These instructions provide information for installation, electrical connection, process connection and calibration of 107 Differential Pressure Switches.107Differential Pressure Switch Process pressure is sensed by a diaphragm and piston assembly. The piston responds to differential pressure and moves a shaft that actuates (deactuates) an electrical switching element. Low side pressure and a wetted adjustable range springoppose high side pressure. Calibration is accomplished by adjusting the range spring with the set point adjustment screw.Design and specifications are subject to change without notice.For latest revision, go to NOTE: If you suspect that a product is defective, contact the factory or the SOR ® Representative in your area for a returnauthorization number (RMA). This product should only be installed by trained and competent personnel.stallation, electrical connection, process Pressure Switches. ms tohat actuates ent. Low nge springs accomplished byoint adjustment screw.e, contact thea for a return uld only be107ELUse care during installation not to inadvertently move the electrical switchingelement or its housing. Movement of either could disturb the relative positions ofinternal working parts and alter calibration or render the device inoperative.The 107 Differential Pressure Switch is suited for draft range service as well as industrial air and gas services which are compatible with the wetted parts and within nameplate specifications. Contact the SOR representative in your area or the factory in Lenexa, Kansas for details.InstallationThe 107 is position sensitive. Mount the 107 so that the diaphragm is vertical (as shown above). Non-vertical mounting positions will cause calibration scale error.If condensation is expected within process piping, pressure ports should be located at 6o’clock to prevent moisture accumulation within the instrument. If condensation is not expected, the pressure ports can be positioned to any location as long as the diaphragm remains vertical.Securely mount the base plate bracket to flat surface using suitable bolts.Hazardous Locations - 107EL ❶❷❸❹❺❻❶❷❸❼❽Non-Hazardous Locations - 107ALThe high-pressure side (marked HIGH) and the low pressureside (marked LOW) have 1/8” NPT(F) process connectionsunless 1/4” NPT(F) adapters were specified.❶ Set point adjustment screw (not shown)❷ High side process connection❸ Low side process connection ❹ Hermetically sealed switching element capsule❺ 18 AWG wire leads (not shown)❻ 1/2” NPT(M) electrical conduit connection❼ 3/4” NPT(F) electrcial conduit connection❽ Weatherproof switching element housingEnsure that wiring conforms toall applicable local and nationalelectrical codes and install unit(s)according to relevant national andlocal safety codes.The SOR pressure switches have been evaluated as Type-A safety related hardware. To meet the necessary installation requirements for the SIL system, the following information must be utilized:Proof Test Interval shall be one year.Units may only be installed for use in Low Demand Mode.Products have a HFT (Hardware Fault Tolerance) of 0, and were evaluated in a1oo1 (one out of one) configuration.Form 1538 (03.12) ©2012 SOR Inc.107AL (weatherproof):Interrupt electrical power. Remove top cover plate.107EL (explosion proof): Hermetically sealed switching element capsule has18” - 18 AWG wire leads color coded and markedC - Common, NO - Normally Open, NC - Normally Closed and G - Ground (earth). (See below.)Wire Lead Color CodeSee SOR Catalog 459 for reference dimension drawings. For certified dimension drawings, contact the factory.Units in hazardous locations-prior to removal from service, make surethat the work area is declassifi ed. Failure to do so could result in severepersonal injury or substantial property damage.DPDT (2 SPDT)SPDT Blue (C) Red (NO) Black (NC)Yellow (C2)Orange (NO2)Brown (NC2)Blue (C)Red (NO)Black (NC)Green (GND)Green (GND)LO HI NO 1NO 2Differential PressureHI LO Differential PressureNormal Calibration: Turn set point adjustment screw to move spring guide plateinto alignment with desired set point on calibration scale.Precise Calibration: Device calibrated without reference to calibration scaleand low side vented.Test apparatus: ManometerVariable pressure sourceTest light or ohmmeter ❶ Connect variable pressure source to manometer and high side pressure port.❷ Connect test light or ohmmeter to C-Common and NO - Normally Open switching element contacts.❸ Raise pressure and note manometer reading when circuit closes.❹ Slowly drop pressure and note manometer reading when circuit opens.❺ Use a screwdriver to turn set point adjusting screw: counterclockwise to increase set point, or clockwise to decrease set point.❻ Repeat steps 3, 4 and 5 until contacts change at desired increasing or decreasing differential pressure set point.Do not remove other covers or attempt to adjust other parts of themechanism. All have been precisely positioned at the factory andshould not be moved in the fi eld.。
SOR 中文操作手册

压力开关使用说明书
概述
本说明书是关于SOR压力开关在安装、过程联接、电气联接和调校方面的说明,此种形式压力开关不推荐用于存在高冲击压且高频率循环的高液压工作场合。
注意:如果您发现某台开关有损坏,请尽快与工厂或SOR产品当地服务代表联系,以获得返修登记号码,如果该产品无法返回工厂维修,应由授权的产品服务代表提供现场服务,请与工厂或SOR公司当地服务代表联系技术支持事宜。
设计与规范的改动请恕不另行通知。
电气联接
警告:在危险环境下开启防爆型开关,在盖移动前一定要保证电源已被断开,否则会导致严重的个人伤害和巨大的工厂损毁。
在开关壳内防置过多的导线或不当的联接可能会防碍开关正常的工作。
真空开关(接线图解)
当设定点为真空时,参
照图一当设定点为正压时,参照图二
兰(公用)黑(常开)红(常闭) 黄(公用2) 棕(常开2) 桔红(常闭2)绿(地线)
图一
第1页/ 2页 ISO 9001质量体系认证
图二。
SOR压力开关样本

Pressure and Vacuum Switches for Process ApplicationsForm 216SOR ® Pressure Switchesare rugged fi eld-mounted instruments. Thepressure sensing element of the SOR pressure switch is a force-balance, piston-actuated assembly. The sensing element is sealed by a fl exible diaphragm and a static o-ring. A wide selection of wetted parts materials for media compatibility and containment are available. A metal diaphragm may be welded to thepressure port for certain applications, thereby eliminating the o-ring.Application InformationThe SOR pressure switches in this catalog are suitable for a variety of process applications. Basic models with standard wetted parts are normally suitable for air, oil, water and non-corrosive processes. See the Quick Selection Guide on pages 4 and 5. Specifi c application requirements can normally be met by selecting optional components, such as switching elements, diaphragm systems and pressure ports. See How to Order on page 3. Certain applications may require customized specials. Consult the SOR representative in your area or the factory.This catalog describes switches that are: • General Purpose • Weathertight• Conventional Explosion ProofOther specifi c types of switches available through your SOR representative are:• Hermetically Sealed (for hazardous locations)• Pivot Seal (for high shock pressuresand cycle rates)• Differential Pressure• Temperature (remote and direct mount)• Electronic and Mechanical Level • Electronic Pressure12L6B36NNFeatures SwitchesComplete Product LineStandard models and customized specials cover pressure range from30 inches Hg VAC to 4000 psi.Robust ConstructionRugged, high-cycle rate tolerance, long life, not critical to vibration, high overrange and proof pressures, excellent corrosionresistance to hostile environments. Instrument QualityHigh resolution of Set Points, high repeatability, narrow dead band,negligible temperature effect.Wetted PartsWide selection materials, process connection confi gurations and sizes.Optional “fi re-safe” pressure sensor.Snap-Action Electrical SwitchingWide selection UL Listed and CSA Certifi ed switching elements for ACand DC service. Optional “hermeticallysealed” capsule for hazardous and hostile environments.Field AdjustableSelf-locking adjustment, no special tools required. No-charge factory calibration.Cost EffectiveSimple and fast installation without special tools, long service life, norequired periodic service or spareparts.UL Listed, CSA Certifi ed, ATEXCertifi ed, FM, JIS/RIIS Approved ModelsMeets most code and customer requirements.Built-In QualityRigid quality standards maintained from raw material to fi nished product.ServiceFactory sales engineers and area SOR representatives provideeffective and prompt worldwideservice.DeliveryRoutine shipments 7 to 10 working days. Emergency shipments via sameday air.Warranty3 years from date of manufacture.Quick Selection GuideBasic SOR pressure switches with standard wetted parts are normally suitable for air, oil, water and non-corrosive processes. The Quick Selection Guide on pages 4 and 5 shows these basic SOR pressure and vacuum switches. Corrosive service and particular customer requirements may require optional components. Refer to How to Order section below to build a customized model number or the dedicated page to locate optional components, such as switching elements, diaphragm systems, pressure ports and accessories. Each position in the model number, except Accessories, must have a designator.Design and specifi cations are subject to change without notice. For latest revision, see .6NN-K5-M4-C2A-YYModel Number SystemDiaphragmHousingPistonSwitching Element Range SpringPressure PortAccessoriesApplicationsSOR pressure switches in this catalog are suitable for a wide variety of continuous pressure applications. Specifi c application requirements can normally be met by selecting optional components, such as, switching elements, diaphragm systems and pressure ports. Certain applications may require customized specials. Consult the SOR representative in your area or the factory.How to OrderInformation and data in this catalog are formatted to provide a convenient guide to assistinstrument engineers, plant engineers and end users in selecting pressure switches for their unique applications.Steps 1 through 5 are required. Step 6 is optional. Orders must have complete Model Numbers, i.e. each component must have a designator.Step 1: Select Piston-Spring adjustable range/Set Point from Specifi cations (pages 7 & 8). (Piston/Spring combination determines adjustable range.)Step 2: Select Housing for type of pressure switch and service (page 9).Step 3: Select electrical Switching Element for electrical service (pages 10 & 11).Step 4: Select Diaphragm and O-Ring for process compatibility and containment (pages 12 & 13).Step 5:Select Pressure Port for process compatibility and connection (page 14).Step 6: Select Accessories required for service (page 16).How to OrderSwitchesExplosion ProofWeathertightBasic SOR pressure switches with standard wetted parts are normally suitable for air, oil, waterand non-corrosive processes. Corrosive service and particular customer requirements may require optional components. Refer to How to Order on page 3 to locate optional components, such as, housing, switching elements, diaphragm systems, pressure ports and accessories. Each position in the model number, except Accessories, must have a designator.WeathertightExplosion ProofStandard Construction• Housing: NN - aluminum; L - cast iron• Switching Element: SPDT; N - 10 amps @ 250 VAC; K - 15 amps @ 250 VAC• Diaphragm & O-ring: N4 - primary (wetted)diaphragm, TCP; o-ring (wetted) Buna-N• Pressure Port: 1/4” NPT(F); B1A - aluminum; F1A - carbon steelNotes1. See balance of catalog for construction options.2. Dead band values are expressed as typical expected at mid-range for a particular model number. See Dead Band Considerations on page 8.3. Design and specifi cations subject to changewithout notice. For latest revision, see.Standard Construction• Housing: NN - aluminum; L - cast iron• Switching Element: SPDT; K - 15 amps @ 250 VAC• Diaphragm & O-ring: N4 - primary (wetted)diaphragm, TCP; o-ring (wetted) Buna-N• Pressure Port: 1/4” NPT(F); B1A - aluminum; F1A - carbon steelNotes1. See balance of catalog for construction options.2. Dead band values are expressed as typical expected at mid-range for a particular model number. See Dead Band Considerations on page 8.3. Design and specifi cations subject to change without notice. For latest revision, see .WeathertightExplosion ProofExplosion ProofWeathertightStandard Construction• Housing: NN - aluminum; L - cast iron• Switching Element: SPDT; K - 15 amps @ 250 VAC • Diaphragm & O-ring: N4 - primary (wetted) diaphragm, TCP; o-ring (wetted) Buna-N. Piston 56 primary (wetted) diaphragm, 316SS.• Pressure Port: 1/4” NPT(F); B1A - aluminum; F1A - carbon steelNotes1. See balance of catalog for construction options.2. Dead band values are expressed as typical expected at mid-range for a particular model number. See Dead Band Considerations on page 8.3. Design and specifi cations subject to change without notice. For latest revision, see .Quick Selection Guide - VacuumPressure SwitchA bi-stable electromechanical device that actuates/deactuates one or more electrical switching element(s) at a predetermined discrete pressure/vacuum (Set Point) upon rising or falling pressure/vacuum.Adjustable RangeThe span of pressure between upper and lower limits within which the pressure switch can be adjusted to actuate/deactuate. It is expressed for increasing pressure.Set PointThat discrete pressure at which the pressure switch is adjusted to actuate/deactuate on rising or falling pressure. It must fall within the adjustable range and be called out as increasing or decreasing pressure.Dead BandThe difference in pressure between theincreasing Set Point and the decreasing Set Point. It is expressed as typical, which is an average with the increasing Set Point at mid-range for a pressure switch with the standard K switching element. It is normally fi xed (non-adjustable).Fire-SafeThe ability of a welded seal pressure sensor to contain the process at elevated temperatures up to 1200°F at the rated overrange pressure, unsupported by the body of the pressure switch.Hermetically SealedA welded steel capsule with glass-to-metal, factory-sealed electrical leads that isolates the electrical switching element(s) from the environment.OverrangeThe maximum input pressure that can be continuously applied to the pressure switch without causing permanent change of Set Point, leakage or material failure.SwitchesGlossary of T ermsSOR recognizes that there is no industry convention with respect to terminology and defi nitions pertinent to pressure switches. This glossary applies to SOR pressure switches.Proof PressureThe maximum input pressure that can be continuously applied to the pressure switch without causing leakage or catastrophic material failure. Permanent change of Set Points may occur, or the device may be rendered inoperative.RepeatabilityThe ability of a pressure switch to successively operate at a Set Point that is approached from a starting point in the same direction and returns to the starting point over three consecutive cycles to establish a pressure profi le.Repeatability on SOR switches will be smaller than 1% of full scale per ISA/ANSI S51.1. SPDT Switching ElementSingle-Pole, Double Throw (SPDT) has three connections: C — Common, NO — Normally Open and NC — Normally Closed, whichallows the switching element to be electrically connected to the circuit in either NO or NC state.DPDT Switching ElementDPDT is two synchronized SPDT switching elements which actuate together at increasing Set Point and deactuate together at decreasing Set Point. Discrete SPDT switching elements allow two independent circuits to be switched; i.e., one AC and one DC.The synchronization linkage is factory set, and is not fi eld adjustable. Synchronization is verifi ed by connecting test lamps to the switching elements and observing them go “On” simultaneously at actuation and “Off” simultaneously at deactuation.6NN-K5-M4-C2A-YY This table is a listing of piston-spring combinations and the corresponding adjustable ranges, dead bands, overrange and proof pressures. Adjustable range is expressed for increasing pressure; the Set Point must be within the adjustable range. Dead band is expressed as typical. See Dead Band Considerations on page 8.1. Dead band values are expressed as typicalexpected at mid-range with the standard Kswitching element assembly installed. Whenoptional switching elements are specifi ed,corresponding dead band multipliers shownon pages 8 and 10 must be applied.2. The 12/66 piston/spring combination isavailable with the N switching element only.3. Adjustable range becomes 10 to 45 in. wcwhenever switching elements other than K, KA,W or D are used.4. Special ranges may be possible. Consult thefactory or the SOR representative in your area. 5. Diaphragms may have an additional effect ondead band. See page 13, Note 9.6. Diaphragm life may be limited by using T or Hswitching elements with Numbers 1 and9pistons.7. Metric bar (mbar) values are practicalequivalents of the reference English values; notnecessarily exact mathematical conversions.This data appears on the product nameplatewhen metric engineering units are specifi ed.8. A breather drain (Accessory KK, see page 16)should be specifi ed when low pressureadjustable ranges are used in environmentswith signifi cant ambient temperature changes.9. Filled isolators attached to the pressure switchwill affect dead band.This table is a listing of piston–spring combinations and the corresponding adjustable ranges, dead bands, overrange and proof pressures. SOR vacuum switches are compound; they will operate in either vacuum or pressure modes. Adjustable range is expressed from maximum vacuum decreasing to zero gauge andincreasing to maximum pressure. Dead band is expressed as typical. See dead band considerations below. The Set Point must be within the adjustable range. A vacuum switch is generally better suited than a pressure switch for Set Points very near zero gauge.Notes1. Dead band values are expressed as typical expected at mid-range with the standard K switching element assembly installed. When optional switching elements are specifi ed, corresponding dead band multipliers shown below must be applied.2. Special ranges may be possible. Consult the factory or the SOR representative in your area.3. Diaphragms may have an additional effect on dead band. See page 13, Note 9.4. Metric bar (mbar) values are practical equivalents of the reference English values; not necessarily exact mathematical conversions. This data appears on the product nameplate when metric engineering units are specifi ed.1. Dead band values are expressed as typical expected atmid-adjustable range using the standard K switching element. When optional switching elements are specifi ed, corresponding dead band multipliers must be applied.2. Dead bands are fi xed (non-adjustable), except when T or H switching elements are used.3. Dead band can be adjustable by selecting T or H switching element. (Diaphragm life may be limited when used with Numbers 1 and 9 pistons.)4. Dead band multipliers must be applied to the typical dead band value shown for piston-spring combination in specifi cations, pages 7 and 8, whenever optional switching elements other than K, KA or W are used.5. Dead band can be widened by selecting an optional switching element with a multiplier greater than 1.0. Example: Model 6NN-G5-M4-C2A-YY Typical Dead Band 1.4 psi G-Switching Element multiplier = 3 Corrected Typical Dead Band 1.4 x 3 = 4.2 psi6. See item #9, page7.Dead Band Considerations52NN-K 116-M4-C2A-YYClass II, Group E, F, & G; Divisions 1 *L*S*LC*T A*J4NNN6P3Electrical: 3/4” NPT(F) - Left, Right Material: AluminumSee Agency Listings pages 17 & 18.See Switching Element Groups 1, 2, 3 & 4 below.N3N4RN RBSwitchesStep 2: Housing*BD only available with RN, RT housings.*C micro switch is not available in L, S and TA housings.*CA micro switch only available in PP, NN, N3 and N4 housings.Switches Step 3: Switching Element6NN-K5-M4-C2A-YYCross reference compatibility chart on page 9 to ensure that switching element will fi t in housing. Review notes on page 11 for more details.SwitchesStep 3: Switching Element6NN-K 5-M4-C2A-YYNotes1. Double switching elements have wire leads except when supplied in housings RB, RM, RN, RS, RT, B3, B4, B5, B6 and J4. Terminal blocks are standard in these housings.2. Dead band multipliers must be applied to thetypical dead band fi gures given in the specifi cation tables on pages 7 and 8.3. Switching element ambient temperature limits:-65 to 400o F (-54 to 200o C) B, Y, W-65 to 250o F (-54 to 120oC) A, E, & J-40 to 167o F (-40 to 75oC) AF, AG, E F , EG,JF, JG-13 to 158o F (-25 to 70o C) BD-65 to 180o F (-54 to 80o C) All others4. The hermetically sealed switching elementcapsule is ATEX Approved, UL Listed, CSA Certifi ed and SAA Approved as an explosion-proof snap switch according to the following table with conditions and exceptions specifi ed in Note 3.5. Switching elements W, & Y have Elgiloy springs.6. Certain switching elements can handle greater voltage and/or amperage. Consult the factory should your requirements exceed catalog values. All switching elements above except BD are UL Recognized and CSA Certifi ed. The DC current ratings marked with an asterisk (*) are not UL Listed but have been verifi ed by testing and/or experience.7. Ambient temperature is reduced to 200°F (93°C) for J, JJ, A, AA, E, EE, B, BB, Y, YY, & W switching elements when CV accessory is selected.CAUTION: The switching element assemblyhas been precisely positioned in the housing at the factory for optimum performance. Any inadvertent movement or replacement in the fi eld will degrade performance, could render the device inoperative, and can void the warranty unless factory authorized proceduresare followed.Notes Array1. N4 diaphragm system is standard, but requiresa designator in the model number. It is normallysuitable for air, oil, water and noncorrosiveprocesses. M2 diaphragm system is standardon Number 56 vacuum switches. (See notes10 & 13.)2. U7 designates a welded fl ush-type diaphragm.Available only in 1” NPT(M) 316SS onNumbers 5 & 6 pistons with K switchingelement. See page 15.3. U8 designates the welded fi re-safe diaphragmsystem. 316SS is stocked. Not available onNumber 1 piston or vacuum switches.Example: U8-C2A is a 316SS fi re-safe weldeddiaphragm system. See page 15.4. U9 designates a welded diaphragm system.Not available on vacuum switches.Example: U9-A1A is a Monel weldeddiaphragm system. See page 15.5. Other diaphragm and o-ring combinations maybe available. Consult the factory or the SORrepresentative in your area for more information.6. Wetted parts have been selected asrepresenting the most suitable commerciallyavailable material for use in the service intended.However, they do not constitute a guaranteeagainst corrosion or permeation, since processes vary from plant to plant and concentration ofharmful fl uids, gases or solids vary from time totime in a given process. Empirical experienceby users should be the fi nal guide. Alternatematerials are generally available.(Continued on page 13.)7. N3 diaphragm system utilizes a durableback-up diaphragm for high cycle-rate, highshock applications where Buna-N and TCP are compatible with the process. Consult factory if process temperatures are well below freezing.8. This table shows allowable minimum andmaximum temperatures for o-rings. Consult the factory for temperatures down to –65°F onfi re- safe and welded metal diaphragmsystems.9. Dead bands are slightly higher when usingH, J, N3, N6, U or W series diaphragmoptions. Consult the factory.10. Diaphragm systems N1, N3, N4, N5, N6, N7,N8, P1, R1, S1, S2, W2, W4, W5, W6, Y1,U8, U9 are not available on Number 56vacuumswitches.11. M9 diaphragm system is suggested for steamapplications up to 400°F.12. If Kalrez, EPR or Viton is selected for hightemperature process media or ambienttemperature requirements, the A, B, E, J, W or Y switching elements are suggested withreference to the table in Note 3, page 11. 13. Only diaphragm systems N1, N4, N5, N7, N8and P1 are available on the 12-66 piston-springcombination.SwitchesStep 5: Pressure Port6NN-K5-M4-C2A -YYNotes1. Select designators for material and connection size. Large bold-face letters denote those items generally available from stock. Small light-face letters denote items with limited stock and possible long delivery.2. 1/4” and 1/2” tapered BSP(F) pressure ports are available. Consult factory.3. Combinations are possible when a particular connection size is not available for the range (piston/spring) desired. For example, if 2” NPT(F) is desired for a Number 4 piston, the Number 12 pressure port can be supplied. The piston would be designated as Number 124 and the overrange and proof pressures for Number 12 apply. Note: 124, 125 and 126 are the only available combinations.4. Many other materials such as PVC, Kynar, etc., are available. Denote materials not shown by specifying an X followed by the required connection size, and describe the material.Examples:X2A = PVC pressure port with 1/2” NPT(F) connection.X1A = Titanium pressure port with 1/4” NPT(F) connection.Non-metal pressure ports generally reduce proof pressure and may reduce overrange pressure. The pressure port material may limit the process temperature. Delivery may be longer than normal.5. Raised-face and fl at-face fl anges to match ASA 150 and ASA 300 lb. in commercially available materials can be supplied on Series 12 and 4 pistons by adding an X suffi x to the model numbers and specifying “X - (size) inch (material) (raised- or fl at-) face fl ange to match ASA (rating) lb.”6. Brass not available on Piston Numbers 9 and 1.7. 1/4” NPT(F) Flushing Port standard on C6A pressure ports.*C4A only available with Pistons 5 & 6 when U7 diaphragm is specifi ed. See page 15.See next page for presentation of welded diaphragm and FM Approved fire-safe systems.Pressure and Vacuum SwitchesWelded Diaphragm & Fire-Safe SystemsFactory Mutual System Approved - U.S Patent Number 4,438,305Two-inch Pressure PortThe wide pressure port minimizes the possibility of clogging when the process media is sludgy or viscous. See page 20 for dimensions. A 2” NPT(F) pressure port with a 1/4” NPT(F) fl ushing port can be supplied with a welded diaphragm, or with a conventional diaphragm and o-ring combination.ConnectionPiston ShaftDiaphragmSwitches Step 6: Accessories6NN-K5-M4-C2A-YY*Consult the factory for materials other than 316/316L.CSATIISATEXBASEEFASOR Pressure Switches in this catalog may be specifi ed with manual reset electrical switching elements D or M. D actuates automatically on increasing pressure. M actuates automatically on decreasing pressure. Depress the button to manually reset. Housings must be RB (weathertight) or S (explosion proof) because of the requirement of a hub for the manual reset assembly. Refer to page 3 for How to Order instructions.Shipping WeightsManual Reset ButtonRB - Weathertight S - Explosion ProofSwitchesManual ResetActual shipping weights may vary from the charted values because of product material, confi guration and packaging requirements.NotePK Pipe Kit adds approximately 1.5 lbs. (0.7 kgs). TB Junction box adds approximately 5 lbs (2.25 kgs).Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certifi ed drawings for a particular model number.Notes 1. Dimensions in this catalog are expressed as millimeters over inches (Linear = mm/in.). 2. Dimensions marked with an asterisk (*) on housing dimension drawings (pages 20 through 31) vary with respect to process connection size. The chart below lists these dimension variances. 3. Electrical Connection Size: 3/4” NPT(F) standard. 1/2” NPT(F), 1/2” NPT(M), M20 x 1.5, PG 13.5, PF 3/4” optional. Consult the factory for compatibility with selected housing or agencylisting.DimensionsSwitchesDimensionsDimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certifi ed drawings for a particular model number.Wide Pressure Port: C6ASee description on page 15.Pipe Mounting Kit: PKDrawing # 0091354Drawing # 0090300Drawing # 0091353Junction Box with T erminalBlock:TBDimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certifi ed drawings for a particular model number.Weathertight - NEMA 4, 4X, IP65Housing PP, P3 and PF are General Purpose.(Cover gasket is not installed.)Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certifi ed drawings for a particular model number.Piston Numbers 5, 6, 1, 9, 56Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certifi ed drawings for a particular model number.Open BracketDesignators: H3Piston Numbers 5, 6, 9, 1, 56Drawing # 0090027Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certifi ed drawings for a particular model number.Weathertight - NEMA 4, 4X, IP65Designators: N6Piston Numbers Drawing 0090020Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certifi ed drawings for a particular model number.Conventional Explosion ProofDimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certifi ed drawings for a particular model number.Conventional Explosion ProofDesignators: SPiston Numbers 5, 6, 9, 1, 56Drawing # 0090147Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certifi ed drawings for a particular model number.Conventional Explosion ProofPiston Numbers 5, 6, 9, 1, 56SC shown. LC identical except right-handelectrical connection only.Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certifi ed drawings for a particular model number.Conventional Explosion ProofPiston Numbers 5, 6, 9, 1, 56Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certifi ed drawings for a particular model number.Explosion ProofDimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certifi ed drawings for a particular model number.Weathertight - NEMA 4, 4X, IP65Drawing # 0090271Designators: RB Manual ResetPiston Numbers 5, 6, 1, 9, 56Pressure and VacuumSwitches Dimensions Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certifi ed drawings for a particular model number.Conventional Explosion ProofDrawing # 0090169Designators: S Manual ResetPiston Numbers 5, 6, 1, 9, 56*Refer to Dimensions table on page 19 for changes in length due to process connection size, including A dimension.Registered Quality System to ISO 9001:200032/32Form 913-888-2630echOsonix Level TransmittersT emperature SwitchesP r e s s u r eFlowLevelLevel SwitchesFlow SwitchesPressure SwitchesSOR ®offers a full line of commercial-grade process instruments.TemperatureRegistered Quality System to ISO 9001:2000Form 216 (04.08) ©2008 SOR Inc.We Deliver Quality On TimeSOR Europe, Ltd.Star RoadPartridge Green, Sussex RH13 8RA, United Kingdom Phone +44-140-371-1331Fax +44-140-371-0177sales@SOR - ChinaRoom 903, No. 10 Building Wan Da PlazaNo. 93 Jian Guo Road Chao Yang District Beijing, China 100022Phone +86 (10) 5820 8767Fax +86 (10) 5820 8770SOR Inc.14685 West 105th Street Lenexa, Kansas 66215Phone 913-888-2630Toll Free 800-676-6794Fax 913-888-0767Process Instrumentation。
SOR压力开关

Application Information
The SOR pressure switches in this catalog are suitable for a variety of process applications. Basic models with standard wetted parts are normally suitable for air, oil, water and noncorrosive processes. See the Quick Selection Guide on page 3. Specific application requirements can normally be met by selecting optional components, such as switching elements, diaphragm systems and pressure ports. See How to Order on page 3. Certain applications may require customized specials. Consult the SOR representative in your area or the factory. This catalog describes switches that are: • General Purpose • Weathertight • Conventional Explosion Proof
压力和差压变送器详细详解使用说明书

压力和差压变送器详细使用说明(一)差压变送器原理与使用本节根据实际使用中的差压变送器主要介绍电容式差压变送器。
1. 差压变送器原理压力和差压变送器作为过程控制系统的检测变换部分,将液体、气体或蒸汽的差压(压力)、流量、液位等工艺参数转换成统一的标准信号(如DC4mA~20mA 电流),作为显示仪表、运算器和调节器的输入信号,以实现生产过程的连续检测和自动控制。
差动电容式压力变送器由测量部分和转换放大电路组成,如图1.1所示。
图1.1 测量转换电路图1.2 差动电容结构差动电容式压力变送器的测量部分常采用差动电容结构,如图1.2所示。
中心可动极板与两侧固定极板构成两个平面型电容H C和L C。
可动极板与两侧固定极板形成两个感压腔室,介质压力是通过两个腔室中的填充液作用到中心可动极板。
一般采用硅油等理想液体作为填充液,被测介质大多为气体或液体。
隔离膜片的作用既传递压力,又避免电容极板受损。
当正负压力(差压)由正负压导压口加到膜盒两边的隔离膜片上时,通过腔室内硅油液体传递到中心测量膜片上,中心感压膜片产生位移,使可动极板和左右两个极板之间的间距不相对,形成差动电容,若不考虑边缘电场影响,该差动电容可看作平板电容。
差动电容的相对变化值与被测压力成正比,与填充液的介电常数无关,从原理上消除了介电常数的变化给测量带来的误差。
2. 变送器的使用(1)表压压力变送器的方向低压侧压力口(大气压参考端)位于表压压力变送器的脖颈处,在电子外壳的后面。
此压力口的通道位于外壳和压力传感器之间,在变送器上360°环绕。
保持通道的畅通,包括但不限于由于安装变送器时产生的喷漆,灰尘和润滑脂,以至于保证过程通畅。
图1.3为低压侧压力口。
图1.3 低压侧压力口(2)电气接线①拆下标记“FIELD TERMINALS”电子外壳。
②将正极导线接到“PWR/COMN”接线端子上,负极导线接到“-”接线端子上。
注意不得将带电信号线与测试端子(test)相连,因通电将损坏测试线路中的测试二极管。
压差开关使用说明

3S压差控制器
用途:
3S系列压差控制器,通常用于水,油系列中控制供液管与回液管的压差控制,一
种典型的应用是,把阀门安装在系统水(油)泵附近的旁通管路中,当系列液管二端的压差升高(或降低)而超过控制器设定值时,则阀门进而开大(或关小),从而系统液管二端的压差减小,达到系统的正常运行.
概述:3S系列压差控制器的两侧各有一个具有高灵敏感度的感压元件,元件二端的压力一旦变化,即引起开关机构动作来控制系统的设备.
电器参数:
电流电压COSA.C.125/250无诱导电流112满载电流0.7512瞬时电流0.4572
性能参
数: Mpa 型号调节范围开关差工厂设定压差最大工作压力
MinMaxOFFONJC15C0.03—0.2≤0.030.050.021.70JC2C0.01—0.150.050.03 0.0151.70JC35C0.05—0.350.10.10.051.70JC60CH0.1-0.600.10.350.403.30 注:以上控制器的接头螺纹均为M12*1.25.如果客户需要英制螺纹则须在型号后加缀“E”即可.一般采用的英制螺纹为7/16”-20UNF,另有延时功能的型号后加缀T需订做。
触点形式:
1:公共接点1-3:压力上升时关闭1-5:压力下降时关闭
箭头表示压差增大时的动作方向安装注意: 1. 在安装控制器接管
时,不要把进出口端的方向搞错.在安装控制器接管时,控制器的螺母与接头必须用二把10”板手板紧.
青岛悦联 15:29:21
贴有标签HP的接头是接高压,另一头接低压。
SOR简介

SOR开关简介SOR公司是美国著名的压力开关生产厂商,是世界上唯一的可生产压力、差压、温度、液位及流量开关的厂商,它生产的开关广泛应用于电厂及石油化工领域。
目前该厂商生产的多种类型高品质开关,在我国的大、中型火力发电厂有着极为广泛的使用,对电厂发电机组系统的保护和可靠运行起到了很好的作用。
SOR开关符合国际质量标准ISO9001,此产品的高可靠性和精度得到所有用户的肯定。
在2001年年度中,国内的300MW以上火力发电新建机组几乎全部采用SOR 逻辑开关来对全厂系统进行保护。
由此可见,此品牌开关在电力行业的用户信誉是其他品牌开关所无法比拟的。
1、压力开关工作范围广(-15--4000psi),设点稳定,重复率高,死区小,几乎不受温度影响。
开关品种齐全,范围设计合理,并对各种使用环境均有专业工况。
2、差压开关重复率高,死区小,受温度及静力影响小。
107系列是低压差压开关,其设点稳定,精度高,是电厂的炉保系统应用广泛的一种差压开关。
102/103系列可承受较高静压,而所测压差可很微小,且精确度很高,故在电厂管道滤网上广泛应用。
3、温度开关受环境温度影响小,反应快速,重复率高,死区小。
工作范围:-45℃--540℃4、液位开关有机械式和电子式等多种形式,其机械式开关利用磁吸合原理,工作可靠,无毒,不使用水银等有毒物质,完全符合当今的环保要求。
其独特的陶瓷开关,使SOR的液位开关的适用温度得以大大提高,完全满足电力行业的各种工况。
5、超声波物位变送器-高能量在苛刻的工况下(粉尘,泡沫,蒸汽)有很强的穿透能力高能量的声波确保所接收的回波在能量衰减后仍可用于测量-低频低频声脉冲波比高频有更强的穿透力,距离更远低频比高频受到更少的质体干扰最大的测量范围可达80m-自动增益调节无需进行空罐操作来消除虚假回波的干扰,始终能够锁定真实物位回波,不会造成回波信号的丢失唯一可根据工况情况自行调节的产品可以在其他产品失败的工况下工作SOR部分电厂用户清单上海外高桥电厂4×300MW √√√上海吴泾热电厂2×300MW√√上海华能石洞口第二电厂2×600MW √√上海杨树浦电厂2×125MW √√上海闸北电厂4×100MW燃机√上海金山石化自备电厂2×200MW √√浙江嘉兴电厂一期2×300MW √√浙江嘉兴电厂二期5#/6#机2×600MW √浙江台州电厂2×300MW √√浙江北仑港电厂2×600MW √√浙江宁波纸厂自备电厂2×50MW√浙江温州电厂2×300MW √浙江长兴电厂2×300MW √浙江秦山核电厂二期2×600MW √√√浙江秦山核电厂三期2×600MW √江苏利港电厂2×600MW √江苏徐塘电厂(以大代小)2×300MW √√江苏彭城电厂2×300MW √江苏南化自备电厂2×50MW √√江苏扬子石化自备电厂2×125MW √江苏金陵石化自备电厂2×50MW √√江苏华能南京电厂2×300MW √江苏华能南通电厂2×300MW √√江苏华能太仓电厂2×300MW √江苏华能淮阴电厂2×200MW √江苏华能淮阴电厂二期2×300MW √√江苏新海电厂2×125MW √江苏南京下关电厂2×135MW √江苏镇江高姿电厂4×135MW √√江苏盐城电厂2×135MW √江苏扬州电厂2×200MW √√江苏扬州第二电厂2×600MW √√江苏江阴夏港苏龙电厂4×135MW √江苏江阴夏港苏龙电厂二期2×300MW √江苏太仓港环保电厂一期2×135MW √√江苏太仓港环保电厂二期2×300MW √√江苏太仓港环保电厂三期2×300MW √√江苏南通天生港电厂4×135MW √√江苏南通天生港电厂二期2×300MW √√江苏南京扳桥电厂2×135MW √江苏镇江谏壁电厂2×300MW √√江苏贾旺电厂4×135MW √√√江苏大屯发电厂2×135MW √江苏华润常熟电厂3×600MW √√安徽平圩电厂2×600MW √安徽田家庵电厂1×300MW √安徽铜陵电厂1×300MW √√安徽淮北电厂2×300MW √安徽洛河电厂4×300MW √安徽马钢自备电厂2×50MW √√√安徽安庆电厂2×300MW √福建厦门嵩屿电厂2×300MW √√√福建漳平电厂2×100MW √福建邵武电厂2×125MW √广东华能汕头电厂2×300MW √√广东珠江电厂2×300MW √√广东沙角B厂,C厂2×600MW √√广东珠海电厂2×600MW √√大亚湾核电站√湖南石门电厂2×300MW √√湖南湘潭电厂2×300MW √√湖南株州电厂2×300MW √√湖南益阳电厂2×300MW √√湖南鲤鱼江电厂2×300MW √√湖北襄樊电厂4×300MW √√湖北汉川电厂2×300MW √√湖北武钢自备电厂2×200MW √√湖北黄石电厂2×300MW √√湖北蒲圻电厂2×300MW √河南首阳山电厂2×300MW √√河南安阳电厂2×300MW √河南信阳电厂2×300MW √√河南登封电厂2×300MW √√√河南永城电厂2×300MW √√河南新乡电厂2×135MW √河南神火电厂2×135MW √河南周口电厂2×135MW √山东石横电厂4×300MW √山东胜利油田自备电厂2×300MW √山西阳泉电厂2×300MW √√山西太原第一热电厂2×300MW √√山西太原第一热电厂二期2×600MW √√山西河曲电厂一期2×600MW √√北京石景山热电厂2×100MW √北京第二热电厂2×200MW √河北沙岭子电厂4×300MW √√河北定州电厂2×600MW √√天津大港电厂2×300MW √天津大唐盘山电厂二期2×600MW √√哈尔滨第三热电厂2×300MW √√吉林省吉林热电厂2×200MW √华能大连电厂2×300MW √√陕西渭河电厂2×300MW √陕西蒲城电厂2×300MW √√√陕西神木电厂2×100MW √√陕西宝鸡电厂4×300MW √陕西西郊热电厂2×300MW √√甘肃靖远电厂2×300MW √√甘肃西固电厂2×125MW √√甘肃平凉电厂4×300MW √√内蒙达旗电厂2×300MW √√√内蒙国华准格尔电厂2×600MW √√内蒙托克多电厂二期2×600MW √√宁夏大坝电厂2×300MW √√云南曲靖电厂2×300MW √√贵州安顺电厂2×300MW √√√四川成都热电厂2×142MW √√巴基斯坦恰希玛核电站一期2×350MW √巴基斯坦木扎法戈电厂2×300MW √越南协福电厂2×100MW √√√伊朗萨汉姆燃机电厂2×350MW √√孟加拉巴库电厂2×125MW √√主要OEM配套厂家名称压力开关液位开关电子式液位产品北京良乡√√北京重型机器厂√√√上海汽轮机厂√√上海电机厂√√上海锅炉厂√上海电站辅机厂√√上海电力修造厂√上海水泵厂√上海鼓风机厂√√上海重型机器厂√√杭州汽轮机厂√√杭州锅炉厂√东方汽轮机厂√东方电机厂√东方锅炉厂√哈尔滨汽轮机厂√哈尔滨电机厂√哈尔滨锅炉厂√沈阳鼓风机厂√√沈阳水泵厂√。
SOR_NN系列_压力开关_差压开关

美国SOR NN系列压力开关差压开关2008-07-07 10:22:46 作者:佚名来源:西安奥信自动化仪表有限责任公司浏览次数:2 文字大小:【大】【中】【小】•美国SORNN系列压力开关差压开关美国SOR美国SOR差压开关美国SOR温度开关美国SOR液位开关美国SOR流量开关SOR公司是世界上著名的开关制造公司,是一家集压力开关、差压开关、温度、液位、流量于一体的专业化国际公司,其产品具有耐高压、美国SOR NN系列压力开关差压开关美国SOR美国SOR差压开关美国SOR温度开关美国SOR液位开关美国SOR流量开关SOR公司是世界上著名的开关制造公司,是一家集压力开关、差压开关、温度、液位、流量于一体的专业化国际公司,其产品具有耐高压、高温、防震、防腐蚀、抗冲击力、切换差小等特点,广泛应用于石油、化工、电力、冶金、制药、造纸、食品等行业。
技术特点SOR压力开关采用国际标准的连接部件,标准型可用于空气、油、水和各种非腐蚀性介质,对于腐蚀性介质的特殊应用,SOR压力开关同时也提供了可选择的功能部件。
SOR压力开关突出的宽整定范围和低死区性能和多接点选项完全可以替代传统的接点压力表应用,大接点容量,可以直接控制水泵和电动机等动力设备,简化控制回路,减少系统维护量,进而提高系统的可靠性和安全性。
技术参数◆接点容量: 250VAC 15A , 30VDC 5(10)A◆环境温度:可达 -54~200℃◆防护等级: NEMA4 、 NEMA4X 、 IP65 、 IP68◆隔爆: 0 、 1 、 2 区; Group I 、 Group IIA 、 Group IIB 、 Group IIC ; ClassI 、 Class II 、 ClassIII 等NN 系列◆压力 / 真空 / 复合开关◆抗恶劣环境◆ CSA 、 CE 认证◆低成本、经济型◆单设定点,配刻度线◆整定范围 1~480bar◆最小标准死区 0.007bar◆典型标准死区 0.3bar◆最大标准死区 7barSOR单设定点压力开关选型表型号设定值范围kg/cm2回程差kg/cm2防爆产品型号9NN-K4-N4-F1A 7.03-35.15 0.37 9L-K4-N4-F1A9NN-K5-N4-F1A 14.06-70.31 0.65 9L-K5-N4-F1A9NN-K45-N4-F1A 14.06-123.04 1.05 9L-K45-N4-F1A最大承受压力 175.77 kg/cm2 ;出厂实验压力 421.85kg/cm26NN-K2-N4-F1A 0.49-2.11 0.046L-K2-N4-F1A6NN-K3-N4-F1A 0.84-7.03 0.066L-K3-N4-F1A6NN-K5-N4-F1A 1.41-12.66 0.106L-K5-N4-F1A6NN-K45-N4-F1A 1.76-19.33 0.136L-K45-N4-F1A最大承受压力 105.46 kg/cm2 ;出厂实验压力 175.77kg/cm2SOR压力开关采用国际标准的连接部件,标准型可用于空气、油、水和各种非腐蚀性介质,对于腐蚀性介质的特殊应用,SOR压力开关同时也提供了可选择的功能部件。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
概述:此说明书提供101/121系列差压开关的安装,电气连接,过程连接和标定方面的信息。
注:SOR不建议现场对开关进行修改和修理。
产品应该返回SOR进行检查和必要的修理工作。
请与工厂联系以便获得返修登记号码。
任何现场的工作都应该由合格的技术工程师使用工厂授权的操作步骤来进行操作。
工作原理:膜片和活塞集合感应工艺压力。
活塞对差压进行反应,移动使电子开关元件动作(或不动作)的轴杆。
压力低的一边和一个可调范围的弹簧进行与高压力方面的作用。
弹簧范围的可调整性决定设定点(参见标定部分)。
警告:小心安装,避免移动电子开关元件或它的外壳。
如果产生两者之一的移动可能会改变标定或使开关不动作。
设计与规范的改动请恕不另行通知。
安装:1、确保开关外壳用合适的螺栓安装在面板架或安装柱上。
重要:当把外壳和整体安装面板用螺栓固定在不规则或不平坦的表面时,在外壳和安装表面安装橡胶垫片,防止外壳的变形。
警告:在平整表面的安装失败会在外壳上产生扭转力,从而可能导致误动作或不工作。
2、不建议通过压力接口或电气接口进行在线安装。
3、建议安装方位为:压力高的连接口在6点钟位置。
尽管如此,装置仍可以在任何位置安装。
可选的呼吸排放管线应该位于允许潮湿气体从外壳内部排出的位置。
呼吸排放管线应保持喷涂和外来物体的清洁。
过程连接使用两个扳手连接工艺管线和引压口:一个固定引压口上的六角螺母,另一个旋紧工艺管或管接头。
高压端(标有HI)和低压端(标有LO)有标准的1/4“NPT(F)或1/4”BSP(F)连接。
重要:刚硬的工艺管必须最小程度的弯曲或扭转,否则可能会打乱内部部件的顺序位置,从而在安装后改变标定或使装置不工作。
小心避免过程压力口从外壳上的松动或外壳从电气部分松动。
101/121系列差压开关使用说明书电气连接确保连线与所有的当地和国际的电气方面的规定一致,根据相关的国际和当地的安全规定来安装。
警告:在打开防爆型开关的上盖之前,必须断开电源。
否则,会导致严重的人员伤害或财产的损坏。
进行电气连接时,要避免电器开关元件的移动。
电气连接不是螺纹接线端就是18”长的电线连接。
螺纹接线端和接线端子由电子部分外壳内部的绝缘板确定。
参考图1所示的不同颜色电线的连线图。
FIGURE 1注:不应在开关壳内放置过多导线或进行不当连接,可能会影响开关的正常工作。
标定迷你密封型打开防风雨盒盖。
用1/8”六角扳手旋转调整螺母到要求的设定点。
顺时针旋转调整螺母来升高设定点,逆时针减小设定点。
使用粗略或精密设定点标定步骤。
其他类型使用3/4”开口扳手,顺时针旋转六角调整螺母,升高设定点,逆时针减小设定点。
在外壳内壁的标定比例尺上垂直看到的调整螺母的上限是一个大概的设定点。
如果需要粗略或精密的设定点调校,可参考相应的标定步骤。
粗略标定步骤1、连接可变的压力源到测试表和高压力端口2、通过C-公共端连接测试灯或欧姆表和NO-常开开关元件触点。
3、当回路闭合时,升高压力注意测试表的读数。
4、当开路时,缓慢减小压力注意测试表的读数。
5、顺时针旋转设定点调整螺母,升高设定点,或逆时针减小设定点。
6、重复步骤3,4和5直到在要求的升高或降低差压设定点上的开关触点的动作。
精密标定步骤精密标定步骤依靠稳定的系统压力。
在模拟的压力应用场合进行差压开关的标定可以加强设定点精度。
建议使用下面的测试仪器。
1、差压计2、可变压力源3、排放和均衡阀4、测试灯或欧姆表确定在升高或降低设定点时是否有临界设定点的出现,使用相应的程序进行调校。
对于升高差压过程中的出现的临界设定点1、通过C-公共端把NO-常开开关部件触点和连续显示灯或欧姆表连接。
2、关闭排放阀,打开均衡阀,同等升高HI和LO端至一个固定的压力使得差压开关在正常的操作条件下3、在稳定的固定压力下,关闭均衡阀,隔绝HI和LO端4、保持高端压力的稳定,轻轻打开LO端排放阀,来减小LO端压力(升高差压)直到显示器出现需要的差压设定点。
关闭排放阀稳定差压。
检查开关触点与下面的差压趋势图。
依照图下面与开关触点状态匹配的说明进行操作。
参见SOR#468的尺寸参考图。
若需确切尺寸图联系工厂。
如果触点在临界升高差压设定点精密动作,重复步骤2-4按照要求校验标定。
标定完成。
如果达到临界升高差压值,触点打开,逆时针旋转设定点调整端直到触点动作,重复步骤2-4。
如果达到临界升高差压值,触点关闭,顺时针旋转设定点调整端直到触点断开。
从这点,逆时针旋转设定点调整端直到触点动作,重复步骤2-4。
对于下降差压过程中的出现的临界设定点1、通过C-公共端把NO-常开开关部件触点和连续显示灯或欧姆表连接。
2、关闭排放阀,打开均衡阀,同等升高HI和LO端的压力至正常操作的高端压力值3、随着正常的HI端压力的稳定,关闭均衡阀,隔绝HI和LO端4、轻轻打开LO端排放阀,来减小LO端压力(升高差压)直到数字显示器出现正常操作差压。
关闭排放阀来稳定差压。
触点应该在达到正常操作差压时关闭(或动作)。
如果触点始终在正常操作差压打开,逆时针旋转设定点调整端直到触点动作。
5、保持高端压力稳定,轻轻打开LO端排放阀,来升高LO端压力(减少差压值)直到需要的差压设定点出现在数字显示器上。
关闭均衡阀来稳定差压。
检查开关触点与下面的差压趋势图。
依照图下面与开关触点状态匹配的说明进行操作。
如果触点在临界下降差压设定点精密断开,重复步骤2-5按照要求校验标定。
标定完成。
如果达到临界下降差压值,触点打开,逆时针旋转设定点调整端直到触点动作,从这点,顺时针旋转设定点调整端直到触点改变,重复步骤2-5。
如果达到临界下降差压值,触点关闭,顺时针旋转设定点调整端直到触点改变。
重复步骤2-5。
SOR 102系列差压开关使用说明书防爆型-AD外壳JIS/RIIS认证的IIC-T6 –JS外壳CENELEC (BASEEFA)认证的EEx d IIC T6-CL附件1、凸边帽遮住设定点调整端2、高压端过程连接1/4”NPT(F)[1/2”NPT(F)]3、严密密封的开关元件引出18”长的导线4、电气接口1/2”NPT(M)5、电气接口3/4”NPT(F)6、全天候开关外壳(外壳下有接线端子)全天候型-W1外壳概述此说明书提供102系列差压开关的安装,电气连接,过程连接和标定方面的信息。
设计与规范的改动请恕不另行通知。
工作原理:活塞集合感应工艺压力。
活塞对差压进行反应,移动与一个扭转的十字型轴连接的杆。
十字轴的一端连接到与弹簧范围有关的杆上,另一端有一个使电子开关部件动作的横杆。
应用场合:102系列差压开关适用于范围宽广的工艺和液压场合,从空气,水,液压流体到高腐蚀、高温的场合。
有关细节请垂询当地SOR代理商或美国SOR工厂。
警告:安装时不要移动开关元件和外壳。
任何不经意的移动会扰乱相关内部工作部件的位置或影响标定和正常工作。
安装确保连线与所有的当地和国际的电气方面的规定一致,根据相关的国际和当地的安全规定来安装。
安全安装支架或底盘,与管道支柱水平,安装盘表面使用合适的螺栓。
102系列不属于对位置敏感的器件,可以全位置安装过程连接高压端(HI)和低压端(LO)有标准的1/4“NPT(F)或1/2”NPT(F)可选。
警告:如果介质中有存在悬浮不洁净颗粒的话,建议在HI和LO的连接口安装20micron的过滤器。
电气连接全天候型:断开电源。
打开上盒盖。
接线端是标准型,除了B,BB,W和Y型高温开关元件。
绝缘板上标有C-公共端,NO-常开,NC-常闭。
如果是2-SPDT,则还有C2,NO2,NC2。
防爆型:警告:用于危险环境时,从应用场合撤出前,确定工作区域已被降低危险级。
否则会导致人员和财产的严重危害。
严密密封的开关元件有18”长的18AWG不同颜色的导线引出接线端,标有C-公共端,NO-常开,NC-常闭和G-地。
如果使用2-SPDT,则有额外的引线标有C2,NO2,NC2。
特殊条件使用CENELEC(BASEEFA),JIS/RIIS安全型1、装置和开关必须配有接线盒,且确保与仪表集合IIC结合。
AD外壳:配CENELEC(BASEEFA)认证的接线盒。
JS 外壳:JIS/RIIS认证的接线盒。
2、当开关与增强型安全接线盒一起使用时,集合必须可以通过BS 5501:Part 1:1997规定的冲击实验。
3、增强型安全区域,密封必须最小满足IP54等级。
4、开关必须放置在现有入口的区域中标定粗略标定:标定的开关不用参考系统(稳定)压力(低端排放)。
测试仪器:压力表变化压力源测试灯或欧姆表1、打开全天候型开关的凸边帽2、用5/32Allen扳手插入到设定点调整端3、连接测试灯或欧姆表到C和NO端4、升高压力至要求的设定点。
5、顺时针旋转扳手升高设定点,逆时针减小设定点。
用测试灯或欧姆表检测开关动作。
6、对于下降压力设定点,减小压力到需要的设定点,重复步骤5。
7、取下扳手,盖好凸边帽。
精密标定标定的开关要依靠系统(稳定)压力。
标定在模拟系统中或趋向于实际的应用场合中进行,会增强动作的精密性测试仪器:差压表变化压力源测试灯或欧姆表排放阀和均衡阀1、打开全天候型开关的凸边帽2、用5/32Allen扳手插入到设定点调整端3、连接测试灯或欧姆表到C和NO端4、升高同样的压力在HI和LO端至系统(稳定)操作压力(均衡阀)打开5、升高差压,调整设定点:关闭均衡阀,泄放LO端压力,直到显示器上出现需要的压力,测试灯或欧姆表确认设定点。
顺时针旋转扳手升高设定点,逆时针减小设定点。
用测试灯或欧姆表检测开关动作。
6、对于下降差压设定点:差压必须大于或等于上升设定点,然后轻轻打开均衡阀直到显示器上出现需要的下降压力,测试灯或欧姆表确认设定点。
有必要的话重复步骤5。
7、取下扳手,盖好凸边帽。
警告:不要打开其他盒盖或调整其他机械元件。
所有的元件都已经在工厂精密设定好,不应在现场变动。
尺寸-102系列此资料中的尺寸仅供参考。
若变动恕不通知。
特殊型号的确切图纸请询工厂。
下面中所示的尺寸上面为mm,下面为inch。
(JS的尺寸与AD的相同,除了接线盒。
未提供接线盒的尺寸是由于通过认证的厂商在设计和尺寸上有差异)107系列差压开关使用说明概述此说明书提供107系列差压开关的安装,电气连接,过程连接和标定方面的信息。
设计与规范的改动请恕不另行通知。
工作原理膜片和活塞集合感应过程压力。
活塞对差压做出反应,推动使开关元件工作的轴。
低压端压力和与介质接触的可调范围的弹簧一起与高压端压力工作。
调整设定点端,改变弹簧的范围,从而完成标定。
应用107系列差压开关适用于通风领域和工业空气、气体,这些介质需与开关的接触介质部分的材质相适应且在铭牌的规格内。
细节部分请垂询SOR工厂和代理商。
警告:警告:安装时不要移动开关元件和外壳。