单、参数、值、柱状图等在下拉菜单窗口显示,每个窗口最多显示5行。
导航按钮所选的行或值反白显示。
4,显示分配给键F1至F4的功能,与这四个键上下对应,例如:功能键是动态的,且具有前后关系。
功能键可通过【1.6命令】给这些键分配其他功能。
5,6,二〇一二年九月七日星期五三、变频器状态代码四、设置窗口示例第3 页/共10页五、第一次通电-设置语言和访问等级设置为Chinese。
二〇一二年九月七日星期五第5 页/共10页六、以后通电屏幕显示如下二〇一二年九月七日星期五七、访问参数示例:访问加速斜坡八、变频器菜单的操作方法已经设置过参数的变频器上电时,首先显示变频器的型号,3秒钟以后自动转到【变频器菜单】。
若操作者没有进行操作,10秒后自己转入【DISPLAY显示】,显示内容将根据相关参数设置而改变。
通过按导航按钮或ESC键,用户可以进入【主菜单】。
旋转导航按钮选择【变频器菜单】、【访问等级】、【打开/另存为】、【密码】、【语言】等菜单。
一般来说,我们只需要按导航按钮进入【变频器菜单】即可,其余几种很少用。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
警告
不正确的变频器操作
• 如果变频器长时间没有通电,则其电解电容器的性能将会下降。 • 如果变频器将在很长一段时间内不使用,应每两年将变频器至少通电 5 小时,以恢复 电容器的性能,然后检查其工作情况。建议不要将变频器与线电压直接连接,应使用 可调的 AC 电压源逐渐加压。 不按照使用说明会导致设备损坏。
v 按照此文件中的说明安装变频器 v 安装任意一个内部与外部选件
b 4 给变频器接线
v v v v 连接电机,确保电压一致 连接控制线路 连接速度给定 在确保电源关闭之后连接电源
编程 v 1 请参考编程手册
5
初步建议
吊运与贮存
为了在安装之前保护变频器,吊运和贮存时应将其放在原始包装内,并确保周围条件能够满足要求。
Altivar 71 异步电机变频器
安装手册
0.37 KW (0.5 HP)...45 KW (60 HP) / 200 - 240V 0.75 KW (1 HP)...75 KW (100 HP) / 380 - 480V
目录
开始之前 ____________________________________________________________________________________________________ 4 变频器安装步骤_______________________________________________________________________________________________ 5 初步建议 ____________________________________________________________________________________________________ 6 变频器额定值 ________________________________________________________________________________________________ 7 安装与温度条件 _____________________________________________________________________________________________ 10 壁挂式或落地式安装的柜子_____________________________________________________________________________________ 12 安装图形显示终端 ____________________________________________________________________________________________ 14 充电 LED 的位置 _____________________________________________________________________________________________ 15 安装选项卡 _________________________________________________________________________________________________ 16 安装 EMC ( 电磁兼容 ) 板 ______________________________________________________________________________________ 18 接线建议 ___________________________________________________________________________________________________ 19 功率端子 ___________________________________________________________________________________________________ 21 控制端子 ___________________________________________________________________________________________________ 23 可选端子 ___________________________________________________________________________________________________ 25 连线图 _____________________________________________________________________________________________________ 30 在 IT ( 隔离的或阻抗接地中点 ) 系统中运行 ________________________________________________________________________ 39 电磁兼容性 , 连线 ____________________________________________________________________________________________ 40
3 相电源电压: 200…240 V 50/60 Hz
3 相电机 200...240 V 电机 铭牌上指示的 功率 (1) kW 0.37 0.75 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 HP 0.5 1 2 3 5 7.5 10 15 20 25 30 40 50 60 线路电源 ( 输入 ) 最大线电流 (2) 在 200 V 时 在 240 V 时 A 3.5 6.1 11.3 15 19.3 25.8 35 45 53.3 71.7 77 88 124 141 167 A 3.1 5.3 9.6 12.8 16.4 22.9 30.8 39.4 45.8 61.6 69 80 110 127 147 kA 5 5 5 5 5 5 22 22 22 22 22 22 22 22 22 kVA 1.3 2.2 4 5.3 6.8 9.2 12.4 15.9 18.8 25.1 27.7 32 42.4 51 65 A 9.6 9.6 9.6 9.6 9.6 9.6 23.4 23.4 93.6 93.6 100 100 250 250 250 A 3 4.8 8 11 13.7 17.5 27.5 33 54 66 75 88 120 144 176 预期最大线 视在功率 电流 Isc 变频器 ( 输出 ) 最大启动电 额定电流 最高瞬时电流 (1) In (1) 流 (3) 60 s 时 A 4.5 7.2 12 16.5 20.6 26.3 41.3 49.5 81 99 112 132 180 216 264 2s时 A 4.9 7.9 13.2 18.1 22.6 28.8 45.3 54.5 89.1 109 124 145 198 238 290 ATV71H037M3(4) ATV71H075M3(4) ATV71HU15M3(4) ATV71HU22M3(4) ATV71HU30M3(4) ATV71HU40M3(4) ATV71HU55M3(4) ATV71HU75M3(4) ATV71HD11M3X(4) ATV71HD15M3X(4) ATV71HD18M3X ATV71HD22M3X ATV71HD30M3X ATV71HD37M3X ATV71HD45M3X Altivar 71 型号 (5)
警告
损坏的设备
不要操作或安装任何看起来已损坏的变频器。 不按照使用说明会导致设备损坏。
安装时吊运
45° 最大
ALTIVAR 71 变频器,一直到 ATV71HD15M3X 与 ATV71HD18N4,可以不用搬运设备就可 从包装中取出并进行安装。 大型变频器安装时必须使用吊钩。因此,为其专门配备了吊耳。 起吊过程中必须注意下面描述的预防措施。
预防措施
阅读并了解 “编程手册”中的使用说明。
警告
线电压不一致
在加电与配置变频器之前,应确保线电压与变频器铭牌上所示的电源电压范围适应。如果线电压与电源电压范围不一致, 就有可能损坏变频器。 不按照使用说明会导致设备损坏。
DANGER 危险
Hale Waihona Puke 无意的设备操作• 在接通与配置 Altivar 71 之前,为了防止意外起动,应检查并确认 PWR ( 断电 ) 输入无效 ( 状态 0)。 • 在接通 Altivar 71 之前或在退出配置菜单时, 因运行命令能使电机立即起动, 故应检查并确认分配给运行命令的输入为无 效 ( 状态 0)。 不按照使用说明会导致死亡或严重伤害。
如果人员安全方面要求禁止没有必要或意料之外的起动,则由 Altivar 71 的断电 (Power Removal) 功能实现电子锁定。 此功能需要使用符合标准 EN 954-1 第 3 类的连接图以及依照 IEC/EN 61508 的安全完整性等级 2。 断电功能比任何运行命令都具有优先权。
6
变频器额定值
4
变频器安装步骤
安装 b 1 变频器交付
v 检查并确认印在标签上的目录编号与定购单上的相同 v 去除 Altivar 的包装,检查在运输过程中有无损坏
b 2 检查线电压
执行步骤 1 至 4 时 必须关闭电源。
v 检查并确认线电压与变频器的电压范围适应 ( 见第 7 页与第 8 页 )
b 3 安装变频器
单相电源电压: 200...240 V 50/60 Hz
3 相电机 200...240 V 电机 铭牌上指示的 功率 (1) kW 0.37 0.75 1.5 2.2 3 4 5.5 HP 0.5 1 2 3 5 7.5 线路电源 ( 输入 ) 最大线电流 (2) 在 200 V 时 在 240 V 时 A 6.9 12 18.2 25.9 25.9 34.9 47.3 A 5.8 9.9 15.7 22.1 22 29.9 40.1 kA 5 5 5 5 5 22 22 kVA 1.4 2.4 3.7 5.3 5.3 7 9.5 A 9.6 9.6 9.6 9.6 9.6 9.6 23.4 A 3 4.8 8 11.0 13.7 17.5 27.5 预期最大线 视在功率 电流 Isc 变频器 ( 输出 ) 最大启动电 额定电流 最高瞬时电流 (1) In (1) 流 (3) 60 s 时 A 4.5 7.2 12 16.5 20.6 26.3 41.3 2s时 A 4.9 7.9 13.2 18.1 22.6 28.8 45.3 ATV71H075M3(4) ATV71HU15M3(4) ATV71HU22M3(4) ATV71HU30M3(4) ATV71HU40M3(4)(6) ATV71HU55M3(4)(6) ATV71HU75M3(4)(6) Altivar 71 型号 (5)